Plan Review Stops For Permit 05091425 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
199 |
Status |
P |
Date |
2008-08-27 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2008-08-27 |
Time |
18:50 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2008-08-27 |
Time |
18:50 |
Sent To |
|
|
Notes |
2008-08-27 18:51:51 | STRUCTURAL CALCULATION AND SHOP DRAWING SUBMITTAL FOR | | GLASS GUARDRAIL LOCATED AT 2ND FLOOR ELEVATOR LOBBY | | OVERLOOKING MAIN LOBBY. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
198 |
Status |
P |
Date |
2008-05-24 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2008-05-24 |
Time |
15:18 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2008-05-24 |
Time |
15:17 |
Sent To |
|
|
Notes |
2008-05-24 15:18:47 | SUBMITTAL ON 5/1/08 FOR CALCULATIONS ON RAILINGS AT | | POOL DECK LEVEL. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
196 |
Status |
P |
Date |
2008-05-24 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2008-05-24 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2008-05-24 |
Time |
15:08 |
Sent To |
|
|
Notes |
2008-05-24 15:09:19 | SUBMITTAL ON 5/1/08 FOR CALCULATIONS ON RAILINGS AT | | BUILDING ENTRY |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
195 |
Status |
P |
Date |
2008-05-24 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2008-05-24 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2008-05-24 |
Time |
15:06 |
Sent To |
|
|
Notes |
2008-05-24 15:07:53 | ARCHITECTURAL REVISION SUBMITTED ON 4/17/08 FOR SHEET | | A-2.1.2. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
194 |
Status |
P |
Date |
2008-04-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2008-04-09 |
Time |
18:13 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2008-04-09 |
Time |
18:13 |
Sent To |
|
|
Notes |
2008-04-09 18:22:41 | SUBMITTAL FOR ROOF FLASHING DETAILS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
193 |
Status |
P |
Date |
2008-04-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2008-04-09 |
Time |
17:09 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2008-04-09 |
Time |
17:09 |
Sent To |
|
|
Notes |
2008-04-09 17:12:00 | ARCHITECTURAL REVISION FOR SHEETS A-1.1, A-1.5, | | A-2.1.6, A-2.4.2, A-2.4.5, AND A-6.5 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
192 |
Status |
P |
Date |
2008-02-13 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2008-02-13 |
Time |
19:56 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2008-02-13 |
Time |
19:56 |
Sent To |
|
|
Notes |
2008-02-13 19:57:18 | SUBMITTAL ON 1/11/08 FOR 4 HR FIRESTOP JOINT DETAIL |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
191 |
Status |
P |
Date |
2007-12-24 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-12-24 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-12-24 |
Time |
16:17 |
Sent To |
|
|
Notes |
2007-12-24 16:18:19 | SUBMITTAL FOR 9TH FLOOR SAUNA/STEAM ROOM SHOP DRAWINGS | | AND PRODUCT DATA |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
190 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-12-21 |
Time |
21:56 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-12-21 |
Time |
21:56 |
Sent To |
|
|
Notes |
2007-12-21 21:57:06 | SUBMITTTAL FOR MECHANICAL AND ADHESIVE ATTACHMENT OF | | EIFS ARCHITECTURAL MOLDING |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
189 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-12-21 |
Time |
21:42 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-12-21 |
Time |
21:42 |
Sent To |
|
|
Notes |
2007-12-21 21:46:36 | STRUCTURAL SUBMITTAL FOR ROOF LEVEL MECHANICAL PIPE | | BRIDGES |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
188 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-12-21 |
Time |
21:36 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-12-21 |
Time |
21:36 |
Sent To |
|
|
Notes |
2007-12-21 21:36:50 | SUBMITTAL FOR PRECAST VENEER AND COPING ATTACHMENT | | CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
187 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-12-21 |
Time |
21:26 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-12-21 |
Time |
21:26 |
Sent To |
|
|
Notes |
2007-12-21 21:27:54 | SUBMITTAL FOR COPPER ROOFTOP SPHERE ATTACHMENT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
186 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-12-21 |
Time |
21:20 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-12-21 |
Time |
21:20 |
Sent To |
|
|
Notes |
2007-12-21 21:21:29 | SHOP DRAWINGS AND CALCULATIONS FOR LOUVERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
185 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-12-21 |
Time |
21:19 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-12-21 |
Time |
21:19 |
Sent To |
|
|
Notes |
2007-12-21 21:20:35 | SUBMITTAL FOR VILLA TRASH ROOM 2 TRASH CHUTE SHOP | | DRAWING |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
184 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-12-21 |
Time |
21:06 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-12-21 |
Time |
21:06 |
Sent To |
|
|
Notes |
2007-12-21 21:07:08 | ARCHITECTURAL SUBMITTAL FOR ROOF FLASHING AND EXPANSION | | JOINT DETAILS AND PRODUCT DATA |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
183 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-12-21 |
Time |
20:53 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-12-21 |
Time |
20:53 |
Sent To |
|
|
Notes |
2007-12-21 21:06:05 | STRUCTURAL SUBMITTAL FOR VILLA ROOF TRUSS SHOP DRAWINGS | | AND CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
182 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-12-21 |
Time |
20:41 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-12-21 |
Time |
20:41 |
Sent To |
|
|
Notes |
2007-12-21 20:42:28 | ARCHITECTURAL REVISION FOR SHEETS A-8.1, A-8.4, A-9.3.1 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
181 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-12-21 |
Time |
20:30 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-12-21 |
Time |
20:30 |
Sent To |
|
|
Notes |
2007-12-21 20:31:09 | SUBMITTAL FOR ROOF TILE ATTACHMENT CALCULATIONS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
180 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-12-21 |
Time |
20:21 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-12-19 |
Time |
20:09 |
Sent To |
|
|
Notes |
2007-12-21 20:23:37 | ARCHITECTURAL REVISION FOR SHEETS A-1.1, A-2.1.4, | | A-2.1.5, A-2.3.6, A-2.7.1, A-6.1, A-6.5, A-6.9 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
179 |
Status |
P |
Date |
2007-11-19 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-11-19 |
Time |
11:18 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-11-19 |
Time |
11:18 |
Sent To |
|
|
Notes |
2007-11-19 11:19:55 | SUBMITTAL ON 11/16/07 FOR STOREFRONT SHOP DRAWING AND | | CALCULATIONS PREVIOUSLY REVIEWED ON 11/12/07 AND | | 9/23/07. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
178 |
Status |
F |
Date |
2007-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-11-12 |
Time |
17:45 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-11-12 |
Time |
17:44 |
Sent To |
|
|
Notes |
2007-11-12 18:33:19 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | SUBMITTAL ON 10/23/07 FOR CALCULATIONS, SHOP DRAWINGS, | | AND PRODUCT APPROVALS FOR STOREFRONT | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | 1) FBC* 1606.1SHEET 1 OF 10 OF THE SUBMITTED | | CONTINENTAL GLASS SYSTEM SERIES 3000 ALUMINUM WINDOW | | WALL SYSTEM PRODUCT APPROVAL NOA# 05-1220.17 STATES | | THAT THE MAXIMUM ALLOWABLE MASONRY OPENING HEIGHT IS | | 10'-1 3/8". HOWEVER, SHEET 5 (WINDOW S6) OF THE | | SUBMITTED ENGINEERING EXPRESS (FRANK BENNARDO, P.E.) | | SHOP DRAWINGS SHOWS THE A REQUIREMENT FOR A MASONRY | | OPENING HEIGHT OF 14'-10" WHICH EXCEEDS THE MAXIMUM | | ALLOWED BY THE PRODUCT APPROVAL.SUBMIT A PRODUCT | | APPROVAL THAT COVERS THE REQUIRED WINDOW SIZE. | | | | 2) FBC 1606.1SHEET 14 OF THE SUBMITTED "TUBE STEEL | | CALCULATIONS" FROM ENGINEERING EXPRESS (FRANK BENNARDO, | | P.E.) STATES THAT THE TRIBUTARY SPAN OF THE HORIZONTAL | | MULLION FOR S4 IS 6'-4.5".HOWEVER, SHEET 6 (WINDOW | | S4) OF THE SUBMITTED ENGINEERING EXPRESS (FRANK | | BENNARDO, P.E.) SHOP DRAWINGS SHOWS THAT THE TRIBUTARY | | SPAN SHOULD BE AT LEAST 7'-0" (DUE TO ARCHED TOP). | | SUBMIT CALCULATIONS THAT REFLECT THE ACTUAL TRIBUTARY | | SPAN. | | | | 3) FBC 1606.1SHEETS 10, 12, AND 14 OF THE SUBMITTED | | "TUBE STEEL CALCULATIONS" FROM ENGINEERING EXPRESS | | (FRANK BENNARDO, P.E.) STATES A REQUIRED WALL THICKNESS | | OF 3/8" FOR THE HORIZONTAL MULLIONS FOR WINDOW 7 AND | | S4.HOWEVER,SHEET 8, DETAIL 7.1, OF THE SUBMITTED | | ENGINEERING EXPRESS (FRANK BENNARDO, P.E.) SHOP | | DRAWINGS SHOWS A WALL THICKNESS OF ONLY 1/4". AMEND THE | | SHOP DRAWING DETAIL TO ENSURE THAT THE TUBE MULLION | | WALL THICKNESS THAT IS REQUIRED BY THE CALCULATIONS | | WILL BE PROVIDED. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
177 |
Status |
P |
Date |
2007-10-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-10-18 |
Time |
18:53 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-10-18 |
Time |
18:53 |
Sent To |
|
|
Notes |
2007-10-18 18:55:54 | SUBMITTAL ON 10/12/07 FOR EIFS PRODUCT DATA, AND | | ASSOCIATED ADHESIVE PRODUCT DATA AND MECHANICAL | | FASTENER PRODUCT DATA AND SHOP DRAWING | | | | MUST SUBMIT ENGINEERING FOR FIVE (5) FASTENERS | | SUPPORTING WEIGHT OF 8'-0" LONG EIFS PANEL | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | TELEPHONE: (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
176 |
Status |
P |
Date |
2007-10-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-10-18 |
Time |
18:50 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-10-18 |
Time |
18:50 |
Sent To |
|
|
Notes |
2007-10-18 18:53:14 | REVISION FOR SHEET A-2.7.5 AND A-2.7.6 PREVIOUSLY | | PASSED BY BUILDING/STRUCTURAL AND NOW PASSED BY | | PLUMBING WITH PROVISO |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
175 |
Status |
P |
Date |
2007-10-05 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-10-05 |
Time |
19:21 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-10-05 |
Time |
19:21 |
Sent To |
|
|
Notes |
2007-10-05 19:22:19 | SUBMITTAL ON 9/28/07 FOR TRASH CHUTE SHOP DRAWING | | CHANGES. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
174 |
Status |
P |
Date |
2007-10-05 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-10-05 |
Time |
19:18 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-10-05 |
Time |
19:18 |
Sent To |
|
|
Notes |
2007-10-05 19:21:12 | SUBMITTAL ON 9/27/07 FOR COMMENT RESPONSE ADDRESSING | | THE 9/23/07 PLAN REVIEW COMMENTS RELATED TO GAPS IN | | RAILING PATTERN ON SHEET A-6.9 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
173 |
Status |
P |
Date |
2007-10-05 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-10-05 |
Time |
19:14 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-10-05 |
Time |
19:14 |
Sent To |
|
|
Notes |
2007-10-05 19:17:52 | SUBMITTAL ON 9/25/07 FOR EXTERIOR CEILING FRAMING | | CALCULATIONS AND SHOP DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
172 |
Status |
P |
Date |
2007-10-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-10-01 |
Time |
20:47 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-10-01 |
Time |
20:47 |
Sent To |
|
|
Notes |
2007-10-01 20:52:41 | REVISION SUBMITTED 7/25/07.SHEET A-7.15 SENT TO | | ZONING FOR REVIEW DUE TO INCREASE IN HEIGHT OF WALL | | ABOVE ARCADE.ZONING REVIEWED AND STAMPED ON 9/26/07. | | REVISION OK. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
171 |
Status |
F |
Date |
2007-10-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-10-01 |
Time |
20:18 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-10-01 |
Time |
20:18 |
Sent To |
|
|
Notes |
2007-10-01 20:36:17 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | SUBMITTAL ON 9/24/07 FOR EIFS SYSTEMS TEST REPORT. | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | 1) THE SUBMITTED METAL FRAMING CALCULATIONS ARE OK AND | | HAVE BEEN STAMPED | | | | 2) THE REVISED ARCHITECTURAL SHEETS ARE OK AND HAVE | | BEEN STAMPED BECAUSE THEY STATE THE REQUIREMENT FOR | | ASTM E 136 COMPLIANCE. | | | | 3) FBC 202DEFINITION OF "NON-COMBUSTIBLE MATERIAL". | | NON-COMBUSTIBLE MATERIAL IS THAT WHICH HAS PASSED THE | | TEST PROCEDURE SET FORTH IN ASTM E 136.THE SUBMITTED | | PRODUCT TEST REPORT CANNOT BE STAMPED BECAUSE THE TEST | | STANDARD USED TO TEST THE STO CLASSIC NEXT SYSTEM WAS | | NFPA 285 NOT ASTM E 136, SO THE PRODUCT HAS NOT BEEN | | SHOWN TO MEET THE REQUIREMENTS FOR NON-COMBUSTIBLE | | MATERIAL.PROVIDE A TEST REPORT BASED ON THE ASTM E | | 136 TEST STANDARD. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
170 |
Status |
P |
Date |
2007-10-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-10-01 |
Time |
20:11 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-10-01 |
Time |
20:11 |
Sent To |
|
|
Notes |
2007-10-01 20:15:38 | REVISION SUBMITTED 9/24/07 FOR SHEETS A-6.1, A-6.2, | | A-6.3, A-6.5, A-6.8, A-6.9 AND A-8.3.REVISED | | ARCHITECTURAL SHEETS ARE OK BECAUSE THEY STATE | | REQUIREMENT FOR ASTM E 136 COMPLIANCE.THE SUBMITTED | | PRODUCT TEST REPORT CANNOT BE STAMPED AS THE TEST | | STANDARD USED WAS NFPA 285 NOT ASTM E 136 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
169 |
Status |
P |
Date |
2007-09-23 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-23 |
Time |
17:40 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-23 |
Time |
17:40 |
Sent To |
|
|
Notes |
2007-09-23 17:41:50 | REVISION SUBMITTED 7/25/07.SHEET A-7.15 SENT TO | | ZONING FOR REVIEW DUE TO INCREASE IN HEIGHT OF WALL | | ABOVE ARCADE |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
168 |
Status |
F |
Date |
2007-09-23 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-23 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-23 |
Time |
16:02 |
Sent To |
|
|
Notes |
2007-09-23 16:18:06 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | REVISION SUBMITTED 7/3/07 | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | 1) FBC 1015.3SHEET A-6.9 HAS BEEN REVISED TO | | INCORPORATE DETAIL F WHICH SHOWS "DECORATIVE RAILING" | | ABOVE THE ARCADE.THE RAILING DESIGN HAS PROPORTIONS | | THAT LEAVE GAPS THAT EXCEED 4 INCHES BETWEEN RAILS. | | SHEET A-6.1, OKEECHOBEE BLVD ELEVATION SHOWS SLIDING | | GLASS DOORS GIVING ACCESS TO THESE RAILINGS.THE | | ORNAMENTAL PATTERN SHALL BE ARRANGED SO THAT A 4 INCH | | SPHERE CANNOT PASS THROUGH ANY OPENING. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | TELEPHONE: (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
167 |
Status |
F |
Date |
2007-09-23 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-23 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-23 |
Time |
14:52 |
Sent To |
|
|
Notes |
2007-09-23 15:00:47 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | SUBMITTAL ON 9/4/07 FOR TRASH CHUTE SHOP DRAWING | | REVISION | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | 1) IT IS NOTED THAT THERE IS A COPY OF A 9/26/06 (2006) | | STAMP FROM ROGER FRY ARCHITECT ON A LETTER FROM | | WILKINSON HI RISE ON SOUND TRANSMISSION, BUT THERE IS | | NO STAMP FROM ROGER FRY ARCHITECT ON THE REVISED SHOP | | DRAWINGS.THE REVISED SHOP DRAWINGS MUST HAVE A SHOP | | DRAWING REVIEW STAMP FROM THE ARCHITECT OF RECORD. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
166 |
Status |
P |
Date |
2007-09-23 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-23 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-23 |
Time |
14:47 |
Sent To |
|
|
Notes |
2007-09-23 14:48:24 | SUBMITTAL ON 8/30/07 FOR FPL VAULT LOUVERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
165 |
Status |
P |
Date |
2007-09-23 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-23 |
Time |
14:25 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-23 |
Time |
14:25 |
Sent To |
|
|
Notes |
2007-09-23 14:27:05 | SUBMITTAL ON 8/24/07 FOR VILLAS ROOF TRUSS SHOP DRAWING | | AND CALCS FOR ALTERNATIVE METAL TRUSS ATTACHMENT |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
164 |
Status |
P |
Date |
2007-09-23 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-23 |
Time |
14:20 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-23 |
Time |
14:20 |
Sent To |
|
|
Notes |
2007-09-23 14:20:40 | SUBMITTAL ON 8/21/07 FOR WINDOW WASHING SYSTEM SHOP | | DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
163 |
Status |
P |
Date |
2007-09-23 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-23 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-23 |
Time |
14:10 |
Sent To |
|
|
Notes |
2007-09-23 14:11:24 | SUBMITTAL ON 8/10/07 FOR VILLAS ROOF TRUSS SHOP | | DRAWINGS AND CALCS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
162 |
Status |
F |
Date |
2007-09-23 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-23 |
Time |
12:45 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-23 |
Time |
12:45 |
Sent To |
|
|
Notes |
2007-09-23 13:26:57 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | SUBMITTAL ON 7/20/07 FOR CALCULATIONS, SHOP DRAWINGS, | | AND PRODUCT APPROVALS FOR STOREFRONT | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | 1) AS STATED IN THE PREVIOUS REVIEW OF THESE DOCUMENTS | | ON 6/26/07, THE PRODUCT APPROVALS THAT ARE FOR PRODUCTS | | DIFFERENT FROM THE THOSE THAT HAVE ALREADY BEEN | | REVIEWED/STAMPED FOR THIS PROJECT ARE CONSIDERED | | REVISIONS AND A REVISION FEE IS DUE.THE PACKET WAS | | AGAIN INCORRECTLY SUBMITTED AS A ZERO FEE SUBMITTAL. | | IT IS A REVISION AND THE APPROPRIATE REVISION FEE OF | | $50 PLUS $10 FOR EACH NEW PRODUCT HAS NOW BEEN APPLIED | | ONCE FOR THE ORIGINAL REVISION SUBMITTAL AND AGAIN FOR | | THIS RE-SUBMITTAL OF THE REVISION.THE OUTSTANDING FEE | | IS $200 [CALCULATED AS 2X(50 + 5X10)]. | | | | 2) FBC* 1606.1THE CONTINENTAL GLASS SYSTEM SERIES | | 3000 ALUMINUM WINDOW WALL SYSTEM PRODUCT APPROVAL NOA# | | 05-1220.18 STATES THAT THE MAXIMUM NEGATIVE DESIGN | | PRESSURE SHALL NOT EXCEED -110 PSF.HOWEVER, SHEET 5 | | OF THE THE SUBMITTED ENGINEERING EXPRESS (FRANK | | BENNARDO, P.E.) SHOP DRAWINGS SHOWS THE A REQUIREMENT | | FOR NEGATIVE PRESSURE OF -130 PSF, AND REFERS TO | | RATIONAL ANALYSIS TO JUSTIFY EXCEEDING THE -110 PSF | | NEGATIVE DESIGN PRESSURE LIMIT OF THE PROPOSED PRODUCT. | | NO RATIONAL ANALYSIS WAS SUBMITTED.SUBMIT ORIGINAL | | SIGNED AND SEALED RATIONAL ANALYSIS CALCULATION | | SHEETS. | | BECAUSE THE REVIEW OF THE SHOP DRAWINGS CANNOT BE | | COMPLETED WITHOUT THE REFERENCE ATIONAL ANALYSIS | | CALCULATIONS, ALL COPIES OF THE STAMPED PRODUCT | | APPROVALS HAVE BEEN RETURNED.NO COPIES HAVE BEEN | | RETAINED, SO THEY WILL ALL NEED TO BE RE-SUBMITTED AS A | | COMPLETE PACKAGE WHEN THE RATIONAL ANALYSIS | | CALCULATIONS AND THE SHOP DRAWINGS ARE SUBMITTED. | | BECAUSE THEY HAVE ALL BEEN REVIEWED ALREADY THEY MAY | | ALL BE BROUGHT IN AS ZERO FEE SUBMITTALS. | | | | 3) THE PURPOSE OF THE SUBMITTED "TUBE STEEL | | CALCULATIONS" FROM ENGINEERING EXPRESS (FRANK BENNARDO, | | P.E.) COULD NOT BE DETERMINED.HOWEVER IT IS NOTED | | THAT THESE CALCULATIONS MAKE REPEATED REFERENCE TO A | | WIND PRESSURE OF 49 PSF.ACCORDING TO THE RWDI WIND | | TUNNEL TEST REPORT THERE IS NO LOCATION ON THIS | | BUILDING WITH A WIND PRESSURE AS LOW AS 49 PSF.ALL | | SUBMITTED COPIES OF THESE CALCULATIONS ARE BEING | | RETURNED TO THE CONTRACTOR. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | TELEPHONE: (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
161 |
Status |
P |
Date |
2007-09-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-09 |
Time |
20:27 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-09 |
Time |
20:27 |
Sent To |
|
|
Notes |
2007-09-09 20:27:53 | SUBMITTAL ON 8/17/07 FOR HIGH ROOF AREA 12 SHORING | | LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
160 |
Status |
P |
Date |
2007-09-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-09 |
Time |
20:25 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-09 |
Time |
20:25 |
Sent To |
|
|
Notes |
2007-09-09 20:25:32 | SUBMITTAL ON 8/16/07 FOR HIGH ROOF AREA 2 SHORING | | LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
159 |
Status |
P |
Date |
2007-09-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-09 |
Time |
20:21 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-09 |
Time |
20:21 |
Sent To |
|
|
Notes |
2007-09-09 20:21:53 | SUBMITTAL ON 8/14/07 FOR HIGH ROOF AREA 7B SHORING | | LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
158 |
Status |
P |
Date |
2007-09-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-09 |
Time |
20:17 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-09 |
Time |
20:17 |
Sent To |
|
|
Notes |
2007-09-09 20:18:39 | SUBMITTAL ON 7/312/07 FOR HIGH ROOF AREA 1 SHORING | | LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
157 |
Status |
P |
Date |
2007-09-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-09 |
Time |
20:11 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-09 |
Time |
20:10 |
Sent To |
|
|
Notes |
2007-09-09 20:14:56 | SUBMITTAL ON 7/27/07 FOR VILLAS SE HIGH ROOF SHORING | | LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
156 |
Status |
F |
Date |
2007-09-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-09 |
Time |
19:56 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-09 |
Time |
19:56 |
Sent To |
|
|
Notes |
2007-09-09 20:08:41 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | SUBMITTAL ON 7/10/07 FOR CALCULATIONS AND SHOP DRAWINGS | | FOR EXTERIOR FRAMING AND DROP CEILINGS | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | 1) FBC* 104.1.5 AND 104.2.1.3THE CALCULATION SHEETS | | AND SHOP DRAWINGS ALL REFER TO A PROJECT LOCATED AT | | 2828 CORAL WAY, MIAMI, FL.THE PROJECT LOCATION IS 550 | | OKEECHOBEE BLVD, WEST PALM BEACH, FL.ALL SUBMITTED | | DOCUMENTS ARE RETAINED AS PART OF THE RECORD RETENTION | | PROGRAM MANDATED BY STATUTE AND ARE REQUIRED TO STATE | | THE CORRECT PROJECT LOCATION.PLEASE REMOVE ALL | | REFERENCES TO THE INCORRECT LOCATION. | | SUGGESTION: FOR EVERY CALCULATION PAGE, TITLE PAGE, | | CONTENTS PAGE AND DRAWING SHEET, STRIKE OUT ALL | | REFERENCES TO 2828 CORAL WAY, MIAMI, FL AND APPLIY A | | STAMP (OR LABEL) WITH THE CORRECT ADDRESS OF 550 | | OKEECHOBEE BLVD, WEST PALM BEACH, FL. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
155 |
Status |
P |
Date |
2007-09-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-09 |
Time |
19:48 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-09 |
Time |
19:48 |
Sent To |
|
|
Notes |
2007-09-09 19:50:01 | SUBMITTAL ON 7/10/07 FOR HIGH ROOF LEVEL SHORING | | CALCULATIONS AND SHOP DRAWING |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
154 |
Status |
P |
Date |
2007-09-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-09 |
Time |
19:38 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-09 |
Time |
19:38 |
Sent To |
|
|
Notes |
2007-09-09 19:39:26 | SUBMITTAL ON 7/10/07 FOR INTERMEDIATE ROOF LEVEL | | ELEVATION +207'-4" SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
153 |
Status |
P |
Date |
2007-09-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-09 |
Time |
19:35 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-09 |
Time |
19:34 |
Sent To |
|
|
Notes |
2007-09-09 19:35:36 | SUBMITTAL ON 7/10/07 FOR MAIN ROOF LEVEL SLAB POUR 2 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
152 |
Status |
P |
Date |
2007-09-09 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-09-09 |
Time |
18:59 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-09-09 |
Time |
18:59 |
Sent To |
|
|
Notes |
2007-09-09 19:01:36 | SUBMITTAL ON 7/2/07 FOR MAIN ROOF LEVEL SLAB POUR 3 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
151 |
Status |
P |
Date |
2007-07-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-07-01 |
Time |
08:49 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-07-01 |
Time |
08:49 |
Sent To |
|
|
Notes |
2007-07-01 08:49:46 | SUBMITTAL ON 6/26/07 FOR MAIN ROOF LEVEL SLAB POUR 1 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
150 |
Status |
P |
Date |
2007-07-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-07-01 |
Time |
08:44 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-07-01 |
Time |
08:44 |
Sent To |
|
|
Notes |
2007-07-01 08:46:26 | SUBMITTAL ON 6/22/07 FOR 9TH FLOOR GARAGE SLAB POUR 3 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
149 |
Status |
F |
Date |
2007-07-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-07-01 |
Time |
08:34 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-07-01 |
Time |
08:34 |
Sent To |
|
|
Notes |
2007-07-01 08:35:57 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | REVISION SUBMITTED ON 6/20/07 FOR ROOF TRUSS SHOP | | DRAWING | | | | 1)THERE IS NO REVIEW STAMP FROM THE DESIGNER OF | | RECORD FOR THE PROJECT.ALL SHOP DRAWINGS AND | | CALCULATIONS MUST BE REVIEWED BY THE DESIGNER OF RECORD | | AND A SHOP DRAWING REVIEW STAMP MUST BE APPLIED TO THEM | | BEFORE SUBMITTAL TO THIS OFFICE. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
148 |
Status |
P |
Date |
2007-07-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-07-01 |
Time |
08:33 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-07-01 |
Time |
08:33 |
Sent To |
|
|
Notes |
2007-07-01 08:34:01 | SUBMITTAL ON 6/19/07 FOR 20TH FLOOR TOWER SLAB POUR 2 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
147 |
Status |
P |
Date |
2007-07-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-07-01 |
Time |
08:29 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-07-01 |
Time |
08:29 |
Sent To |
|
|
Notes |
2007-07-01 08:30:46 | SUBMITTAL ON 6/14/07 FOR 9TH FLOOR GARAGE SLAB POUR 2 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
146 |
Status |
P |
Date |
2007-07-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-07-01 |
Time |
08:27 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-07-01 |
Time |
08:27 |
Sent To |
|
|
Notes |
2007-07-01 08:27:35 | SUBMITTAL ON 6/11/07 FOR 20TH FLOOR TOWER SLAB POUR 3 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
145 |
Status |
P |
Date |
2007-07-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-07-01 |
Time |
08:23 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-07-01 |
Time |
08:23 |
Sent To |
|
|
Notes |
2007-07-01 08:24:21 | SUBMITTAL ON 6/11/07 FOR 20TH FLOOR TOWER SLAB POUR 1 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
144 |
Status |
F |
Date |
2007-07-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-07-01 |
Time |
08:05 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-07-01 |
Time |
08:05 |
Sent To |
|
|
Notes |
2007-07-01 08:18:01 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | REVISION SUBMITTED ON 6/7/07 FOR ROOF TRUSS SHOP | | DRAWING AND CALCULATION | | | | 1)THERE IS NO REVIEW STAMP FROM THE DESIGNER OF | | RECORD FOR THE PROJECT.ALL SHOP DRAWINGS AND | | CALCULATIONS MUST BE REVIEWED BY THE DESIGNER OF RECORD | | AND A SHOP DRAWING REVIEW STAMP MUST BE APPLIED TO THEM | | BEFORE SUBMITTAL TO THIS OFFICE. | | | | 2) 61G15-23.002(2)FL. ADMIN. CODE.IT IS NOTED THAT | | THE PRINTED NAME AND PRINTED LICENSE NUMBER FOR THE | | ENGINEER, AND CERTIFICATE OF AUTHORIZATION NUMBER FOR | | THE ENGINEERING BUSINESS (MOODY ENGINEERING, INC.) IS | | INCLUDED ON THE SHOP DRAWINGS.HOWEVER THAT | | INFORMATION MUST BE BE PRINTED ON THE CALCULATIONS | | ALSO.CURRENTLY IT IS ONLY THERE IN THE FORM OF THE | | RAISED SEAL, WHICH DOES NOT REPRODUCE WHEN SCANNED FOR | | ARCHIVING.THIS INFORMATION MUST BE MUST BE ADDED TO | | THE FIRST (SIGNED AND SEALED) SHEET OF THE CALCULATION | | REPORT.THE SHEET DOES NOT HAVE TO BE SIGNED AND | | SEALED AGAIN, THE INFORMATION MAY BE ADDED BY HAND. | | (471.025 F.S. AND 471.023 F.S.). | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
143 |
Status |
P |
Date |
2007-07-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-07-01 |
Time |
08:01 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-07-01 |
Time |
08:01 |
Sent To |
|
|
Notes |
2007-07-01 08:02:27 | SUBMITTAL ON 6/5/07 FOR INTERMEDIATE ROOF SLAB SHORING | | SHOP DRAWINGS AND CALCS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
142 |
Status |
P |
Date |
2007-07-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-07-01 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-07-01 |
Time |
07:55 |
Sent To |
|
|
Notes |
2007-07-01 08:00:55 | SUBMITTAL ON 6/5/07 FOR 9TH FLOOR VILLA SLAB POUR 1 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
141 |
Status |
P |
Date |
2007-07-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-07-01 |
Time |
07:50 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-07-01 |
Time |
07:50 |
Sent To |
|
|
Notes |
2007-07-01 07:52:22 | SUBMITTAL ON 6/5/07 FOR MAIN ROOF LEVEL SLAB SHORING | | SHOP DRAWING AND CALCS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
140 |
Status |
P |
Date |
2007-07-01 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-07-01 |
Time |
07:45 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-07-01 |
Time |
07:45 |
Sent To |
|
|
Notes |
2007-07-01 07:48:07 | SUBMITTAL ON 6/5/07 FOR 19TH FLOOR TOWER SLAB POUR 2 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
139 |
Status |
F |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
11:53 |
Sent To |
|
|
Notes |
2007-06-30 12:18:48 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | SUBMITTAL ON 5/31/07 FOR WINDOW WASHING SYSTEM SHOP | | DRAWINGS | | | | 1)THERE IS NO REVIEW STAMP FROM THE DESIGNER OF | | RECORD FOR THE PROJECT.ALL SHOP DRAWINGS MUST BE | | REVIEWED BY THE DESIGNER OF RECORD AND A SHOP DRAWING | | REVIEW STAMP MUST BE APPLIED TO THE SHOP DRAWINGS | | BEFORE SUBMITTAL TO THIS OFFICE. | | | | 2) THE TITLE BLOCK ON THE PLANS STATE AN INCORRECT | | PROJECT ADDRESS/LOCATION.THE PROJECT STATED IS 2828 | | CORAL WAY, MIAMI.THE PLANS MUST IDENTIFY THE CORRECT | | PROJECT LOCATION. | | | | 3)THE FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL | | REGULATION (DBPR) WEBSITE SHOWS THE LICENSE STATUS OF | | THE WINDOW WASHING SYSTEM ENGINEER AS DELINQUENT.SEE | | ATTACHED PRINTOUT.THE ENGINEER MUST RESOLVE THIS WITH | | THE DBPR/ FLORIDA BOARD OF PROFESSIONAL ENGINEERS, AND | | HAVE THE WEBSITE UPDATED, BEFORE THE PLANS ARE | | RE-SUBMITTED TO THIS OFFICE. | | | | 4) FBC* 106.1ENGINEER'S SIGNATURE.ONLY ONE OF THE | | SIX SHEETS SUBMITTED HAS AN ORIGINAL SIGNATURE FROM THE | | ENGINEER.THE OTHER OTHER SHEETS ALL HAVE A RAISED | | SEAL OVER PHOTOCOPIED SIGNATURE.AN ORIGINAL (WET) | | SIGNATURE IS REQUIRED ON ALL DOCUMENTS PREPARED BY A | | PROFESSIONA ENGINEER. (REF: 471.023 F.S.) | | | | 5) 61G15-23.002(2)FL. ADMIN. CODE.THE NO PRINTED | | NAME AND PRINTED LICENSE NUMBER FOR THE ENGINEER MUST | | BE ADDED TO EACH SHEET.ALSO, THE ADDRESS OF THE | | ENGINEER (NOT THE COMPANY) IS REQUIRED ON EACH SHEET | | UNLESS PRO-BEL ENTERPRISES IS REGISTERED AS AN | | 'ENGINEERING BUSINESS' WITH THE FLORIDA BOARD OF | | PROFESSIONAL ENGINEERS (FBPE) AND HAS AN ENGINEERING | | BUSINESS NUMBER (CERTIFICATE OF AUTHORIZATION NUMBER) | | ISSUED BY THE FBPE.IF IT IS, THEN PRO-BEL'S | | ENGINEERING BUSINESS NUMBER (CERTIFICATE OF | | AUTHORIZATION NUMBER) MUST BE PRINTED ON THE PLANS. | | PLANS SIGNED & SEALED BY A PROFESSIONAL | | ENGINEER SHALL INCLUDE EITHER THE NAME, | | ADDRESS AND LICENSE NUMBER OF THE | | ENGINEER OR, THE NAME AND LICENSE NUMBER | | OF THE ENGINEER AND THE NAME, ADDRESS | | AND CERTIFICATE OF AUTHORIZATION NUMBER | | OF THE ENGINEERING BUSINESS THROUGH | | WHICH THE ENGINEER IS PRACTICING | | (471.025 F.S. AND 471.023 F.S.). | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
138 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
11:48 |
Sent To |
|
|
Notes |
2007-06-30 11:48:52 | SUBMITTAL ON 5/29/07 FOR 19TH FLOOR TOWER POUR 3 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
137 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
11:44 |
Sent To |
|
|
Notes |
2007-06-30 11:45:03 | SUBMITTAL ON 5/29/07 FOR 19TH FLOOR TOWER POUR 1 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
136 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
11:42 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
11:42 |
Sent To |
|
|
Notes |
2007-06-30 11:42:42 | SUBMITTAL ON 5/22/07 FOR ROOF TRUSS SHOP DRAWINGS AND | | CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
