Plan Review Details - Permit 05091425
Plan Review Stops For Permit 05091425
Review Stop B BUILDING (STRUCTURAL)
Rev No 199 Status P Date 2008-08-27 Cont ID  
Sent By rbrown Date 2008-08-27 Time 18:50 Rev Time 0.00
Received By rbrown Date 2008-08-27 Time 18:50 Sent To  
Notes
2008-08-27 18:51:51STRUCTURAL CALCULATION AND SHOP DRAWING SUBMITTAL FOR
 GLASS GUARDRAIL LOCATED AT 2ND FLOOR ELEVATOR LOBBY
 OVERLOOKING MAIN LOBBY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 198 Status P Date 2008-05-24 Cont ID  
Sent By rbrown Date 2008-05-24 Time 15:18 Rev Time 0.00
Received By rbrown Date 2008-05-24 Time 15:17 Sent To  
Notes
2008-05-24 15:18:47SUBMITTAL ON 5/1/08 FOR CALCULATIONS ON RAILINGS AT
 POOL DECK LEVEL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 196 Status P Date 2008-05-24 Cont ID  
Sent By rbrown Date 2008-05-24 Time 15:08 Rev Time 0.00
Received By rbrown Date 2008-05-24 Time 15:08 Sent To  
Notes
2008-05-24 15:09:19SUBMITTAL ON 5/1/08 FOR CALCULATIONS ON RAILINGS AT
 BUILDING ENTRY

Review Stop B BUILDING (STRUCTURAL)
Rev No 195 Status P Date 2008-05-24 Cont ID  
Sent By rbrown Date 2008-05-24 Time 15:06 Rev Time 0.00
Received By rbrown Date 2008-05-24 Time 15:06 Sent To  
Notes
2008-05-24 15:07:53ARCHITECTURAL REVISION SUBMITTED ON 4/17/08 FOR SHEET
 A-2.1.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 194 Status P Date 2008-04-09 Cont ID  
Sent By rbrown Date 2008-04-09 Time 18:13 Rev Time 0.00
Received By rbrown Date 2008-04-09 Time 18:13 Sent To  
Notes
2008-04-09 18:22:41SUBMITTAL FOR ROOF FLASHING DETAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 193 Status P Date 2008-04-09 Cont ID  
Sent By rbrown Date 2008-04-09 Time 17:09 Rev Time 0.00
Received By rbrown Date 2008-04-09 Time 17:09 Sent To  
Notes
2008-04-09 17:12:00ARCHITECTURAL REVISION FOR SHEETS A-1.1, A-1.5,
 A-2.1.6, A-2.4.2, A-2.4.5, AND A-6.5

Review Stop B BUILDING (STRUCTURAL)
Rev No 192 Status P Date 2008-02-13 Cont ID  
Sent By rbrown Date 2008-02-13 Time 19:56 Rev Time 0.00
Received By rbrown Date 2008-02-13 Time 19:56 Sent To  
Notes
2008-02-13 19:57:18SUBMITTAL ON 1/11/08 FOR 4 HR FIRESTOP JOINT DETAIL

Review Stop B BUILDING (STRUCTURAL)
Rev No 191 Status P Date 2007-12-24 Cont ID  
Sent By rbrown Date 2007-12-24 Time 16:17 Rev Time 0.00
Received By rbrown Date 2007-12-24 Time 16:17 Sent To  
Notes
2007-12-24 16:18:19SUBMITTAL FOR 9TH FLOOR SAUNA/STEAM ROOM SHOP DRAWINGS
 AND PRODUCT DATA

Review Stop B BUILDING (STRUCTURAL)
Rev No 190 Status P Date 2007-12-21 Cont ID  
Sent By rbrown Date 2007-12-21 Time 21:56 Rev Time 0.00
Received By rbrown Date 2007-12-21 Time 21:56 Sent To  
Notes
2007-12-21 21:57:06SUBMITTTAL FOR MECHANICAL AND ADHESIVE ATTACHMENT OF
 EIFS ARCHITECTURAL MOLDING