135 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
11:13 |
Sent To |
|
|
Notes |
2007-06-30 11:15:54 | SUBMITTAL ON 5/22/07 FOR 18TH FLOOR TOWER POUR 2 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
134 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
11:07 |
Sent To |
|
|
Notes |
2007-06-30 11:09:45 | SUBMITTAL ON 5/17/07 FOR GARAGE SHORING SHOP DRAWING | | AND CALCULATIONS.SEE RFI # 268 FOR ENGINEER OF RECORD | | REVIEW. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
133 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
10:53 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
10:53 |
Sent To |
|
|
Notes |
2007-06-30 10:53:53 | SUBMITTAL ON 5/17/07 FOR 18TH FLOOR TOWER POUR 3 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
132 |
Status |
N |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
10:51 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
10:51 |
Sent To |
|
|
Notes |
2007-06-30 10:52:10 | SUBMITTAL ON 5/17/07 FOR 18TH FLOOR TOWER POUR 1 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
131 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
10:48 |
Sent To |
|
|
Notes |
2007-06-30 10:48:27 | SUBMITTAL ON 5/10/07 FOR 17TH FLOOR TOWER POUR 2 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
130 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
10:45 |
Sent To |
|
|
Notes |
2007-06-30 10:46:00 | SUBMITTAL ON 5/9/07 FOR 18TH FLOOR TOWER POOL DECK | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
129 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
10:43 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
10:43 |
Sent To |
|
|
Notes |
2007-06-30 10:43:52 | SUBMITTAL ON 5/9/07 FOR 17TH FLOOR TOWER POUR 3 SHORING | | LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
128 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
10:39 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
10:39 |
Sent To |
|
|
Notes |
2007-06-30 10:40:16 | SUBMITTAL ON 5/3/07 FOR 17TH FLOOR TOWER POUR 1 SHORING | | LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
127 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
10:36 |
Sent To |
|
|
Notes |
2007-06-30 10:37:31 | SUBMITTAL ON 5/3/07 FOR 4TH FLOOR GARAGE POUR 1 SHORING | | LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
126 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
10:34 |
Sent To |
|
|
Notes |
2007-06-30 10:34:56 | SUBMITTAL ON 5/2/07 FOR 8TH FLOOR VILLA POUR 3 SHORING | | LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
125 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
10:22 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
10:22 |
Sent To |
|
|
Notes |
2007-06-30 10:23:03 | SUBMITTAL ON 4/30/07 FOR 16TH FLOOR TOWER POUR 3 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
124 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
10:18 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
10:18 |
Sent To |
|
|
Notes |
2007-06-30 10:19:59 | SUBMITTAL ON 4/27/07 FOR 8TH FLOOR GARAGE POUR 2 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
123 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
10:13 |
Sent To |
|
|
Notes |
2007-06-30 10:14:10 | SUBMITTAL ON 4/26/07 FOR 16TH FLOOR TOWER POUR 2 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
122 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
10:09 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
10:09 |
Sent To |
|
|
Notes |
2007-06-30 10:10:22 | SUBMITTAL ON 4/20/07 FOR 8TH FLOOR GARAGE POUR 1 | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
121 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
10:04 |
Sent To |
|
|
Notes |
2007-06-30 10:06:17 | SUBMITTAL ON 4/9/07 FOR 9TH FLOOR POST-TENSION SLAB | | SHOP DRAWINGS AND CALCS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
120 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
09:56 |
Sent To |
|
|
Notes |
2007-06-30 09:58:40 | SUBMITTAL 4/3/07 FOR EXTERIOR CEILING/SOFFIT METAL | | FRAMING |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
119 |
Status |
P |
Date |
2007-06-30 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-30 |
Time |
09:39 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-30 |
Time |
09:39 |
Sent To |
|
|
Notes |
2007-06-30 09:41:07 | SUBMITTAL ON 6/29/07 FOR GUARDRAILS, HANDRAILS, STAIRS | | AND MISC. METALS SHOP DRAWINGS AND CALCULATIONS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
118 |
Status |
F |
Date |
2007-06-27 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-27 |
Time |
08:11 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-27 |
Time |
08:11 |
Sent To |
|
|
Notes |
2007-06-27 09:58:44 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | SUBMITTAL ON 3/30/07 FOR ROOFING PRODUCT APPROVALS AND | | SPECS | | | | 1) FBC* 106.3.3ALL PRODUCT APPROVALS, SHOP DRAWINGS | | AND CALCULATIONS SHALL BE REVIEWED BY THE DESIGNER OF | | RECORD AND STAMPED WITH HIS/HER SHOP DRAWING REVIEW | | STAMP PRIOR TO SUBMITTAL FOR BUILDING OFFICIAL REVIEW. | | THERE ARE NO SHOP DRAWING REVIEW STAMPS, FROM THE | | DESIGNER OF RECORD, ON ANY OF THE SUBMITTED DOCUMENTS. | | | | 2) THE SUBMITTED SANTAFE SPANISH 'S' CLAY ROOF TILE | | PRODUCT APPROVAL NOA# 05-0921.02 IS A REVISION FROM THE | | CLAY FOREVER, LLC ALTUSA "S" CLAY ROOF TILE PRODUCT | | APPROVAL 05-0901.06 (FL # 5559) THAT WAS REVIEWED AND | | STAMPED ON 9/9/06.REVISED ATTACHMENT CALCULATIONS | | WOULD BE REQUIRED BECAUSE THE ROOF TILE REVISION WAS | | ALSO INTRODUCED UNDER THE ROOFING SUB-PERMIT # | | 07060198, AND THE CALCULATIONS SUBMITTED UNDER THAT | | PERMIT NUMBER GENERATED THE FOLLOWING PLAN REVIEW | | COMMENT: | | FBC 1609.1WIND PRESSURES.BASED ON THE RWDI WIND | | TUNNEL TEST REPORT, SHEET S-6.00 OF THE STRUCTURAL | | PLANS FOR THE BUILDING (UNDER PERMIT # 05091425) SHOWS | | NEGATIVE WINDPRESSURES RANGING FROM -70 PSF TO -150 | | PSF.THESE DESIGN PRESSURE ARE FAR HIGHER THAN THE | | PRESSURES ASSUMED IN THE SUBMITTED ATLANTIC & CARIBBEAN | | ROOFING CONSULTING, LLC REPORTS 06-1274 L REV. AND | | 06-1274 H REV. (BOTH DATED 6/5/07) FOR THE | | DESIGN/SELECTION OF THE TILE AND ATTACHMENT FOR THE | | LOWER AND HIGHER ROOF.SUBMIT CALCULATIONS THAT MEET | | THE DESIGN PRESSURES ON STRUCTURAL PLAN SHEET S-6.00. | | IT IS NOTED THAT THE ATLANTIC & CARIBBEAN ROOFING | | CONSULTING, LLC REPORTS 06-1274 L AND 06-1274 H (BOTH | | DATED 8/15/06, PRIOR TO REVISION) DID MEET THE REQUIRED | | WIND PRESSURES, AND WERE CONSEQUENTLY REVIEWED AND | | STAMPED ON 9/9/06 UNDER PERMIT # 05091425. | | | | 3) FLORIDA ADMINISTRATIVE CODE RULE 9B-72EITHER | | STATEWIDE OR LOCAL (CITY OF WEST PALM BEACH) PRODUCT | | APPROVAL IS REQUIRED.WHERE THE FLORIDA DEPARTMENT OF | | COMMUNITY AFFAIRS (DCA) HAS ISSUED A STATEWIDE PRODUCT | | APPROVAL FL # FOR THE PROPOSED PRODUCT, THE APPROPRIATE | | STATEWIDE PRODUCT APPROVAL COVER SHEET SHALL BE | | ATTACHED TO THE SUBMITTEDMIAMI-DADE NOA.FOR | | REFERENCE, THE ATTACHED EXAMPLE STATEWIDE PRODUCT | | APPROVAL COVER SHEET FL 644, FOR JOHNS MANVILLE | | MODIFIED BITUMEN ROOFING SYSTEM OVER LIGHTWEIGHT | | CONCRETE DECKS, HAS BEEN DOWNLOADED FROM THE DCA | | WEBSITE AT: | | WWW.FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX | | PLEASE SUBMIT STATEWIDE COVER SHEETS FOR ALL OF THE | | PROPOSED PRODUCTS THAT HAVE DCA PRODUCT APPROVAL. | | | | 4) ROOF TILE PRODUCT APPROVAL.A REVISION FEE, OF $50 | | PLUS AN ADDITIONAL $10 FOR EACH PRODUCT APPROVAL THAT | | IS DIFFERENT FROM THOSE THAT HAVE ALREADY BEEN | | REVIEWED/STAMPED FOR THIS PROJECT, IS DUE.THE PRODUCT | | APPROVALS SHALL BE BROUGHT BACK AS A REVISION, NOT A | | (ZERO FEE) SUBMITTAL. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
117 |
Status |
F |
Date |
2007-06-26 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-26 |
Time |
18:22 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-26 |
Time |
18:22 |
Sent To |
|
|
Notes |
2007-06-26 18:40:56 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | SUBMITTAL ON 4/30/07 FOR STOREFRONT DOOR AND WINDOW | | PRODUCT APPROVALS AND SHOP DRAWINGS | | | | 1) FBC* 106.3.3ALL PRODUCT APPROVALS, SHOP DRAWINGS | | AND CALCULATIONS SHALL BE REVIEWED BY THE DESIGNER OF | | RECORD AND STAMPED WITH HIS/HER SHOP DRAWING REVIEW | | STAMP PRIOR TO SUBMITTAL FOR BUILDING OFFICIAL REVIEW. | | THERE ARE NO SHOP DRAWING REVIEW STAMPS ON ANY OF THE | | SUBMITTED DOCUMENTS. | | | | 2)FLORIDA ADMINISTRATIVE CODE RULE 9B-72EITHER | | STATEWIDE OR LOCAL (CITY OF WEST PALM BEACH) PRODUCT | | APPROVAL IS REQUIRED.WHERE THE FLORIDA DEPARTMENT OF | | COMMUNITY AFFAIRS (DCA) HAS ISSUED A STATEWIDE PRODUCT | | APPROVAL FL # FOR THE PROPOSED PRODUCT, THE APPROPRIATE | | STATEWIDE PRODUCT APPROVAL COVER SHEET SHALL BE | | ATTACHED TO THE SUBMITTEDMIAMI-DADE NOA.FOR | | REFERENCE, THE ATTACHED EXAMPLE STATEWIDE PRODUCT | | APPROVAL COVER SHEET FL 5854, FOR YKK SERIES 35H | | ALUMINUM ENTRANCE DOOR, HAS BEEN DOWNLOADED FROM THE | | DCA WEBSITE AT: | | WWW.FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX | | PLEASE SUBMIT STATEWIDE COVER SHEETS FOR ALL OF THE | | PROPOSED PRODUCTS THAT HAVE DCA PRODUCT APPROVAL. | | | | 3) A REVISION FEE, OF $50 PLUS AN ADDITIONAL $10 FOR | | EACH PRODUCT APPROVAL THAT IS DIFFERENT FROM THOSE THAT | | HAVE ALREADY BEEN REVIEWED/STAMPED FOR THIS PROJECT, IS | | DUE.THE PRODUCT APPROVALS SHALL BE BROUGHT BACK AS A | | REVISION, NOT A (ZERO FEE) SUBMITTAL. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
116 |
Status |
F |
Date |
2007-06-25 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-25 |
Time |
19:22 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-25 |
Time |
19:22 |
Sent To |
|
|
Notes |
2007-06-25 19:38:05 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | SUBMITTAL ON 5/11/07 FOR DECORAWALL "PROMOULD" | | ARCHITECTURAL DETAILS. | | | | 1)FBC 1406.2.2ARCHITECTURAL TRIM.ARCHITECTURAL | | TRIM MORE THAN 40 FEET ABOVE GRADE, ON TYPE I AND II | | BUILDINGS, SHALL BE CONSTRUCTED OF APPROVED | | NON-COMBUSTIBLE MATERIALS AND SHALL BE SECURED WITH | | METAL OR OTHER APPROVED NON-COMBUSTIBLE BRACKETS.THE | | SUBMITTED SHOP DRAWINGS AND SPECIFICATION DO NOT CALL | | OUT MECHANICAL FASTENING FOR THE MOLDINGS ON THIS | | PROJECT.ALSO, THE SUBMITTED SPECIFICATION DOES NOT | | SHOW THAT THE CORE MATERIAL HAS BEEN TESTED IN | | ACCORDANCE WITH ASTM E 136 TO VERIFY THAT IS | | NON-COMBUSTIBLE (REF: FBC 703.4.1).IT IS NOTED THAT | | THE "COATING" HAS BEEN TESTED TO ASTM E 84, BUT NO TEST | | DATA WAS SUBMITTED FOR THE CORE MATERIAL.SUBMIT | | DOCUMENTATION (MARKED UP IF NECESSARY) TO SHOW | | COMPLIANCE WITH THE MECHANICAL FASTENING AND ASTM E 136 | | NON-COMBUSTIBILITY REQUIREMENTS. | | | | 2) FBC 1609.1WIND LOADS.SUBMIT TEST DATA AND/OR | | ATTACHMENT CALCULATIONS TO JUSTIFY THE MOULDING | | ATTACHMENT RESISTANCE TO WIND LOAD AND SELF WEIGHT. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
115 |
Status |
P |
Date |
2007-06-25 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-25 |
Time |
18:46 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-25 |
Time |
18:46 |
Sent To |
|
|
Notes |
2007-06-25 18:47:28 | REVISION SUBMITTED ON 4/30/07 FOR DOOR SCHEDULE SHEET | | A-4.1 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
114 |
Status |
P |
Date |
2007-06-24 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-24 |
Time |
18:36 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-24 |
Time |
18:36 |
Sent To |
|
|
Notes |
2007-06-24 18:39:49 | SUBMITTAL ON 4/30/07 FOR UL FIRE RATED WALL ASSEMBLY | | (UL LISTING # V452) FOR USE ADJACENT TO WET AREAS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
113 |
Status |
F |
Date |
2007-06-24 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-24 |
Time |
18:12 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-24 |
Time |
18:12 |
Sent To |
|
|
Notes |
2007-06-24 18:24:42 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | SUBMITTAL ON 3/15/07 FOR GUARDRAILS, HANDRAILS, STAIRS | | AND MISC. METALS SHOP DRAWINGS. | | | | 1) FBC* 106.1ENGINEER'S SIGNATURE AND SEAL, AND | | ENGINEERING BUSINESS CERTIFICATE OF AUTHORIZATION | | NUMBER.THE ENGINEERING LETTER AT THE BEGINNING OF | | EACH SECTION (I.E. AFTER EACH TAB) OF THE SUBMITTED | | BINDER IS A PHOTOCOPY, AND IS MISSING THE ENGINEER'S | | ORIGINAL SIGNATURE AND SEAL, AND THE ENGINEERING | | BUSINESS (OR CERTIFICATE OF AUTHORIZATION) NUMBER FOR | | STRUCTURES INTERNATIONAL, INC.THE ENGINEER SHALL | | APPLY AN ORIGINAL SIGNATURE, RAISED SEAL AND | | CERTIFICATE OF AUTHORIZATION NUMBER (DBPR WEBSITE SHOWS | | IT AS EB 9446, CAN BE ADDED BY HAND) TO EACH LETTER. | | (REF: 471.023 F.S.)**QUOTE PERMIT# ON ALL | | CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
112 |
Status |
P |
Date |
2007-06-16 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-16 |
Time |
18:34 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-16 |
Time |
18:34 |
Sent To |
|
|
Notes |
2007-06-16 18:37:52 | REVISION SUBMITTED ON 3/15/07 FOR SHEETS A-0.2, A-1.1, | | A-1.5, A-2.1.2, A-2.3.5, A-2.4.4, AND A-4.3 | | | | SHEETS A-2.4.5, A-2.4.6, AND A-4.1 RETURNED WITHOUT | | STAMPING BECAUSE LATER REVISIONS OF THESE SHEETS HAVE | | ALREADY BEEN REVIEWED AND STAMPED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
111 |
Status |
P |
Date |
2007-06-16 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-06-16 |
Time |
18:32 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-06-16 |
Time |
18:32 |
Sent To |
|
|
Notes |
2007-06-16 18:34:23 | REVISION SUBMITTED ON 3/15/07 FOR SHEETS A-2.4.2, | | A-2.4.3, A-2.4.5, A-2.4.6, AND A-4.1 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
110 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:56 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:55 |
Sent To |
|
|
Notes |
2007-04-18 22:56:31 | STRUCTURAL SUBMITTAL ON 4/18/07 FOR TOWER 16TH FLOOR | | SLAB, POUR 1 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
109 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:53 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:53 |
Sent To |
|
|
Notes |
2007-04-18 22:53:46 | STRUCTURAL SUBMITTAL ON 4/13/07 FOR TOWER 15TH FLOOR | | SLAB, POUR 3 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
108 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:50 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:50 |
Sent To |
|
|
Notes |
2007-04-18 22:51:07 | STRUCTURAL SUBMITTAL ON 4/11/07 FOR GARAGE 7TH FLOOR | | SLAB, POUR 3 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
107 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:48 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:48 |
Sent To |
|
|
Notes |
2007-04-18 22:48:44 | STRUCTURAL SUBMITTAL ON 4/11/07 FOR TOWER 15TH FLOOR | | SLAB, POUR 2 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
106 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:45 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:45 |
Sent To |
|
|
Notes |
2007-04-18 22:45:55 | STRUCTURAL SUBMITTAL ON 4/6/07 FOR TOWER 15TH FLOOR | | SLAB, POUR 1 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
105 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:43 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:43 |
Sent To |
|
|
Notes |
2007-04-18 22:43:53 | STRUCTURAL SUBMITTAL ON 4/3/07 FOR TOWER 14TH FLOOR | | SLAB, POUR 3 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
104 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:39 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:39 |
Sent To |
|
|
Notes |
2007-04-18 22:40:15 | STRUCTURAL SUBMITTAL ON 4/2/07 FOR TOWER 14TH FLOOR | | SLAB, POUR 2 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
103 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:36 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:36 |
Sent To |
|
|
Notes |
2007-04-18 22:37:30 | STRUCTURAL SUBMITTAL ON 3/30/07 FOR GARAGE 7TH FLOOR | | SLAB, POUR 1 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
102 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:33 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:33 |
Sent To |
|
|
Notes |
2007-04-18 22:34:10 | STRUCTURAL SUBMITTAL ON 3/27/07 FOR TOWER 14TH FLOOR | | SLAB, POUR 1 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
101 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:29 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:29 |
Sent To |
|
|
Notes |
2007-04-18 22:30:05 | STRUCTURAL SUBMITTAL ON 3/22/07 FOR VILLA 6TH FLOOR | | SLAB SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
100 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:25 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:25 |
Sent To |
|
|
Notes |
2007-04-18 22:25:44 | STRUCTURAL SUBMITTAL ON 3/21/07 FOR TOWER 13TH FLOOR | | SLAB, POUR 3 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
99 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:22 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:22 |
Sent To |
|
|
Notes |
2007-04-18 22:22:35 | STRUCTURAL SUBMITTAL ON 3/21/07 FOR TOWER 13TH FLOOR | | SLAB, POUR 2 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
98 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:18 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:18 |
Sent To |
|
|
Notes |
2007-04-18 22:19:35 | STRUCTURAL SUBMITTAL ON 3/15/07 FOR GARAGE 6TH FLOOR | | SLAB, POUR 2 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
97 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:13 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:13 |
Sent To |
|
|
Notes |
2007-04-18 22:15:29 | STRUCTURAL SUBMITTAL ON 3/14/07 FOR TOWER 13TH FLOOR | | SLAB, POUR 1 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
96 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:11 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:11 |
Sent To |
|
|
Notes |
2007-04-18 22:12:06 | STRUCTURAL SUBMITTAL ON 3/9/07 FOR GARAGE 6TH FLOOR | | SLAB, POUR 1 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
95 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:09 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:09 |
Sent To |
|
|
Notes |
2007-04-18 22:09:26 | STRUCTURAL SUBMITTAL ON 3/8/07 FOR TOWER 12TH FLOOR | | SLAB, POUR 3 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
94 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
22:05 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
22:05 |
Sent To |
|
|
Notes |
2007-04-18 22:05:49 | STRUCTURAL SUBMITTAL ON 3/7/07 FOR TOWER 12TH FLOOR | | SLAB, POUR 2 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
93 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
21:58 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
21:58 |
Sent To |
|
|
Notes |
2007-04-18 22:02:48 | STRUCTURAL SUBMITTAL ON 3/5/07 FOR GARAGE 5TH FLOOR | | SLAB, POUR 3 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
92 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
21:57 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
21:57 |
Sent To |
|
|
Notes |
2007-04-18 21:58:01 | STRUCTURAL SUBMITTAL ON 3/5/07 FOR TOWER 12TH FLOOR | | SLAB, POUR 1 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
91 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
21:50 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
21:50 |
Sent To |
|
|
Notes |
2007-04-18 21:51:11 | STRUCTURAL SUBMITTAL ON 3/5/07 FOR TOWER 11TH FLOOR | | SLAB, POUR 3 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
90 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
21:49 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
21:49 |
Sent To |
|
|
Notes |
2007-04-18 21:49:55 | STRUCTURAL SUBMITTAL ON 3/5/07 FOR TOWER 11TH FLOOR | | SLAB, POUR 2 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
89 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
21:45 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
21:44 |
Sent To |
|
|
Notes |
2007-04-18 21:46:22 | STRUCTURAL SUBMITTAL ON 2/22/07 FOR GARAGE 5TH FLOOR | | SLAB, POUR 2 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
88 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
21:39 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
21:39 |
Sent To |
|
|
Notes |
2007-04-18 21:41:20 | SUBMITTAL ON 2/22/07 FOR ONE TIME PRODUCT APPROVAL | | 06-2093 FROM MIAMI-DADE PRODUCT CONTROL DIVISION FOR | | MIAMI WALL SERIES SINGLE HUNG WINDOW TO ADDRESS PROVISO | | OF 9/6/06. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
87 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
21:29 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
21:29 |
Sent To |
|
|
Notes |
2007-04-18 21:31:52 | SUBMITTAL ON 2/20/07 FOR ONE TIME PRODUCT APPROVAL | | 06-2094 FROM MIAMI-DADE PRODUCT CONTROL DIVISION FOR | | MIAMI WALL SERIES 100 ALUMINUM SLIDING GLASS DOOR TO | | ADDRESS PROVISO OF 9/6/06. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
86 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
21:17 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
21:17 |
Sent To |
|
|
Notes |
2007-04-18 21:18:33 | STRUCTURAL SUBMITTAL ON 2/13/07 FOR GARAGE 5TH FLOOR | | SLAB, POUR 1 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
85 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
21:13 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
21:13 |
Sent To |
|
|
Notes |
2007-04-18 21:13:59 | STRUCTURAL SUBMITTAL ON 2/13/07 FOR TOWER 11TH FLOOR | | SLAB, POUR 1 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
84 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
21:09 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
21:09 |
Sent To |
|
|
Notes |
2007-04-18 21:10:30 | STRUCTURAL SUBMITTAL ON 2/13/07 FOR TOWER 10TH FLOOR | | SLAB, POUR 3 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
83 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
21:04 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
21:04 |
Sent To |
|
|
Notes |
2007-04-18 21:06:16 | STRUCTURAL SUBMITTAL ON 2/13/07 FOR TOWER 10TH FLOOR | | SLAB, POUR 2 SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
82 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
20:47 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
20:47 |
Sent To |
|
|
Notes |
2007-04-18 20:49:20 | STRUCTURAL SUBMITTAL ON 2/8/07 FOR ROOF, AND | | INTERMEDIATE AND HIGH ROOF SLAB POST-TENSION FRICTION | | LOSS CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
81 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
20:41 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
20:41 |
Sent To |
|
|
Notes |
2007-04-18 20:43:30 | STRUCTURAL SUBMITTAL ON 2/8/07 FOR ADDITIONAL SLAB | | SHORING CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
80 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
20:36 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
20:36 |
Sent To |
|
|
Notes |
2007-04-18 20:37:31 | STRUCTURAL SUBMITTAL ON 2/8/07 FOR VILLA 4TH FLOOR SLAB | | SHORING LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
79 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
20:31 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
20:31 |
Sent To |
|
|
Notes |
2007-04-18 20:32:52 | STRUCTURAL SUBMITTAL ON 2/8/07 FOR VILLA AND GARAGE 9TH | | FLOOR SHORING DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
78 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-18 |
Time |
20:25 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-18 |
Time |
20:25 |
Sent To |
|
|
Notes |
2007-04-18 20:26:44 | STRUCTURAL SUBMITTAL ON 2/8/07 FOR TOWER ROOF SLAB | | POST-TENSION SHOP DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
77 |
Status |
P |
Date |
2007-04-06 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-06 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-06 |
Time |
10:12 |
Sent To |
|
|
Notes |
2007-04-06 10:14:45 | SUBMITTAL ON 4/5/07 FOR ALUMA SYSTEMS INC. MAIN ROOF | | SHORING CALCULATIONS AND SHOP DRAWINGS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
76 |
Status |
P |
Date |
2007-04-06 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-04-06 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-04-06 |
Time |
10:10 |
Sent To |
|
|
Notes |
2007-04-06 10:12:10 | SUBMITTAL ON 4/5/07 FOR LEVEL 7, POUR 2, SHORING | | LETTERS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
75 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
20:11 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
20:11 |
Sent To |
|
|
Notes |
2007-02-11 20:18:05 | SUBMITTAL ON 2/5/07 FOR 4TH FLOOR, POUR 2 SHORING | | INSPECTION LETTERS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
74 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
20:09 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
20:09 |
Sent To |
|
|
Notes |
2007-02-11 20:11:03 | SUBMITTAL ON 2/5/07 FOR 4TH FLOOR, POUR 2 SHORING | | INSPECTION LETTERS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
73 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
20:04 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
20:04 |
Sent To |
|
|
Notes |
2007-02-11 20:06:10 | SUBMITTAL ON 2/2/07 FOR 8TH FLOOR VILLA AND GARAGE | | SHORING CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
72 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
20:03 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
20:03 |
Sent To |
|
|
Notes |
2007-02-11 20:04:33 | SUBMITTAL ON 2/2/07 FOR 8TH FLOOR VILLA AND GARAGE | | SHORING SHOP DRAWING |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
71 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
19:57 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
19:57 |
Sent To |
|
|
Notes |
2007-02-11 19:57:41 | SUBMITTAL ON 1/30/07 FOR 9TH FLOOR, POUR 2 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
70 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
19:54 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
19:54 |
Sent To |
|
|
Notes |
2007-02-11 19:54:22 | SUBMITTAL ON 1/30/07 FOR 9TH FLOOR, POUR 3 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
69 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
19:50 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
19:50 |
Sent To |
|
|
Notes |
2007-02-11 19:50:54 | SUBMITTAL ON 1/24/07 FOR 9TH FLOOR, POUR 1 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
68 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
19:46 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
19:46 |
Sent To |
|
|
Notes |
2007-02-11 19:47:34 | SUBMITTAL ON 1/19/07 FOR 8TH FLOOR, POUR 3 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
67 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
19:43 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
19:43 |
Sent To |
|
|
Notes |
2007-02-11 19:44:15 | SUBMITTAL ON 1/16/07 FOR 8TH FLOOR, POUR 2 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
66 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
19:35 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
19:35 |
Sent To |
|
|
Notes |
2007-02-11 19:43:23 | SUBMITTAL ON 1/16/07 FOR 3RD FLOOR SHORING INSPECTION | | LETTER FOR THE VILLAS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
65 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
19:32 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
19:32 |
Sent To |
|
|
Notes |
2007-02-11 19:35:07 | SUBMITTAL ON 1/12/07 FOR 3RD FLOOR, POUR 2 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
64 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
19:30 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
19:30 |
Sent To |
|
|
Notes |
2007-02-11 19:31:59 | SUBMITTAL ON 1/11/07 FOR 8TH FLOOR, POUR 1 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
63 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
19:27 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
19:27 |
Sent To |
|
|
Notes |
2007-02-11 19:28:29 | SUBMITTAL ON 1/8/07 FOR 7TH FLOOR, POUR 3 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
62 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
19:25 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
19:25 |
Sent To |
|
|
Notes |
2007-02-11 19:26:35 | SUBMITTTAL ON 1/24/07 FOR WINDOW AND SLIDING GLASS DOOR | | CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
61 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
19:14 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
19:14 |
Sent To |
|
|
Notes |
2007-02-11 19:15:09 | SUBMITTTAL ON 1/24/07 FOR WINDOW AND SLIDING GLASS DOOR | | SHOP DRAWINGS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
60 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
17:44 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
17:44 |
Sent To |
|
|
Notes |
2007-02-11 17:45:52 | REVISION SUBMITTED ON 12/18/06 FOR GAZEBO SHEET A-9.3 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
59 |
Status |
F |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-02-11 |
Time |
15:35 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-02-11 |
Time |
15:35 |
Sent To |
|
|
Notes |
2007-02-11 17:34:08 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | REVISION SUBMITTED 12/18/06 FOR CLUBROOM AND FITNESS | | CENTER BUILDOUT. | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | 1) FBC 704.1.2.3OCCUPANCY SEPARATION FOR FITNESS | | CENTER AND CLUB LOUNGE.THE PLANS SHALL STATE THE | | TOTAL AREA OF THE FITNESS CENTER AND TOTAL AREA OF THE | | CLUB LOUNGE.PER FBC 304.1.2 THEY ARE CLASSIFIED AS | | ASSEMBLY OCCUPANCY.IF THE AREA EXCEEDS 2,000 SQ FT, | | THEY SHALL BE SEPARATED FROM THE RESIDENTIAL OCCUPANCY | | BY 2 HOUR FIRE RESISTANT CONSTRUCTION.THE FITNESS | | CENTER AND CLUB LOUNGE BOTH EXCEED 750 SQ FT SO, PER | | FBC 704.1.2.2, THEY CANNOT BE CONSIDERED AS INCIDENTAL | | TO THE RESIDENTIAL OCCPANCY.AMEND THE PLANS TO STATE | | THE AREA OF THE FITNESS CENTER AND CLUB LOUNGE, AND | | INCREASE THE OCCUPANCY SEPARATION FIRE RESISTANCE TO 2 | | HOURS IF APPROPRIATE. | | | | 2) FBC 1012.1.2FITNESS CENTER DOOR 51.THE DOOR TO | | THE EXIT ACCESS CORRIDOR IS SHOWN SWINGING INTO THE | | FITNESS CENTER.THE DOOR SHALL OPEN IN THE DIRECTION | | OF EGRESS.AMEND THE PLANS. | | | | 3) FBC 1012.7FITNESS CENTER EGRESS DOORS.PER FBC | | 1004.1.2 NOT LESS THAN TWO EGRESS DOORS ARE REQUIRED. | | THE DOOR SCHEDULE ON SHEET A-4.1 SPECIFIES MAGNETIC | | LOCKS (HARDWARE NOTE 9) FOR DOOR 51 AND DOOR 50 | | (LEADING TO THE POOL DECK WHICH GIVES ACCESS TO STAIR | | 3).PER FBC 1012.7 MAGNETIC LOCKS ARE NOT PERMISSABLE | | FOR REQUIRED EGRESS SERVING ASSEMBLY OCCUPANCIES. | | SPECIFY PANIC HARDWARE OR FIRE/EXIT HARDWARE FOR DOOR | | 51.ALSO, EITHER SPECIFY PANIC HARDWARE OR FIRE/EXIT | | HARDWARE FOR DOOR 50, OR PROVIDE A SECOND DOOR FROM THE | | FITNESS CENTER TO THE EXIT ACCESS CORRIDOR. | | | | 4) FBC 1012.1.2CLUB LOUNGE DOOR 66.THE DOOR TO THE | | EXIT ACCESS CORRIDOR IS SHOWN SWINGING INTO THE CLUB | | LOUNGE.THE DOOR SHALL OPEN IN THE DIRECTION OF | | EGRESS.AMEND THE PLANS. | | | | 5) FBC 1012.7CLUB LOUNGE EGRESS DOORS.PER FBC | | 1004.1.2 NOT LESS THAN TWO EGRESS DOORS ARE REQUIRED. | | THE DOOR SCHEDULE ON SHEET A-4.1 SPECIFIES MAGNETIC | | LOCKS (HARDWARE NOTE 9) FOR DOOR 66 AND DOOR 50 | | (LEADING TO THE POOL DECK WHICH GIVES ACCESS TO STAIR | | 3).PER FBC 1012.7 MAGNETIC LOCKS ARE NOT PERMISSABLE | | FOR REQUIRED EGRESS SERVING ASSEMBLY OCCUPANCIES. | | SPECIFY PANIC HARDWARE OR FIRE/EXIT HARDWARE FOR DOOR | | 66 AND DOOR 50. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
58 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:58 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:58 |
Sent To |
|
|
Notes |
2007-01-07 13:00:31 | SUBMITTAL ON 1/3/07 FOR 7TH FLOOR, POUR 2 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
57 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:57 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:56 |
Sent To |
|
|
Notes |
2007-01-07 12:58:08 | SUBMITTAL ON 1/3/07 FOR 3RD FLOOR, POUR 1 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
56 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:52 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:52 |
Sent To |
|
|
Notes |
2007-01-07 12:53:21 | SUBMITTAL ON 12/27/06 FOR 7TH FLOOR, POUR 1 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
55 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:50 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:50 |
Sent To |
|
|
Notes |
2007-01-07 12:51:12 | SUBMITTAL ON 12/22/06 FOR 6TH FLOOR, POUR 3 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
54 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:48 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:48 |
Sent To |
|
|
Notes |
2007-01-07 12:49:12 | SUBMITTAL ON 12/22/06 FOR VILLA 2ND FLOOR SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
53 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:45 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:45 |
Sent To |
|
|
Notes |
2007-01-07 12:45:49 | SUBMITTAL ON 12/19/06 FOR 6TH FLOOR, POUR 6 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
52 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:42 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:42 |
Sent To |
|
|
Notes |
2007-01-07 12:43:00 | SUBMITTAL ON 12/19/06 FOR 2ND FLOOR, POUR 2 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
51 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:38 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:38 |
Sent To |
|
|
Notes |
2007-01-07 12:39:48 | SUBMITTAL ON 12/14/06 FOR 9TH FLOOR POST-TENSION SLAB | | DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
50 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:27 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:27 |
Sent To |
|
|
Notes |
2007-01-07 12:28:46 | SUBMITTAL ON 12/14/06 FOR 9TH FLOOR POST-TENSION SLAB | | CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
49 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:24 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:24 |
Sent To |
|
|
Notes |
2007-01-07 12:25:43 | SUBMITTAL ON 12/14/06 FOR 8TH FLOOR POST-TENSION SLAB | | DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
48 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:19 |
Sent To |
|
|
Notes |
2007-01-07 12:20:03 | SUBMITTAL ON 12/14/06 FOR GARAGE 8TH FLOOR POST-TENSION | | SLAB CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
47 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:14 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:14 |
Sent To |
|
|
Notes |
2007-01-07 12:15:18 | SUBMITTAL ON 12/14/06 FOR 6TH FLOOR, POUR 1 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
46 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:10 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:10 |
Sent To |
|
|
Notes |
2007-01-07 12:12:19 | SUBMITTAL ON 12/8/06 FOR 5TH FLOOR, POUR 3 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
45 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:06 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:06 |
Sent To |
|
|
Notes |
2007-01-07 12:08:59 | SUBMITTAL ON 12/8/06 FOR GARAGE 3RD THRU 7TH FLOOR | | POST-TENSION SLAB CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
44 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
12:03 |
Sent To |
|
|
Notes |
2007-01-07 12:04:16 | SUBMITTAL ON 12/8/06 FOR GARAGE 3RD THRU 7TH FLOOR | | POST-TENSION SLAB DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
43 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
11:58 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
11:58 |
Sent To |
|
|
Notes |
2007-01-07 11:58:49 | SUBMITTAL ON 12/6/06 FOR 11TH THRU 20TH FLOOR SHORING | | DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
42 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
11:53 |
Sent To |
|
|
Notes |
2007-01-07 11:55:14 | SUBMITTAL ON 12/6/06 FOR2ND THRU 7TH FLOOR SHORING | | CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
41 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
11:49 |
Sent To |
|
|
Notes |
2007-01-07 11:50:42 | SUBMITTAL ON 12/6/06 FOR VILLA/GARAGE 3RD THRU 7TH | | FLOOR SHORING DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
40 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
11:38 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
11:38 |
Sent To |
|
|
Notes |
2007-01-07 11:39:02 | SUBMITTAL ON 12/4/06 FOR 5TH FLOOR, POUR 2 | | SHORING/RE-SHORING INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
39 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
11:35 |
Sent To |
|
|
Notes |
2007-01-07 11:36:25 | REVISION SUBMITTED ON 11/30/06 FOR APPLICATION OF SOUND | | INSULATION ON TRASH CHUTE INSTALLATION |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
38 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
11:26 |
Sent To |
|
|
Notes |
2007-01-07 11:27:44 | SUBMITTAL ON 11/30/06 FOR 5TH FLOOR, POUR 1 | | SHORING/RE-SHORING INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
37 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
11:23 |
Sent To |
|
|
Notes |
2007-01-07 11:24:37 | SUBMITTAL ON 11/21/06 FOR 4TH FLOOR, POUR 3 | | SHORING/RE-SHORING INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
36 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
11:20 |
Sent To |
|
|
Notes |
2007-01-07 11:21:25 | SUBMITTAL ON 11/17/06 FOR 4TH THRU 20TH FLOOR | | POST-TENSION SLAB DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
35 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
11:12 |
Sent To |
|
|
Notes |
2007-01-07 11:13:38 | SUBMITTAL ON 11/17/06 FOR 4TH THRU 20TH FLOOR | | POST-TENSION SLAB CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
34 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
11:02 |
Sent To |
|
|
Notes |
2007-01-07 11:06:10 | SUBMITTAL ON 11/17/06 FOR 4TH THRU 20TH FLOOR | | SHORING/RE-SHORING DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
33 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
10:52 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
10:52 |
Sent To |
|
|
Notes |
2007-01-07 10:53:21 | SUBMITTAL ON 11/16/06 FOR 4TH FLOOR, POUR 2 SHORING | | INSPECTION LETTER. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
32 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
10:50 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
10:50 |
Sent To |
|
|
Notes |
2007-01-07 10:50:58 | SUBMITTAL ON 11/13/06 FOR ROLLING DOOR SHOP DRAWING |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
31 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
10:44 |
Sent To |
|
|
Notes |
2007-01-07 10:45:01 | SUBMITTAL ON 11/13/06 FOR 4TH THRU 20TH FLOOR SHORING | | CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
30 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
10:40 |
Sent To |
|
|
Notes |
2007-01-07 10:41:40 | SUBMITTAL ON 11/13/06 FOR 4TH FLOOR POUR 1 SHORING | | INSPECTION LETTER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
29 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
10:34 |
Sent To |
|
|
Notes |
2007-01-07 10:36:41 | SUBMITTAL ON 11/13/06 FOR 4TH, 5TH , 6TH THRU 10TH, AND | | GARAGE 2ND FLOOR SHORING/RE-SHORING DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
28 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
10:28 |
Sent To |
|
|
Notes |
2007-01-07 10:29:05 | SUBMITTAL ON 11/13/06 FOR 3RD FLOOR SHORING DRAWINGS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
27 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
10:21 |
Sent To |
|
|
Notes |
2007-01-07 10:22:11 | SUBMITTAL ON 11/13/06 FOR 3RD FLOOR SHORING | | CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
26 |
Status |
P |
Date |
2007-01-07 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-01-07 |
Time |
10:16 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-01-07 |
Time |
10:16 |
Sent To |
|
|
Notes |
2007-01-07 10:17:56 | SUBMITTAL ON 11/13/06 FOR GARAGE LEVEL 2 AND 3 | | SHORING/RE-SHORING CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
25 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
11:53 |
Sent To |
|
|
Notes |
2006-11-12 11:54:20 | SUBMITTAL ON 11/3/06 FOR PTE STRAND CO. 2ND LEVEL | | PARKING PT PLANS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
24 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
11:44 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
11:44 |
Sent To |
|
|
Notes |
2006-11-12 11:45:26 | SUBMITTAL ON 11/3/06 FOR PTE STRAND CO. 2ND LEVEL | | PARKING PT FRICTION LOSS CALCULATIONS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
23 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
11:41 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
11:41 |
Sent To |
|
|
Notes |
2006-11-12 11:42:16 | SUBMITTAL ON 11/3/06 FOR UNITED FORMING, INC. LEVEL 3, | | POUR 3 SHORING/RESHORING LETTER. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
22 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
11:39 |
Sent To |
|
|
Notes |
2006-11-12 11:40:23 | SUBMITTAL ON 10/23/06 FOR UNITED FORMING, INC. LEVEL 3, | | POUR 2 SHORING/RESHORING LETTER. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
21 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
11:28 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
11:28 |
Sent To |
|
|
Notes |
2006-11-12 11:32:30 | SUBMITTAL ON 10/16/06 FOR ALUMA SYSTEMS INC./UNITED | | FORMING, INC. 2ND FLOOR AND 10TH THRU 20TH FLOOR | | (PARTIAL) SHORING PLANS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
20 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
11:25 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
11:25 |
Sent To |
|
|
Notes |
2006-11-12 11:25:58 | SUBMITTAL ON 10/10/06 FOR UNITED FORMING, INC. LEVEL 3, | | POUR 1 SHORING/RESHORING LETTER. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
19 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
11:22 |
Sent To |
|
|
Notes |
2006-11-12 11:22:57 | SUBMITTAL ON 9/27/06 FOR UNITED FORMING, INC. LEVEL 2, | | POUR 3 SHORING/RESHORING LETTER. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
18 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
11:19 |
Sent To |
|
|
Notes |
2006-11-12 11:20:35 | SUBMITTAL ON 9/20/06 FOR PTE STRAND CO. 3RD FLOOR PT | | DRAWINGS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
17 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
11:12 |
Sent To |
|
|
Notes |
2006-11-12 11:14:07 | SUBMITTAL ON 9/20/06 FOR PTE STRAND CO. 3RD FLOOR PT | | FRICTION LOSS CALCULATIONS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
16 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
11:09 |
Sent To |
|
|
Notes |
2006-11-12 11:12:37 | SUBMITTAL ON 9/20/06 FOR UNITED FORMING, INC. 3RD FLOOR | | SHORING PLAN AND DETAILS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
15 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
11:03 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
11:03 |
Sent To |
|
|
Notes |
2006-11-12 11:04:57 | SUBMITTAL ON 9/20/06 FOR UNITED FORMING, INC. LEVEL, 2, | | POUR 2 SHORING/RESHORING LETTER. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
14 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
11:00 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
11:00 |
Sent To |
|
|
Notes |
2006-11-12 11:02:05 | SUBMITTAL ON 9/20/06 FOR UNITED FORMING, INC. | | CAST-IN-PLACE CONCRETE FRAMING AND SHORING | | CALCULATIONS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
13 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
10:54 |
Sent To |
|
|
Notes |
2006-11-12 10:55:01 | SUBMITTAL ON 9/8/06 FOR UNITED FORMING, INC. SHORING | | INSPECTION PERSONNEL LETTER. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
12 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
10:47 |
Sent To |
|
|
Notes |
2006-11-12 10:50:12 | SUBMITTAL ON 9/8/06 FOR UNITED FORMING, INC. LEVEL 2, | | POUR 1 SHORING LETTER. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
11 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
10:44 |
Sent To |
|
|
Notes |
2006-11-12 10:45:31 | SUBMITTAL ON 9/8/06 FOR CRAVEN THOMPSON FINISH FLOOR | | ELEVATION / FLOOD ELEVATION LETTER. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
10 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
10:38 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
10:38 |
Sent To |
|
|
Notes |
2006-11-12 10:40:27 | SUBMITTAL ON 9/8/06 FOR ARDAMAN & ASSOCIATES IN-SITU | | SOIL DENSITY TEST LETTER. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
9 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
10:35 |
Sent To |
|
|
Notes |
2006-11-12 10:37:29 | SUBMITTAL ON 9/8/06 FOR ARDAMAN & ASSOCIATES SPT AND | | POST VIBROFLOTATION TREATMENT PROCEDURE LETTER. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
8 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
10:27 |
Sent To |
|
|
Notes |
2006-11-12 10:35:06 | SUBMITTAL ON 9/8/06 FOR FORM BOARD SURVEY |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
10:23 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
10:23 |
Sent To |
|
|
Notes |
2006-11-12 10:24:47 | STRUCTURAL SUBMITTAL ON 8/25/06 FOR 2ND FLOOR SHORING | | PLANS AND CALCULATIONS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
10:04 |
Sent To |
|
|
Notes |
2006-11-12 10:09:31 | STRUCTURAL SUBMITTAL ON 8/31/06 FOR 2ND AND 3RD LEVEL | | PT DRAWINGS | | | | --IMPORTANT-- | | I HAVE WRITTEN THE NAME AND LICENSE NUMBER OF MIAN | | ABDUL HAMID, P.E. ON THE PLANS.THE INFORMATION LISTED | | BELOW SHALL BE INCLUDED ON ALL FUTURE SUBMITTALS OR | | THEY WILL BE DENIED: | | PURSUANT TO 61G15-23.002(2)FL. ADMIN. CODE, PLANS | | SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL | | INCLUDE EITHER THE NAME, ADDRESS AND LICENSE NUMBER OF | | THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE | | ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF | | AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS | | THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S. | | AND 471.023 F.S.). | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2006-11-12 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-11-12 |
Time |
09:50 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-11-12 |
Time |
09:50 |
Sent To |
|
|
Notes |
2006-11-12 09:53:21 | STRUCTURAL SUBMITTAL ON 8/31/06 FOR 2ND AND 3RD LEVEL | | PT FRICTION LOSS CALCULATIONS |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2006-09-06 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-09-06 |
Time |
22:29 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-09-06 |
Time |
22:29 |
Sent To |
|
|
Notes |
2006-09-06 00:00:00 | BUILDING PLAN REVIEW | | ******PROVISO******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | -PROVISO- | | SUBMIT STRUCTURAL MULLION SHOP DRAWINGS | | FOR ALL STOREFRONT OVER 144" TALL.THE | | SUBMITTED ARCH ALUMINUM SERIES L-300 | | IMPACT WALL STOREFRONT PRODUCT NOA# | | 01-0619.01 STATES A MAXIMUM UNIT HEIGHT | | OF 144". THIS IS NOT SUFFICIENT TO COVER | | THE SIZE OF STOREFRONT SPECIFIED ON | | SHEETS A-4.1 AND A-4.2 OF THE PLANS. | | PER THE 8/25/06 MEETING WITH GLASS | | ENGINEERING INC., STRUCTURAL MULLIONS | | WILL BE INCORPORATED AND SHEETS A-4.1 | | AND A-4.2 WILL BE AMENDED TO REFLECT | | THIS AND CALL FOR SHOP DRAWINGS 'BY | | OTHERS' TO BE SUBMITTED FOR REVIEW. | | | | -PROVISO- | | SUBMIT ONE-TIME PRODUCT APPROVAL FOR | | SLIDING GLASS DOORS.DOOR SCHEDULE | | SHEET A-4.1 SHOWS A PROPOSED SLIDING | | GLASS DOOR HEIGHT OF 10'-0". PER THE | | 8/25/06 MEETING WITH GLASS ENGINEERING | | INC., THEY WILL BE APPLYING FOR A ONE | | TIME PRODUCT APPROVAL FOR THE 10'-0" | | DOOR AND WILL PROVIDE THREE COPIES OF | | THE APPROVAL.ONE-TIME APPROVAL WAS | | PREVIOUSLY GRANTED FOR A DIFFERENT | | PROJECT. | | | | -PROVISO- | | SUBMIT ONE-TIME PRODUCT APPROVAL FOR | | SINGLE HUNG WINDOW.WINDOW SCHEDULE | | SHEET A-4.2 SHOWS SINGLE HUNG WINDOW | | HEIGHTS UP TO 9'-4".PER THE 8/25/06 | | MEETING WITH GLASS ENGINEERING INC., | | THEY WILL BE APPLYING FOR A ONE TIME | | PRODUCT APPROVAL FOR THE 9'-4" HIGH | | WINDOW AND WILL PROVIDE THREE COPIES OF | | THE APPROVAL.ONE-TIME APPROVAL WAS | | PREVIOUSLY GRANTED FOR A DIFFERENT | | PROJECT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2006-08-27 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-08-27 |
Time |
19:19 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-08-27 |
Time |
19:18 |
Sent To |
|
|
Notes |
2006-08-27 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | ARE NUMBERED AS PER THE BUILDING PLAN | | REVIEW OF 7/23/06: | | | | 6) PRODUCT APPROVALS.SUBMITTAL OF | | PRODUCT APPROVALS IS NOTED. ONLY ONE | | COPY OF EACH PRODUCT APPROVAL HAS BEEN | | SUBMITTED AT THIS STAGE.THREE COPIES | | WILL BE REQUIRED FOR PERMIT ISSUANCE. | | EACH PRODUCT APPROVAL SHALL HAVE A | | STATEWIDE PRODUCT APPROVAL COVER SHEET. | | ALTERNATIVELY, AN APPLICATION FOR LOCAL | | PRODUCT APPROVAL WILL BE REQUIRED.THE | | FOLLOWING COMMENTS APPLY TO THE | | SUBMITTED PRODUCT APPROVALS: | | (A)MODIFIED BITUMEN ROOFING SYSTEM. | | SUBMITTAL OF THE ENHANCED FASTENER | | DENSITY CALCULATIONS IS NOTED.THE | | CONTENT IS OK BUT THE SIGNATURES ARE | | PHOTOCOPIED AND EACH COPY MUST HAVE THE | | AN ORIGINAL 'WET' SIGNATURE OF DONALD | | FLOOD, P.E.ALSO, PER THE 8/25/06 | | MEETING WITH ARTURO PENA, THREE COPIES | | OF THE REFERENCED JOHNS MANVILLE PRODUCT | | APPROVAL NOA# 04-0401.04 WILL BE | | SUBMITTED.THE PRODUCT APPROVAL MUST BE | | MARKED OR SEPARATED TO SHOW WHICH SYSTEM | | IS PROPOSED (THE CALCULATIONS REFERENCE | | THE SYSTEM ON PAGE 30). | | (B)ROOF TILE:SUBMITTAL OF THE | | ALTUSA 'S' PRODUCT APPROVAL NOA# | | 05-0901.06 IS NOTED.ALSO, SUBMITTAL OF | | THE TILE ATTACHMENT CALCULATIONS IS | | NOTED.THE CONTENT OF THE CALCULATION | | PACKAGE IS OK BUT THE SIGNATURES ARE | | PHOTOCOPIED AND EACH COPY MUST HAVE THE | | ORIGINAL 'WET' SIGNATURE OF DONALD | | FLOOD, P.E. | | (C)EXTERIOR DOORS. SEE COMMENT 6(J) | | THRU 6(N). | | (D)STOREFRONT.THE SUBMITTED ARCH | | ALUMINUM SERIES L-300 IMPACT WALL | | STOREFRONT PRODUCT NOA# 01-0619.01 | | STATES A MAXIMUM UNIT HEIGHT OF 144". | | THIS IS NOT SUFFICIENT TO COVER THE SIZE | | OF STOREFRONT SPECIFIED ON SHEETS A-4.1 | | AND A-4.2 OF THE PLANS.PER THE 8/25/06 | | MEETING WITH GLASS ENGINEERING INC., | | STRUCTURAL MULLIONS WILL BE INCORPORATED | | AND SHEETS A-4.1 AND A-4.2 WILL BE | | AMENDED TO REFLECT THIS AND CALL FOR | | SHOP DRAWINGS 'BY OTHERS' TO BE | | SUBMITTED FOR REVIEW. | | (E)SLIDING GLASS DOORS.THE | | SUBMITTED MIAMI WALL SYSTEMS SERIES 100 | | SLIDING GLASS DOOR PRODUCT APPROVAL NOA# | | 01-0123.02 HAS A MAXIMUM DOOR HEIGHT OF | | 102".DOOR SCHEDULE SHEET A-4.1 SHOWS A | | PROPOSED SLIDING GLASS DOOR HEIGHT OF | | 10'-0" WHICH EXCEEDS THE MAXIMUM COVERED | | BY THE PRODUCT APPROVAL.PER THE | | 8/25/06 MEETING WITH GLASS ENGINEERING | | INC., THEY WILL BE APPLYING FOR A ONE | | TIME PRODUCT APPROVAL FOR THE 10'-0" | | DOOR AND WILL PROVIDE THREE COPIES OF | | THE APPLICATION FORM/LETTER SO THAT A | | PROVISO MAY BE GIVEN. | | (F)SINGLE HUNG WINDOW.THE | | SUBMITTED MIAMI WALL SERIES 122 ALUMINUM | | SINGLE HUNG WINDOW PRODUCT APPROVAL NOA# | | 03-1008.03 HAS A MAXIMUM HEIGHT OF 72". | | WINDOW SCHEDULE SHEET A-4.2 SHOWS SINGLE | | HUNG WINDOW HEIGHTS UP TO 9'-4" WHICH | | EXCEED THE MAXIMUM COVERED BY THE | | PRODUCT APPROVAL.PER THE 8/25/06 | | MEETING WITH GLASS ENGINEERING INC., | | THEY WILL BE APPLYING FOR A ONE TIME | | PRODUCT APPROVAL FOR THE 9'-4" HIGH | | WINDOW AND WILL PROVIDE THREE COPIES OF | | THE APPLICATION FORM/LETTER SO THAT A | | PROVISO MAY BE GIVEN. | | (G) FIXED WINDOW.IT IS NOTED THAT | | FIXED WINDOW COVERED BY THE SUBMITTED | | MIAMI WALL PRODUCT APPROVAL NOA# | | 04-0322.09 WILL BE USED UNDER THE SINGLE | | HUNG WINDOWS TO FORM THE 'SINGLE HUNG | | WINDOW OVER FIXED WINDOW' CONFIGURATION. | | AN APPROPRIATE MULLION PRODUCT APPROVAL | | MUST BE SUBMITTED OR SHEET A-4.2 SHALL | | BE AMENDED TO SHOW THAT A STRUCTURAL | | MULLION IS TO BE INCORPORATED AND THAT | | SHOP DRAWINGS WILL BE SUBMITTED 'BY | | OTHERS' FOR REVIEW. | | (H)MULLIONS. SEE COMMENTS (D) & (G). | | (I)IF THERE IS A STATEWIDE PRODUCT | | APPROVAL THAT COVERS ANY OF THE | | SUBMITTED PRODUCT APPROVAL NOA'S, THE | | STATEWIDE PRODUCT APPROVAL COVER SHEET | | MUST BE ATTACHED TO THE FRONT OF THE | | NOA. | | (J)STOREFRONT DOOR.PER THE 8/25/06 | | MEETING WITH GLASS ENGINEERING INC. THE | | 9'-0" STOREFRONT DOOR IS NOT AVAILABLE | | SO SHEET A-4.1 MUST BE AMENDED TO REDUCE | | THE HEIGHT OF THE STOREFRONT DOORS. | | (K)LOUVER DOOR.BOTH THE COVER | | SHEET AND PAGE 41 OF THE SUBMITTED | | INTERTEK TESTING SERVICES REPORT# | | 3080611 STATE THAT THE MAXIMUM DESIGN | | PRESSURE FOR THE LOUVER DOOR IS +60 PSF | | AND -60 PSF.THE MINIMUM REQUIRED | | DESIGN PRESSURE REQUIRED FOR THIS | | PROJECT IS +70 PSF AND - 70 PSF.SUBMIT | | AN ALTERNATIVE PRODUCT APPROVAL. | | (L)SINGLE HOLLOW METAL DOOR.THE | | SUBMITTED CURRIES PRODUCT APPROVAL NOA# | | 01.1102.02 IS FOR A 7'-0" HIGH DOOR. | | SHEET A-4.1 SHOWS DOOR TYPE 10 AS AN | | 8'-0" HIGH DOOR.SUBMIT AN ALTERNATIVE | | PRODUCT APPROVAL. | | (M)DOUBLE HOLLOW METAL DOOR.THE | | SUBMITTED CURRIES PRODUCT APPROVAL NOA# | | 02-0924.04 IS OK BUT TWO OF THE | | AVAILABLE OPTIONS HAVE DESIGN PRESSURES | | WHICH ARE LESS THAN THE MINIMUM +70 PSF | | AND - 70 PSF REQUIRED FOR THIS PROJECT. | | THOSE TWO OPTIONS MUST BE STRUCK FROM | | ALL THREE COPIES OF THE PRODUCT APPROVAL | | THAT ARE SUBMITTED FOR PERMITTING. | | (N)ROLL UP DOOR.THE SUBMITTED | | CORNELL IRON WORKS INC. PRODUCT APPROVAL | | NOA# 03-0925.07 IS HARDLY LEGIBLE (POOR | | COPY) BUT APPEARS TO STATE A MAXIMUM | | DESIGN PRESSURE OF +60 PSF AND -60 PSF. | | THE MINIMUM REQUIRED DESIGN PRESSURE | | REQUIRED FOR THIS PROJECT IS +70 PSF AND | | - 70 PSF.SUBMIT AN ALTERNATIVE PRODUCT | | APPROVAL. | | | | 16) FBC 411.2.3VEHICLE IMPACT | | WALLS/GUARDRAILS. CONTRARY TO THE | | COMMENT RESPONSE DATED 7/28/06, WALL | | TYPE W-30, SHOWN AT THE NORTH WALL OF | | THE PARKING GARAGE ON 2ND FLOOR FRAMING | | PLAN SHEET S-1.01, SEPARATES AREAS OF | | DIFFERENT FLOOR SLAB LEVEL.ON ONE SIDE | | IS THE 2ND FLOOR PARKING AND ON THE | | OTHER SIDE IS THE VOID ABOVE THE 1ST | | FLOOR COMMMERCIAL SPACE TO THE NORTH. | | IN FACT SHEET S-1.01 STATES "SLAB EDGE" | | AT THIS LOCATION.WALL TYPE W-30 IS A | | PARKING IMPACT WALL AND SHOULD BE SHOWN | | AS SUCH ON THE SHEET S-4-4.1 WALL | | SCHEDULE. | | | | 28) TO EXPEDITE REVIEW OF A RESUBMITTAL | | WHICH REQUIRES NEW PLANS IN ORDER TO | | ADDRESS THE ABOVE COMMENTS, THE OLD | | SHEETS SHALL BE REMOVED AND THE NEW | | SHEETS INSERTED.ONE COPY OF EACH OLD | | SHEET SHOULD BE STAPLED/CLIPPED TO THE | | REMAINING OLD SHEETS, TO FORM A SET OF | | 'OLD/VOID SHEETS', FOR COMPARISON OF | | REVISIONS WHEN REVIEWING THE RESUBMITTED | | PLANS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | TELEPHONE: (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-07-23 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-07-23 |
Time |
23:41 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-07-23 |
Time |
19:04 |
Sent To |
|
|
Notes |
2006-07-23 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | ARE NUMBERED AS PER THE BUILDING PLAN | | REVIEW OF 2/10/06: | | | | 1) 713.13 F.S. NOTICE OF COMMENCEMENT. | | THE RESPONSE IS NOTED.INFORMATIVE: A | | NOTICE OF COMMENCEMENT SHALL BE RECORDED | | AT PALM BEACH COUNTY COURTHOUSE AND A | | COPY SUBMITTED TO THIS OFFICE BEFORE A | | PERMIT CAN BE ISSUED. BLANK FORMS ARE | | AVAILABLE FROM THIS | | OFFICE. | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | 90 DAYS OF RECORDING. | | | | 2) IMPACT FEES. THE RESPONSE IS NOTED. | | INFORMATIVE: THE PLANS SHALL BE TAKEN | | TO PALM BEACH COUNTY BUILDING DEPARTMENT | | FOR IMPACT FEE ASSESSMENT. THEY SHALL BE | | STAMPED AT THAT OFFICE AND A COPY OF THE | | PAID RECEIPT SUBMITTED TO THE CITY OF | | WEST PALM BEACH DEPT OF CONSTRUCTION | | SERVICES BEFORE A PERMIT CAN BE ISSUED. | | | | 5) FBC 13-103.1.1.1 ENERGY CODE | | COMPLIANCE FORMS.EACH COPY OF THE | | SUBMITTED ENERGY CODE COMPLIANCE FORM | | SHALL BE COMPLETED SO THAT SHEET 1 SHOWS | | THE OWNER, PROJECT ADDRESS, ZIP CODE, | | PERMIT NUMBER AND SHEET 2 MUST | | INCORPORATE THE ARCHITECTURAL FIRM | | CERTIFICATE OF AUTHORIZATION NUMBER IN | | THE SPACE PROVIDED. | | | | 6) PRODUCT APPROVALS.SUBMITTAL OF | | PRODUCT APPROVALS IS NOTED. EACH PRODUCT | | APPROVAL SHALL HAVE A STATEWIDE PRODUCT | | APPROVAL COVER SHEET.ALTERNATIVELY, AN | | APPLICATION FOR LOCAL PRODUCT APPROVAL | | WILL BE REQUIRED.THE FOLLOWING | | COMMENTS APPLY TO THE SUBMITTED PRODUCT | | APPROVALS: | | (A)MODIFIED BITUMEN ROOFING SYSTEM. | | SUBMITTAL OF GAF RUBERIOD ROOF SYSTEM | | PRODUCT APPROVAL NOA# 03-0501.03 IS | | NOTED.PAGES 9 THROUGH 30 SHALL BE | | MARKED TO SHOW WHICH ONE OUT OF THE MANY | | INCLUDED SYSTEM TYPES IS PROPOSED.THE | | CHOSEN SYSTEM MUST BE APPROPRIATE FOR | | THE CONRETE DECK SPECIFIED ON SHEET | | A-8.3.ALSO, IF ENHANCED FASTENER | | DENSITY IS REQUIRED TO IN ORDER TO MEET | | THE UPLIFT PRESSURES FOR ZONES 2 AND 3 | | (PER RWDI WIND LOAD STUDY REPORT), | | CALCULATIONS MUST BE SUBMITTED IN | | COMPLIANCE WITH ROOFING APPLICATION | | STANDARD RAS 117. | | (B)ROOF TILE:THE SUBMITTED PRODUCT | | APPROVAL NOA# 01-0703.04 IS FOR ENTERA | | ESTATE 'S' TILE.THIS DOES NOT | | CORRELATE WITH ROOF DETAIL SHEET A-8.3 | | WHICH SPECIFIES ALTUSA SANTA FE 'S' | | TILE. THE PERMIT DOCUMENTS SHALL NOT | | INCORPORATE CONFLICTING PROPOSALS. | | ALSO, THE RWDI WIND LOAD STUDY REPORT | | STATES UPLIFT PRESSURES OF UP TO 170 PSF | | ON THE SLOPED ROOF.SUBMIT TILE | | ATTACHMENT CALCULATIONS TO JUSTIFY THE | | USE OF THE PROPOSED TILE AND ATTACHMENT | | METHOD FOR PRESSURES UPTO 170 PSF. | | (C)EXTERIOR DOORS.SUBMITTAL OF | | PRODUCT APPROVAL FOR GLAZED ALUMINUM | | OUTSWING DOORS IS NOTED, BUT NO EXTERIOR | | DOOR PRODUCT APPROVALS WERE SUBMITTED. | | SUBMIT PRODUCT APPROVALS FOR THE | | STOREFRONT DOORS (9'-0" TALL), LOUVER | | DOORS, HOLLOW METAL DOORS AND ROLL-UP | | DOORS. | | (D)STOREFRONT.THE SUBMITTED ARCH | | ALUMINUM SERIES L-300 IMPACT WALL | | STOREFRONT PRODUCT NOA# 01-0619.01 | | STATES A MAXIMUM UNIT HEIGHT OF 144". | | THIS IS NOT SUFFICIENT TO COVER THE SIZE | | OF STOREFRONT SPECIFIED ON SHEETS A-4.1 | | AND A-4.2 OF THE PLANS.SUBMIT AN | | ALTERNATIVE PRODUCT APPROVAL. | | (E)SLIDING GLASS DOORS.THE | | SUBMITTED MIAMI WALL SYSTEMS SERIES 100 | | SLIDING GLASS DOOR PRODUCT APPROVAL NOA# | | 01-0123.02 HAS A MAXIMUM DESIGN PRESSURE | | RATING OF 100 PSF (BOTH POSITIVE AND | | NEGATIVE) AND A MAXIMUM DOOR HEIGHT OF | | 102".PER THE SUBMITTED RWDI WIND LOAD | | STUDY REPORT THE SLIDING GLASS DOORS | | WILL BE SUBJECT TO NEGATIVE WIND | | PRESSURE OF -110 PSF WHICH EXCEEDS THAT | | ALLOWED BY THE PRODUCT APPROVAL.ALSO, | | DOOR SCHEDULE SHEET A-4.1 SHOWS A | | PROPOSED SLIDING GLASS DOOR HEIGHT OF | | 10'-0" WHICH EXCEEDS THE MAXIMUM COVERED | | BY THE PRODUCT APPROVAL.SUBMIT AN | | ALTERNATIVE PRODUCT APPROVAL. | | (F)SINGLE HUNG WINDOW.THE | | SUBMITTED MIAMI WALL SERIES 122 ALUMINUM | | SINGLE HUNG WINDOW PRODUCT APPROVAL NOA# | | 03-1008.03 HAS A MAXIMUM HEIGHT OF 72". | | WINDOW SCHEDULE SHEET A-4.2 SHOWS SINGLE | | HUNG WINDOW HEIGHTS UP TO 9'-4" WHICH | | EXCEED THE MAXIMUM COVERED BY THE | | PRODUCT APPROVAL.ALSO, IS IT THE | | INTENTION TO INSTALL THIS WINDOW ON TOP | | OF THE FIXED WINDOW TO FORM THE 'SINGLE | | HUNG WINDOW OVER FIXED WINDOW' | | CONFIGURATION THAT IS SHOWN ON THE | | WINDOW SCHEDULE SHEET? SUBMIT AN | | ALTERNATIVE PRODUCT APPROVAL THAT COVERS | | WINDOWS OF THE REQUIRED HEIGHT. | | (G) FIXED WINDOW.SUBMITTAL OF THE | | MIAMI WALL SERIES 122 ALUMINUM FIXED | | WINDOW PRODUCT APPROVAL NOA# 04-0322.09 | | IS NOTED.FROM THE ELEVATIONS SHOWN ON | | WINDOW SCHEDULE SHEET A-4.2, IT IS NOT | | CLEAR WHERE THIS PRODUCT IS TO BE USED. | | PLEASE CLARIFY. | | (H)MULLIONS.IN ADDRESSING THE | | ABOVE COMMENTS PLEASE NOTE THAT SOME OF | | THE WINDOW CONFIGURATION MAY REQUIRE | | MULLIONS.IF SO PLEASE SUBMIT PRODUCT | | APPROVAL FOR APPROPRIATE MULLIONS. | | (I)IF THERE IS A STATEWIDE PRODUCT | | APPROVAL THAT COVERS ANY OF THE | | SUBMITTED PRODUCT APPROVAL NOA'S, THE | | STATEWIDE PRODUCT APPROVAL COVER SHEET | | MUST BE ATTACHED TO THE FRONT OF THE | | NOA. | | | | 11) FBC* 104.2.1FIRE SEPARATION PLANS. | | RECOMMENDATION:THE INCLUSION OF A | | LEGEND ON SHEET A-2.1.2 IS NOTED. | | HOWEVER, THERE IS STILL SOME AMBIGUITY | | IN THE PLANS.FOR EXAMPLE, ON SHEETS | | A-2.1.4 AND A-2.1.5, THE WALLS ADJACENT | | TO THE BREEZEWAY HAVE NO SHADING BUT | | THEY HAVE A NOTE STATING A 2-HOUR FIRE | | RESISTANCE RATING.THE LIFE SAFETY | | PLANS LS-1 TO LS-5 ARE NOT | | OVER-COMPLICATED.PLEASE CONSIDER USING | | THEM TO CLARIFY THE FIRE RESISTANCE | | RATING OF THE WALLS WITH 'DASHED' LINE | | TYPES AND A CORRESPONDING LEGEND. | | | | 12) FBC 1012.1.29TH FLOOR CLUBROOM. | | THE DOUBLE DOORS FROM THE CLUBROOM TO | | THE CORRIDOR SHALL SWING IN THE | | DIRECTION OF EGRESS FROM THE CLUBROOM. | | AMEND THE PLAN. | | | | 16) FBC 411.2.3VEHICLE IMPACT | | WALLS/GUARDRAILS.IT IS NOTED THAT | | SHEETS A-2.7.1 TO A-2.7.4 NOW REFER TO | | THE STRUCTURAL PLANS.WALL TYPE W-30 IS | | SHOWN AT THE NORTH WALL OF THE PARKING | | GARAGE, ON 2ND FLOOR FRAMING PLAN SHEET | | S-1.01.PLEASE CONFIRM THAT WALL TYPE | | W-30 IS A PARKING IMPACT WALL, ASTHE | | WALL SCHEDUKE ON SHEET S-4.1, DOES NOT | | STATE THAT IT IS. | | | | 20) FBC 2603.6.4DYPLAST MOLDINGS, | | SHEET A-6.9.THIS COMMENT HAS NOT BEEN | | PROPERLY ADDRESSED.CONTRARY TO THE | | COMMENT RESPONSE SHEETT, NO DYPLAST | | PRODUCT DATA WAS SUBMITTED.THE | | SUBMITTED URETHANE TECHNOLOGIES TEST | | REPORT# 542317 IS FOR UTD FR SPRAY COAT. | | IN ANY EVENT, THE REPORT SHOWS A FLAME | | SPREAD INDEX OF 30.FBC 2603.6.4 | | REQUIRES AFLAME SPREAD INDEX OF 25 OR | | LESS.PLEASE PROVIDE | | MANUFACTURER'S SPECIFICATION FOR THE | | FLAME SPREAD AND COMBUSTIBILITY OF THE | | DYPLAST MOLDINGS. | | | | 26) FBC 11-4.1.3SHEETS A-2.1.2 AND | | A-2.1.3 NOW SHOW A 1-3/4" SLAB RECESS. | | THE NOTES REFER TO ID DRAWINGS BUT NO ID | | PLANS WERE SUBMITTED.PLEASE CLARIFY | | THE PROPOSED FINISHED FLOOR LEVEL TO | | MAINTAIN THE ACCESSIBLE ROUTE THROUGH | | THE BUILDING. | | | | 27)FBC 1015.2 GUARDRAIL HEIGHT.SHEET | | A-7.6, SECTION C AND SHEET A-7.7, | | SECTION C NOW SHOW A LOW WALL DETAIL | | THAT PROVIDES A 'STEP' WHICH WOULD | | REDUCE THE EFFECTIVE HEIGHT OF THE | | GUARDRAIL.A CHAMFERED EDGE SHOULD BE | | INCORPORATED LIKE THAT WHICH WAS | | INDICATED ON SHEET A-3.5, SECTIONS 2 AND | | 3. | | | | 28) TO EXPEDITE REVIEW OF A RESUBMITTAL | | WHICH REQUIRES NEW PLANS IN ORDER TO | | ADDRESS THE ABOVE COMMENTS, THE OLD | | SHEETS SHALL BE REMOVED AND THE NEW | | SHEETS INSERTED.ONE COPY OF EACH OLD | | SHEET SHOULD BE STAPLED/CLIPPED TO THE | | REMAINING OLD SHEETS, TO FORM A SET OF | | 'OLD/VOID SHEETS', FOR COMPARISON OF | | REVISIONS WHEN REVIEWING THE RESUBMITTED | | PLANS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | TELEPHONE: (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-02-20 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-02-20 |
Time |
23:30 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2006-02-10 |
Time |
08:18 |
Sent To |
|
|
Notes |