Review Stop B BUILDING (STRUCTURAL)
Rev No 189 Status P Date 2007-12-21 Cont ID  
Sent By rbrown Date 2007-12-21 Time 21:42 Rev Time 0.00
Received By rbrown Date 2007-12-21 Time 21:42 Sent To  
Notes
2007-12-21 21:46:36STRUCTURAL SUBMITTAL FOR ROOF LEVEL MECHANICAL PIPE
 BRIDGES

Review Stop B BUILDING (STRUCTURAL)
Rev No 188 Status P Date 2007-12-21 Cont ID  
Sent By rbrown Date 2007-12-21 Time 21:36 Rev Time 0.00
Received By rbrown Date 2007-12-21 Time 21:36 Sent To  
Notes
2007-12-21 21:36:50SUBMITTAL FOR PRECAST VENEER AND COPING ATTACHMENT
 CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 187 Status P Date 2007-12-21 Cont ID  
Sent By rbrown Date 2007-12-21 Time 21:26 Rev Time 0.00
Received By rbrown Date 2007-12-21 Time 21:26 Sent To  
Notes
2007-12-21 21:27:54SUBMITTAL FOR COPPER ROOFTOP SPHERE ATTACHMENT

Review Stop B BUILDING (STRUCTURAL)
Rev No 186 Status P Date 2007-12-21 Cont ID  
Sent By rbrown Date 2007-12-21 Time 21:20 Rev Time 0.00
Received By rbrown Date 2007-12-21 Time 21:20 Sent To  
Notes
2007-12-21 21:21:29SHOP DRAWINGS AND CALCULATIONS FOR LOUVERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 185 Status P Date 2007-12-21 Cont ID  
Sent By rbrown Date 2007-12-21 Time 21:19 Rev Time 0.00
Received By rbrown Date 2007-12-21 Time 21:19 Sent To  
Notes
2007-12-21 21:20:35SUBMITTAL FOR VILLA TRASH ROOM 2 TRASH CHUTE SHOP
 DRAWING

Review Stop B BUILDING (STRUCTURAL)
Rev No 184 Status P Date 2007-12-21 Cont ID  
Sent By rbrown Date 2007-12-21 Time 21:06 Rev Time 0.00
Received By rbrown Date 2007-12-21 Time 21:06 Sent To  
Notes
2007-12-21 21:07:08ARCHITECTURAL SUBMITTAL FOR ROOF FLASHING AND EXPANSION
 JOINT DETAILS AND PRODUCT DATA

Review Stop B BUILDING (STRUCTURAL)
Rev No 183 Status P Date 2007-12-21 Cont ID  
Sent By rbrown Date 2007-12-21 Time 20:53 Rev Time 0.00
Received By rbrown Date 2007-12-21 Time 20:53 Sent To  
Notes
2007-12-21 21:06:05STRUCTURAL SUBMITTAL FOR VILLA ROOF TRUSS SHOP DRAWINGS
 AND CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 182 Status P Date 2007-12-21 Cont ID  
Sent By rbrown Date 2007-12-21 Time 20:41 Rev Time 0.00
Received By rbrown Date 2007-12-21 Time 20:41 Sent To  
Notes
2007-12-21 20:42:28ARCHITECTURAL REVISION FOR SHEETS A-8.1, A-8.4, A-9.3.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 181 Status P Date 2007-12-21 Cont ID  
Sent By rbrown Date 2007-12-21 Time 20:30 Rev Time 0.00
Received By rbrown Date 2007-12-21 Time 20:30 Sent To  
Notes
2007-12-21 20:31:09SUBMITTAL FOR ROOF TILE ATTACHMENT CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 180 Status P Date 2007-12-21 Cont ID  
Sent By rbrown Date 2007-12-21 Time 20:21 Rev Time 0.00
Received By rbrown Date 2007-12-19 Time 20:09 Sent To  
Notes
2007-12-21 20:23:37ARCHITECTURAL REVISION FOR SHEETS A-1.1, A-2.1.4,
 A-2.1.5, A-2.3.6, A-2.7.1, A-6.1, A-6.5, A-6.9