2006-02-10 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | 1) 713.13 F.S.A NOTICE OF COMMENCEMENT | | SHALL BE RECORDED AT PALM BEACH COUNTY | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | BLANK FORMS ARE AVAILABLE FROM THIS | | OFFICE. | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | 90 DAYS OF RECORDING. | | | | 2) IMPACT FEES. THE PLANS SHALL BE TAKEN | | TO PALM BEACH COUNTY BUILDING DEPARTMENT | | FOR IMPACT FEE ASSESSMENT. THEY SHALL BE | | STAMPED AT THAT OFFICE AND A COPY OF THE | | PAID RECEIPT SUBMITTED TO THE CITY OF | | WEST PALM BEACH DEPT OF CONSTRUCTION | | SERVICES BEFORE A PERMIT CAN BE ISSUED. | | | | 3) INFORMATIVE: | | A SEPARATE PERMIT APPLICATION WILL BE | | REQUIRED FOR THE SWIMMING POOL AND SPA. | | ALSO, A SEPARATE PERMIT APPLICATION WILL | | BE REQUIRED FOR THE CANVAS CANOPIES AND | | FRAMES IF FULL MATERIAL AND DESIGN | | DETAILS ARE NOT PROVIDED AS PART OF THE | | BUILDING PERMIT PLAN SET. | | | | 4) FBC 1606.1.1WIND TUNNEL TEST | | REPORT.SUBMIT THREE COPIES OF THE RWDI | | REPORT 05-1427, REFERENCED ON SHEET | | S-0.0 UNDER THE GENERAL NOTES | | SUB-HEADING 'WIND LOADS' | | | | 5) FBC 13-103.0ENERGY CODE COMPLIANCE | | SHALL BE DEMONSTRATED BY SUBMITTAL OF | | APPROPRIATE CODE COMPLIANCE FORMS | | | | 6) SUBMIT PRODUCT APPROVALS FOR THE | | FIXED WINDOWS, SINGLE HUNG WINDOWS, | | STOREFRONT, SLIDING GLASS DOORS, | | EXTERIOR DOORS AND BUILT-UP ROOFING, | | CONCRETE TILE AND METAL PANEL ROOF | | COVERINGS. | | NOTE: FL. ADMIN CODE RULE 9B-72 (IN | | EFFECT SINCE OCTOBER 1, 2003) REQUIRES | | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR | | SITE-SPECIFIC PRODUCT APPROVAL.THE | | SUBMITTAL SHOULD INCLUDE THE STATEWIDE | | PRODUCT APPROVAL NUMBER (FL###), | | AVAILABLE FROM THE DEPT OF COMMUNITY | | AFFAIRS PRODUCT APPROVAL WEBSITE WWW. | | FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX | | (IF YOU FIND THAT THE QUOTED WEB PAGE IS | | NO LONGER AVAILABLE, PLEASE INFORM THE | | PLAN REVIEWER) | | | | 7) FBC 503.2.6TYPE II CONSTRUCTION, | | SPECIAL UNLIMITED HEIGHT.THIS SECTION | | ALLOWS THE BUILDING HEIGHT TO EXCEED THE | | 80' LIMIT STATED IN TABLE 600 FOR TYPE | | II CONSTRUCTION, BUT IT REQUIRES THE | | ROOF AND ITS SUPPORTING STRUCTURE TO | | HAVE A FIRE RESISTANCE OF NOT LESS THAN | | 1-1/2 HOURS.THE TABLE ON SHEET A-0.1, | | UNDER GENERAL NOTE 7, STATES THAT THE | | FIRE RESISTANCE OF THE ROOF IS TO BE A | | MINIMUM OF 1 HOUR.AMEND THIS TO 1-1/2 | | HOURS. | | | | 8) FBC 411.4.1FOR AN ENCLOSED PARKING | | GARAGE (GROUP S) OF TYPE II | | CONSTRUCTION, TABLE 500 LIMITS THE | | MAXIMUM NUMBER OF STORIES TO 6.SHEET | | A-0.1, GENERAL NOTE #5, STATES THE THE | | RESIDENTIAL AND PARKING GARAGE | | OCCUPANCIES ARE CONSIDERED MIXED USE. | | ALTHOUGH FBC 303.2 STATES THAT A MIXED | | OCCUPANCY BUILDING IS GOVERNED BY THE | | HEIGHT AND AREA LIMITATIONS OF IT'S | | PRINCIPAL USE (IN THIS CASE | | RESIDENTIAL), IT GOES ON TO STATE THAT | | ACCESSORY OCCUPANCIES SHALL NOT BE | | LOCATED AT A HEIGHT GREATER THAN THAT | | PERMITTED FOR SUCH AN OCCUPANCY GROUP IN | | THE THE TYPE OF CONSTRUCTION BEING USED. | | IN A TYPE II RESIDENTIAL BUILDING, THE | | PARKING GARAGE OCCUPANCY SHALL NOT | | OCCUPY ANY SPACE ABOVE THE SIXTH STORY. | | AMEND THE CONSTRUCTION TYPE. | | | | 9) FBC 11-4.1.2(5)(B)VAN ACCESSIBLE | | PARKING. THE PARKING DATA ON SHEET A-0.1 | | STATES THAT 17 ACCESSIBLE SPACES ARE | | BEING PROVIDED.1 IN EVERY 8 ACCESSIBLE | | SPACES SHALL BE VAN ACCESSIBLE.A | | MINIMUM VERTICAL CLEARANCE OF 98 INCHES | | IS REQUIRED AT SUCH SPACES, AND ALONG AT | | LEAST ONE VEHICLE ACCESS ROUTE TO THE | | SPACE FROM THE SITE ENTRANCE.PLEASE | | ANNOTATE THE PLANS TO DEMONSTRATE | | COMPLIANCE.ALSO, THE NOTE ABOUT | | PARKING GARAGE BARRIER HEIGHT, ON SHEET | | A-2.7.1 IS NOT CLEAR. AMEND THE NOTE TO | | DEMONSTRATE COMPLIANCE WITH THE ABOVE | | REQUIREMENT. | | | | 10) FBC 412.5SMOKE CONTROL.THE PLANS | | SHALL CLEARLY DESCRIBE THE PROVISION OF | | ONE OF THE FORMS OF SMOKE CONTROL LISTED | | IN THE CODE.ANNOTATE THE PLANS. | | | | | | 11) FBC* 104.2.1FIRE SEPARATION PLANS. | | PLEASE ADD CLEAR ANNOTATION TO THE PLANS | | (OR USE LINE TYPES AND A LEGEND) TO | | DEMONSTRATE COMPLIANCE WITH CHAPTER 7, | | FIRE RESISTANT MATERIALS AND | | CONSTRUCTION.THE REFERENCE TO THESE | | REQUIREMENTS ON SHEET A-0.1, GENERAL | | NOTE #5 AND SHEET A-1.1 NOTE #4 IS | | ACKNOWLEDGED, BUT CLEAR DIAGRAMMATIC | | REPRESENTATION IS REQUIRED.FOR | | EXAMPLE, SHEET A-2.1.5 STATES "SHADING | | INDICATES 4 HR FIRE RATED MASONRY WALL & | | COLUMNS" AT THE FPL TRANSFORMER VAULT, | | BUT NO SHADING IS SHOWN.THE WALLS ARE | | SHOWN THE SAME AS THE 2 HR RATED WALLS. | | | | 12) FBC* 104.2.1LIFE SAFETY PLANS.SO | | THAT COMPLIANCE WITH CHAPTER 10, MEANS | | OF EGRESS CAN BE DETERMINED, PLEASE | | SUBMIT 1/8"=1'-0" SCALE PLANS, FOR EACH | | STORY, SHOWING OCCUPANCY COUNTS AND | | DISTANCE TO EXIT FOR THE RESIDENTIAL, | | GARAGE, POOL DECK AND OTHER COMMON | | OCCUPANCY AREAS. | | | | 13) FBC* 104.2.1ROOM DESIGNATIONS, | | SHEET A-1.5.THE OCCUPANCY FOR THE | | ROOMS TO THE NORTH AND WEST OF THE POOL | | HAVE NOT BEEN STATED.AMEND THE PLAN. | | IT IS NOTED THAT THESE ROOMS ARE | | REFERENCED ON SHEETS A-2.4.2 AND A-2.4.5 | | AS FITNESS CENTER AND CLUBROOM UNDER | | SEPARATE PERMIT.FOR CLARITY, A NOTE | | SHOULD BE ADDED TO SHEET A-1.5 ALSO. | | | | 14) FBC 1001.1POOL DECK EGRESS.THE | | EXIT DOOR LEADING TO STAIR #4 IS NOTED, | | BUT THE EXIT DOOR LEADING TO STAIR #3 IS | | SHOWN AS A SINGLE DOOR.THE DOORS WITH | | SCHEDULE REFERENCE NUMBER 50, LEAD FROM | | THE POOL DECK INTO THE 'FITNESS CENTER | | AND CLUBROOM' WHICH DO NOT APPEAR TO | | COMMUNICATE WITH THE EXIT ACCESS | | CORRIDOR.PLEASE CLARIFY THE PROVISION | | OF EXITTING FROM THE POOL DECK AREA. | | SEE THE TWO RELATED COMMENTS ABOVE. | | | | 15) FBC 1003.3.5WIDTH OF EXIT, SHEET | | A-2.1.1.THE EXIT PASSEGEWAY LEADING TO | | THE EXIT DISCHARGE FROM STAIR NO.1 IS | | SHOWN AS REDUCING IN WIDTH FROM 5'-0" TO | | 4'-0".AT NO POINT ALONFG AN EXIT PATH | | MAY THE EXIT WIDTH BE DECREASED. | | | | 16) FBC 411.2.3VEHICLE IMPACT | | WALLS/GUARDRAILS, SHEETS A-2.7.1 TO | | A-2.7.4.ANNOTATE THE PLANS TO | | DEMONSTRATE COMPLIANCE WITH THE | | REQUIREMENT FOR IMPACT GUARDING AT THE | | ENDS OF THE 2ND FLOOR PARKING SPACES | | THAT ARE ADJACENT TO THE VOID OVER THE | | COMMERCIAL TENANT SPACE, AND THE PARKING | | SPACES, ON ALL FLOORS, THAT ARE ADJACENT | | TO THE RAMP, WHERE THE DIFFERENCE IN | | ADJACENT FLOOR ELEVATION IS GREATER THAN | | 1'-0".THE SAME APPLIES TO THE 2ND FOOR | | TO 8TH FLOOR PARKING SPACES ADJACENT TO | | THE EAST EXTERIOR WALL. | | | | 17) FBC 1608.2.1HANDRAIL STRENGTH, | | SHEET A-3.1 STAIR RAILING NOTE #2 IS | | ACKNOWLEDGED.PLEASE ADD A NOTE TO THE | | PLANS TO STATE THAT THE HANDRAILS SHALL | | BE DESIGNED AND CONSTRUCTED FOR A | | CONCENTRATED LOAD OF 200 LB AND A LINE | | LOAD OF 50 PLF.THESE LOADS SHALL NOT | | BE APPLIED SIMULTANEOUSLY BUT SHALL BE | | APPLIED INDIVIDUALLY AT ANY POINT, AND | | IN ANY DIRECTION, TO PRODUCE MAXIMUM | | STRESS IN EACH OF THE COMPONENTS OR | | SUPPORTS.SEE THE COMMENT BELOW, ALSO, | | WITH RESPECT TO THE GUARDING | | REQUIREMENT FOR THE STAIRS. | | | | 18) FBC 1608.2.2GUARDRAIL STRENGTH, | | SHEET A-3.5.ANNOTATE THE PLAN TO STATE | | THAT THE BALCONY RAILINGS (GUARDRAILS) | | SHALL BE DESIGNED AND CONSTRUCTED FOR A | | CONCENTRATED LOAD OF 200 LB APPLIED IN | | ANY DIRECTION AT THE TOP OF THE | | GUARDRAIL, A CONCENTRATED HORIZONTAL | | LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA | | AT ANY POINT, AND A LINE LOAD OF 50 PLF | | APPLIED HORIZONTALLY AT THE REQUIRED | | GUARDRAIL HEIGHT WITH A SIMULTANEOUS | | LINE LOAD OF 100 PLF APPLIED VERTICALLY | | DOWNWARD ON THE TOP OF THE GUARDRAIL. | | THESE LOADS SHALL NOT BE APPLIED | | SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT | | SHALL BE APPLIED INDIVIDUALLY TO PRODUCE | | MAXIMUM STRESS IN EACH OF THE COMPONENTS | | OR SUPPORTS. | | | | 19) FBC 1015.2GUARDRAIL HEIGHT, SHEET | | A-3.5, SECTIONS 2 AND 3.CHAMFER/SLOPE | | THE CONCRETE CAP PROFILE INWARD SO THAT | | IT DOES NOT PROVIDE A 'STEP' WHICH WOULD | | REDUCE THE EFFECTIVE HEIGHT OF THE | | GUARDRAIL. | | | | 20) FBC* 104.2.1DYPLAST MOLDINGS, | | SHEET A-6.9.PLEASE PROVIDE | | MANUFACTURER'S SPECIFICATION FOR THE | | FLAME SPREAD AND COMBUSTIBILITY OF THE | | DYPLAST MOLDINGS. | | | | 21) FBC 1606.1SOFFITS AND CEILINGS, | | SHEETS A-7.15 AND A-7.16.THE | | BREEZEWAY, ARCADE AND COVERED ENTRY | | DRIVE CEILINGS SHALL BE DESIGNED TO | | RESIST THE WIND PRESSURES FOR COMPONENTS | | AND CLADDING. | | | | 22) FAIR HOUSING ACT, SHEET A-0.1.ALL | | OF THE DWELLING UNITS ARE 'COVERED | | UNITS'. IT IS NOTED THAT THERE ARE NO | | TYPICAL PLANS FOR THE UNIT TYPES TO SHOW | | HOW THEY WILL MEET THE REQUIREMENTS OF | | THE FAIR HOUSING ACT.SUBMIT DETAILS TO | | DEMONSTRATE COMPLIANCE. | | | | 23) FBC 2103MASONRY WALL DETAILS, | | SHEET S0.03.THE VERTICAL REINFORCEMENT | | COLUMN OF THE TABLE ON THE 'TYPICAL | | EXTERIOR REINFORCED MASONRY WALL | | DETAILS' IS INCOMPLETE. | | | | 24) FBC* 104.2.1IT IS NOTED THAT THE | | SUBMITTED PLANS ARE NOT COMPLETE. | | ADDITIONAL COMMENTS MAY ARISE WHEN THE | | REQUIRED PLANS ARE SUBMITTED. | | | | 25) TO EXPEDITE REVIEW OF A RESUBMITTAL | | WHICH REQUIRES NEW PLANS IN ORDER TO | | ADDRESS THE ABOVE COMMENTS, THE OLD | | SHEETS SHALL BE REMOVED AND THE NEW | | SHEETS INSERTED.ONE COPY OF EACH OLD | | SHEET SHOULD BE STAPLED/CLIPPED TO THE | | REMAINING OLD SHEETS, TO FORM A SET OF | | 'OLD/VOID SHEETS', FOR COMPARISON OF | | REVISIONS WHEN REVIEWING THE RESUBMITTED | | PLANS. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | TELEPHONE: (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
27 |
Status |
P |
Date |
2008-04-07 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2008-04-07 |
Time |
15:04 |
Rev Time |
0.45 |
Received By |
jleahy |
Date |
2008-04-07 |
Time |
15:04 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
26 |
Status |
F |
Date |
2008-03-26 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2008-03-26 |
Time |
16:02 |
Rev Time |
2.30 |
Received By |
jleahy |
Date |
2008-03-26 |
Time |
15:58 |
Sent To |
|
|
Notes |
2008-03-26 16:00:16 | I WOULD LIKE A LIST IN SEQUENCE OF WHAT IS TO BE TURNED | | ON AND WHEN. | | | | PLEASE LIST SYSTEM BY SYSTEM TO BE TURNED ON.EX. | | ELEVATORS, A/C PUMPS, COMMON AREA POWER, GARAGE ECT | | ECT. | | | | THANKS | | | | JAKE |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
25 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
24 |
Status |
P |
Date |
2008-02-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-02-09 |
Time |
08:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-02-09 |
Time |
08:11 |
Sent To |
|
|
Notes |
2008-02-11 08:12:18 | REVISIONS OK PENDING MECHANICAL, FIRE AND BUILDING | | OFFICIAL RULING ON FUEL TANK. | | SHEETS E-2, E-19A, AND E-20 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
23 |
Status |
P |
Date |
2008-02-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-02-05 |
Time |
19:26 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-02-05 |
Time |
19:26 |
Sent To |
PC |
|
Notes |
2008-02-05 19:26:40 | REV #27 FOR E-6 . |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
22 |
Status |
P |
Date |
2007-12-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-12-24 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-12-24 |
Time |
15:05 |
Sent To |
B |
|
Notes |
2007-12-24 15:06:13 | SAUNA SUBMITTALS. | | | | UNIT SHOWS LISTING PER NRTL. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
21 |
Status |
P |
Date |
2007-12-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-12-24 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-12-24 |
Time |
14:55 |
Sent To |
PC |
|
Notes |
2007-12-24 14:56:07 | REVS SUBMITTED 12/11 | | SHEETS E6, 7, 22, 24 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
20 |
Status |
P |
Date |
2007-12-24 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-12-24 |
Time |
14:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-12-24 |
Time |
14:45 |
Sent To |
PC |
|
Notes |
2007-12-24 14:48:03 | REV'S WHICH WERE ON HOLD FROM 11/2 WERE REVIEWED. | | SHEET 19A WAS NOT STAMPED DUE TO COMMENTS FROM MECH FOR | | LOCATION OF FUEL. | | | | SHEETS 18,22 AND 24 OK |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
19 |
Status |
F |
Date |
2007-11-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-11-29 |
Time |
15:29 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-11-29 |
Time |
15:29 |
Sent To |
|
|
Notes |
2007-11-29 15:29:30 | ** DENIED REVISION FOR E-19A. SUBMITTED 11/7 | | | | 1) NOTE: PLEASE SEE MECHANICAL REVIEW DATE 11/20/07 AS | | TANKS SHOWN ON ELECTRICAL PLANS IS NOT PERMITTED. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
18 |
Status |
P |
Date |
2007-11-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-11-02 |
Time |
14:33 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-11-02 |
Time |
14:33 |
Sent To |
FIRE |
|
Notes |
2007-11-02 14:35:07 | REV FROM 10/22, | | SHEETS E-1- E-6 FOR ACCESS CONTROLS. ELECTRICAL IS OK, | | A SEPARATE LOW VOLTAGE PERMIT IS REQUIRED FOR LOW | | VOLTAGE SYSTEMS. | | PLANS SENT TO FIRE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
17 |
Status |
P |
Date |
2007-10-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-10-30 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-10-30 |
Time |
11:43 |
Sent To |
|
|
Notes |
2007-10-30 11:44:36 | TEMP PASSED STATUS AS MECH, AND FIRE REVIEW NEEDS TO BE | | DONE FOR NEW FUEL TANK. | | WILL NEED TO KEEP ELECTRICAL SHEETS IF OK AND ONCE ALL | | REVIEWS ARE DONE. | | PREVIOUS REVISION IS STILL ON HOLD. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
16 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
|
Time |
13:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-10-17 |
Time |
13:06 |
Sent To |
PC |
|
Notes |
2007-10-17 13:14:26 | SHEETS E-18-19 OUTFRONT UNDER "M" ON HOLD UNTIL FUEL | | AND GENERATOR REVISIONS CAN BE VERIFIED FOR HB 7121 ON | | OTHER REVISIONS. | | THE OTHER REVISIONS SUBMITTED AT THE SAME TIME AHVE NOT | | BEEN REVIEWED AS OF YET. | | PLANS WILL BE UNDER "M" LARGE BINS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
15 |
Status |
F |
Date |
2007-10-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-10-07 |
Time |
09:58 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-10-07 |
Time |
09:58 |
Sent To |
PC |
|
Notes |
2007-10-07 09:59:51 | REV FOR E-8, 23 AND 24, LIGHTING REVISIONS. | | | | COMMENTS FROM6/9/07 AND 6/29/07 STILL NEED TO BE | | ADDRESSED. | | EACH REVIEW STOPWILL REMAIN IN A *F* STATUS EVEN IF | | SOME SHEETS ARE OK AND PASSED UNTIL HB 7121 IS | | ADDRESSED. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
14 |
Status |
F |
Date |
2007-08-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-26 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-26 |
Time |
15:24 |
Sent To |
PC |
|
Notes |
2007-08-26 16:17:13 | REV FOR SHEETS E6 AND 24 ARE OK AND STAMPED. | | | | | | COMMENTS FROM6/9/07 AND 6/29/07 NEED TO BE | | ADDRESSED. | | EACH REVIEW STOPWILL REMAIN IN A *F* STATUS EVEN IF | | SOME SHEETS ARE OK AND PASSED UNTIL HB 7121 IS | | ADDRESSED. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
13 |
Status |
F |
Date |
2007-08-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-26 |
Time |
16:08 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-26 |
Time |
15:24 |
Sent To |
PC |
|
Notes |
2007-08-26 16:09:57 | REV'S FOR E, 2,3,4,5,6,7,8,16,20,21,22,23 AND 24. | | STAMPED OK. | | | | | | | | SHEETS E18, AND 19 WILL NOT BE REVIEWED AND STAMPED | | UNTIL COMMENTS FROM 6/9/07 AND 6/29/07 ARE ADDRESSED. | | EACH REVIEW STOP WILL REMAIN IN A *F* STATUS EVEN IF | | SOME SHEETS ARE OK AND PASSED. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
12 |
Status |
F |
Date |
2007-06-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-06-29 |
Time |
08:17 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-06-29 |
Time |
07:33 |
Sent To |
PC |
|
Notes |
2007-06-29 08:17:40 | | | | | *** UNSAT *** | | | | 1) NOTE: PLEASE SEE THE NOTES WHICH WERE GIVEN ON | | 6/9/07 WITH RESPECT TO THE NEW FLORIDA LEGISLATIVE | | REQUIREMENTS FOR BACK UP POWER. PLEASE KNOW THAT NO | | FURTHER REVISIONS WILL BE GRANTED FOR THE ELECTRICAL | | SERVICE RISER OR REVISIONS WHICH AFFECT THE SERVICE, | | GENERATOR TO THE BUILDING UNTIL THIS NOTE IS | | ADDRESSED. | | PLEASE SEE THE NOTE BELOW WHICH IS COPIED FROM THE | | REVIEW OF 6/9/07 | | | | ** | | 1) NOTE: PLEASE SEE THE NEW FLORIDA STATE STATUTES WITH | | RESPECT TO THE NEW HOUSE BILL 7121 WHICH WAS SIGNED | | INTO LAW JULY OF 07. | | PLEASE SEE THERE ARE SEVERAL STATUTES WHICH WERE | | AFFECTED. PLEASE SEE THAT AN INDUSTRY BULLETIN IS BEING | | PLACED IN WITH THE REVIEW NOTES AS ADDITIONAL | | INFORMATION. | | *ONCE THIS INFORMATION IS READ AND STATUTES REVIEWED, | | PLEASE PROVIDE ALL INFORMATION AS REQUIRED ON PLANS AND | | DOCUMENTATION FOR REVIEW. | | PLEASE KNOW THAT SOME OF THIS INFORMATION WILL ALSO BE | | NEEDED BY THE FIRE MARSHAL, STATE BOARD FOR ELEVATORS | | ETC. | | ** | | | | ** PLEASE SEE THE REVISIONS ON SHEETS E5,10, 11, 21 AND | | 22 WERE OK AND STAMPED. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
11 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-06-09 |
Time |
16:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-06-09 |
Time |
14:28 |
Sent To |
FIRE |
|
Notes |
2007-06-09 16:38:24 | REVISIONSSUBMITTED 5/17/07 OK, STAMPED FOR ELECTRICAL | | AND ROUTED TO FIRE FOR REVIEW. | | | | SHEETS E,1,2,3,4,5,6,7,8,9,10,11,12,13,23 AND 24. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
10 |
Status |
F |
Date |
2007-06-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-06-09 |
Time |
15:27 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-06-09 |
Time |
14:28 |
Sent To |
|
|
Notes |
2007-06-09 15:28:34 | ** THIS REVIEW STOP WILL BE PLACED AS *FAILED* EVEN AS | | SOME SHEETS WERE OK. | | | | ** REVIEW OF REVISIONS SUBMITTED 4/30/07 | | | | | | ** SEE NOTES BELOW AS SOME SHEETS IN REVISIONS | | SUBMITTED 4/30/07 ARE VOIDED/UNSAT/OK* | | | | ** PLEASE SEE SHEETS E-5,6,8,23 AND 24 WERE VOIDED AS | | THESE SAME SHEETS HAVE ALREADY BEEN SUBMITTED WITH THE | | SAME REVISIONS AND NEW REVISIONS ON MAY 17, 2007. AS | | THESE SHEETS CONTAIN THE SAME INFORMATION THEY WERE | | VOIDED IN SETS. | | | | ** PLEASE SEE SHEET E-18 WAS FAILED, NOTES BELOW WITH | | RESPECT TO NEW FLORIDA STATUTES AND HIGH-RISE | | RESIDENTIAL BUILDINGS. | | | | ** PLEASE SEE SHEETS E-14, 20,21 AND 22 STAMPED OK. | | | | 1) NOTE: PLEASE SEE THE NEW FLORIDA STATE STATUTES WITH | | RESPECT TO THE NEW HOUSE BILL 7121 WHICH WAS SIGNED | | INTO LAW JULY OF 07. | | PLEASE SEE THERE ARE SEVERAL STATUTES WHICH WERE | | AFFECTED. PLEASE SEE THAT AN INDUSTRY BULLETIN IS BEING | | PLACED IN WITH THE REVIEW NOTES AS ADDITIONAL | | INFORMATION. | | *ONCE THIS INFORMATION IS READ AND STATUTES REVIEWED, | | PLEASE PROVIDE ALL INFORMATION AS REQUIRED ON PLANS AND | | DOCUMENTATION FOR REVIEW. | | PLEASE KNOW THAT SOME OF THIS INFORMATION WILL ALSO BE | | NEEDED BY THE FIRE MARSHAL, STATE BOARD FOR ELEVATORS | | ETC. | | | | ** PLEASE SUBMIT THE ABOVE FOR REVIEW, IF THERE ARE ANY | | QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING THIS | | OFFICE OR REVIEWER. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
9 |
Status |
P |
Date |
2007-03-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-03-22 |
Time |
07:10 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-03-21 |
Time |
19:56 |
Sent To |
FIRE |
|
Notes |
2007-03-22 07:11:42 | REV FOR PAGE E-2, OK FOR ELECTRICAL REVIEW. | | SENT TO FIRE |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
N |
Date |
2007-01-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-13 |
Time |
15:22 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-01-13 |
Time |
15:22 |
Sent To |
|
|
Notes |
2007-01-13 15:26:50 | REVS , ARE ARCHITECTURAL WHICH ARE DATED SUBMITTED | | 12/18, | | PREVIOUS ELEC REV SUBMITTED SAME DATE DONE SEPARATELY/ |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2006-12-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-12-31 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-12-31 |
Time |
12:11 |
Sent To |
PC |
|
Notes |
2006-12-31 13:29:12 | ** RELDINED ** | | | | | | LV ACESS CONTROL SYSTEM TO BE UNDER A SEPARATE PERMIT , | | INCLUDING SUBMITTING ALL SPECS ON CONTROL /DOOR | | CLOSURE/ CARD READER DEVICES TO BE INSTALLED. THIS WILL | | BE REVIEWED BY FIRE AND ELEC. ANY SYSTEM/DEVICES SHALL | | NOT IMPEDE WITH THE MENAS OF EGRESS IN ANY FASHION | | UNDER NORMAL OR EMERGENCY CONDITIONS. LS 101 7.2.1.5.1 | | | | ** REVISION FOR ADDITION OF PANEL LE, SOME OTHER MINOR | | ITEMS INCLUDING NEW ELECTRICLA IN GYM AREA. | | | | SHEETS E-5,-,18,19A,20,21,22 AND 24. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
P |
Date |
2006-12-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-12-31 |
Time |
12:07 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-12-31 |
Time |
10:28 |
Sent To |
PC |
|
Notes |
2006-12-31 12:10:59 | REVISONS DATED 10/16/06FROM ELECTRICLA ENGINEER FOR | | THE FOLLOWING SHEETS. | | MOST SHEETS FOR VALUE ENGINEERING OF FEEDERSFROM | | COPPER TO ALUMINUM. REVISED FEEDERS ON RISER AND PANEL | | SCHEDULES | | GATE CONTROLS, | | DUCT DETECTOR, J-BOXES IN UNITS, AND SPARE CONDUITS AND | | OTHER MINOR MISC ITEMS. | | | | SHEETS | | E-2,9,10,11,12,13,17, 18,20,21,AND 22 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2006-11-05 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-11-05 |
Time |
08:46 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-11-05 |
Time |
08:34 |
Sent To |
|
|
Notes |
2006-11-05 08:47:20 | STAMPED TWO COPIES OF MANUFACTURES SPECS/CUT SHEETS FOR | | FIRE PUUMP, FIRE PUMP CONTROLLER, GEN, ATS, BUS DUCT | | ETC. | | SENT BACK TOMR BROWN FOR OTHER TRADES TO STAMP. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2006-09-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-09-01 |
Time |
14:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-09-01 |
Time |
14:45 |
Sent To |
|
|
Notes |
2006-09-01 00:00:00 | NEW REVISEDSHEET SP-1 ADDED INTO SETS | | SHOWING THE MIN OF 8HRS FOR FIRE PUMP. | | OK. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2006-08-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-08-16 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-08-14 |
Time |
20:10 |
Sent To |
|
|
Notes |
2006-08-16 00:00:00 | REVIEW IN PROGRESS | | *** PASSED PENDING *** | | | | | | CALLED, ENGINEER OF RECORD AND MR PENA, | | FOR INFORMATION ON FIRE PUMP FUEL | | USAGE/CONSUMPTION PER HR. NEED TO HAVE | | IN RECORD SETS, SO THAT A MIN OF 8HRS OF | | ON-SITE FUEL IS PRVOIDED FOR FIRE PUMP. | | | | | | ELECTRICAL PLAN ARE STAMPED. | 2006-08-14 00:00:00 | PLANS IN ELECTRICAL FOR REVIEW. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-06-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-06-18 |
Time |
09:49 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-06-11 |
Time |
20:07 |
Sent To |
|
|
Notes |
2006-06-18 00:00:00 | REVIEW IN PROGRESS. | | ****** UNSAT 2ND REVIEW ****** | | | | ** PLEASE SEE SOME COMMENTS FROM FIRST | | REVIEW AND SOME NEW COMMENTS DUE TO | | COMPLETE RISER ETC NOW SUBMITTED. | | | | | | ** IMPORTANT** | | WHEN SUBMITTING MANUFACTURES SPECS/CUT | | SHEETS, PRODUCT APPROVALS, STRUCTURAL | | CALCS ETC,PLEASE PLACE IN A BINDER OF | | SOME TYPE AND LABEL EACH SECTION/PRODUCT | | FOR EASY REFERENCE. THIS WOULD HELP | | GREATLY IN THE PLAN REVIEW PROCESS AND | | KEEPING ALL SUBMITTIALS IN ORDER. | | | | 1) NOTE: PLEASE CORRELATE ALL | | SPEC/MANUFACTURES CUT SHEETS SUBMITTED | | WITH PLANS. | | PLEASE SEE TWO DIFFERENT GENERATORS, TWO | | DIFFERENT SIZES, TWO DIFFERENT ATS'S. | | PLEASE SEE RISER AND PLANS. | | 215.5 | | | | 2) NOTE: PLEASE SEE SEE ATS IS STILL | | BEING SHOWN AS 3-POLE ON PLANS/ RISER | | AND SUBMITTIALS. | | PLEASE SEE RISER ALSO INDICATES 4-POLE | | AS REQUIRED IN ONE LOCATION. | | PLEASE SEE E-19 SHOWS 3-POLE ALSO. | | 215.5 | | | | 3) NOTE: PLEASE SEE FIRE PUMP SPECS FOR | | DIESEL FP TANK, INDICATES 300 GALS IN ON | | ONE SHEET AND 270 GALS ON ANOTHER? | | PLEASE SPECIFY THE CORRECT SIZE TANK, | | PLEASE SPECIFY THE GPH CONSUMPTION OF | | THE DIESEL FIRE PUMP. | | ** PLEASE VERIFY MIN 8HRS? | | 215.5, UNABLE TO VERIFY. PLEASE SEE | | NFPA-20 CHAPTER 11 | | | | 4) NOTE: PLEASE SEE NO "JOBSITE SPEC | | BOOKS" WERE SUBMITTED. THIS IS REQUIRED. | | | | 5) NOTE: PLEASE SEE RISER NOTE #7A IS | | BEING INDICATED YET THIS COULD NOT BE | | LOCATED ON RISER. THIS IS FOR METER/UNIT | | RISER. | | 215.5 | | | | 6) NOTE: PLEASE SEE NOTE #3 ON HOUSE | | RISER INDICATES GFI PROTECTION. (SHOULD | | BE GFP.) | | 215.5 | | | | 7) NOTE: PLEASE SEE NOTE #5 HOUSE RISER | | NOTES, (3-POLE ATS), SEE NOTES ABOVE AND | | CORRELATE. | | 215.5 | | | | 8) NOTE: PLEASE SEE MAIN FOR "TDP" IS | | SHOWN AS 1000A'S ON E-19, YET THIS IS | | NOTED ON HOUSE RISER NOTES AS BEING | | 1200A'S FOR FUTURE> | | THE LOAD ON THIS "TDP" IS NOT KNOWN AT | | THIS TIME>?? | | PLEASE VERIFY AS A 1000A DISCONNECT MAY | | FEED A 1200A DISC, AND IS BEING NOTED | | FOR COORDINATION. | | 215.5 | | | | 9) NOTE: PLEASE SEE UNIT C-2 MISSING | | CIRCUITING FOR KITCHEN WALL. | | THIS WAS NOTED AND REDLINED ON PREVIOUS | | PLANS. | | 215.5 | | ** THIS CAN BE REDLINED** | | | | 10) NOTE: PLEASE SEE UNIT C-9 AS | | LOCATION OF SD IN DEN SHOULD BE LOCATED | | WITHIN 12" OF THE HIGHEST POINT OF THE | | CEILING. IN UNIT C-9.1 THE SD WAS | | RELOCATED AND SEEMS TO BE THE SMAE | | LAYOUT. | | NFPA-72 11.8.3.5 | | ** THIS CAN BE REDLINED.** | | | | 11) NOTE: PLEASE SEE PANEL NOTATIONS ON | | E-20 INDICATE PANELS "TR1", TR2" AND TF | | PANELS BEING LOCATED ON THAT PAGE, | | HOWEVER THESE ARE ON E-22 | | 215.5 | | | | 12) NOTE: PLEASE SEE MISPRINT FOR TWO | | PANELS "LP'S" ON LOWER RIGHT HAND CORNER | | OF E-22. | | ** THIS CAN BE REDLINED ** | | | | 13) NOTE: PLEASE INDICATE THE | | PHOTO-METRICS FOR STAIRS UNDER EM POWER, | | AS ONLY THE TYPICAL DETAILS FOR TWO | | STAIR TOWERS WERE LOCATED FOR LEVELS | | UNDER NORMAL. | | LS 101 7.8.1.3,7.9.2.2 | | | | **PLEASE BE AWARE OF ANY COMMENTS FROM | | OTHER TRADES WHICH HAVE AN AFFECT ON | | ELECTRICAL PLANS. | | | | ** WHEN RESUBMITTING PLANS, PLEASE BE | | SURE TO REMOVE ANY OLD/VOIDED SHEETS AND | | ONLY INSERT NEW REVISED SHEETS INTO | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | 2006-06-11 00:00:00 | ONE ROLL IN ELECTRICAL FOR REVIEW, |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-12-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-12-13 |
Time |
08:01 |
Rev Time |
15.00 |
Received By |
dpalmer |
Date |
2005-12-09 |
Time |
16:28 |
Sent To |
|
|
Notes |
2005-12-13 00:00:00 | ********** UNSAT *************** | | | | SOUTH TOWER @CITY PLACE | | 550 OKEECHOBEE BLVD. | | | | **** PLEASE KNOW, PLANS SUBMITTED ARE | | NOT COMPLETE, THERFORE A COMPLETE REVIEW | | FOR CODE COMPLIANCE CAN NOT BE DONE AT | | THIS TIME. | | PLEASE SEE THE BELOEW ITEMS KNOWN AT | | THIS TIME. | | | | 1)NOTE: PLEASE SUBMIT ALL MANUFACTURE | | SPECIFICATION SHEETS/ CUT SHEETS FOR | | FIRE PUMP(DIESEL) FIRE PUMP CONTROLLER, | | GENERATOR, AUTOMATIC TRANSFER SWITCH | | (ATS) AND ANY SUB BASE FUEL TANKS OR | | FUEL TANKS FOR DIESEL FIRE PUMP. | | PLEASE SURE ALL INFORMATION SUBMITTED | | MUST SHOW LISTINGS FROM A NATIONALLY | | RECOGNIZED TESTING LAB. (NRTL). | | PLEASE BE SURE ALL FIRE PUMP CONTROLLERS | | ETC COMPLY WITH NFPA-20 AND OTHER | | APPLICABLE CODES. | | | | 2)NOTE: PLEASE SEE PLANS INDICATE 600KW, | | YET RISER DIAGRAM SHOWS 400KW GEN. | | PLEASE ALSO VERIFY IF THE ATS WILLL BE A | | 4-POLE AND GEN TO BE SEPARTAELY DERIVED. | | | | PLEASE SEE 700.6DWHICH IN ORDER TO | | INDICATE A GROUND FAULT IN SOLIDLY | | GROUNDED WYE EMERGENCY SYSTEMS OF MORE | | THAN 150 VOLTS TO GROUND AND | | CIRCUIT-PROTECTIVE DEVICES RATED 1000 | | AMPERES OR MORE. THE SENSOR FOR THE | | GROUND-FAULT SIGNAL DEVICES SHALL BE | | LOCATED AT, OR AHEAD OF, THE MAIN SYSTEM | | DISCONNECTING MEANS FOR THE EMERGENCY | | SOURCE, AND THE MAXIMUM SETTING OF THE | | SIGNAL DEVICES SHALL BE FOR A | | GROUND-FAULT CURRENT OF 1200 AMPERES. | | INSTRUCTIONS ON THE COURSE OF ACTION TO | | BE TAKEN IN EVENT OF INDICATED GROUND | | FAULT SHALL BE LOCATED AT OR NEAR THE | | SENSOR LOCATION. | | ALTHOUGH 700.26 INDICATES THAT | | GROUND-FAULT PROTECTION OF EQUIPMENT IS | | NOT REQUIRED ON THE ALTERNATE SOURCE FOR | | EMERGENCY SYSTEMS, GROUND FAULTS CAN | | OCCUR ON SUCH SYSTEMS, AND THEY CAN | | RESULT IN EQUIPMENT BURNDOWN. BECAUSE OF | | THE EMERGENCY NATURE OF SUCH SYSTEMS, | | AUTOMATIC DISCONNECT IN THE EVENT OF A | | GROUND FAULT IS INAPPROPRIATE. DETECTION | | OF SUCH A FAULT, HOWEVER, IS DESIRABLE | | SO THAT THE CONDITION CAN BE CORRECTED. | | PLEASE PROVIDE ALL INFORMATION AS NEEDED | | FROM MANUFACTURE TO VERIFY, AS SOME | | MANUFACTURES ALREADY KNOW TO THIS OFFICE | | DO REQUIRE THE SWITCHING OF THE NEUTRAL | | IN ORDER FOR THE GFP SENSING TO WORK | | CORRECTLY. | | | | 3)NOTE:PLEASE SEE PLANS E-2 REFERENCE | | TO SEE LAYOUT OF FIRE COMMAND ROOM ON | | E-19, HOWEVER THIS LAYOUT IS "BLANK". | | PLEASE SEE NFPA-72, 101 WITH ALL MIN | | EQUIPMENT REQUIRED IN SUCH ROOM. PLEASE | | INDICATE THESE ITEMS ON PLANS. | | FIRE ALARM CONTROL PANEL, GENERATOR | | ANNUCIATOR PANEL, SHUNTS ETC. | | PLEASE ALSO SEE NOTE FOR EM LTS. | | | | 4)NOTE: PLEASE SEE THAT NO PLANS WERE | | SUBMIT TO SHOW POOL AREA LAYOUT , | | LIGHTING, RECEPTS ETC. | | UNABLE TO VERIFY MIN REQUIRED BY CODE | | FOR THESE AREAS. | | | | 5)NOTE: PLEASE PROVIDE REFERENCE TO THE | | 2002 NEC ON PLANS. | | PLEASE ALSO REFERENCE 2002 NFPA-72, AND | | THE 2003 NFPA-101. | | | | 6)NOTE: PLEASE PROVIDE COMPLETE | | PHOTOMETRICS FOR ALL CORRIDOR, STAIR | | TOWER AND EGRESS PATHS. PLEASE SEE 101 | | 7.8 WHICH REQUIRES A MIN OF 10FT CANDLES | | MIN FOR STAIR WELLS AND 1FT MIN UNDER EM | | CONDITIONS. | | PLEASE SEE 7.9.2.2 WHICH REQUIRES WIRING | | OF EM LTS TO BE SUCH IN THE EVENT OF THE | | SWITCHING OF A SWITCH, BREAKER ETC OR | | THE TRIPPING OF A SINGLE OCP DEVICE WILL | | IN NO WAY LEAVE ANY ONE AREA OF EGRESS | | IN TOTAL DARKNESS. IN ORDER TO | | ALLEAVIATE THIS , A MIN BATTTERY BACK UP | | FIXTURE OF SOME TYPEWILL BE REQUIRED | | TO POVIDE THE MIN 1FT CANDLE FOR MIN | | TIME. | | | | | | 7)NOTE: PLEASE SEE ALL MAIN ELECTRICAL | | ROOMS, FIRE COMMAND ROOM, GEN RM, FIRE | | PUMP RM AND ELEVATOR EQUIPMENT ROOMS ETC | | SHALL A BATTERY BACK UP TYPE OF LIGHTING | | FIXTURE. | | 700.16, LS 101 7-9, 90.4 | | | | 8)NOTE: PLEASE SEE 620.23 AND 620.24 | | WHICH REQUIRES EQUIPMENT ROOMS/AREAS TO | | HAVE A DEDICATED BRANCH CIRCUIT FOR | | RECEPTS AND LIGHTING.PLEASE SEE A | | DEDICATE CIRCUIT WAS LOCATED FOR RECEPT, | | HOWEVER LIGHTING COULD NOT BE VERIFIED. | | | | 9)NOTE: PLEASE SEE FIRE REVIEW FOR EXACT | | LOCATIONS OF ANY "KNOX BOX" LOCATION(S) | | WHICH MAY BE REQUIRED. ONE OR MORE | | LOCATIONS SHALL BE PLACED/NOTED ON | | PLANS. | | | | 10)NOTE: PLEASE SHOW ALL ROOM/AREA | | DESIGNATIONS ON PLANS. PLEASE SEE AREAS | | IN UNITS. PLEASE SEE AREAS WHICH NOW | | INDICATE THE 15A, #14 CIRCUITS IN AREAS | | WHICH APPEAR TO BE DINING AREAS. | | PLEASE SEE 210.52B1,210.11C1 | | | | 11)NOTE: : PLEASE SEE 210.63 FOR | | REQUIMENTS OF GFI RECEPTS FOR ALL A/C | | EQUIPMENT. PLEASE SEE THESE COULD NOT BE | | LOCATED ON ROOF PLANS ETC. | | | | 12)NOTE: PLEASE PROVIDE SPECIFIC NOTES | | ON SHEETS CONTAINING A LARGER SCALE OF | | ELECTRICAL ROMMS. THE NOTE FOR 110.26 | | WAS FOUND ON RISER SHEET, HOWEVER PLEASE | | INCLUDE THIS ON ABOVE SHEETS. | | | | 13)NOTE: PLEASE SEE SOME AREAS, WHICH | | ARE LABELED AS ELEVATORS RMS ARE SHOWN | | BLANK? | | E-7 | | | | 14)NOTE: PLEASE PROVIDE DETAIL FOR ALL | | FLOOR PENETRATIONS AND PENETRATIONS FOR | | BUC-DUCT INDICATION THE MIN 4" CURBING. | | 368.6B2 | | | | 15)NOTE: PLEASE INDICATE THE EQUIPMENT | | GROUNDING METHOD OF BUS-DUCT. PLEASE | | PROVIDE CUT SHEET FROM MANUFACTURE. | | PLEASE SEE LOCAL AMENDMENTS WHICH REUIRE | | THE EQUIPMENT GROUNDING TO BE | | COPPER.250.62 | | | | 16)NOTE: PLEASE PROVIDE COLOR CODING OF | | ELECTRICAL WIRING PER 215.8 OFLOCAL | | AMENDMENTS. 120/208 BLK,RED, BLUE, | | WHITE. | | 277/480V BROWN, PURPLE, YELLOW, GREY. | | SEE OTHERS IF ANY OTHER ELECTRICAL | | VOLTAGES ARE TO BE USED. | | | | | | 17)NOTE: PLEASE SEE SOME CIRCUTING | | MISSING ON UNITS PLANS. THESE HAVE BEEN | | REDLINED FOR AREAS OF COMMENT. | | | | 18)NOTE: PLEASE SEE SOME UNITS MISSING | | RECEPTS PER 210.52. | | PLEASE SEE REDLINED SET, ONLY A COUPLE. | | | | 19)NOTE: PLEASE SEE C 2.2 WHICH MENTIONS | | TO SEE ENLARGE AREA TO SHOW DETAIL, | | HOWEVER THIS SEEMS TO BE BLANK ON PLANS. | | | | 20)NOTE:PLEASE SEE THAT ALL RECEPTS | | SHOWN IN CLOSETS FOR LV TRNSFORMERS TO | | BE "PLUGGED IN" SHALL BE LOCATED ATLEAST | | 12" MIN FROM SHELVING. THESE MAY BE | | LOCATED ABOVE DOOR WAYS. | | PLEASE SEE PLUG-IN TYPE TRANSFORMERS | | CREATE VERY HIGH TEMPS AND SOME IN THIS | | JURISTICTION HAVE HEATED TO THE POINT OF | | MELTING, AND CUSE OF FIRE IN CLOSETS AND | | CLOSE PROIMITY TO COMBUSTIBLES. PLEASE | | SEE THIS CREATES A LIFE-SAFETY SITUATION | | AND ANY UNITS CONTAININGOCP, THERMAL | | CUT-OUT DEVICES WILL BE REQUIRED TO BE | | LOCATED AS ABOVE. 110.26,240.24D | | | | 21)NOTE: PLEASE SEE SOME UNITS IN WHICH | | THERE SEEMS TO BE TWO DIFFERENT HEIGHTS | | IN BEDRM CEILINGS. PLEASE SEE NFPA-72 | | 11.8.3.5 WHICH REQUIRES THESE SD'S TO BE | | LOCATED WITHIN 12" OF THE HIGHESRT POINT | | OF THE FLAT CEILING AREA. | | PLEASE SEE REDLINED PLANS FOR LOCATIONS. | | | | 22)NOTE: PLEASE SEE SOME UNITS WHICH | | INDICATE A HIGHER LOAD OF 122.5A'S ON A | | 125A BREAKER. PLEASE VERIFY AS THIS DOES | | NOT SEEM TO LEAVE ANY ALLOTMENT FOR | | FURTURE WIRING EXPANTION OF LOADS. | | THIS IS THE LOAD AFTER ALL PERMITTED | | DE-RATING BY NEC. | | PLEASE ALSO SEE ANY ARE VERYCLOSE TO | | THE 100A'S PROVIDED. | | 90.8 | | | | 23)NOTE: PLEASE SEE AREAS OF PLANS WHICH | | CONTAIN "WHITE-OUT" AND HAND-DRAWN | | CHNAGES MADE. (RISER SHEET). | | PLEASE SEE FS 471.025 ETC WHICH DOES NOT | | PERMIT ANY HAND DRAWN CHANGES TO PLANS, | | UNLESS EACH INDIVIDUAL CHANGE IS SIGNED | | AND DATED BY THE SAID ENGINEER OF | | RECORD. | | | | 24)NOTE:PLEASE PROVIDE COMPLETE NOTES | | WITH RESPECT TO THE LOCATIONS OF SMOKE | | DETECTORS. 11.8.3.5 | | SMOKE ALARMS AND SMOKE DETECTORS | | INSTALLED WITHIN A 6.1-M (20-FT) | | HORIZONTAL PATH OF A COOKING APPLIANCE | | SHALL BE EQUIPPED WITH AN | | ALARM-SILENCING MEANS OR BE OF THE | | PHOTOELECTRIC TYPE. | | SMOKE ALARMS AND SMOKE DETECTORS SHALL | | NOT BE INSTALLED WITHIN A 914-MM | | (36-IN.) HORIZONTAL PATH FROM A DOOR TO | | A KITCHEN OR A BATHROOM CONTAINING A | | SHOWER OR TUB. | | SMOKE ALARMS AND SMOKE DETECTORS SHALL | | NOT BE INSTALLED WITHIN A 914-MM | | (36-IN.) HORIZONTAL PATH FROM THE SUPPLY | | REGISTERS OF A FORCED AIR HEATING OR | | COOLING SYSTEM AND SHALL BE INSTALLED | | OUTSIDE OF THE DIRECT AIRFLOW FROM THOSE | | REGISTERS AND 5' MIN FROM RETURN AIR | | GRILLES. | | SMOKE ALARMS AND SMOKE DETECTORS SHALL | | NOT BE INSTALLED WITHIN A 914-MM | | (36-IN.) HORIZONTAL PATH FROM THE TIP OF | | THE BLADE OF A CEILING-SUSPENDED | | (PADDLE) FAN. | | | | 25)NOTE:PLEASE SHOW GROUNDING SYSTEM | | FOR ALL TRANSFORMER. PLEASE INCLUDE | | GROUNDING OF THESE TRANSFOMERS ON RISER | | DIAGRAM IN NOTES/LINE DIAGRAM. | | 250.30, 250.50 ETC. | | PLEASE PROVIDE THIS LINE DIAGRAM ON | | RISER SHEET. | | | | 26)NOTE:PLEASE SEE NO GFP INDICATED FOR | | HDP. 230.95. 240.13 ETC. | | | | 27)NOTE: PLEASE SEE ANY PROPOSED | | LIGHTNING PROTECTION SYSTEM SHALL BE | | INSTALLED AND ACCEPTABLE PER NFPA-780. | | ALTHOUGH A LIGHTNING PROTECTION SYSTEM | | IS NOT SHOWN ON ANY PLANS, PLEASE BE | | SURE A NOTE IS PLACED ON "ROOF-TOP" | | SHEET WITH REFERENCE TO NFPA-780. | | AS NOTED IN MEETING , "LIGHTNING | | PREVENTION" SYSTEMS ARE NOT PERMITTED OR | | ACCEPTABLE IN THIS JURISTICTION. | | | | 28)NOTE: PLEASE SEE THIS NOTE IS ALL | | ENCOMPASSING OF ELECTRICAL RISER, | | EQUIPMENT SCHEDULE, LOAD CALCULATIONS, | | PANEL SCHEDULES AND CALCUALTIONS ETC. | | | | ** PLEASE COMPLETE ALL OF THE ABOVE AND | | SUBMIT FOR REVIEW. | | PLEASE CORRELATE ALL PANEL SCHEDULS , | | EQUIPMENT WITH RISER | | PLEASE COMPLETE RISER WITH INFORMATION | | FOR EQUIPMENT, FEEDERS ETC. | | PLEASE SEE MANY AREAS OF LOAD | | CALCULATIONS WHICH ONLY INDICATE | | XXXXXXX'S. | | PLEASE SEE 2002 NEC. | | | | ** PLEASE KNOW THERE MAY BE OTHER | | COMMENTS DUE TO THE INCOMPLETE PLANS AT | | THIS TIME. | | | | ** PLEASE SEE REDLINED PLANS FOR | | POSSIBLE LOCATIONS. | | | | PLEASE SUBMITTHE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE TO GO OVER COMMENTS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | | | | | | 2005-12-09 00:00:00 | ONE ROLL IN ELECTRIC FOR REVIEW. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2006-07-26 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2006-07-26 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2006-07-26 |
Time |
13:06 |
Sent To |
|
|
Notes |
2006-07-26 00:00:00 | PASS 7-26-06,RASIK CHOKSHI805-6723 |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2005-10-06 |
|
|
Cont ID |
|
Sent By |
mamini |
Date |
2005-10-06 |
Time |
13:21 |
Rev Time |
1.00 |
Received By |
mamini |
Date |
2005-10-06 |
Time |
13:21 |
Sent To |
|
|
Notes |
2005-10-06 00:00:00 | FAILED: | | 1. AT THE PRESENT TIME, THE DEPARTMENT | | OF PUBLIC UTILITIES AND ENGENEERING | | SERVICES IS IN PROCESS OF DOING CAPACITY | | STUDIES FOR WATER AND SEWER CONNECTIONS | | IN SURROUNDING AREA.THE CIVIL | | ENGINEERING PLAN REVIEW CAN NOT PROCEED | | UNTIL SUCH STUDIES ARE COMPLETED AND | | CONNECTION TO THE SERVICES ARE APPROVED. | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | MOHAMMAD R. AMINI |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
22 |
Status |
P |
Date |
2008-09-09 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2008-09-09 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2008-09-09 |
Time |
11:27 |
Sent To |
|
|
Notes |
2008-09-09 11:39:06 | GRAPHIC DISPLAY SHOP DRAWING FOR THE SMOKE CONTROL | | PANEL. | | | | 1. THE NEW PANEL IS TO BE TESTED AND THE PROPER | | DOCUMENTATION IS TO BE PROVIDED TO THE MEHCANICAL | | DIVISION AND THE FIRE RESCUE DEPARTMENT INDICATING THAT | | THE PANEL OPERATES CORRECTLY. | | | | 2. THE EXISTING SMOKE CONTROL EQUIPMENT LOCATED IN THE | | FIELD HAD BEEN PREVIOUSLY TESTED WHEN SMOKE CONTROL | | COMPONENTS WERE CONNECTED TO THE FIRE ALARM CONTROL | | PANEL. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | 804-4709 PHONE | | 804-4774 FAX | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
21 |
Status |
F |
Date |
2008-08-12 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-08-12 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-08-11 |
Time |
17:16 |
Sent To |
|
|
Notes |
2008-08-11 17:25:24 | *****SUBMITTAL (FOR FIREMAN'S OVERRIDE PANEL) | | DENIED***** | | | | | | 1.THE PLANS SHALL BE SUBMITTED WITH NO INK, PENCIL, | | OR DARKENED/WHITE-OUTED MARKINGS. | | | | 2.THE SCOPE OF WORK ADDRESS SHALL BE IN THE TITLE | | BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | CAPT. MICHAEL A, WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
20 |
Status |
P |
Date |
2008-05-12 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-05-12 |
Time |
12:02 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-05-12 |
Time |
11:54 |
Sent To |
|
|
Notes |
2008-05-12 12:00:42 | *****APPROVED***** | | | | | | REVIEWED REVISED PLAN SHEETS A-8.5, A-9.2.1, AND | | A-9.2.2;NO FIRE STAMP NEEDED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
19 |
Status |
P |
Date |
2008-02-21 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-02-21 |
Time |
14:43 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-02-21 |
Time |
14:38 |
Sent To |
M |
|
Notes |
2008-02-21 14:42:51 | *****TCO PLAN APPROVED***** | | | | | | THE TCO PLAN OUTLINE SUBMITTED BY THE RELATED | | GROUP/MOSS & ASSOCIATES WAS REVIEWED AND APPROVED FOR | | LIFE SAFETY COMPLIANCE. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
18 |
Status |
P |
Date |
2008-02-21 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-02-21 |
Time |
14:37 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-02-21 |
Time |
13:03 |
Sent To |
|
|
Notes |
2008-02-21 13:45:18 | *****REVISION APPROVED***** | | | | | | REVISED PLAN SHEETS A1.1,A-1.5, A-2.1.6,A-2.4.2, | | A-2.4.5, AND A-6.5 WERE REVIEWED;PLAN SHEETS A1.1AND | | A-2.1.6 WERE STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
17 |
Status |
P |
Date |
2008-02-21 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-02-21 |
Time |
11:30 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-02-21 |
Time |
11:15 |
Sent To |
|
|
Notes |
2008-02-21 11:25:03 | *****REVISION APPROVED***** | | | | THE COMMENT FROM FIRE REVIEW STOP #16 HAS BEEN | | ADDRESSED;REVISED PLAN SHEET E-2 STAMPED, INITIALED, | | AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
16 |
Status |
F |
Date |
2007-12-20 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-12-20 |
Time |
12:43 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-12-20 |
Time |
12:35 |
Sent To |
|
|
Notes |
2007-12-20 12:43:25 | *****UNSAT***** | | | | | | PLEASE ADDRESS ELECTRICAL AND PLUMBING COMMENTS. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
15 |
Status |
P |
Date |
2007-11-27 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-11-27 |
Time |
11:18 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-11-27 |
Time |
10:33 |
Sent To |
|
|
Notes |
2007-11-27 11:12:54 | *****APPROVED REVISION***** | | | | | | REVIEWED REVISED PLAN SHEET A-8.1 (8/27/07), A-8.4 | | (10/3/07), AND A-9.3.1 (8/9/07) ;NO FIRE-STAMPING | | NEEDED FOR THESE SHEETS. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
14 |
Status |
P |
Date |
2007-11-13 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-11-13 |
Time |
13:37 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-11-13 |
Time |
13:07 |
Sent To |
|
|
Notes |
2007-11-13 13:31:11 | *****APPROVED REVISION DATED 10/04/07***** | | | | | | REVISED PLAN SHEET E-19A STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
13 |
Status |
P |
Date |
2007-11-07 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-11-07 |
Time |
15:53 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-11-07 |
Time |
15:53 |
Sent To |
|
|
Notes |
2007-11-07 15:55:10 | REVISED SHEETS E-1, E-2, E-3, E-4, E-5, AND E-6. ACCESS | | CONTROL TO COMPLY WITH NFPA 101, SEC. 7.2.1.6.2. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
12 |
Status |
P |
Date |
2007-11-06 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-11-06 |
Time |
17:54 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-11-06 |
Time |
17:32 |
Sent To |
|
|
Notes |
2007-11-06 17:54:49 | *****APPROVED, REVISION DATED 09/07/07***** | | | | | | REVISED PLAN SHEETS A-1.1, A-2.14,A-2.15, A-2.3.6, | | A-2.7.1, A-6.1, A-6.5, AND A-6.9 WERE REVIEWED AND | | APPROVED;PLAN SHEET A-6.1 WAS STAMPED, INITIALED, AND | | DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
11 |
Status |
P |
Date |
2007-09-18 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-09-18 |
Time |
15:44 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-09-18 |
Time |
15:28 |
Sent To |
|
|
Notes |
2007-09-18 15:38:48 | *****APPROVED***** | | | | | | REVISED PLAN SHEET SP-1 STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
10 |
Status |
N |
Date |
2007-07-02 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-07-02 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-07-02 |
Time |
10:25 |
Sent To |
|
|
Notes |
2007-07-02 10:27:34 | REVISIONS DATED 4/27/07 TO MECHANICAL AND PLUMBING | | SHEETS. IT DOES NOT APPEAR THAT THERE ARE ANY CHANGES | | THAT EFFECT LIFE SAFETY. ANY REVISIONS MADE TO FIRE | | PROTECTION SYSTEMS ARE TO BE SUBMITTED UNDER THAT | | SPECIFIC PERMIT AND ILLUSTRATED ON SPECIFIC PLANS. | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
9 |
Status |
P |
Date |
2007-06-29 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-06-29 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-06-29 |
Time |
14:35 |
Sent To |
E |
|
Notes |
2007-06-29 14:48:35 | *****REVISIONS (RE LIGHTS)APPROVED***** | | | | | | THE SCOPE OF WORK ON THESE REVISED ELECTRICAL PLAN | | SHEETS HAVE NO BEARING UPON LIFE SAFETY. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
8 |
Status |
P |
Date |
2007-04-30 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-04-30 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-04-30 |
Time |
13:47 |
Sent To |
|
|
Notes |
2007-04-30 14:02:08 | *****REVISION #9[2/02/07]APPROVED****** | | | | | | REVISED PLAN SHEETS SP-8 THRU SP-12 SHOWING FIRE | | SPRINKLERS IN DRYER SHAFT TO BE INSTALLED AT TOP AND | | BOTTOM FLOOR ONLU WERE STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
7 |
Status |
F |
Date |
2007-04-09 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-04-09 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-04-09 |
Time |
11:54 |
Sent To |
|
|
Notes |
2007-04-09 12:13:07 | *****UNSAT***** | | | | | | UNABLE TO LOCATE REVISION #12 ON THE SUBMITTED PLAN | | SHEETS. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
6 |
Status |
P |
Date |
2007-03-26 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-03-26 |
Time |
19:15 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-03-26 |
Time |
19:06 |
Sent To |
|
|
Notes |
2007-03-26 19:14:56 | *****REVISION APPROVED***** | | | | | | SHEET NUMBER E-2 (REVISED DATE 03/01/07) STAMPED, | | INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
P |
Date |
2007-01-30 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-01-30 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-01-30 |
Time |
11:45 |
Sent To |
|
|
Notes |
2007-01-30 11:47:00 | REVISED ARCHITECTURAL SHEETS ONLY DATED 11/17/06. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2006-08-29 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-08-29 |
Time |
07:23 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-08-29 |
Time |
07:23 |
Sent To |
|
|
Notes |
2006-08-29 00:00:00 | ***PROVISO*** | | | | 1) THESE PLANS APPEARED TO HAVE BEEN | | REVISED ON SHEET LS.2 AT STAIR #(2) EXIT | | DOORS CONVERGE AT ONE ANOTHER. EXITING | | FROM THE GARAGE AND CORRIDOR COULD | | POSSIBLY BECOME UNUSEABLE DUE TO PERSONS | | EXITING FROM BOTH THESE AREAS. PLEASE | | REVISE THIS AREA WHERE EXIT CONVERGENCE | | OCCURS. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FOR MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2006-07-17 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2006-07-17 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2006-07-17 |
Time |
10:26 |
Sent To |
|
|
Notes |
2006-07-17 00:00:00 | 1. IT APPEARS THAT ON LS-3 TRAVEL | | DISTANCE ROUTES ARE TRAVELING OVER A | | PARKING SPACE WHERE A VEHICLE WOULD BE | | PARKED. THIS OCCURS IN THE VICINITY OF | | STAIR # 4. THIS ROUTE IS INDICATED FOR | | THREE DIFFERENT PLACES. | | | | 2. PLEASE EXPLAIN HOW THE TWO DOORS WORK | | SINCE THEY ARE IN CLOSE PROXIMITY TO ONE | | ANOTHER ON LS-2. THE GARAGE AREA DOOR | | AND STAIR # 4 DOOR. | | | | 3. SHOULD THE TWO 184 FEET TRAVEL | | DISTANCE ROUTES SHOWN ON PAGE LS-1 | | TRAVEL PAST THE PUMP ROOM AND JANITORS | | CLOSET INTO THE HALLWAY TO REACH THE | | EXIT WHICH IS CLOSER. | | | | 4. NO DOOR (S) SHOWN AT 58 OCCUPANT | | ARROW FROM CLUBROOM SHOWN ON LS-4. | | PLEASE ADVISE. | | | | 5. PLEASE EXPLAIN IN SWINGING DOORS FROM | | THE CLUBROOM NEAR THE 33 FEET TRAVEL | | DISTANCE ROUTE. IS THIS THE CORRECT | | DIRECTION FOR THESE DOORS TO SWING. | | | | 6. COULD NOT LOCATE BUILDING ADDRESS ON | | THE ELEVATIONS THAT FACE OKEECHOBEE | | BOULEVARD. INFORMATION LOCATED ON PAGE | | A-10.1. OKAY. | | | | 7. IT APPEARS THAT THE PREVIOUS COMMENTS | | HAVE BEEN ADDRESSES. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER | | 804-4709 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2005-11-18 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2005-11-18 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2005-11-18 |
Time |
16:31 |
Sent To |
|
|
Notes |
2006-01-04 00:00:00 | ******DENIED****** | | | | PLAN REVIEW WAS STARTED BY F.M. M. | | CARSILLO AND STOPPED AFTER 32 COMMENTS. | | THE FOLLOWING IS A CONTINUATION OF THE | | SAME PLAN REVIEW: | | | | 33) A MINIMUM OF (2) FIRE DEPARTMENT | | CONNECTIONS REQUIRED FOR HIGHRISE | | BUILDINGS. | | | | 34) THE FIRE ALARM SYSTEM SHALL BE UL | | CERTIFIED FOR CENTRAL STATION SERVICE. | | | | 35) LOCKING KNOX BOX CAPS REQUIRED FOR | | FIRE DEPARTMENT CONNECTIONS. | | | | 36) THE FIRE ALRM SYSTEM SHALL MEET THE | | SURVIVABILITY REQUIREMENTS OF NFPA 72. | | | | 37) THE BUILDING IS TO MEET ALL HIGHRISE | | REQUIREMENTS IN ACCORDANCE WITH | | APPLICABLE BUILDING AND FIRE CODES. | | | | 38) SEPARATE SHOP DRAWINGS AND PERMITS | | REQUIRED FOR FIRE SPRINKLER AND FIRE | | ALARM SYSTEMS. | | | | 39) SEPARATE SHOP DRAWINGS AND | | MANUFACTURER SPEC SHEETS REQUIRED FOR | | FIRE PUMP AND ASSOCIATED EQUIPMENT. | | | | 40) PLEASE NOTE THAT VARIOUS CODE | | EDITIONS ON SHT SP-14 ARE INCORRECT. | | NFPA 101 AND NFPA 1, 2003 EDITION, NFPA | | 13, 2002 EDITION, NFPA 14, 2003 EDITION, | | AND NFPA 20, 2003 EDITION. | | | | 41) IN ADDITION TO ELECTRONIC SWITCHES, | | THE DOUBLE CHECK DETECTOR ASSEMBLY SHALL | | BE SECURED WITH A LOCK AND CHAIN. | | | | 42) ALL ELEVATORS TO COMPLY WITH ASME | | A17.1. | | | | 43) PARKING GARAGE TO COMPLY WITH THE | | APPLICABLE BUILDING CODES AND NFPA 88A. | | | | 44) PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILINGS IN | | TERMS OF CLASS A,B, OR C. | | | | 45) AN ADDRESS IS REQUIRED ON BUILDING | | AND SHALL BE A MINIMUM OF 6" IN HEIGHT | | AND CONTRASTING WITH BACKGROUND. | | | | 46) ALL SMOKE DETECTORS SHALL BE LOCATED | | A MINIMUM OF (3) FEET FROM AC DIFFUSERS. | | | | 47) FIRE ALARM SYSTEM SHALL BE CLASS A, | | STYLE D OR FULLY ADDRESSABLE. | | | | | | MIKE WENNERGREN, CAPTAIN/WPFR | | FIRE PLANS REVIEW (561) 805-6722 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 2005-11-18 00:00:00 | 1. CONSTRUCTION, DEMOLITION, AND | | RENOVATION TO COMPLY WITH NFPA 241. | | | | 2. EXIT STAIRS ARE TO BE KEPT UP | | WITH CONSTRUCTION. | | | | 3. TEMPORTARY STANDPIPES ARE | | REQUIRED WHEN THE BUILDING REACHES | | THREE STORIES OR THIRTY FEET IN HEIGHT. | | | | 4. DEBRIS REMOVAL SHALL OCCUR | | DAILY. | | | | 5. NO CUTTING OR WELDING IS TO BE | | PERFORMED WITHOUT APPROVAL FROM | | THE BUREAU OF FIRE PREVENTION AND | | COMPLIANCE WITH NFPA 51B. | | | | 6. WHAT WILL BE THE NAME OF THE NEW | | STREET. | | | | 7. WET FIRE HYDRANTS ARE REQUIRED PRIOR | | TO, DURING ,AND AFTER CONSTRUCTION. | | | | 8. SUITABLE ROADS REQUIRED FOR FIRE | | AND PARAMEDICAL EQUIPMENT. | | | | 9. COULD ONLY LOCATE ONLY TWO FIRE | | HYDRANTS ON PAGE C-13. NOT ENOUGH | | FIRE HYDRANTS. | | | | 10. PLEASE REVIEW CODE TAB BOX TO | | ENSURE PROPER INFORMATION. | | | | 11. KNOX-BOXES WILL BE REQUIRED. | | | | 12. ALL COMMERCIAL SPACES MUST BE FIRE | | SPRINKLER PROTECTED PRIOR TO | | RECEIVING A C OF O. | | | | 13. COULD NOT LOCATE EXIT SIGNS GARAGE, | | GROUND FLOOR. | | | | 14. NO EXIT SIGNS SECOND FLOOR, PAGE | | E-3. | | | | 15. EXIT SIGNS APPEAR TO BE MISSING | | ON PAGE E-4. WHERE ARE THE ARE THE | | EXIT SIGNS LOCATED FOR THE GARAGE. | | CORRIDOR NEAR ELECTRICAL ROOM # 3 | | DISPLAYS NO EQUIPMENT. | | | | 16. SAME PROBLEM ON PAGE E-5. | | | | 17. EXIT SIGNS SHALL NOT EXCEED 100 | | FEET APART. | | | | 18. ELECTRICAL PLANS DO NOT APPEAR TO | | BE COMPLETE. | | | | 19. PLEASE INDICATE FIRE RATINGS OF | | SHAFTS SHWON ON PAGE AC-14. | | | | 20. MECHANICAL EQUIPMENT SHOWN IN | | SOME STAIRWELLS. ONLY CERTAIN | | EQUIPMENT IS ALLOWED IN STAIRWELLS. | | | | 21. PLEASE XPLAIN GATE IN PARKING GARAGE | | ON PAGE A-1.1. | | | | 22. PLEASE SUBMIT A LIFE SAFETY PLAN | | FOR REVIEW. | | | | 23. DOORS FOR THE POOL DECK ON THE 9TH | | FLOOR APPEAR TO SWING IN THE WRONG | | DIRECTION. | | | | 24. PLEASE INDICATE OCCUPANT LOAD | | FOR POOL AND POOL DECK. | | | | 25. PLEASE EXPLAIN CARD READERS AND HOW | | THEY WILL EFFECT EXITING. | | | | 26. SOFFITS ARE NOT TO INTERFERE WITH | | ANY OPERATION OF REQUIRED FIRE | | SPRINKLERS. | | | | 27. PLEASE PROVIDE PRESCRIPTVE STRENGTH | | REQUIREMENTS FOR ALL HANDRAILS AND | | GUARDRAILS. | | | | 28. PLEASE INDICATE WHICH ELEVATORS | | WILL BE STRETCHER ACCESSIBLE. SIGNS WILL | | BE REQUIRED. | | | | 29. ELEVATOR WARNING SIGNS WILL BE | | REQUIRED. | | | | 30. STAIRWELL SIGNS WILL BE REQUIRED. | | | | 31. TACTILE SIGNAGE REQUIRED AT STAIRS. | | | | 32. WHAT SIZE IS THE RISER AND TREADS | | SHOWN ON PAGE A-2.1.3. | | | | ACCORDING TO DEWEY PALMER, NEW SHEETS | | ARE TO BE SUBMITTED BY THE ARCHITECT. | | THE REVIEW WAS STOPPED BECAUSE THE PLANS | | WERE NOT COMPLETE. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER | | 804-4709 |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
1 |
Status |
F |
Date |
2007-11-20 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-11-20 |
Time |
08:58 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-11-20 |
Time |
08:55 |
Sent To |
|
|
Notes |
2007-11-20 08:58:16 | REVIEW: 1ST | | ACTION: DENIED | | | | FBC 2001 W/ 2003 SUPPLEMENTS | | NFPA 37-94 | | | | 1. P-1A AND P-1B: INSTALLATIONS OF ABOVE GROUND FUEL | | TANKS IN EXCESS OF 550 GALLONS ARE REQUIRED TO BE | | APPROVED BY THE PALM BEACH COUNTY DEPARTMENT OF | | ENVIRONMENTAL RESOURCE MANAGEMENT. PLANS SHALL BE | | SUBMITTED AND APPROVED BY DERM PRIOR TO BEING REVIEWED | | FOR CODE COMPLIANCE AND MADE PART OF THE PERMIT RECORD. | | FOR MORE INFORMATION PLEASE CONTACT DERM AT | | 561-233-2400 OR VISIT | | HTTP://WWW.CO.PALM-BEACH.FL.US/ERM/INDEX.ASP. | | | | 2. P-1A AND P-1B: FUEL STORAGE FOR STATIONARY | | COMBUSTION ENGINES SHALL COMPLY WITH NFPA 37-94 IN | | ACCORDANCE WITH FBC, M 915.1. THE FOLLOWING CONDITIONS | | WHICH ARE SHOWN ON PLANS ARE IN VIOLATION OF NFPA 37-94 | | SEC. 6-3.2.3.1: | | | | A) UNENCLOSED DAY TANKS (I.E., TANKS NOT IN A ROOM BY | | THEMSELVES) WHICH ARE USED FOR EMERGENCY PURPOSES SHALL | | NOT EXCEED 660 GALLONS. | | B) TWO OR MORE TANKS WITH AN AGGREGATE CAPACITY MORE | | THAN 660 GALLONS SHALL NOT BE CONNECTED TO ONE ENGINE. | | C) THE AGGREGATE CAPACITY OF ALL UNENCLOSED DAY AND | | SUPPLY TANKS IN A BUILDING SHALL NOT EXCEED 1,320 | | GALLONS. | | D) DAY AND SUPPLY TANKS WITH INDIVIDUAL CAPACITIES | | LARGER THAN 660 GALLONS OR THOSE TANKS WHICH CAUSE THE | | AGGREGATE CAPACITY TO EXCEED 1,320 GALLONS IN A | | BUILDING SHALL BE ENCLOSED IN ACCORDANCE WITH SEC. | | 6-3.5. ROOMS CONTAINING ONLY TANKS SHALL BE CONSTRUCTED | | OF WALLS, FLOOR AND TOP HAVING A FIRE RESISTANCE RATING | | OF NOT LESS THAN 3 HOURS WITH THE WALLS BONDED TO THE | | FLOOR IN ACCORDANCE WITH 6-3.5.1. PLEASE SEE THIS | | SECTION FOR ADDITIONAL REQUIREMENTS. | | | | 3. IF THE 1500 GALLON DAY TANK IS ENCLOSED IN A 3-HOUR | | ROOM AS REQUIRED BY 6-3.2.3.1 AND 6-3.5, THEN THE | | AGGREGATE TOTAL OF THE SUPPLY TANKS FOR THE GENERATOR | | AND THE FIRE PUMP WILL BE LESS THAN THE MAXIMUM | | AGGREGATE 1,320 GALLONS ALLOWED FOR UNENCLOSED TANKS | | AND NO ADDITIONAL 3-HOUR ENCLOSURES WILL BE REQUIRED BY | | THIS SECTION. | | | | 4. PLEASE VERIFY COMPLIANCE WITH SECTIONS 6-4 THROUGH | | 6-8 REGARDING FUEL FLOW CONTROL, FILLING, PIPING AND | | TRANSFER OF LIQUID FUEL TO ENGINES. | | | | NOTE: A SEPARATE FUEL PERMIT IS REQUIRED FOR FUEL | | STORAGE SYSTEMS. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2006-08-26 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-08-26 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-08-26 |
Time |
16:01 |
Sent To |
|
|
Notes |
2006-08-26 00:00:00 | | | | | PASSED/PROVISO | | | | | | | | GAS APPLIANCE VENTING SHALL BE FIELD | | INSPECTED AND APPROVED. | | MANUF. SPECIFICATION SHEETS SHALL BE | | SUBMITTED AT THE TIME OF GAS PERMIT | | APPLICATION. MANUF. SPECIFICATIONS | | SHEETS REQUIRED FOR THE GAS REGULATORS. | | VENTS FOR REGULATORS SHALL BE MADE OF | | NON COMBUSTABLE MATERIAL. GAS RISER - A | | SHUT OFF VALVE SHALL BE INSTALLED PRIOR | | TO THE REGULATORS WITH A UNION BETWEEN | | OR AFTER REGULATOR. (SHT P-6). SECTION | | 410.2(5). REVISIONS REQUIRED FOR THESE | | SHEETS. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
163 |
Status |
N |
Date |
2008-09-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-09-10 |
Time |
12:49 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-09-10 |
Time |
12:49 |
Sent To |
Z |
|
Notes |
2008-09-10 12:50:03 | TO "Z" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
162 |
Status |
N |
Date |
2008-08-26 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-08-26 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2008-08-26 |
Time |
08:50 |
Sent To |
FIRE |
|
Notes |
2008-08-26 08:50:54 | TO "FIRE" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
161 |
Status |
N |
Date |
2008-08-25 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-08-25 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2008-08-25 |
Time |
14:49 |
Sent To |
FIRE |
|
Notes |
2008-08-25 14:50:21 | TO "FIRE" BOX. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
160 |
Status |
N |
Date |
2008-08-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-08-05 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-08-05 |
Time |
16:05 |
Sent To |
FIRE |
|
Notes |
2008-08-06 14:23:47 | SENT TO MECHANICAL IN ERROR. RE-ROUTED TO FIRE INBOX. | 2008-08-05 16:05:24 | TO "M" BOX/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
159 |
Status |
N |
Date |
2008-07-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-07-17 |
Time |
13:24 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-07-17 |
Time |
13:24 |
Sent To |
P |
|
Notes |
2008-07-17 13:24:59 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
158 |
Status |
N |
Date |
2008-05-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-27 |
Time |
09:01 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-27 |
Time |
09:01 |
Sent To |
B |
|
Notes |
2008-05-27 09:01:50 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
157 |
Status |
N |
Date |
2008-05-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-01 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-01 |
Time |
15:14 |
Sent To |
B |
|
Notes |
2008-05-01 15:14:31 | TO "RBROWN "DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
156 |
Status |
N |
Date |
2008-04-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-17 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-17 |
Time |
16:58 |
Sent To |
B |
|
Notes |
2008-04-17 16:59:22 | TO "RBROWN" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
155 |
Status |
N |
Date |
2008-04-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-14 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-14 |
Time |
14:50 |
Sent To |
FIRE |
|
Notes |
2008-04-14 14:51:17 | TO "F" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
154 |
Status |
N |
Date |
2008-04-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-11 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-11 |
Time |
13:11 |
Sent To |
|
|
Notes |
2008-04-11 13:13:41 | TO "COMM" BD#26 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
153 |
Status |
N |
Date |
2008-03-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-28 |
Time |
10:16 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-28 |
Time |
10:16 |
Sent To |
M |
|
Notes |
2008-03-28 10:16:27 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
152 |
Status |
N |
Date |
2008-03-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-17 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-17 |
Time |
15:00 |
Sent To |
M |
|
Notes |
2008-03-17 15:01:11 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
151 |
Status |
N |
Date |
2008-03-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-06 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-06 |
Time |
15:06 |
Sent To |
P |
|
Notes |
2008-03-06 15:06:59 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
150 |
Status |
N |
Date |
2008-03-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-06 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-06 |
Time |
14:53 |
Sent To |
M |
|
Notes |
2008-03-06 14:54:08 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
149 |
Status |
N |
Date |
2008-03-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-03 |
Time |
12:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-03 |
Time |
12:39 |
Sent To |
B |
|
Notes |
2008-03-03 12:39:41 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
148 |
Status |
N |
Date |
2008-02-08 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-08 |
Time |
09:55 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-08 |
Time |
09:55 |
Sent To |
M |
|
Notes |
2008-02-08 09:55:47 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
147 |
Status |
N |
Date |
2008-02-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-06 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-06 |
Time |
10:30 |
Sent To |
B |
|
Notes |
2008-02-06 10:30:33 | TO "KCONRAD" DESK/SUBMITTAL(TCO PLANS) |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
146 |
Status |
N |
Date |
2008-02-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-06 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-06 |
Time |
10:28 |
Sent To |
P |
|
Notes |
2008-02-06 10:29:09 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
145 |
Status |
N |
Date |
2008-02-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-06 |
Time |
10:28 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-06 |
Time |
10:28 |
Sent To |
M |
|
Notes |
2008-02-06 10:28:44 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
144 |
Status |
N |
Date |
2008-01-31 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-31 |
Time |
11:46 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-31 |
Time |
11:45 |
Sent To |
|
|
Notes |
2008-01-31 11:46:26 | TO "COMM" BD#12 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
143 |
Status |
N |
Date |
2008-01-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-29 |
Time |
11:54 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-29 |
Time |
11:54 |
Sent To |
|
|
Notes |
2008-01-29 12:01:08 | TO "COMM" BD#2 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
142 |
Status |
N |
Date |
2008-01-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-29 |
Time |
11:54 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-29 |
Time |
11:54 |
Sent To |
M |
|
Notes |
2008-01-29 11:54:18 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
141 |
Status |
N |
Date |
2008-01-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-29 |
Time |
11:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-29 |
Time |
11:51 |
Sent To |
E |
|
Notes |
2008-01-29 11:51:44 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
140 |
Status |
N |
Date |
2008-01-11 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2008-01-11 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2008-01-11 |
Time |
10:34 |
Sent To |
B |
|
Notes |
2008-01-11 10:34:47 | TO ROBERT BROWNS DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
139 |
Status |
N |
Date |
2007-12-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-13 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-13 |
Time |
14:57 |
Sent To |
B |
|
Notes |
2007-12-13 14:57:39 | TO "RBROWN' DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
138 |
Status |
N |
Date |
2007-12-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-13 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-13 |
Time |
09:09 |
Sent To |
E |
|
Notes |
2007-12-13 09:10:08 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
137 |
Status |
N |
Date |
2007-11-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-27 |
Time |
15:09 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-27 |
Time |
15:09 |
Sent To |
M |
|
Notes |
2007-11-27 15:09:37 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
136 |
Status |
N |
Date |
2007-11-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-15 |
Time |
14:24 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-15 |
Time |
14:24 |
Sent To |
B |
|
Notes |
2007-11-15 14:25:14 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
135 |
Status |
N |
Date |
2007-11-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-14 |
Time |
12:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-14 |
Time |
12:21 |
Sent To |
B |
|
Notes |
2007-11-14 12:22:17 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
134 |
Status |
N |
Date |
2007-11-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-09 |
Time |
15:36 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-09 |
Time |
15:36 |
Sent To |
B |
|
Notes |
2007-11-09 15:36:49 | TO "RBROWN" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
133 |
Status |
N |
Date |
2007-11-08 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-08 |
Time |
10:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-08 |
Time |
10:41 |
Sent To |
|
|
Notes |
2007-11-21 14:28:58 | TO "COMM" BD#31 | 2007-11-08 10:41:22 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
132 |
Status |
N |
Date |
2007-11-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-05 |
Time |
14:32 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-05 |
Time |
14:32 |
Sent To |
E |
|
Notes |
2007-11-05 14:32:32 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
131 |
Status |
N |
Date |
2007-11-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-05 |
Time |
12:55 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-05 |
Time |
12:55 |
Sent To |
B |
|
Notes |
2007-11-05 12:55:39 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
130 |
Status |
N |
Date |
2007-10-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-30 |
Time |
11:03 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-30 |
Time |
11:03 |
Sent To |
B |
|
Notes |
2007-10-30 11:04:01 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
129 |
Status |
N |
Date |
2007-10-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-24 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-24 |