Review Stop B BUILDING (STRUCTURAL)
Rev No 179 Status P Date 2007-11-19 Cont ID  
Sent By rbrown Date 2007-11-19 Time 11:18 Rev Time 0.00
Received By rbrown Date 2007-11-19 Time 11:18 Sent To  
Notes
2007-11-19 11:19:55SUBMITTAL ON 11/16/07 FOR STOREFRONT SHOP DRAWING AND
 CALCULATIONS PREVIOUSLY REVIEWED ON 11/12/07 AND
 9/23/07.

Review Stop B BUILDING (STRUCTURAL)
Rev No 178 Status F Date 2007-11-12 Cont ID  
Sent By rbrown Date 2007-11-12 Time 17:45 Rev Time 0.00
Received By rbrown Date 2007-11-12 Time 17:44 Sent To  
Notes
2007-11-12 18:33:19BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 10/23/07 FOR CALCULATIONS, SHOP DRAWINGS,
 AND PRODUCT APPROVALS FOR STOREFRONT
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 1606.1SHEET 1 OF 10 OF THE SUBMITTED
 CONTINENTAL GLASS SYSTEM SERIES 3000 ALUMINUM WINDOW
 WALL SYSTEM PRODUCT APPROVAL NOA# 05-1220.17 STATES
 THAT THE MAXIMUM ALLOWABLE MASONRY OPENING HEIGHT IS
 10'-1 3/8". HOWEVER, SHEET 5 (WINDOW S6) OF THE
 SUBMITTED ENGINEERING EXPRESS (FRANK BENNARDO, P.E.)
 SHOP DRAWINGS SHOWS THE A REQUIREMENT FOR A MASONRY
 OPENING HEIGHT OF 14'-10" WHICH EXCEEDS THE MAXIMUM
 ALLOWED BY THE PRODUCT APPROVAL.SUBMIT A PRODUCT
 APPROVAL THAT COVERS THE REQUIRED WINDOW SIZE.
  
 2) FBC 1606.1SHEET 14 OF THE SUBMITTED "TUBE STEEL
 CALCULATIONS" FROM ENGINEERING EXPRESS (FRANK BENNARDO,
 P.E.) STATES THAT THE TRIBUTARY SPAN OF THE HORIZONTAL
 MULLION FOR S4 IS 6'-4.5".HOWEVER, SHEET 6 (WINDOW
 S4) OF THE SUBMITTED ENGINEERING EXPRESS (FRANK
 BENNARDO, P.E.) SHOP DRAWINGS SHOWS THAT THE TRIBUTARY
 SPAN SHOULD BE AT LEAST 7'-0" (DUE TO ARCHED TOP).
 SUBMIT CALCULATIONS THAT REFLECT THE ACTUAL TRIBUTARY
 SPAN.
  
 3) FBC 1606.1SHEETS 10, 12, AND 14 OF THE SUBMITTED
 "TUBE STEEL CALCULATIONS" FROM ENGINEERING EXPRESS
 (FRANK BENNARDO, P.E.) STATES A REQUIRED WALL THICKNESS
 OF 3/8" FOR THE HORIZONTAL MULLIONS FOR WINDOW 7 AND
 S4.HOWEVER,SHEET 8, DETAIL 7.1, OF THE SUBMITTED
 ENGINEERING EXPRESS (FRANK BENNARDO, P.E.) SHOP
 DRAWINGS SHOWS A WALL THICKNESS OF ONLY 1/4". AMEND THE
 SHOP DRAWING DETAIL TO ENSURE THAT THE TUBE MULLION
 WALL THICKNESS THAT IS REQUIRED BY THE CALCULATIONS
 WILL BE PROVIDED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 177 Status P Date 2007-10-18 Cont ID  
Sent By rbrown Date 2007-10-18 Time 18:53 Rev Time 0.00
Received By rbrown Date 2007-10-18 Time 18:53 Sent To  
Notes
2007-10-18 18:55:54SUBMITTAL ON 10/12/07 FOR EIFS PRODUCT DATA, AND
 ASSOCIATED ADHESIVE PRODUCT DATA AND MECHANICAL
 FASTENER PRODUCT DATA AND SHOP DRAWING
  