Time |
10:35 |
Sent To |
B |
|
Notes |
2007-10-24 10:35:41 | TO "RBROWN" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
128 |
Status |
N |
Date |
2007-10-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-22 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-22 |
Time |
10:31 |
Sent To |
E |
|
Notes |
2007-10-22 10:31:52 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
127 |
Status |
N |
Date |
2007-10-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-16 |
Time |
10:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-16 |
Time |
10:19 |
Sent To |
|
|
Notes |
2007-11-05 09:53:58 | TO "COMM" BD#61 | 2007-10-16 10:19:50 | WAITING FOR "COMM" BD--REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
126 |
Status |
N |
Date |
2007-10-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-15 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-15 |
Time |
15:29 |
Sent To |
FIRE |
|
Notes |
2007-10-15 15:30:21 | TO "F" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
125 |
Status |
N |
Date |
2007-10-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-15 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-15 |
Time |
10:10 |
Sent To |
B |
|
Notes |
2007-10-15 10:10:54 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
124 |
Status |
N |
Date |
2007-10-11 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2007-10-11 |
Time |
17:45 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2007-10-11 |
Time |
17:45 |
Sent To |
|
|
Notes |
2007-10-11 17:49:35 | BUILDING SUBMITTAL SENT TO R BROWN FOR REVIEW. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
123 |
Status |
N |
Date |
2007-10-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-10 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-10 |
Time |
14:29 |
Sent To |
M |
|
Notes |
2007-10-10 14:29:33 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
122 |
Status |
N |
Date |
2007-10-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-09 |
Time |
13:15 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-09 |
Time |
13:15 |
Sent To |
E |
|
Notes |
2007-10-25 15:50:02 | TO "COMM" BD#4 | 2007-10-09 13:16:54 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
121 |
Status |
N |
Date |
2007-09-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-28 |
Time |
15:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-28 |
Time |
15:21 |
Sent To |
B |
|
Notes |
2007-09-28 15:21:20 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
120 |
Status |
N |
Date |
2007-09-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-28 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-28 |
Time |
13:08 |
Sent To |
E |
|
Notes |
2007-09-28 13:09:02 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
119 |
Status |
N |
Date |
2007-09-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-28 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-28 |
Time |
11:49 |
Sent To |
B |
|
Notes |
2007-09-28 11:51:58 | TO "RBROWN' DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
118 |
Status |
N |
Date |
2007-09-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-27 |
Time |
16:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-27 |
Time |
16:30 |
Sent To |
|
|
Notes |
2007-09-27 16:31:19 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
117 |
Status |
N |
Date |
2007-09-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-27 |
Time |
12:28 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-27 |
Time |
12:28 |
Sent To |
|
|
Notes |
2007-10-19 08:29:49 | TO "COMM" BD#25 | 2007-09-27 12:28:41 | WAITING FOR "COMM" BD-REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
116 |
Status |
N |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-24 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-24 |
Time |
11:19 |
Sent To |
B |
|
Notes |
2007-09-24 11:19:28 | TO "RBROWN" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
115 |
Status |
N |
Date |
2007-09-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-06 |
Time |
12:40 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-06 |
Time |
12:40 |
Sent To |
M |
|
Notes |
2007-09-06 12:41:04 | TO "M" BOX#REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
114 |
Status |
N |
Date |
2007-09-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-06 |
Time |
08:35 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-06 |
Time |
08:35 |
Sent To |
B |
|
Notes |
2007-09-06 08:35:44 | TO "RBROWN" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
113 |
Status |
N |
Date |
2007-08-31 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-31 |
Time |
09:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-31 |
Time |
09:59 |
Sent To |
B |
|
Notes |
2007-08-31 09:59:44 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
112 |
Status |
N |
Date |
2007-08-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-29 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-29 |
Time |
14:44 |
Sent To |
|
|
Notes |
2007-08-29 14:45:07 | TO "COMM" BD#33--REV DATED FOR 8/3/07 THAT WAS WAITING | | FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
111 |
Status |
N |
Date |
2007-08-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-27 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-27 |
Time |
15:51 |
Sent To |
B |
|
Notes |
2007-08-27 15:52:33 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
110 |
Status |
N |
Date |
2007-08-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-23 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-23 |
Time |
15:52 |
Sent To |
B |
|
Notes |
2007-08-23 15:52:50 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
109 |
Status |
N |
Date |
2007-08-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-23 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-23 |
Time |
11:29 |
Sent To |
M |
|
Notes |
2007-08-23 11:30:17 | TO "RREQUIERO" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
108 |
Status |
N |
Date |
2007-08-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-21 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-21 |
Time |
14:11 |
Sent To |
B |
|
Notes |
2007-08-21 14:11:37 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
107 |
Status |
N |
Date |
2007-08-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-16 |
Time |
10:33 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-16 |
Time |
10:33 |
Sent To |
B |
|
Notes |
2007-08-16 10:34:08 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
106 |
Status |
N |
Date |
2007-08-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-14 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-14 |
Time |
13:17 |
Sent To |
B |
|
Notes |
2007-08-14 13:18:18 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
105 |
Status |
N |
Date |
2007-08-13 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-13 |
Time |
10:52 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-13 |
Time |
10:52 |
Sent To |
B |
|
Notes |
2007-08-13 10:52:40 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
104 |
Status |
N |
Date |
2007-08-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-06 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-06 |
Time |
14:10 |
Sent To |
|
|
Notes |
2007-08-16 15:44:18 | TO "COMM" BD#61 | 2007-08-07 19:36:18 | A SHEETS, ROUTED TO RB INCOMING BOX. | 2007-08-06 14:11:33 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
103 |
Status |
N |
Date |
2007-08-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-02 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-02 |
Time |
11:45 |
Sent To |
B |
|
Notes |
2007-08-02 11:46:17 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
102 |
Status |
N |
Date |
2007-08-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-02 |
Time |
11:38 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-02 |
Time |
11:38 |
Sent To |
|
|
Notes |
2007-08-14 14:53:30 | TO "COMM" BD#19 | 2007-08-02 11:38:31 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
101 |
Status |
N |
Date |
2007-07-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-30 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-30 |
Time |
13:58 |
Sent To |
|
|
Notes |
2007-07-30 13:59:07 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
100 |
Status |
N |
Date |
2007-07-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-30 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-30 |
Time |
13:36 |
Sent To |
E |
|
Notes |
2007-07-30 13:36:24 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
99 |
Status |
N |
Date |
2007-07-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-30 |
Time |
10:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-30 |
Time |
10:43 |
Sent To |
B |
|
Notes |
2007-07-30 10:44:16 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
98 |
Status |
N |
Date |
2007-07-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-27 |
Time |
11:32 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-27 |
Time |
11:32 |
Sent To |
|
|
Notes |
2007-07-27 11:33:10 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
97 |
Status |
N |
Date |
2007-07-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-24 |
Time |
16:44 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-24 |
Time |
16:43 |
Sent To |
B |
|
Notes |
2007-07-24 16:44:23 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
96 |
Status |
N |
Date |
2007-07-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-19 |
Time |
08:25 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-19 |
Time |
08:25 |
Sent To |
M |
|
Notes |
2007-07-19 08:25:45 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
95 |
Status |
N |
Date |
2007-07-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-12 |
Time |
08:57 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-12 |
Time |
08:57 |
Sent To |
B |
|
Notes |
2007-07-12 08:57:34 | TO "RBROWN" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
94 |
Status |
N |
Date |
2007-07-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-11 |
Time |
11:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-11 |
Time |
11:40 |
Sent To |
B |
|
Notes |
2007-07-11 11:42:22 | TO "RBROWN" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
93 |
Status |
N |
Date |
2007-07-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-05 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-05 |
Time |
11:16 |
Sent To |
|
|
Notes |
2007-07-17 15:49:16 | TO "COMM" BD#23 | 2007-07-05 11:16:33 | WAITING FOR "COMM"BD--REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
92 |
Status |
N |
Date |
2007-07-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-03 |
Time |
16:36 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-03 |
Time |
16:36 |
Sent To |
B |
|
Notes |
2007-07-03 16:36:56 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
91 |
Status |
N |
Date |
2007-06-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-29 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-29 |
Time |
10:21 |
Sent To |
B |
|
Notes |
2007-06-29 10:21:45 | TO "RBROWN" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
90 |
Status |
N |
Date |
2007-06-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-27 |
Time |
10:55 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-27 |
Time |
10:55 |
Sent To |
B |
|
Notes |
2007-06-27 10:55:46 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
89 |
Status |
N |
Date |
2007-06-25 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-25 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-25 |
Time |
14:38 |
Sent To |
B |
|
Notes |
2007-06-25 14:38:29 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
88 |
Status |
N |
Date |
2007-06-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-24 |
Time |
17:44 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-24 |
Time |
17:44 |
Sent To |
E |
|
Notes |
2007-06-24 17:44:59 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
87 |
Status |
N |
Date |
2007-06-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-22 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-22 |
Time |
11:19 |
Sent To |
B |
|
Notes |
2007-06-22 11:20:18 | TO "RBROWN" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
86 |
Status |
N |
Date |
2007-06-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-21 |
Time |
10:35 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-21 |
Time |
10:35 |
Sent To |
B |
|
Notes |
2007-06-21 10:35:30 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
85 |
Status |
N |
Date |
2007-06-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-18 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-18 |
Time |
11:21 |
Sent To |
B |
|
Notes |
2007-06-18 11:21:29 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
84 |
Status |
N |
Date |
2007-06-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-11 |
Time |
08:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-11 |
Time |
08:29 |
Sent To |
B |
|
Notes |
2007-06-11 08:29:40 | TO "RBROWN" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
83 |
Status |
N |
Date |
2007-06-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-06 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-06 |
Time |
16:17 |
Sent To |
B |
|
Notes |
2007-06-06 16:17:38 | TO "RBROWN" DESK/ 4 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
82 |
Status |
N |
Date |
2007-06-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-04 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-04 |
Time |
09:23 |
Sent To |
B |
|
Notes |
2007-06-04 09:24:00 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
81 |
Status |
N |
Date |
2007-05-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-29 |
Time |
16:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-29 |
Time |
16:50 |
Sent To |
B |
|
Notes |
2007-05-29 16:51:04 | TO "RBROWN" DESK/ 2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
80 |
Status |
N |
Date |
2007-05-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-23 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-23 |
Time |
10:12 |
Sent To |
B |
|
Notes |
2007-05-23 10:12:33 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
79 |
Status |
N |
Date |
2007-05-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-22 |
Time |
16:38 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-22 |
Time |
16:38 |
Sent To |
B |
|
Notes |
2007-05-22 16:39:12 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
78 |
Status |
N |
Date |
2007-05-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-18 |
Time |
15:32 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-18 |
Time |
15:32 |
Sent To |
E |
|
Notes |
2007-05-18 15:32:53 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
77 |
Status |
N |
Date |
2007-05-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-15 |
Time |
10:27 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-15 |
Time |
10:27 |
Sent To |
B |
|
Notes |
2007-05-15 10:27:44 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
76 |
Status |
N |
Date |
2007-05-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-04 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-04 |
Time |
10:25 |
Sent To |
B |
|
Notes |
2007-05-04 10:25:34 | TO "RBROWN" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
75 |
Status |
N |
Date |
2007-05-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-03 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-03 |
Time |
15:45 |
Sent To |
B |
|
Notes |
2007-05-03 15:45:31 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
74 |
Status |
N |
Date |
2007-05-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-02 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-02 |
Time |
15:48 |
Sent To |
|
|
Notes |
2007-05-14 14:29:42 | TO "COMM" BD#57 | 2007-05-02 15:49:07 | WAITING FOR "COMM" BD-REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
73 |
Status |
N |
Date |
2007-05-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-05-02 |
Time |
09:38 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-05-02 |
Time |
09:38 |
Sent To |
B |
|
Notes |
2007-05-02 09:39:04 | TO "RBROWN" DESK/4 SUBMITTALS AND 1 REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
72 |
Status |
N |
Date |
2007-04-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-27 |
Time |
09:04 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-27 |
Time |
09:04 |
Sent To |
|
|
Notes |
2007-04-27 09:08:09 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
71 |
Status |
N |
Date |
2007-04-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-23 |
Time |
11:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-23 |
Time |
11:41 |
Sent To |
B |
|
Notes |
2007-04-23 11:41:33 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
70 |
Status |
N |
Date |
2007-04-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-19 |
Time |
16:12 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-19 |
Time |
16:12 |
Sent To |
P |
|
Notes |
2007-04-19 16:12:27 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
69 |
Status |
N |
Date |
2007-04-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-18 |
Time |
16:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-18 |
Time |
16:41 |
Sent To |
B |
|
Notes |
2007-04-18 16:41:29 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
68 |
Status |
N |
Date |
2007-04-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-16 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-16 |
Time |
10:02 |
Sent To |
B |
|
Notes |
2007-04-16 10:02:38 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
67 |
Status |
N |
Date |
2007-04-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-11 |
Time |
11:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-11 |
Time |
11:00 |
Sent To |
B |
|
Notes |
2007-04-11 11:01:28 | TO "RBROWN" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
66 |
Status |
N |
Date |
2007-04-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-04-09 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-04-09 |
Time |
09:43 |
Sent To |
B |
|
Notes |
2007-04-09 09:43:54 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
65 |
Status |
N |
Date |
2007-04-06 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2007-04-06 |
Time |
17:21 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2007-04-06 |
Time |
17:21 |
Sent To |
B |
|
Notes |
2007-04-06 17:21:12 | TO ROBERT BROWN |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
64 |
Status |
N |
Date |
2007-04-03 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2007-04-03 |
Time |
17:18 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2007-04-03 |
Time |
17:18 |
Sent To |
B |
|
Notes |
2007-04-03 17:18:44 | TWO SUBMITTALS TO ROBERT BROWN |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
63 |
Status |
N |
Date |
2007-03-27 |
|
|
Cont ID |
|
Sent By |
dpolen |
Date |
2007-03-27 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
dpolen |
Date |
2007-03-27 |
Time |
10:29 |
Sent To |
|
|
Notes |
2007-03-27 10:30:12 | TO ROBERT B. DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
62 |
Status |
N |
Date |
2007-03-26 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2007-03-26 |
Time |
18:30 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2007-03-26 |
Time |
18:30 |
Sent To |
P |
|
Notes |
2007-03-26 18:30:58 | TO KEN STEVENS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
61 |
Status |
N |
Date |
2007-03-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-24 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-24 |
Time |
15:11 |
Sent To |
B |
|
Notes |
2007-03-24 15:11:53 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
60 |
Status |
N |
Date |
2007-03-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-23 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-23 |
Time |
11:53 |
Sent To |
B |
|
Notes |
2007-03-23 11:54:16 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
59 |
Status |
N |
Date |
2007-03-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-23 |
Time |
09:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-23 |
Time |
09:14 |
Sent To |
B |
|
Notes |
2007-03-23 09:14:38 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
58 |
Status |
N |
Date |
2007-03-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-16 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-16 |
Time |
14:47 |
Sent To |
B |
|
Notes |
2007-03-16 14:47:30 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
57 |
Status |
N |
Date |
2007-03-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-16 |
Time |
11:55 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-16 |
Time |
11:55 |
Sent To |
M |
|
Notes |
2007-03-16 11:55:41 | TO "M" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
56 |
Status |
N |
Date |
2007-03-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-16 |
Time |
11:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-16 |
Time |
11:51 |
Sent To |
P |
|
Notes |
2007-03-16 11:51:44 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
55 |
Status |
N |
Date |
2007-03-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-16 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-16 |
Time |
11:24 |
Sent To |
B |
|
Notes |
2007-03-16 11:24:55 | TO "RBROWN" DESK/2 REV'S |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
54 |
Status |
N |
Date |
2007-03-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-16 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-16 |
Time |
11:20 |
Sent To |
B |
|
Notes |
2007-03-16 11:20:47 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
53 |
Status |
N |
Date |
2007-03-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-16 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-16 |
Time |
11:17 |
Sent To |
M |
|
Notes |
2007-03-16 11:18:00 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
52 |
Status |
N |
Date |
2007-03-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-16 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-16 |
Time |
11:08 |
Sent To |
E |
|
Notes |
2007-03-16 11:08:28 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
51 |
Status |
N |
Date |
2007-03-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-16 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-16 |
Time |
10:48 |
Sent To |
P |
|
Notes |
2007-03-16 10:48:59 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
50 |
Status |
N |
Date |
2007-03-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-15 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-15 |
Time |
13:44 |
Sent To |
B |
|
Notes |
2007-03-15 13:45:10 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
49 |
Status |
N |
Date |
2007-03-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-10 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-10 |
Time |
15:00 |
Sent To |
B |
|
Notes |
2007-03-10 15:00:22 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
48 |
Status |
N |
Date |
2007-03-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-09 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-09 |
Time |
13:27 |
Sent To |
B |
|
Notes |
2007-03-09 13:27:55 | TO "RBROWN" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
47 |
Status |
N |
Date |
2007-03-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-03-06 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-03-06 |
Time |
16:19 |
Sent To |
B |
|
Notes |
2007-03-06 16:20:11 | TO "RBROWN" DESK/4 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
46 |
Status |
N |
Date |
2007-02-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-27 |
Time |
11:36 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-27 |
Time |
11:36 |
Sent To |
B |
|
Notes |
2007-02-27 11:36:45 | TO "RBROWN" BOX/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
45 |
Status |
N |
Date |
2007-02-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-22 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-22 |
Time |
11:35 |
Sent To |
B |
|
Notes |
2007-02-22 11:36:32 | TO "RBROWN" DESK/3 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
44 |
Status |
N |
Date |
2007-02-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-14 |
Time |
14:56 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-14 |
Time |
14:56 |
Sent To |
B |
|
Notes |
2007-02-14 14:57:05 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
43 |
Status |
N |
Date |
2007-02-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-12 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-12 |
Time |
09:22 |
Sent To |
B |
|
Notes |
2007-02-12 09:22:33 | TO "RBROWN" DESK/6SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
42 |
Status |
F |
Date |
2007-02-08 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-08 |
Time |
08:16 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-08 |
Time |
08:16 |
Sent To |
B |
|
Notes |
2007-02-08 08:17:08 | TO "RBROWN" DESK/ 2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
41 |
Status |
N |
Date |
2007-02-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-06 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-06 |
Time |
11:12 |
Sent To |
B |
|
Notes |
2007-02-06 11:13:24 | TO "RBROWN" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
40 |
Status |
N |
Date |
2007-02-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-01 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-01 |
Time |
15:15 |
Sent To |
B |
|
Notes |
2007-02-01 15:15:22 | TO "RBROWN" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
39 |
Status |
N |
Date |
2007-01-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-29 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-29 |
Time |
16:34 |
Sent To |
B |
|
Notes |
2007-01-29 16:35:22 | TO "RBROWN" DESK/ 3 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
38 |
Status |
N |
Date |
2007-01-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-18 |
Time |
16:34 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-18 |
Time |
16:34 |
Sent To |
B |
|
Notes |
2007-01-18 16:35:00 | TO "RBROWN" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
37 |
Status |
N |
Date |
2007-01-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-17 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-17 |
Time |
16:20 |
Sent To |
B |
|
Notes |
2007-01-17 16:21:05 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
36 |
Status |
N |
Date |
2007-01-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-17 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-17 |
Time |
16:16 |
Sent To |
P |
|
Notes |
2007-01-17 16:16:36 | TO "P" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
35 |
Status |
N |
Date |
2007-01-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-17 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-17 |
Time |
10:04 |
Sent To |
B |
|
Notes |
2007-01-17 10:05:15 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
34 |
Status |
N |
Date |
2007-01-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-09 |
Time |
19:10 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-09 |
Time |
19:10 |
Sent To |
B |
|
Notes |
2007-01-09 19:10:33 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
33 |
Status |
N |
Date |
2007-01-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-04 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-04 |
Time |
11:40 |
Sent To |
B |
|
Notes |
2007-01-04 11:40:33 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
32 |
Status |
N |
Date |
2007-01-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-01-03 |
Time |
17:37 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-01-03 |
Time |
17:37 |
Sent To |
B |
|
Notes |
2007-01-03 17:38:16 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
31 |
Status |
N |
Date |
2006-12-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-27 |
Time |
15:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-27 |
Time |
15:53 |
Sent To |
B |
|
Notes |
2006-12-27 15:53:30 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
30 |
Status |
N |
Date |
2006-12-26 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-26 |
Time |
14:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-26 |
Time |
14:30 |
Sent To |
B |
|
Notes |
2006-12-26 14:31:24 | TO "RBROWN" DESK/ 2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
29 |
Status |
N |
Date |
2006-12-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-20 |
Time |
11:33 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-20 |
Time |
11:33 |
Sent To |
B |
|
Notes |
2006-12-20 11:33:53 | TO "RBROWN" DESK/ 2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
28 |
Status |
N |
Date |
2006-12-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-19 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-19 |
Time |
09:07 |
Sent To |
P |
|
Notes |
2006-12-19 09:07:24 | TO"P" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
27 |
Status |
N |
Date |
2006-12-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-19 |
Time |
08:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-19 |
Time |
08:59 |
Sent To |
E |
|
Notes |
2006-12-19 09:00:50 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
26 |
Status |
N |
Date |
2006-12-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-19 |
Time |
08:58 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-19 |
Time |
08:58 |
Sent To |
M |
|
Notes |
2006-12-19 08:58:37 | TO "M" BOX/2 REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
25 |
Status |
N |
Date |
2006-12-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-19 |
Time |
08:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-19 |
Time |
08:53 |
Sent To |
|
|
Notes |
2007-01-11 10:02:58 | TO "COMM" BD#30 | 2006-12-19 08:54:20 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
24 |
Status |
N |
Date |
2006-12-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-17 |
Time |
17:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-17 |
Time |
17:41 |
Sent To |
E |
|
Notes |
2006-12-17 17:41:30 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
23 |
Status |
N |
Date |
2006-12-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-17 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-17 |
Time |
14:26 |
Sent To |
B |
|
Notes |
2006-12-17 14:26:44 | TO "RBROWN" DESK/5 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
22 |
Status |
N |
Date |
2006-12-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-12 |
Time |
15:18 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-12 |
Time |
15:18 |
Sent To |
B |
|
Notes |
2006-12-12 15:19:07 | TO "RBROWN" DESK/3 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
21 |
Status |
N |
Date |
2006-12-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-07 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-07 |
Time |
11:44 |
Sent To |
B |
|
Notes |
2006-12-07 11:45:24 | TO "RBROWN' DESK/3 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
20 |
Status |
N |
Date |
2006-12-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-06 |
Time |
13:05 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-06 |
Time |
13:05 |
Sent To |
B |
|
Notes |
2006-12-06 13:06:16 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
19 |
Status |
N |
Date |
2006-12-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-05 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-05 |
Time |
10:31 |
Sent To |
B |
|
Notes |
2006-12-05 10:31:52 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
18 |
Status |
N |
Date |
2006-12-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-01 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-01 |
Time |
11:16 |
Sent To |
B |
|
Notes |
2006-12-01 11:16:31 | TO "RBROWN" DESK/REV-TRASH CHUTE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
17 |
Status |
N |
Date |
2006-12-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-01 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-01 |
Time |
11:13 |
Sent To |
B |
|
Notes |
2006-12-01 11:14:09 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
16 |
Status |
N |
Date |
2006-11-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-21 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-11-21 |
Time |
16:08 |
Sent To |
B |
|
Notes |
2006-11-20 14:22:59 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
15 |
Status |
N |
Date |
2006-11-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-17 |
Time |
11:42 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-11-17 |
Time |
11:42 |
Sent To |
B |
|
Notes |
2006-11-17 11:42:28 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
14 |
Status |
N |
Date |
2006-11-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-15 |
Time |
11:10 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-11-15 |
Time |
11:10 |
Sent To |
B |
|
Notes |
2006-11-15 11:10:59 | TO "RBROWN" DESK/7 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
13 |
Status |
N |
Date |
2006-11-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-06 |
Time |
10:22 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-11-06 |
Time |
10:22 |
Sent To |
B |
|
Notes |
2006-11-06 10:22:28 | TO "RBROWN" DESK/ 2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
12 |
Status |
N |
Date |
2006-10-25 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-10-25 |
Time |
09:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-25 |
Time |
09:07 |
Sent To |
B |
|
Notes |
2006-10-25 09:07:43 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
11 |
Status |
N |
Date |
2006-10-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-10-17 |
Time |
09:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-17 |
Time |
09:53 |
Sent To |
B |
|
Notes |
2006-10-17 09:54:44 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2006-10-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-10-12 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-12 |
Time |
15:26 |
Sent To |
B |
|
Notes |
2006-10-12 15:26:38 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2006-09-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-09-29 |
Time |
09:34 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-29 |
Time |
09:34 |
Sent To |
B |
|
Notes |
2006-09-29 00:00:00 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2006-09-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-09-22 |
Time |
15:27 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-22 |
Time |
15:27 |
Sent To |
B |
|
Notes |
2006-09-22 00:00:00 | TO "RBROWN" DESK/5 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2006-09-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-09-22 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-22 |
Time |
09:06 |
Sent To |
B |
|
Notes |
2006-09-22 00:00:00 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2006-09-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-09-09 |
Time |
16:17 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-09 |
Time |
16:17 |
Sent To |
B |
|
Notes |
2006-09-09 00:00:00 | TO "RBROWN" DESK/ 6 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2006-08-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-08-28 |
Time |
08:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-08-28 |
Time |
08:40 |
Sent To |
B |
|
Notes |
2006-08-28 00:00:00 | TO "RBROWN" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2006-08-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-08-18 |
Time |
09:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-08-18 |
Time |
09:30 |
Sent To |
B |
|
Notes |
2006-08-18 00:00:00 | SUBMITTAL TO "COMM" BD#47 W/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-08-08 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-08-08 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-08-08 |
Time |
11:05 |
Sent To |
|
|
Notes |
2006-08-11 00:00:00 | TO "COMM" BD#47 | 2006-08-08 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-04-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-04-27 |
Time |
15:25 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-04-27 |
Time |
15:25 |
Sent To |
|
|
Notes |
2006-05-22 00:00:00 | TO "COMM" BD#13/ROLLED PLANS BY | | "LMARTINEZ" OFFICE | 2006-04-27 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-02-20 |
|
|
Cont ID |
|
Sent By |
rbrown |
Date |
2006-02-20 |
Time |
23:30 |
Rev Time |
0.00 |
Received By |
rbrown |
Date |
2005-09-28 |
Time |
18:42 |
Sent To |
|
|
Notes |
2005-10-03 00:00:00 | TO "COMM" BD#14/PLANS ON RACK | 2005-09-28 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
P |
Date |
2008-09-10 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2008-09-10 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2008-09-10 |
Time |
16:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
24 |
Status |
P |
Date |
2008-03-31 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-03-31 |
Time |
16:22 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-03-31 |
Time |
13:13 |
Sent To |
PC |
|
Notes |
2008-03-31 16:26:38 | ADDED NEW PAGE AC-30 WITH DERM APPROVAL FOR 1500 GALLON | | FUEL TANK. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
23 |
Status |
P |
Date |
2008-03-25 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-03-25 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-03-25 |
Time |
13:33 |
Sent To |
PC |
|
Notes |
2008-03-25 13:33:53 | PG AC-11 REV.14 OK |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
22 |
Status |
F |
Date |
2008-03-25 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-03-25 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-03-25 |
Time |
13:30 |
Sent To |
PC |
|
Notes |
2008-03-25 13:32:59 | PG AC-30 NEW 1500 GALLON DIESEL STORAGE TANK FOR | | EMERGENCY GENERATOR WITH ALLL RELATED FUEL PIPING. ALL | | ABOVE-GROUND FUEL STORAGE TANKS >550 GALLONS SHALL BE | | SUBMITTED TO PALM BEACH COUNTY DERM FOR PRIOR APPROVAL. | | FOR MORE INFORMATION PLEASE CONTACT DERM AT | | 561-233-2400. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
21 |
Status |
P |
Date |
2008-03-25 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-03-25 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-03-25 |
Time |
10:32 |
Sent To |
PC |
|
Notes |
2008-03-25 13:28:14 | PG AC-5 REV.17 RESTAMP. 3 COPIES RETURNED TO | | CONTRACTOR | | PG AC-19 REV.2 RESTAMP. 3 COPIES RETURNED TO CONTRACTOR |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
20 |
Status |
P |
Date |
2008-02-16 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-02-16 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-02-16 |
Time |
15:18 |
Sent To |
PC |
|
Notes |
2008-02-16 15:20:40 | REVISED PAGES AS FOLLOWS: | | AC-1 REV.12 | | AC-4 REV.15 | | AC-5 REV.17 | | AC-6 REV.9 | | AC-7 REV.21 | | AC-8 REV.2 | | AC-19 REV.2 | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
19 |
Status |
P |
Date |
2008-02-16 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-02-16 |
Time |
13:57 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-02-16 |
Time |
13:53 |
Sent To |
|
|
Notes |
2008-02-16 13:57:47 | PG AC-5 REVISION 16 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
18 |
Status |
P |
Date |
2007-12-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-12-24 |
Time |
08:51 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-12-24 |
Time |
08:51 |
Sent To |
E |
|
Notes |
2007-12-24 08:58:23 | ** SUBMITTAL FOR SAUNA ** | | *** PROVISO *** | | 1) A VENTILATION OPENING INTO THE SAUNA ROOM SHALL BE | | PROVIDED. THE OPENING SHALL BE NOT LESS THAN 4 INCHES | | BY 8 INCHES (102 MM BY 203 MM) LOCATED NEAR THE TOP OF | | THE DOOR INTO THE SAUNA ROOM. PER 2004 FBC/M 914.5. | | | | 2)WARNING NOTICE. | | THE FOLLOWING PERMANENT NOTICE, CONSTRUCTED OF APPROVED | | MATERIAL, SHALL BE MECHANICALLY ATTACHED TO THE SAUNA | | ROOM ON THE OUTSIDE: | | WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE | | EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR | | HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA. | | THE WORDS SHALL CONTRAST WITH THE BACKGROUND AND THE | | WORDING SHALL BE IN LETTERS NOT LESS THAN 0.25-INCH | | (6.4 MM) HIGH. PER 2004 FBC/M 914.5.1. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | | | ** 4-30-08UPDATE TO PROVISO. IF THE SAUNA HEATER IS | | ELECTRIC AND NOT FUEL BURNING THEN VENTILATION WILL NOT | | BE REQUIRED AND SAUNA SHALL BE INSTALLED PER | | MANUFACTURES INSTRUCTIONS, PER 2004 FBC/M 304.1. ** | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
17 |
Status |
P |
Date |
2007-12-07 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-12-07 |
Time |
08:21 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-12-06 |
Time |
16:20 |
Sent To |
PC |
|
Notes |
2007-12-07 08:24:18 | REVISED MECHANICAL AS FOLLOWS: | | AC-1 REV.11 | | AC-2 REV.8 | | AC-3 REV.7 | | AC-4 REV.15 | | AC-13 REV.5 | | AC-24 REV.3 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
16 |
Status |
P |
Date |
2007-10-20 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-10-20 |
Time |
19:28 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-10-20 |
Time |
19:21 |
Sent To |
|
|
Notes |
2007-10-20 19:29:38 | PG AC-13 REV.4 | | PROVISO CONDITION HAS BEEN SATISFIED. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
15 |
Status |
|
Date |
2007-10-06 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-10-06 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-10-06 |
Time |
09:20 |
Sent To |
|
|
Notes |
2007-10-06 09:24:17 | NO REVIEW THIS STOP. CHECK-IN WAS AN ERROR. THIS REVIEW | | CHECKED IN ON 10/5/07.RJR |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
14 |
Status |
P |
Date |
2007-10-06 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-10-06 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-10-05 |
Time |
09:00 |
Sent To |
PC |
|
Notes |
2007-10-06 14:50:17 | AC-1 REV.10 | | AC-7 REV.18,19 | | AC-9 REV.5 | | AC-12 REV.2 | | AC-13 REV.3 W/ PROVISO | | AC-14 REV.14 | | AC-15 REV.3 | | AC-16 REV.5 | | AC-17 REV.2 | | AC-23 REV.15,16,17 | | AC-24 REV.3 | | | | **************PROVISO***************** | | AC-13 UNIT B-1: 6X6 DROP IN BATHROOM IS NO LONGER SHOWN | | TAPPING INTO SUPPLY TRUNK LINE. CORRECT AND RESUBMIT. | | | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
13 |
Status |
P |
Date |
2007-08-24 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-08-24 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-08-24 |
Time |
09:12 |
Sent To |
|
|
Notes |
2007-08-24 13:54:19 | MECH REVS PAGES: AC-1, AC-5, AC-6, AC-7, AC-8, AC-9, | | AC-10, AC-18, AC-19, AC-21, AC-22, AC-23, AC-24, AC-25, | | AC-29 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
12 |
Status |
F |
Date |
2007-08-18 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-08-18 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-08-18 |
Time |
13:40 |
Sent To |
E |
|
Notes |
2007-08-18 13:40:57 | AN ATTEMPT WAS MADE TO REVIEW ALL MECHANICAL REVISIONS | | CURRENTY IN THIS OFFICE. A REVIEW COULD NOT BE | | COMPLETED AT THIS TIME. THERE ARE SOME PAGES WHICH | | APPEAR 3 TIMES IN 3 DIFFERENT SUBMITTALS AND IN 3 | | DIFFERENT STAGES OF BEING REVISED WITH CHANGES THAT ARE | | NOT IN DATED ORDER. THESE MECHANICAL REVISIONS WERE | | SUBMITTED ON THE FOLLOWING DATES: | | | | 7/17/07, 7/27/07 AND 7/31/07 | | | | PLEASE TAKE ALL THREE OF THESE AND CONSOLIDATE THEM | | INTO A CONCISE, UP-TO-DATE SET OF REVISIONS TO BE | | REVIEWED AND INCORPORATED INTO THE PERMIT SET OF | | PLANS. | | | | THE 7/27 SUBMITTAL HAS ACCOMPANYING PLUMBING PLANS. THE | | MECHANICAL PLANS HAVE BEEN REMOVED AND THE PLUMBING | | PLANS ARE ROUTED TO THE PLUMBING REVIEWER'S INBOX. | | | | THE 7/31 SUBMITTAL HAS ACCOMPANYING ELECTRICAL PLANS. | | THE MECHANICAL PLANS HAVE BEEN REMOVED AND THE PLUMBING | | PLANS ARE ROUTED TO THE ELECTRICAL REVIEWER'S INBOX. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
11 |
Status |
F |
Date |
2007-08-18 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-08-18 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-08-18 |
Time |
10:18 |
Sent To |
P |
|
Notes |
2007-08-18 13:38:59 | AN ATTEMPT WAS MADE TO REVIEW ALL MECHANICAL REVISIONS | | CURRENTY IN THIS OFFICE. A REVIEW COULD NOT BE | | COMPLETED AT THIS TIME. THERE ARE SOME PAGES WHICH | | APPEAR 3 TIMES IN 3 DIFFERENT SUBMITTALS AND IN 3 | | DIFFERENT STAGES OF BEING REVISED WITH CHANGES THAT ARE | | NOT IN DATED ORDER. THESE MECHANICAL REVISIONS WERE | | SUBMITTED ON THE FOLLOWING DATES: | | | | 7/17/07, 7/27/07 AND 7/31/07 | | | | PLEASE TAKE ALL THREE OF THESE AND CONSOLIDATE THEM | | INTO A CONCISE, UP-TO-DATE SET OF REVISIONS TO BE | | REVIEWED AND INCORPORATED INTO THE PERMIT SET OF | | PLANS. | | | | THE 7/27 SUBMITTAL HAS ACCOMPANYING PLUMBING PLANS. THE | | MECHANICAL PLANS HAVE BEEN REMOVED AND THE PLUMBING | | PLANS ARE ROUTED TO THE PLUMBING REVIEWER'S INBOX. | | | | THE 7/31 SUBMITTAL HAS ACCOMPANYING ELECTRICAL PLANS. | | THE MECHANICAL PLANS HAVE BEEN REMOVED AND THE PLUMBING | | PLANS ARE ROUTED TO THE ELECTRICAL REVIEWER'S INBOX. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
10 |
Status |
P |
Date |
2007-06-13 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-06-13 |
Time |
13:14 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-06-13 |
Time |
13:11 |
Sent To |
|
|
Notes |
2007-06-13 13:14:50 | RECEIVED REPLACEMENT LETTERS WHICH WERE PREVIOUSLY | | REVIEWED ON 6/5/07. LETTER IS NOTICE OF ACCEPTANCE BY | | THE ENGINEER OF RECORD FOR THE TERMINATION OF RETURN | | AIR DUCT IN THE A/C CLOSET WITH A MINIMUM OF 3 INCHES | | CLEARANCE FROM THE SUPPLY DUCT TO ALLOW PROPER RETURN | | AIR FLOW. | | | | RJR |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
9 |
Status |
F |
Date |
2007-06-05 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-06-05 |
Time |
13:13 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-06-05 |
Time |
13:13 |
Sent To |
PC |
|
Notes |
2007-06-05 13:15:28 | SUBMITTAL LETTER FROM ENGINEER REGARDING RETURN AIR | | CLEARANCE IN APARTMENT A/C CLOSETS. | | | | THIS LETTER IS NOT ACCEPTED. PLEASE SUBMIT 3 COPIES OF | | THE LETTER EACH SIGNED AND SEALED BY THE ENGINEER OF | | RECORD WITH THE ENGINEER'S ORIGINAL SIGNATURE, NOT | | PHOTOCOPIED SIGNATURES. | | | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
8 |
Status |
F |
Date |
2007-06-01 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-06-01 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-05-30 |
Time |
09:56 |
Sent To |
|
|
Notes |
2007-06-01 11:42:15 | PAGES AC-4 AND AC-10 OK, REMAINING PAGES DENIED WITH | | COMMENTS. SEE BELOW: | | | | 1. AC-5: ONLY ONE OF THE TWO DUCTS PENETRATING JANITOR | | CLOSET WALL IS PROTECTED WITH FIRE DAMPER. PLEASE SHOW | | BOTH TO BE PROTECTED IN ACCORDANCE WITH FBC,M 607.1.2. | | | | 2. AC-9: WHAT IS THE DESIGNTION FOR THE ROOFTOP EXHAUST | | FAN ABOVE RISER TX-14? THIS INFORMATION WAS REMOVED | | FROM PREVIOUS PLANS. | | | | 3. AC-18: REVISION 21 REMOVED THE NOTE FOR 2 HOUR RATED | | DUCT, BUT EACH RISER STILL HAS A NOTE CALLING FOR FIRE | | RATED DUCT. PLEASE CLARIFY. IS THE DUCT TO BE RATED OR | | NOT? | | | | 4. AC-18: REVISION 20, PLEASE SHOW HOW HORIZONTAL | | ASSEMBLY PENETRATION AT BOTTOM OF TX-22 IS TO BE | | PROTECTED PER FBC CH.705. | | | | 5. AC-19: EQUIPMENT DESIGNATION ON THIS PAGE DOES NOT | | MATCH WITH RISERS BEING SERVED. EXAMPLE: REVISION SHOWS | | PAC 1 AND 2 FEEDING RISER P/A 1. HOWEVER, REVISED PG | | AC-10 SHOWS PAC-1 FEEDING RISER P/A 1 AND PAC-2 FEEDING | | RISER P/A 4. PLEASE COORDINATE DRAWINGS ACCORDINGLY. | | | | 6. AC-7: PLEASE CHANGE PAC-9 REFERENCES TO PAC-5 IN | | CONJUNCTION WITH REVISION 17. | | | | 7. AC-21 AND 22: ISO-PADS, IF LOCATED IN RETURN AIR | | PLENUMS, SHALL BE NON COMBUSTIBLE OR MEET THE 25/50 | | FLAME SPREAD/SMOKE DEVELOPMENT INDEX PER FBC,M | | 602.2.1. | | | | 8. AC-22: RISER 31 SHOWS PAC-9 ON ROOF. PAC-9 WAS | | RENAMED PAC-5 IN REVISION 17 ON PAGE AC-7. PLEASE | | COORDINATE DRAWINGS. | | | | 9. AC-23: EF-13,14,15,28 ARE ALL MARKED AS PART OF | | REVISION 11, BUT THEY DO NOT APPEAR AS PART OF REVISION | | 11 ON THE PREVIOUS AC-23 WHICH WAS REVIEWED ON SEPT 6, | | 2006. PLEASE MARK ALL REVISIONS CORRECTLY BASED ON WHEN | | THEY ARE FIRST ADDED TO PLANS. | | | | 10. AC-23: EF-28 ON SCHEDULE SHOWS 400 CFM, BUT FLOOR | | PLAN SHOWS 450. WHICH IS CORRECT? EF-29 ON SCHEDULE | | SHOWS 900 CFM, BUT FLOOR PLAN SHOWS 800. WHICH IS | | CORRECT? | | | | 11. AC-24: WHY ARE AC-12,13,14 CROSSED OUT ON HEAT PUMP | | SCHEDULE? SIZES AND OTHER RATINGS HAVE ALSO CHANGED FOR | | THESE UNITS, BUT THEY ARE NOT SHOWN AS HAVING BEEN | | REVISED. PLEASE CLARIFY. | | | | 12. AC-25: DETAIL FOR CONDENSATE OVERFLOW PROTECTION: A | | FLOAT SWITCH MAY BE INSTALLED INSIDE THE UNIT, BUT A | | FLOATSWITCH IS STILL REQUIRED IN THE AUXILIARY DRAIN | | PAN UNDER THE UNIT PER FBC,M 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
7 |
Status |
P |
Date |
2007-03-27 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-03-27 |
Time |
09:32 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-03-27 |
Time |
08:17 |
Sent To |
PC |
|
Notes |
2007-03-27 09:31:57 | REVISED PAGE AC-5 | | | | -------------------PROVISO------------------ | | | | DUCTS PENETRATING RATED ASSEMBLIES IN HVAC PUMP ROOM | | AND JANITOR'S CLOSET APPEAR TO BE MISSING FIRE DAMPERS. | | PLEASE CORRECT AND RESUBMIT PRIOR TO INSPECTION. | | | | RONALD J REGUEIRO | | 561-805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
6 |
Status |
F |
Date |
2007-03-22 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-03-22 |
Time |
18:51 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-03-19 |
Time |
15:09 |
Sent To |
|
|
Notes |
2007-03-22 18:51:38 | DENIED | | | | PAGES AC-4 AND AC-7 | | | | COMMENTS FOR THIS REVIEW ARE NUMBERED TO CORRELATE WITH | | PREVIOUS PLAN REVIEW COMMENTS FOR CONTINUITY. | | | | 1. OK | | | | 2. RESPONSE TO THIS COMMENT STATES "NO CHANGE. NOT PART | | OF THIS REV." IF THAT IS THE CASE, PLEASE REMOVE THE | | CLOUD AND THE DELTA-12 DESIGNATION. FBC 106.1.3. | | | | 3. AC-13 WAS MISTAKENLY OMITTED FROM THIS COMMENT. | | THERE ARE FOUR UNPROTECTED OPENINGS RESULTING FROM DUCT | | PENETRATIONS RELATED TO THIS SYSTEM. PLEASE SEE REVISED | | ARCHITECTURAL DRAWING A-2.4.5 REV. 6 FOR LOCATIONS OF | | ALL RATED WALLS WHICH MAY BE AFFECTED BY BY THESE DUCT | | SYSTEMS. ALL SUCH OPENINGS ARE TO BE PROTECTED PER | | FBC,M 607.1.2. | | | | 4. THIS AREA IS PART OF THE REVISION AS EF 28 AND | | RELATED DUCTS DO NOT APPEAR ON THE PREVIOUSLY REVIEWED | | PLAN (SEE REVISION 11 DATED 2/24/06). THE ADDED WORK ON | | THIS PAGE MAKES IT PART OF THIS REVISION EVEN IF IT IS | | INCORRECTLY DESIGNATED AS BEING PART OF A PREVIOUS | | REVISION. PLEASE CORRECT AND RESUBMIT. FBC 106.1.3. | | | | 5. OK | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
F |
Date |
2007-02-09 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-02-09 |
Time |
08:40 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-02-07 |
Time |
09:58 |
Sent To |
|
|
Notes |
2007-02-09 08:56:54 | -----------------DENIED---------------- | | | | 1. PG AC-4: EF-29 MAY NOT DISCHARGE INTO SHAFT GE3. | | THIS SHOULD BE AN INDIPENDENT SYSTEM DISCHARGING | | DIRECTLY TO THE OUTDOORS PER FBC,M 501.2 AND 501.3. | | | | 2. PG AC-4: REVISION DELTA12 DATED 9/22/06 - I AM | | UNABLE TO DETERMINE ANY CHANGE FROM PREVIOUS PLAN. | | PLEASE CLARIFY. | | | | 3. PG AC-7: BASED ON REVISED ARCHITECTURAL PAGE A-2.4.5 | | DATED 11/17/06, THE DUCT SYSTEM FOR AC-14 HAS SEVERAL | | UNPROTECTED OPENINGS IN RATED WALLS. PLEASE SHOW HOW | | THESE OPENINGS WILL BE PROTECTED IN THE RATED | | ASSEMBLIES PER FBC,M 607.1.2. | | | | 4. PG AC-7: ELEVATOR LOBBY AND STORAGE HVAC PLAN - THIS | | AREA IS MARKED AS REVISION DELTA11 BUT IT DOES NOT | | APPERAR ON PG AC-7 DATED 2/24/06 WHERE DELTA 11 | | ORIGINATED. PLEASE CLARIFY. SAME CONDITION OCCURS ON PG | | AC-23 REGARDING THE ADDITION OF EF 13,14,15 TO | | SCHEDULE. | | | | 5. AC-7: ELEVATOR LOBBY SYSTEM AC-15 HAS SEVERAL | | UNPROTECTED OPENINGS WHERE DUCTS PENETRATE RATED WALLS | | AS SHOWN ON REVISED PAGE A-2.4.3. PLEASE SHOW HOW HESE | | OPENINGS WILL BE PROTECTED PER FBC,M 607.1.2. | | | | RONALD J REGUEIRO | | 561-805-6734 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2006-11-16 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-11-16 |
Time |
07:30 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-11-16 |
Time |
07:30 |
Sent To |
|
|
Notes |
2006-11-16 07:47:24 | PROVISO: | | DRYER EXHAUST SHALL NOT EXCEED THE MANUFACTURER'S | | MAXIMUM LENGTH AS INDICATED IN THE INSTALLATION | | INSTRUCTIONS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2006-08-23 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-08-23 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-08-21 |
Time |
15:31 |
Sent To |
|
|
Notes |
2006-08-23 00:00:00 | PROVISO: | | RESPONSE TO COMMENT #3:ELEVATION | | PROVIDED ON PLAN SHEET AC-5.PLEASE | | NOTE, EXHAUST FROM EF-23 SHALL NOT | | TERMINATE IN A MANNER THAT NOXIOUS | | CONTAMINANTS MY BE DRAWN BACK INTO THE | | FRESH AIR INTAKE (INTAKE LOUVER). | | PLEASE PROVIDE CO SENSOR IN THIS ROOM. | | | | RESPONSE TO COMMENT #11: PLAN SHEET AC-4 | | VENTLATION FOR THE POOL EQUIPMENT ROOM | | #1 MAKE-UP AIR AND THE EXHAUST AIR WILL | | BE INTO THE GARAGE.PLEASE PROVIDE CO | | SENSOR IN THIS ROOM. | | | | PLAN SHEET AC-7 TERMINATION OF EF-12 IS | | WITHIN 3FT THE POOL EQUIPMENT ROOM #2. | | PER 2001 FMC 401.5 OPENING LOCATION FOR | | EXHAUST AND INTAKES SHALL BE LOCATED A | | MINIMUM OF 10 FT FROM BUILDINGS ON THE | | SAME LOT. | | | | RESPONSE TO COMMENT #19:INIDCATES | | GYPSUM BOARD OVER EXPOSED SURFACES OF | | THE DOOR.THIS IS NOT ACCEPTABLE. | | PLEASE PROVIDE SOLUTION / SUBMITTAL | | WITHIN 60 DAYS OF THE PERMIT ISSUANCE. | | | | COMMENT 20:THE FOLLOWING RESIDENTIAL | | HEAT PUMPS AC-7 & AC-8 ARE REQUIRED TO | | HAVE FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | OR BY AREA SMOKE DETECTORS PER 2001 FMC | | 606.2.1 & 606.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2006-07-11 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-07-06 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-07-06 |
Time |
09:44 |
Sent To |
|
|
Notes |
2006-07-06 00:00:00 | | | RESPONSE TO COMMENTS FROM REVIEW DATED | | 12/28/05 | | | | COMMENT #1 - OK | | COMMENT #2 - OK (SEE COMMENT #3) | | | | COMMENT #3 - REPONSE INDICATES SHEET | | AC-5 PROVIDES MUFFLER ELEVATION.PLAN | | ONLY INDICATES MUFFLER EXHAUST TO | | TERMINATE A MINIMUM OF 10 FT FROM O/A | | INTAKES.PLEASE PROVIDE ELEVATION FROM | | THE ADJOINGING GRADE LEVEL.PLEASE | | NOTE, MUFFLER AND EF-23 EXHAUST | | TERMINATIONS ARE WITHIN 10 FT OF THE | | FRESH AIR INTAKE TO THE GENERATOR ROOM. | | | | COMMENT #4 - OK - PLEASE PROVIDE | | INFORMATION ON WHAT WILL BE STORED IN | | THE JANITOR CLOSET #1. | | | | COMMENT #5 - OK FOR THE COMMON AREAS | | ONLY.PLEASE PROVIDE O/A CALCULATIONS | | FOR THE RESIDENCE IN ACCORDANCE WITH | | 2001 FBC 403.3, VENTILATION SYSTEMS FOR | | OTHER THAN R-E (ONE & TWO FAMILY | | DWELLINGS), SHALL BE DESIGNED TO HAVE | | THE CAPACITY TO SUPPLY THE MINIMUM | | OUTDOOR AIR FLOW RATE DETERMINED IN | | ACCORDANCE WITH TABLE 403.3. | | | | COMMENT #6 - OK | | COMMENT #7 - OK | | COMMENT #8 - OK | | COMMENT #9 - OK | | COMMENT #10 - PLAN SHEET AC-14 UNIT C-5, | | PLEASE NOTE, RETURN AIR TO BE EQUAL TO | | SUPPLY INTO THAT AREA.R/A SHALL BE A | | MINIMUM OF 8". | | | | COMMENT #11 - PLAN SHEET AC-4 | | VENTILATION FOR THE POOL EXHAUST AND AIR | | MAKE-UP ARE TERMINATING IN THE ENCLOSED | | GARAGE.GARAGE VENTILATION IS NOT | | CONTINUOUS, THEREFORE HOW WILL THIS | | APPLICATION PROVIDE FRESH AIR INTO THIS | | ROOM.PLAN SHEET AC-7 THE POOL | | EQUIPMENT ROOM LOUVERED DOOR APPEARS TO | | BE WITHIN 3FT OF THE TERMINATION OF | | EF-12.PLEASE INDICATE WHAT CHEMICALS & | | THE AMOUNT THAT WILL BE STORED IN WHICH | | EQUIPMENT ROOM. | | | | COMMENT #12 - OK, PLEASE NOTE, RESPONSE | | INDICATES COMBUSTION AIR CALCULATIONS | | ARE INDICATED ON PLAN SHEET AC-9 & | | AC-11.THERE ARE NO COMBUSTION AIR | | CALCS ON AC-9 BUT AC-7 INSTEAD. | | | | COMMENT #13 - OK, SEE COMMENT 12. | | | | COMMENT #14 - OK | | COMMENT #15 - PLAN SHEET AC-29, PROPOSED | | SMOKE CONTROL SYSTEM.PLEASE INDICATE | | WHICH METHOD IS INTEND TO BE UTILIZED | | UNDER 2001 FBC 412.5 ITEMS 1, 2, 3 OR 4. | | SHOULD SUBMITTAL BE UNDER ITEM 4, THIS | | MUST BE SUBMITTED TO THE BUILDING | | OFFICAL, NEIL MELICK.PLEASE PROVIDE | | ALL SUPPORTING DOCUMENTATION. | | | | COMMENT #16 - OK | | COMMENT #17 - OK | | COMMENT #18 - OK | | **************************************** | | NEW COMMENT | | 19. PLAN SHEET A-4.1 - THE DOOR SCHEDULE | | INDICATES THE A/C CLOSET DOOR IN THE | | APARTMENTS ARE TO BE WOOD.PLEASE | | VERIFY WITH THE DOOR MANUFACTURER IF | | THIS MEETS THE CRITERIA FOR A NON | | COMBUSTIBLE DOOR AS REQUIRED IN 2001 FMC | | 602.2.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2005-12-28 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2005-12-28 |
Time |
16:58 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2005-12-28 |
Time |
16:58 |
Sent To |
|
|
Notes |
2005-12-28 00:00:00 | DENIED:2001 FLORIDA BUILDING CODE | | | | 1.PLAN SHEET AC-1 EMERGENCY GENERATOR | | NOTE STATES 'SEE 1/4" SCALE DRAWING ON | | THIS SHEET FOR LAYOUT.DETAIL FOR THE | | LAYOUT IS NOT SHOWN. | | | | 2.PLEASE PROVIDE DISTANCE TO SIDEWALK | | FROM THE GENERATOR EXHAUST TERMINATION. | | | | 3.PLEASE PROVIDE DETAIL FOR THE | | GENERATOR WITH THE ELEVATION FOR MUFFLER | | EXHAUST.PLAN SHEET A-2.1.6 INDICATES | | LOUVERS, PLEASE SPECIFY INTAKES & | | EXHAUST. | | | | 4.PLAN SHEET AC-1 VENTILATION FOR | | VARIOUS ROOMS ARE NOT INDICATED | | (TELEPHONE, ELECTRICAL, PUMP ROOM, | | OFFICE AREAS, ETC). | | | | 5.PLEASE PROVIDE OUTSIDE AIR | | CALCULATIONS IN ACCORDANCE WITH 2001 FBC | | TABLE 403.3. | | | | 6.PROVIDE CALCULATIONS FOR THE GARAGE | | VENTILATION IN ACCORDANCE WITH 2001 FBC | | 411.4.2. | | | | 7.PLEASE NOTE, PLAN SHEET AC-1 FUTURE | | COMMERCIAL/RETAIL SPACE.SHOULD A | | RESTAURANT BE IN THE FUTURE PLANS | | CONSIDER LAYOUT FOR GREASE DUCT AND | | EXHAUST TERMINATION. | | | | 8.PLAN SHEETS AC-8 & 9 MECHANICAL | | ROOMS.PLANS DO NOT INDICATE | | VENTILATION FOR THE ROOMS. | | | | 9.PROVIDE LAYOUT FOR CONDENSER WATER | | PIPING.INDICATE PIPE SIZE & MATERIAL. | | | | | | 10. AC-12 UNIT C-5 DEN AREA WEST OF THE | | KITCHEN AREA, RETURN AIR IN NOT | | INDICATED.PLAN SHEET A1.1 SHOWS DOOR | | SEPARATING DEN.SHOW COMPLIANCE WITH | | 2001 FMC 601.4.PLEASE NOTE, RETURN AIR | | JUMPERS SHALL COMPLY WITH 2001 FMC 601.4 | | EXCEPTION 1 & 3. | | | | 11. PROVIDE INFORMATION & DETAILS FOR | | THE VENTILATION OF THE POOL EQUIPMENT | | ROOM. | | | | 12. PLAN SHEET P-1 ITEM #2 INDICATES GAS | | LINE.PLEASE INDICATE ALL GAS | | APPLIANCES. | | | | 13. PLAN SHEET P-7 INDICATES A BOILER | | ROOM.PLEASE PROVIDE VENTILATION & | | COMBUSTION AIR CALCULATIONS. | | | | 14. PLEASE PROVIDE SEQUENCE OF | | OPERATION. | | | | 15. PLEASE INDICATE METHOD OF SMOKE | | CONTROL PER 2001 FBC 412.5. | | | | 16. DRYER SHAFT & TRASH CHUTE SHALL BE | | EQUIPPED WITH FIRE SPRINKLERS IN | | ACCORDANCE WITH 2001 FBC 705.2.4.6 & | | NFPA 13 SECTION 8.14.2.2.1 & 13.15.2.1.1 | | | | 17. PLEASE PROVIDE MANUFACTURER | | SUBMITTAL DATA FOR THE GENERATOR, DRYER, | | PUMPS, ETC. | | | | 18. PLEASE PROVIDE ENERGY CALCULATIONS | | PER CHAPTER 13 OF THE 2001 FBC. | | | | PLEASE NOTE, PLANS APPEAR TO BE | | INCOMPLETE WHICH MAY GENERATE ADDITIONAL | | COMMENTS ON SUBSEQUENT REVIEWS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
19 |
Status |
P |
Date |
2008-03-29 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-03-29 |
Time |
13:09 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-03-29 |
Time |
13:09 |
Sent To |
|
|
Notes |
2008-03-29 13:10:02 | REVISIONS APPROVED--SHTS P-1, P-2, P-3, P-4 & P-5 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
18 |
Status |
F |
Date |
2008-02-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-02-23 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-02-23 |
Time |
15:02 |
Sent To |
|
|
Notes |
2008-02-23 15:14:46 | REVISIONS DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1. SHT P-1 PREVIOUS REVISION SIGNED, SEALED & DATED | | 4/18/07 SHOWED UP TO REVISION NUMBER 18. THIS REVISION | | SUBMITTED 2/5/08, SIGNED, SEALED & DATED 1/31/07 HAS | | NEW INFORMATION INDICATED ON REVISION NUMBER 18. ALSO | | MANY PREVIOUSLY APPROVED REVISIONS ARE STILL INDICATED | | ON THE PLANS AS CLOUDS AND REVISION NUMBERS. THESE | | REVISIONS THAT HAVE BEEN PREVIOUSLY APPROVED IF NOT | | SHUT OFF CREATE MANY EXTRA HOURS OF REVIEW. TURN OFF | | ALL PREVIOUSLY APPROVED REVISIONS, (CLOUDS/NUMBERS) AND | | ONLY INDICATE THE REVISION BEING SUBMITTED FOR REVIEW. | | IF THIS IS NOT DONE THEN THE REVISION WILL BE DENIED | | AND SENT BACK BECAUSE IT IS TOO TIME CONSUMING TO | | REVIEW THE TOTAL SHEET LOOKING FOR A FEW REVISIONS WHEN | | REVISIONS ARE SHOWN ALL OVER THE SHEET. SECTION | | 104.2.1.3. | | | | 2. SHT P-2PREVIOUS REVISION SIGNED, SEALED & DATED | | 4/27/07 SHOWED UP TO REVISION NUMBER 18. THIS REVISION | | SUBMITTED 2/5/08, SIGNED, SEALED & DATED 1/31/07 HAS | | NEW INFORMATION INDICATED ON REVISION NUMBER 18. ALSO | | MANY PREVIOUSLY APPROVED REVISIONS ARE STILL INDICATED | | ON THE PLANS AS CLOUDS AND REVISION NUMBERS. THESE | | REVISIONS THAT HAVE BEEN PREVIOUSLY APPROVED IF NOT | | SHUT OFF CREATE MANY EXTRA HOURS OF REVIEW. TURN OFF | | ALL PREVIOUSLY APPROVED REVISIONS, (CLOUDS/NUMBERS) AND | | ONLY INDICATE THE REVISION BEING SUBMITTED FOR REVIEW. | | IF THIS IS NOT DONE THEN THE REVISION WILL BE DENIED | | AND SENT BACK BECAUSE IT IS TOO TIME CONSUMING TO | | REVIEW THE TOTAL SHEET LOOKING FOR A FEW REVISIONS WHEN | | REVISIONS ARE SHOWN ALL OVER THE SHEET. SECTION | | 104.2.1.3. | | | | 3. SHT P-3 PREVIOUS REVISION SIGNED, SEALED & DATED | | 4/27/07 SHOWED UP TO REVISION NUMBER 18. THIS REVISION | | SUBMITTED 2/5/08, SIGNED, SEALED & DATED 1/31/07 HAS | | NEW INFORMATION INDICATED ON REVISION NUMBER 18. ALSO | | MANY PREVIOUSLY APPROVED REVISIONS ARE STILL INDICATED | | ON THE PLANS AS CLOUDS AND REVISION NUMBERS. THESE | | REVISIONS THAT HAVE BEEN PREVIOUSLY APPROVED IF NOT | | SHUT OFF CREATE MANY EXTRA HOURS OF REVIEW. TURN OFF | | ALL PREVIOUSLY APPROVED REVISIONS, (CLOUDS/NUMBERS) AND | | ONLY INDICATE THE REVISION BEING SUBMITTED FOR REVIEW. | | IF THIS IS NOT DONE THEN THE REVISION WILL BE DENIED | | AND SENT BACK BECAUSE IT IS TOO TIME CONSUMING TO | | REVIEW THE TOTAL SHEET LOOKING FOR A FEW REVISIONS WHEN | | REVISIONS ARE SHOWN ALL OVER THE SHEET. SECTION | | 104.2.1.3. | | | | 4. SHT P-5 MANY REVISIONS ARE NOT CLOUDED/NUMBERED ON | | THIS SHEET. ALSO MANY PREVIOUSLY APPROVED REVISIONS ARE | | STILL INDICATED ON THE PLANS AS CLOUDS AND REVISION | | NUMBERS. THESE REVISIONS THAT HAVE BEEN PREVIOUSLY | | APPROVED IF NOT SHUT OFF CREATE MANY EXTRA HOURS OF | | REVIEW. TURN OFF ALL PREVIOUSLY APPROVED REVISIONS, | | (CLOUDS/NUMBERS) AND ONLY INDICATE THE REVISION BEING | | SUBMITTED FOR REVIEW. IF THIS IS NOT DONE THEN THE | | REVISION WILL BE DENIED AND SENT BACK BECAUSE IT IS TOO | | TIME CONSUMING TO REVIEW THE TOTAL SHEET LOOKING FOR A | | FEW REVISIONS WHEN REVISIONS ARE SHOWN ALL OVER THE | | SHEET. SECTION 104.2.1.3. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
17 |
Status |
P |
Date |
2008-02-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-02-23 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-02-23 |
Time |
15:01 |
Sent To |
|
|
Notes |
2008-02-23 15:02:22 | REVISIONS OK--SHTS P-4, P-23 & P-23A |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
16 |
Status |
F |
Date |
2008-02-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-02-23 |
Time |
10:51 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-02-23 |
Time |
10:51 |
Sent To |
|
|
Notes |
2008-02-23 10:51:51 | | | | | | | REVISIONS DENIED | | | | SHTS P-1A & P-1B SHOW REVISIONS FOR DIESEL FUEL FOR THE | | GENERATOR. FUEL GAS IS A MECHANICAL PLAN REVIEW AND AS | | SUCH SHALL BE SUBMITTED UNDER THE MECHANICAL SHEETS AND | | TO THE MECHANICAL PLAN REVIEWER. | | | | THIS HAS BEEN INDICATED IN THE PREVIOUS REVISION | | REVIEWS DATED 12-04-07 & 12-13-07 | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
15 |
Status |
F |
Date |
2007-12-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-12-13 |
Time |
08:12 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-12-13 |
Time |
08:12 |
Sent To |
|
|
Notes |
2007-12-13 08:12:46 | | | | | | | REVISIONS DENIED | | SHTS P-1A & P-1B SHOW REVISIONS FOR DIESEL FUEL FOR | | THE GENERATOR. FUEL GAS IS A MECHANICAL PLAN REVIEW AND | | AS SUCH SHALL BE SUBMITTED UNDER THE MECHANICAL SHEETS | | AND TO THE MECHANICAL PLAN REVIEWER. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
14 |
Status |
F |
Date |
2007-12-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-12-04 |
Time |
12:18 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-12-04 |
Time |
12:18 |
Sent To |
|
|
Notes |
2007-12-04 12:21:49 | | | | | | | REVISIONS DENIED | | SHTS P-1A & P-1B SHOW REVISIONS FOR DIESEL FUEL FOR | | THE GENERATOR. FUEL GAS IS A MECHANICAL PLAN REVIEW AND | | AS SUCH SHALL BE SUBMITTED UNDER THE MECHANICAL SHEETS | | AND TO THE MECHANICAL PLAN REVIEWER. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
13 |
Status |
N |
Date |
2007-10-18 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-10-18 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-10-18 |
Time |
15:51 |
Sent To |
|
|
Notes |
2007-10-18 15:52:59 | | | | | | | | | | | | | SHTS A2.7.5 & A2.7.6 DELETED A PLANTER DRAIN AND A DECK | | DRAIN. THESE CHANGES SHALL BE INDICATED ON THE PLUMBING | | PLANS AND THE STORM ISOMETRIC RISER DIAGRAM | | | | | | | | | | | | | | | | | | | | . |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
12 |
Status |
P |
Date |
2007-09-15 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-15 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-15 |
Time |
09:56 |
Sent To |
|
|
Notes |
2007-09-15 09:59:17 | REVISIONS APPROVED, SHTS P-4 & P-22 | | | | | | | | | | | | SHT P-4 REVISION REQUIRED FOR THE STORM RISER DIAGRAMS | | TO REFLECT THE CHANGES TO THE PRIMARY AND SECONDARY | | ROOF DRAINS AND PIPING REVISEDBY REVISION 11. | | | | | | | | | | . |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
11 |
Status |
P |
Date |
2007-06-09 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-06-09 |
Time |
12:02 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-06-09 |
Time |
12:02 |
Sent To |
|
|
Notes |
2007-06-09 12:03:42 | REVISIONS OK--SHTS P-2, P-3, P-5, P-20, P-23 & | | P-23A |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
10 |
Status |
F |
Date |
2007-06-09 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-06-09 |
Time |
11:58 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-06-09 |
Time |
11:58 |
Sent To |
|
|
Notes |
2007-06-09 12:02:20 | REVISION DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. SHT P-1 NO CHANGES FROM LAST REVISION. (REVISION | | 18). SEE SHEET SIGNED, SEALED, DATED 4-18-2007. | | | | 2. SHT P-4 8TH FLOOR HUB DRAINS, (SAFE WASTE), NOT | | APPROVED. SECTION 1002.1 EACH FIXTURE SHALL HAVE ITS | | OWN TRAP. NO DOUBLE TRAPING. CONNECT EACH HUB DRAIN TO | | THE VENTED LINE. (COMBINATION WASTE & VENT). | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
9 |
Status |
P |
Date |
2007-06-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-06-04 |
Time |
14:42 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-06-04 |
Time |
14:42 |
Sent To |
|
|
Notes |
2007-06-04 14:42:44 | REVISION OK - SHT P-1 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
8 |
Status |
F |
Date |
2007-04-04 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-04-04 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-04-04 |
Time |
07:55 |
Sent To |
|
|
Notes |
2007-04-04 10:59:13 | REVISION/DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1. SHT A-1 SHOW ALL PIPE SIZES DOWNSTREAM OF THE 6" HUB | | DRAINS. TABLE 710.1(1). THESE PIPES SHALL NOT REDUCE IN | | THE DIRECTION OF FLOW PER SECTION 704.2. | | | | 2. SHT A-1 SHOW ALL CLEANOUTS REQUIRED BY SECTIONS | | 708.3.1 & 708.3.3 IN LINES TO NEW 6" HUB DRAINS. | | | | 3. SHT A-1 REVISIONS 10 THRU 15 NOT INDICATED WITH | | CLOUDS OR NUMBERED TRIANGLES. THESE REVISIONS ARE NOT | | APPROVED. SECTION 104.2.1. | | | | 4. ALL CHANGES TO THE SANITARY ON THEFLOOR PLAN SHALL | | BE REFLECTED ON THE SANITARY RISER DIAGRAM. REVISIONS | | WILL BE REQUIRED FOR THE RISER DIAGRAM. SECTION | | 104.2.1. | | | | 5. SHT P-20 DETAIL FOR THE SPRINKLER DRAIN DOES NOT | | REFLECT WHAT IS SHOWN ON THE FLOOR PLAN SHEET P-1. NO | | TRAP IS SHOWN, NO HUB IS SHOWN, NO VENT IS SHOWN AND | | PIPE SIZE WILL BE REQUIRED TO BE 6". SECTIONS 704.2, | | 901.2.1, 1002.1 & 104.2.1. | | | | 6. SHT P-20 NOTESSTATES PROVIDE FLEXIBLE CONNECTION | | TO SITE DRAINAGE. PLEASE PROVIDE A DETAIL SHOWING THE | | CONNECTION AND INDICATING THE MATERIAL TO BE USED. | | SECTIONS 104.2.1, 301.2 & 301.3. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
7 |
Status |
F |
Date |
2007-04-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-04-03 |
Time |
11:47 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-04-03 |
Time |
11:47 |
Sent To |
|
|
Notes |
2007-04-03 12:16:05 | REVISION/ DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1. SHT P-5 PIPE ROUTING IN AREAS 53, 55, 57, 75, 76 | | ALSO CHANGE THE WAY THE SQUARE FOOTAGE ACCUMULATED IN | | THE SYSTEM. THIS WILL CHANGE THE PIPE SIZE IN SOME | | INSTANCES. SEE ALL SECTIONS OF PIPE DOWNSTREAM OF THE | | CHANGES AND MAKE SURE THE SQUARE FOOTAGE IS RECHECKED. | | SECTION 104.2.1 AND TABLE 1106.3. | | | | 2. SHT P-5 NEW DECK DRAINS ADDED AROUND THE GAS HEATER | | SPA SHALL REFLECT THE SQUARE FOOTAGE BEING DRAINED AND | | INDICATE THE PIPE SIZE PER TABLE 1106.3. | | | | 3. SHT P-5 ALL CHANGES TO THE STORM SYSTEM, (DECK | | DRAINS, PLANTER DRAINS OR TRENCH DRAINS), SHALL BE | | REFLECTED IN THE STORM RISER DIAGRAMS. SECTION | | 104.2.1. | | | | 4. SHT P-5 THERE IS CONCERN THAT IF THERE IS BLOCKAGE | | IN THE PRIMARY SYSTEM IN SOME AREAS, THE WATER WILL | | ENTER THE OCCUPIED SPACES BEFORE THE SECONDARY DRAIN, | | OR OVERFLOW SCUPPER. (EXAMPLE AREAS 1 THRU 4, 15, 17, | | 19, 21, 22, 45). SECTIONS 1107.1 & 1107.3. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
6 |
Status |
P |
Date |
2007-04-03 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-04-03 |
Time |
11:46 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-04-03 |
Time |
11:46 |
Sent To |
|
|
Notes |
2007-04-03 11:47:14 | REVISIONS OK - SHTS P-1A REV. #2 & P-5A REV. #3. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
5 |
Status |
F |
Date |
2007-01-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-01-23 |
Time |
09:56 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-01-23 |
Time |
09:56 |
Sent To |
|
|
Notes |
2007-01-23 14:20:27 | | | REVISION DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1. SHT P1 THE DRAINS FROM THE FIRE SPRINKLER SHALL BE | | INDIRECT WASTED AND REQUIRES A TRAP. SECTIONS 802.1.4 & | | 901.2.1. A FLOOR SINK OR HUB DRAIN IS REQUIRED. (SEE | | REVISION 13 - REVISION STATES BLDG DEPT COMMENT. I | | BELIEVE THE COMMENT WAS THAT INDIRECT WASTE RECEPTORS | | ARE NOT ALLOWED IN THE STAIRWELL, NOT THAT THE WASTE | | RECEPTORS ARE NOT NEEDED. SEE PROVISO ON PLANS). PLEASE | | CLARIFY. | | | | 2. SHT P-1 PLEASE TURN OFF ALL PREVIOUS REVISIONS AS | | THIS SLOWS THE REVISION PROCESS DOWN. ONLY INDICATE THE | | REVISIONS BE SUBMITTED AT THIS TIME ON THE PLANS. | | SECTION 104.2.1.-- THERE ARE CHANGES TO THE ROUTING | | OF THEWATER SUPPLY TO THE FIRE PUMP AS WELL AS A | | BYPASS THAT HAS NOT BEEN CLOUDED, NOR INDICATED AS A | | REVISION. CLOUD AND NUMBER ALL REVISIONS. - - MANY | | REVISIONS SHOWN HAVE NO CHANGES TO STAMPED SET OF | | PLANS. PLEASE CLARIFY. (SEE REVISIONS 10 & 12). | | | | 3. SHT P-22REVISION #4 NOT APPROVED. SEE COMMENT #1. | | | | | | **********APPROVED SHEETS********** | | P-5, &P-5A. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
F |
Date |
2007-01-23 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-01-23 |
Time |
06:50 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-01-22 |
Time |
06:50 |
Sent To |
|
|
Notes |
2007-01-23 07:21:32 | | | REVISION DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1. SHT P1 THE DRAINS FROM THE FIRE SPRINKLER SHALL BE | | INDIRECT WASTED AND REQUIRES A TRAP. SECTIONS 802.1.4 & | | 901.2.1. A FLOOR SINK OR HUB DRAIN IS REQUIRED. (SEE | | REVISION 13 - REVISION STATES BLDG DEPT COMMENT. I | | BELIEVE THE COMMENT WAS THAT INDIRECT WASTE RECEPTORS | | ARE NOT ALLOWED IN THE STAIRWELL, NOT THAT THE WASTE | | RECEPTORS ARE NOT NEEDED. SEE PROVISO ON PLANS). PLEASE | | CLARIFY. | | | | 2. SHT P-1 PLEASE TURN OFF ALL PREVIOUS REVISIONS AS | | THIS SLOWS THE REVISION PROCESS DOWN. ONLY INDICATE THE | | REVISIONS BE SUBMITTED AT THIS TIME ON THE PLANS. | | SECTION 104.2.1.-- THERE ARE CHANGES TO THE ROUTING | | OF THEWATER SUPPLY TO THE FIRE PUMP AS WELL AS A | | BYPASS THAT HAS NOT BEEN CLOUDED, NOR INDICATED AS A | | REVISION. CLOUD AND NUMBER ALL REVISIONS. - - MANY | | REVISIONS SHOWN HAVE NO CHANGES TO STAMPED SET OF | | PLANS. PLEASE CLARIFY. (SEE REVISIONS 10 & 12). | | | | | | **********APPROVED SHEETS********** | | P-2, P-3, P-4, P-5, AND NEW SHEET P-5A. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2006-08-26 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-08-26 |
Time |
15:10 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-08-24 |
Time |
17:26 |
Sent To |
|
|
Notes |
2006-08-26 00:00:00 | | | | | | | | | PASSED/PROVISO | | | | SHTS P-1 & P-22 FLOOR DRAINS ARE NOT | | APPROVED IN THE STAIRWELLS. POSITIVE | | PRESSURES CAUSED BY THE STAIRWELL | | PRESSURIZATION MAY CONFLICT WITH SECTION | | 901.2. ALSO PENETRATIONS IN AN EXIT | | ENCLOSUER ASSEMBLY OTHER THAN THOSE | | LIMITED TO NFPA 101 SECTION 7.1.3.2.1(5) | | ARE NOT ALLOWED. - REVISIONS REQUIRED | | FOR THESE SHEETS | | | | | | | | | | GAS APPLIANCE VENTING SHALL BE FIELD | | INSPECTED AND APPROVED. | | MANUF. SPECIFICATION SHEETS SHALL BE | | SUBMITTED AT THE TIME OF GAS PERMIT | | APPLICATION. MANUF. SPECIFICATIONS | | SHEETS REQUIRED FOR THE GAS REGULATORS. | | VENTS FOR REGULATORS SHALL BE MADE OF | | NON COMBUSTABLE MATERIAL. GAS RISER - A | | SHUT OFF VALVE SHALL BE INSTALLED PRIOR | | TO THE REGULATORS WITH A UNION BETWEEN | | OR AFTER REGULATOR. (SHT P-6). SECTION | | 410.2(5). REVISIONS REQUIRED FOR THESE | | SHEETS. | | | | | | | | | | SHTS P-4 & P-21A COOLING TOWER WATER | | RISER DIAGRAM. THE CHECK VALVES TO THE | | FOUNTAINS AND THE TRASH CHUTES ARE NOT | | APPROVED. INSTALL N-36 VACUUM BREAKERS | | FOR THIS APPLICATION. - THE IRRIGATION | | SYSTEM REQUIRES A PRESSURE VACUUM | | BREAKER TO THAT LINE SEPARATE FROM THE | | REST OF THE SYSTEM. - CLARIFY WATER | | PIPING TO POOL HEATERS AS THERE IS MAKE | | UP WATER TO THE COLLECTING TANKS. - | | REVISION REQUIRED FOR THESE SHEETS. | | | | | | | | | | SEE PROVISO REQUIREMENTS FOR SHEETS P-1, | | P-4, P-6, P-21A, & P-22. | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2006-06-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-06-28 |
Time |
14:30 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-06-22 |
Time |
10:13 |
Sent To |
|
|
Notes |
2006-06-28 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 FUEL GAS | | FBC-2001 BUILDING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | FHA-98 DESIGN MANUAL | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | WPB CITY CODE | | | | FROM PREVIOUS REVIEW. COMMENT NUMBER | | SHALL REMAIN THE SAME AS FIRST REVIEW: | | | | 4. SHTS A-1.7, A-1.8, A-2.6.1 THRU | | A-2.6.6, SUBMIT CALCULATIONS FOR PRIMARY | | AND SECONDARY ROOF DRAINS FOR ALL ROOFS. | | SHOW THE LOCATION OF ALL SECONDARY ROOF | | DRAINS FOR ALL ROOFS/DECKS. | | ***RESPONSE NOTED, BUT SCUPPER SCHEDULE | | CALCULATIONS & ROOF DRAIN SF ARE | | DIFFERENT. PLEASE CORRELATE INFORMATION. | | SECTION 104.2.1. | | 5. ALL UNIT TYPES SHALL COMPLY WITH | | FHA-98 DESIGN MANUAL REQUIREMENTS ONE | | THRU SEVEN. SUBMIT DETAILS. | | ***RESPONSE NOTED, BUT BATH #2 IN UNITS | | B-1, C-1, C-2, C-2.1, C-2.2, C-3, C-4, | | C-5, C-6, C-7, C-8, & D-1, AS WELL AS | | THE M/B OF UNITS C-9 & C-9.1. SHOW THE | | OPENING FOR THE W/C'S. OPENINGS SHALL BE | | A MINIMUM 33" WIDE WITH THE W/C BEING | | 18" OFF THE WALL TO THE CENTERLINE OF | | THE FIXTURE & 15" TO ADJACENT FIXTURE OR | | VANITY CABINET. W/C'S BETWEEN FIXTURES | | SHALL BE 18" OFF ONE FIXTURE AND 15" OFF | | THE OTHER WITH A MINIMUM 33" OPENING. | | SEE PAGES 7.43, 7.44 & 7.45. - | | REINFORCING FOR FOLDING GRAB BARS MUST | | BE SUBSTANTIAL BECAUSE OF THEIR | | CANTILEVERED DESIGN. 20 GAUGE SHEET | | METAL BACKING DOES NOT APPEAR TO BE | | SUBSTANTIAL. PLEASE INDICATE WITH | | CALCULATIONS HOW THIS WILL BE CONSIDERED | | SUBSTANTIAL. (SEE PAGE 28). | | | | 9. SHTS A-2.7.5 & A-10.1 MORE | | INFORMATION IS REQUIRED FOR THE | | FOUNTAINS. PLEASE INDICATE IF THERE WILL | | BE WATER SUPPLY LINES AND OR DRAINAGE | | LINES FOR FOUNTAINS. IF WATER SUPPLY | | LINES ARE INSTALLED, BACKFLOW PREVENTION | | IS REQUIRED. IF DRAINS ARE INSTALLED, | | THEY SHALL CONNECT TO THE SANT. SYSTEM | | AND THE OVERFLOW SHALL DRAIN TO STORM. | | PLEASE CLARIFY. SECTIONS 104.2.1 & 608. | | ***RESPONSE NOTED, BUT NO BACKFLOW | | PREVENTORS ARE SHOWN ON PLANS. PLEASE | | INDICATE WHERE THESE CAN BE FOUND AS | | THERE IS NO WATER RISER DIAGRAM FOR THE | | COOLING TOWER WATER. PLEASE SUBMIT A | | WATER RISER DIAGRAM SHOWING ALL PIPE | | SIZE, VALVES, BACKFLOWS ETC. FOR THE | | COOLING TOWER SYSTEM. SECTION 104.3.1.1. | | - FOUNTAIN AT PORTE-COCHERE PLAZA TO BE | | BY SEPARATE PERMIT, BUT WILL THE DRAIN | | LINE, OVERFLOW LINE AND WATER SUPPLY TO | | THE FOUNTAIN BE RUN TO FOUNTAIN AT THAT | | TIME? SECTION 104.2.1. | | | | 18. SHT P-4 SUBMIT CALCULATIONS FOR | | PRIMARY AND SECONDARY ROOF DRAINS. SHOW | | SF OF EACH DRAINED AREA PLUS 1/2 AREA OF | | ALL VERTICAL WALLS INCLUDING PARAPETS, | | PLUS THE AREA OF ROOFS THAT DRAIN ONTO | | THE ROOF/DECK AREA FROM ABOVE. | | ***RESPONSE NOTED, BUT P-6 SCUPPER | | SCHEDULE CALCULATIONS TOTAL AREA SERVED | | BY DRAIN ON SCHEDULE DOES NOT REFLECT | | THE TOTAL SHOWN ON SHT P-5 DECK DRAINS & | | PLANTER DRAINS. MANY TOTAL AREAS ARE NOT | | CORRECT. PLEASE RECHECK THE ADDITION. | | SECTION 104.2.1 AND TABLE 1106.3. | | | | 22. SHT P-7 SUBMIT CALCULATION FOR | | PRIMARY AND SECONDARY ROOF DRAINS. (SEE | | COMMENT #18). SECTIONS 1106 & 1107. | | ***RESPONSE NOTED, BUT SCUPPER SCHEDULE | | CALCULATIONS TOTAL AREA SERVED BY DRAIN | | DOES NOT REFLECT SF ON ROOF PLAN. PLEASE | | CORRELATE INFORMATION. SECTION 104.2.1. | | | | 33. SHT P-18 RISERS 86, 87, 81, 80 LOWER | | OFFSET VENTS REQUIRED. (SHOW AT LOWEST | | OFFSET) SECTION 915.3. | | ***RESPONSE NOTED, BUT THE LOWER OFFSET | | VENTS ARE STILL NOT SHOWN ON RISERS 80, | | 81, AND 87A. | | | | 36. THE FOLLOWING INFORMATION IS | | REQUIRED FOR GAS PERMIT APPLICATION: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | FUEL GAS CODE. | | ***RESPONSE NOTED, BUT THE ISOMETRIC | | INDICATES THE POOL/SPA HEATERS ARE ON | | THE 8TH FLOOR, BUT THE FLOOR PLAN SHOWS | | THE HEATERS ON THE 9TH FLOOR. PLEASE | | CORRELATE RISER WITH FLOOR PLAN. - SOME | | CUT SECTIONS SHOW NO LENGTH AS REQUIRED. | | SEE FROM THE METER TO THE FIRST RISER, | | THE OFFSET ON THE RUN TO THE WATER | | HEATERS, AND THE DROP TO THE WATER | | HEATERS IS NOT SHOWN. | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES (A)(3) | | ***RESPONSE NOTED, BUT NOT ALL CUT | | SECTIONS ARE GIVEN TO VERIFY DEVELOPED | | LENGTH. | | | | H. SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER FBC-2001 FUEL GAS CODE | | SECS. 502 THRU 506. | | ***RESPONSE NOTED, BUT NO VENTING | | INFORMATION INDICATED. | | | | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2001 FUEL GAS CODE SEC 402.2. | | ***RESPONSE NOTED, BUT MANUF. | | SPECIFICATION SHEETS FOR ALL GAS | | EQUIPMENT SHALL BE SUBMITTED FOR REVIEW. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | **************NEW COMMENTS************** | | | | 1B. SHT A-2.7.5 MORE INFORMATION IS | | REQUIRED FOR THE SCUPPERS. SUBMIT A | | DETAIL INDICATING WHERE THE SCUPPER WILL | | BE PIPED TO. SHOW SCUPPER HEIGHT & | | WIDTH, AND INDICATE THE DISTANCE FROM | | THE DECK TO THE FLOW LINE. SHOW THE AREA | | TO BE DRAINED BY EACH EOS AND INDICATE | | THE SQUARE FOOTAGE BEING DRAINED BY EACH | | EOS. - INDICATE THE TERMINATION POINT | | FOR EACH EOS. SECTION 104.2.1. | | | | 2B. EMERGENCY OVERFLOW SCUPPERS SHALL BE | | LOCATED AS CLOSE AS PRACTICABLE TO THE | | REQUIRED VERT LEADERS, AND SHALL BE A | | MINIMUM 4" IN HEIGHT. SECTION 1503.4.2. | | | | 3B. SUBMIT A EMERGENCY OVERFLOW SCUPPER | | ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE | | SIZES. SECTION 1O3.1.1. | | | | 3B. SHT P-1 RELIEF VENT REQUIRED FOR | | AAV'S, (STUDOR VENTS). SECTION 917.3.2. | | | | 4B. SHT P-1 SANITARY RISERS 44A, & 51A | | ARE NOT SHOWN ON THE FLOOR PLAN. PLEASE | | CLARIFY. SECTION 104.2.1. | | | | 5B. SHT P-1 CONDENSATE LINE IS CONNECTED | | TO THE SANITARY BUILDING DRAIN BETWEEN | | RISERS 43 & 39. THIS IS NOT APPROVED. | | MUNICIPAL CODE SECTION 90-125(5). | | | | 6B. SHT P-1 10 DD'S SHOWN AS RWL'S. | | PLEASE CORRELATE INFORMATION. SECTION | | 104.2.1. | | | | 7B. SHT P-2 RWL DESIGNATIONS COVERED UP | | BY RECTANGLE GRID REFERANCES AT COL. | | LINES 57.1-R.1, 57.1-N.1, 57.1-C.1 AND | | OVER A SANT. RISER DESIGNATION AT COL. | | LINE 57.1-B.2. PLEASE MOVE REFERENCES. | | SECTION 104.2.1. | | | | 8B. SHT P-2 10 3" DD'S ARE SHOWN AS | | RWL'S. PLEASE CORRELATE INFORMATION. | | SECTION 104.2.1. | | | | 9B. SHT P-2 6"RWL 3500SF UP & DOWN IS | | SHOWN AS 3200SF AT ROOF DRAIN. PLEASE | | CORRELATE INFORMATION. SECTION 104.2.1. | | | | 10B. SHT P-3 3RD FLOOR AND 7TH FLOOR ARE | | DIFFERENT FROM FLOORS 4, 5, & 6 AND EACH | | OTHER, SO HOW CAN ALL FLOORS BE TYPICAL? | | PLEASE CLARIFY. SECTION 104.2.1. | | | | 11B. SHT P-3 PLEASE INDICATE THE SQUARE | | FOOTAGE FOR ALL DECK DRAINS. SECTION | | 104.2.1 AND TABLE 1106.3. | | | | 12B. SHT P-36"RWL 3500SF UP & DOWN IS | | SHOWN AS 3200SF @ THE ROOF DRAIN. PLEASE | | CORRELATE INFORMATION. SECTION 104.2.1. | | | | 13B. SHT P-4RWL'S INDICATED AS PD'S OR | | DD'S ON STORM RISERS. PLEASE CLARIFY. | | SECTION 104.2.1. | | | | 14B. SHT P-6 SCUPPER SCHEDULE | | CALCULATIONS, CHECK ADDITION OF SF ON | | AREAS 22, 62, 79, & 106. SECTION | | 102.1.1. | | | | 15B. SHT P-7 WHITE-OUT IS NOT APPROVED | | ON SIGNED/SEALED SETS OF PLANS SUBMITTED | | FOR RECORD. SECTION 104.2.1.3. | | | | 16B. SHT P-7 SUBMIT A WATER RISER | | DIAGRAM ISOMETRIC FOR PIPING IN BOILER | | ROOM THAT REFLECTS THE LAYOUT ON THE | | FLOOR PLAN. SHOW ALL PIPE SIZES, VALVES, | | VACUUM RELIEF VALVES, CIRCULATION PUMPS, | | THERMAL EXPANSION CONTROL, THERMOMETERS, | | ETC. FOR THE DOMESTIC WATER HEATER & | | STORAGE TANK. SECTION 104.3.1.1. | | | | 17B. SHT P-7 BOILER ROOM DETAIL THE COLD | | WATER SUPPLY APPEARS TO BE PASSING THRU | | THE HOT WATER STORAGE TANK. PLEASE | | CLARIFY. SECTION 104.2.1. | | | | 18B. SHT P-13 PLEASE INDICATE WHAT IS AT | | THE TOP OF ALL COLD WATER RISERS. NO | | REFERENCE SYMBOL IS SHOWN ON SHT P-2 | | PLUMBING LEGEND. IF THEY ARE AIR | | CHAMBERS, THEY ARE NOT APPROVED. | | SECTIONS 104.2.1, 604.9, & PDI-WH 201. | | | | 19B. SHT P-16 RISER 44A/51A MAXIMUM 20 | | FIXTURE UNITS ON 4" STACK PER TABLE | | 912.3. | | | | 20B. SHT P-17 RISERS 52A, & 84AARE NOT | | FOUND ON THE HORIZONTAL BUILDING | | SANITARY DRAIN ISOMETRIC RISER DIAGRAM. | | SHTP-22. PLEASE CLARIFY. SECTION | | 104.2.1. | | | | 21B. SHT P-18 RISER 87A NOT FOUND ON THE | | HORIZONTAL BUILDING SANITARY DRAIN | | ISOMETRIC RISER DIAGRAM. SHT P-22 PLEASE | | CLARIFY. SECTION 104.2.1. | | | | 22B. SHT P-19 RISER 34/57 SHOWS NO | | CONNECTION TO STACK FOR FLOORS 15, 17, & | | 19. PLEASE CLARIFY. SECTION 104.2.1. | | | | 23B. SHT P-20 SPRINKLER DRAIN DETAIL. A | | TRAP AND A VENT ARE REQUIRED FOR THIS | | LINE. SECTIONS 901.2.1. & 1002.1. | | | | 24B. SHT P-22 HORIZONTAL SANITARY RISER | | DOES NOT REFLECT THE FLOOR PLAN. NO | | DRAIN LINES FOR THE FIRE SPRINKLER | | DRAINS. - FUTURE LINE, (4" 20FU), | | UPSTREAM OF RISER 68,69,70,72,73,74 NOT | | SHOWN. - FLOOR DRAIN UPSTREAM OF RISER | | 59-67 & 71 NOT SHOWN. - OFFSET FOR RISER | | 6 NOT SHOWN. - 2ND FLOOR OFFSET FOR | | RISER 22-26, 33-36, & 41 NOT SHOWN. | | SECTION 104.2.1. | | | | 25B. SHT P-22 RELIEF VENTS REQUIRED FOR | | ALL AAV'S, (STUDOR VENTS). SECTION | | 917.3.2. | | | | 26B. SHT P-22 SHOW THE VENT PIPING FOR | | ALL FUTURE LINES SHOWING ALL PIPE SIZES, | | AND INDICATE WHICH STACK THE VENTS | | CONNECT INTO. SECTION 104.2.1 AND TABLE | | 916.1. | | | | 27B. SHT P-22 RECHECK ALL DFU'S ADDITION | | IN SANITARY RISER. SOME ADDITION IS NOT | | CORRECT AND THIS AFFECT THE PIPE SIZING | | IN SOME CASES. (SEE RED LINE CORRECTIONS | | ON ONE SET OF PLANS. SECTION 104.2.1 AND | | TABLE 710.1(1). (NOTE: BATHROOM GROUP | | CONSISTING OF W/C, LAV, BIDET, AND TUB | | OR SHOWER IS 5FU, AND WITH AN EXTRA LAV | | AND SHOWER IS 8FU. - SOME RISERS APPEAR | | TO INDICATE MORE FIXTURE UNITS THAN ARE | | ACTUALLY SHOWN. - TRAPS FOR FIXTURES | | OVER 2" SHALL BE SIZED PER TABLE 709.2. | | (EXAMPLE: 3" FLOOR DRAIN IS 5FU). | | | | 28B. SHT P-22 RISER 22,23,24 DOES NOT | | SHOW PIPING FROM POOL EQUIPMENT ROOM, | | NOR FROM THE 2 FOUNTAINS AS INDICATED ON | | SHT P-3. PLEASE CORRELATE. SECTION | | 104.2.1. | | | | 29B. SHT P-22 SHOW THE CLEANOUTS WHERE | | REQUIRED PER SECTIONS 708.3.1, 708.3.3 & | | 708.3.5. (ALSO SHOW ON SHT P-1). | | | | 30B. SHT P-22 SHOW TRAPS AND VENTING FOR | | THE FIRE SPRINKLER DRAIN LINES AS | | REQUIRED IN SECTIONS 901.2.1 & 1002.1. | | | | 31B. SHT P-23 STORM RISER DIAGRAM, SHOW | | SF DRAINED BY EACH DD. - 4" RD(2000SF) | | DOES NOT REFLECT THE ROOF PLAN, NOR | | CALCULATIONS (1900SF). - 6" DD (4350SF) | | DOES NOT REFLECT 9TH FLOOR PLAN. (SHTS | | P-1 & P-3 4450SF) PLEASE CORRELATE | | SECTION 104.2.1. - CLEANOUTS REQUIRED | | PER SECTION 1101.8. (ALSO SHOW ON SHT | | P-1. | | | | 32B. SHT P-23A STORM RISER DIAGRAM DOES | | NOT REFLECT THE FLOOR PLAN. FOUNTAIN | | OVERFLOWS ARE NOT SHOWN. - OFFSET ON THE | | 9TH FLOOR FOR ROOF DRAIN 3200SF IS SHOWN | | ON THE 8TH FLOOR ON THE FLOOR PLAN. - | | SHOME SF FOR SOME DRAINS DO NOT REFLECT | | THE FLOOR PLAN AND/OR CALCULATIONS. | | PLEASE CORRELATE. - NO SF SHOWN FOR MANY | | DD'S AND CAN NOT VERIFY PIPE SIZE UNTIL | | SF FOR ALL DD'S IS SHOWN. SECTION | | 104.2.1 AND TABLE 1106.3. | | | | 33B. SHT P-32A CLEANOUTS REQUIRED PER | | SECTION 1101.8 SHALL BE SHOWN. (ALSO ON | | SHT P-1). | | | | 34B. BACKFLOW PREVENTION REQUIRED FOR | | IRRIGATION ON THE 9TH FLOOR. SECTION | | 608.13. | | | | 35B. A SEPARATE RPZV BACKFLOW IS | | REQUIRED FOR THE COOLING TOWER WATER | | SUPPLY LINE. (NOT SHOWN ON CIVIL SHEETS) | | | | 36B. SEE ATTACHED SHEET CONCERNING THE | | DESIGN PROFESSIONALS AND FS 53.80(2)(B). | | THIS IS GIVEN AS A NOTICE ONLY. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2005-12-17 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2005-12-17 |
Time |
11:57 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2005-12-15 |
Time |
17:44 |
Sent To |
|
|
Notes |
2005-12-17 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 FUEL GAS | | FBC-2001 BUILDING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | FHA-98 DESIGN MANUAL | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | WPB CITY CODE | | | | 1. PLANS APPEAR TO BE INCOMPLETE AS | | SUBMITTED. MORE COMMENTS MAY BE | | FORTHCOMING NEXT REVIEW. | | 2. SHT L-6 MISSING. (SEE INDEX ON SHT | | L-1). SECTION 104.2.1. | | 3. SHT A-0.1 INDEX INDICATES THAT SHTS | | A-5.1 THRU A-5.6 HAVE KITCHEN AND | | BATHROOM ELEVATIONS, NOTES & DETAILS. | | THESE SHEETS WERE NOT SUBMITTED. SECTION | | 104.2.1. | | 4. SHTS A-1.7, A-1.8, A-2.6.1 THRU | | A-2.6.6, SUBMIT CALCULATIONS FOR PRIMARY | | AND SECONDARY ROOF DRAINS FOR ALL ROOFS. | | SHOW THE LOCATION OF ALL SECONDARY ROOF | | DRAINS FOR ALL ROOFS/DECKS. | | 5. ALL UNIT TYPES SHALL COMPLY WITH | | FHA-98 DESIGN MANUAL REQUIREMENTS ONE | | THRU SEVEN. SUBMIT DETAILS. | | 6. NOT USED | | 7. ALL ARCHITECT SHEETS. SEAL OF THE | | ARCHITECT SHALL IMPART INFORMATION | | REQUIRED BY FAC/FS. LITTLE OR NO | | INFORMATION CAN BE GLEANED FROM THE SEAL | | ON SOME SHEETS. PLEASE BE SURE EACH | | SHEET IS SEALED CORRECTLY & INFORMATION | | REQUIRED IS IMPARTED ON EACH SHEET. FAC | | 61G1-16.004 & FS 481.2055. | | 8. SHT A-2.7.5 SHOW THE LOCATION OF ALL | | SECONDARY DRAINS REQUIRED BY SECTION | | 1107. | | 9. SHTS A-2.7.5 & A-10.1 MORE | | INFORMATION IS REQUIRED FOR THE | | FOUNTAINS. PLEASE INDICATE IF THERE WILL | | BE WATER SUPPLY LINES AND OR DRAINAGE | | LINES FOR FOUNTAINS. IF WATER SUPPLY | | LINES ARE INSTALLED, BACKFLOW PREVENTION | | IS REQUIRED. IF DRAINS ARE INSTALLED, | | THEY SHALL CONNECT TO THE SANT. SYSTEM | | AND THE OVERFLOW SHALL DRAIN TO STORM. | | PLEASE CLARIFY. SECTIONS 104.2.1 & 608. | | 10. SHT A-2.7.5 SEPARATE PERMITS | | REQUIRED FOR THE POOL & SPA POOL. | | (INFORMATIONAL). | | 11. SHT P-1 NO PIPING SHOWN TO FLOOR | | DRAINS IN THE TRASH ROOM AND IN THE PUMP | | ROOMS. SECTION 104.2.1. | | 12. SHT P-1 NO PIPING SHOWN TO RISERS | | 29, 30, & 44 THRU 51. SECTION 104.2.1. | | 13. SHT P-1 RISERS 10 & 26 NOT SHOWN ON | | FLOOR PLAN. SECTION 104.2.1. | | 14. SHT P-2 NO FLOOR PLANS FOUND FOR THE | | FLOOR PLAN A-1.2. PLEASE CLARIFY. | | SECTION 104.2.1. | | 15. SHT P-2 4"-180FU DOWNSTREAM OF RISER | | S/51A IS NOT CORRECT. PLEASE CHECK | | FIGURES. SECTION 104.2.1. | | 16. SHT P-2 RECALCULATE FU'S DOWNSTREAM | | OF RISERS 64 & 65. SECTION 104.2.1. | | 17. SHT P-2 INDICATE FU VALUE FOR RISERS | | 75 & 82. SECTION 104.2.1. | | 18. SHT P-4 SUBMIT CALCULATIONS FOR | | PRIMARY AND SECONDARY ROOF DRAINS. SHOW | | SF OF EACH DRAINED AREA PLUS 1/2 AREA OF | | ALL VERTICAL WALLS INCLUDING PARAPETS, | | PLUS THE AREA OF ROOFS THAT DRAIN ONTO | | THE ROOF/DECK AREA FROM ABOVE. | | 19. SHT P-4 NUMEROUS RWL'S & DECK DRAINS | | ARE SHOWN FOR DD & PLANTER DRAINS ON THE | | 9TH FLOOR, BUT NO PIPING IS SHOWN | | INDICATING WHERE THE DRAINS ARE DRAINING | | TO. PLEASE CLARIFY. SHOW PIPING ON RWL | | RISER DIAGRAMS. ALSO NO RWL'S FOR THESE | | DRAINS ARE SHOWN ON SUBSEQUENT SHEETS. | | SECTION 104.2.1. | | 20. SHT P-5 SHOW THE LOCATION OF ALL | | SECONDARY DRAINS REQUIRED IN SECTION | | 1107. | | 21. SHT P-5 RWL 3200SF NOT SHOWN ON THE | | FLOOR PLAN. (NEAR RISER 79) 104.2.1. | | 22. SHT P-7 SUBMIT CALCULATION FOR | | PRIMARY AND SECONDARY ROOF DRAINS. (SEE | | COMMENT #18). SECTIONS 1106 & 1107. | | 23. SHT P-7 SUBMIT A DETAIL FOR THE | | BOILER ROOM. SHOW THE PIPING LAYOUT | | INCLUDING ALL PIPE SIZES, VALVES, VACUUM | | RELIEF VALVES, CIRCULATION PUMPS, P&T | | VALVES, PAN DRAINS, THERMAL EXPANSION | | CONTROL ECT. INDICATE ALL PIPE | | MATERIALS. SECTION 104.2.1. | | 24. SHTS P-8 THRU P-12 ALL UNITS WATER | | RISER DIAGRAMS. WATER HAMMER ARRESTOR | | REQUIRED AT THE REFRIGERATOR ICE MAKER | | IN AN "EFFECTIVE RANGE". PDI-WH 201 AND | | MANUF. INSTALLATION REQUIREMENTS. | | 25. SHT P-13 FLUSH RING RISER FOR THE | | TRASH CHUTE REQUIRES BACKFLOW | | PROTECTION. PLEASE INDICATE THE METHOD | | OF PROTECTION. SECTION 608. | | 26. SHT P-13 WATER RISER 13 INDICATES 1" | | COLD WATER SUPPLY TO WATER HEATERS, BUT | | HOT WATER RISERS SHOW 2". PLEASE | | CLARIFY. SECTION 104.2.1. | | 27. SHT P-14 PLEASE INDICATE MATERIAL | | USED AND TYPE OF SYSTEM. SECTION | | 104.2.1. | | 28. P-16 SANT. RISERS 44A 7 51A. PER | | SECTION 914.1 A RELIEF VENT IS REQUIRED | | AT EACH 10TH INTERVAL BEGINING WITH THE | | TOP FLOOR. | | 29. SUBMIT A SANITARY HORIZONTAL RISER | | DIAGRAM IN ISOMETRIC FORM FOR THE | | BUILDING DRAIN. INDICATE ALL PIPE SIZES | | AND SHOW THE LOCATION OF ALL RISERS. | | SHOW DRAINAGE FIXTURE UNITS AS IT | | ACCUMULATES IN THE SYSTEM. SECTION | | 104.3.1.1. | | 30. SUBMIT A STORM ISOMETRIC RISER | | DIAGRAM FOR THE HORIZONTAL PIPING OF THE | | BUILDING STORM DRAIN. SHOW ALL PIPE | | SIZES, RISER LOCATIONS, AND THE SQUARE | | FOOTAGE AS IT ACCUMULATES IN THE SYSTEM. | | SECTION 104.3.1.1. | | 31. SUBMIT STORM RWL RISER DIAGRAMS. | | SHOW ALL PIPE SIZES, OFFSETS & SQUARE | | FEET. | | 32. SHT P-15 RISER 7 FIRST FLOOR TUB | | MISLABLED AS A SHOWER. SECTION 104.2.1. | | 33. SHT P-18 RISERS 86, 87, 81, 80 LOWER | | OFFSET VENTS REQUIRED. (SHOW AT LOWEST | | OFFSET) SECTION 915.3 | | 34. SHT P-19 RISER 41 RELIEF VENT | | REQUIRED. SECTION 914. | | 35. P-20 SPRINKLER DRAIN DETAIL, DRAIN | | TO CONNECT TO THE SANITARY SYSTEM, NOT | | THE STORM AS SHOWN. CITY CODE 90-203. | | 36. THE FOLLOWING INFORMATION IS | | REQUIRED FOR GAS PERMIT APPLICATION: | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2001 | | FUEL GAS CODE. | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | C. TYPE OF GAS, (LP OR NATURAL) | | D. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | THRU 402.5.2 AND TABLES 402(1) THRU | | 402(34). | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES (A)(3). | | F. SUBMIT CALCULATIONS FOR COMBUSTION | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | GAS CODE SECTION 304. | | G. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | H. SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER FBC-2001 FUEL GAS CODE | | SECS. 502 THRU 506. | | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2001 FUEL GAS CODE SEC 402.2 | | J. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | K. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND | | APPURTENANCES PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | 37. ALL PLUMBING SHEETS. ENGINEERS SEAL | | SHALL SHOW ALL INFORMATION REQUIRED BY | | FAC 61G15-23.001 & FS 481.025 | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
10 |
Status |
P |
Date |
2008-09-10 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2008-09-10 |
Time |
16:54 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2008-09-10 |
Time |
16:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
9 |
Status |
P |
Date |
2008-01-31 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2008-01-31 |
Time |
16:18 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2008-01-31 |
Time |
16:18 |
Sent To |
|
|
Notes |
2008-01-31 16:19:39 | REVISION TO ADD DOOR TO THE FUEL TANK ROOM. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
8 |
Status |
P |
Date |
2007-11-08 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-11-08 |
Time |
17:38 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-11-08 |
Time |
17:38 |
Sent To |
|
|
Notes |
2007-11-08 17:39:10 | AIRCRAFT WARNING LIGHT |
|
|
Review Stop |
Z |
ZONING |
Rev No |
7 |
Status |
P |
Date |
2007-10-23 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-10-23 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-10-23 |
Time |
11:15 |
Sent To |
|
|
Notes |
2007-10-23 11:16:43 | FOR REVISION #37 - CHANGING THE RAILING ABOVE ARCADE | | AND ADDING/REVISING DOORS TO COMMERCIAL UNITS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
6 |
Status |
P |
Date |
2007-09-26 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-09-26 |
Time |
17:39 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-09-26 |
Time |
17:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
5 |
Status |
P |
Date |
2007-07-23 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-07-23 |
Time |
17:05 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-07-23 |
Time |
17:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2007-01-22 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2007-01-22 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2007-01-22 |
Time |
10:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2006-08-22 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2006-08-22 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2006-08-22 |
Time |
15:50 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2006-07-18 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2006-05-23 |
Time |
16:15 |
Rev Time |
0.00 |
Received By |
eschneid |
Date |
2006-05-23 |
Time |
16:15 |
Sent To |
|
|
Notes |
2006-07-18 00:00:00 | 1) MINOR AMENDMENT REQUIRED TO MODIFY | | THE PLAZA AREA, INCLUDING THE | | LANDSCAPING, AND THE CHANGED LANDSCAPE | | ON THE EAST FACADE. | | | | 2) THE COLUMN/WALL ELEMENT MAY NOT BE | | 16'6" TALL (PG A-10.1)DISCUSSED WITH | | JOE VERDONE ON THE ACCEPTIBLE HEIGHT. | | | | CONTACT ERIC SCHNEIDER (561) 822-1435. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2008-03-26 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2005-10-05 |
Time |
10:00 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2005-10-05 |
Time |
9:30 |
Sent To |
|
|
Notes |
2005-10-05 00:00:00 | 1) REQUIRE MINOR AMENDMENT REFLECTING | | THE MOVEMENT AND CHANGE IN BUILDING | | FOORPRINT ON BOTH THE SITE AND LANDSCAPE | | PLANS.PLEAE PROVIDE UPDATED PARKING | | COUNTS AS INTERIOR PARKING CONFIGURATION | | HAS CHANGED. | | 2) METAL ROOF WOOD REQUIRE CRA APPROVAL. | | PLANNING STAFF DOES NOT SUPPORT THE | | PAINTED ALUMINUM. | | 3) THE PROPOSED 12 FOOT TALL OBELISK IN | | THE FOUNTAIN IS NOT APPROVED BY PLANNING | | STAFF. | | | | CONTACT ERIC SCHNEDER (561) 822-1435. |
|
|