 MUST SUBMIT ENGINEERING FOR FIVE (5) FASTENERS
 SUPPORTING WEIGHT OF 8'-0" LONG EIFS PANEL
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 176 Status P Date 2007-10-18 Cont ID  
Sent By rbrown Date 2007-10-18 Time 18:50 Rev Time 0.00
Received By rbrown Date 2007-10-18 Time 18:50 Sent To  
Notes
2007-10-18 18:53:14REVISION FOR SHEET A-2.7.5 AND A-2.7.6 PREVIOUSLY
 PASSED BY BUILDING/STRUCTURAL AND NOW PASSED BY
 PLUMBING WITH PROVISO

Review Stop B BUILDING (STRUCTURAL)
Rev No 175 Status P Date 2007-10-05 Cont ID  
Sent By rbrown Date 2007-10-05 Time 19:21 Rev Time 0.00
Received By rbrown Date 2007-10-05 Time 19:21 Sent To  
Notes
2007-10-05 19:22:19SUBMITTAL ON 9/28/07 FOR TRASH CHUTE SHOP DRAWING
 CHANGES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 174 Status P Date 2007-10-05 Cont ID  
Sent By rbrown Date 2007-10-05 Time 19:18 Rev Time 0.00
Received By rbrown Date 2007-10-05 Time 19:18 Sent To  
Notes
2007-10-05 19:21:12SUBMITTAL ON 9/27/07 FOR COMMENT RESPONSE ADDRESSING
 THE 9/23/07 PLAN REVIEW COMMENTS RELATED TO GAPS IN
 RAILING PATTERN ON SHEET A-6.9

Review Stop B BUILDING (STRUCTURAL)
Rev No 173 Status P Date 2007-10-05 Cont ID  
Sent By rbrown Date 2007-10-05 Time 19:14 Rev Time 0.00
Received By rbrown Date 2007-10-05 Time 19:14 Sent To  
Notes
2007-10-05 19:17:52SUBMITTAL ON 9/25/07 FOR EXTERIOR CEILING FRAMING
 CALCULATIONS AND SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 172 Status P Date 2007-10-01 Cont ID  
Sent By rbrown Date 2007-10-01 Time 20:47 Rev Time 0.00
Received By rbrown Date 2007-10-01 Time 20:47 Sent To  
Notes
2007-10-01 20:52:41REVISION SUBMITTED 7/25/07.SHEET A-7.15 SENT TO
 ZONING FOR REVIEW DUE TO INCREASE IN HEIGHT OF WALL
 ABOVE ARCADE.ZONING REVIEWED AND STAMPED ON 9/26/07.
 REVISION OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 171 Status F Date 2007-10-01 Cont ID  
Sent By rbrown Date 2007-10-01 Time 20:18 Rev Time 0.00
Received By rbrown Date 2007-10-01 Time 20:18 Sent To  
Notes
2007-10-01 20:36:17BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 9/24/07 FOR EIFS SYSTEMS TEST REPORT.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) THE SUBMITTED METAL FRAMING CALCULATIONS ARE OK AND
 HAVE BEEN STAMPED
  
 2) THE REVISED ARCHITECTURAL SHEETS ARE OK AND HAVE
 BEEN STAMPED BECAUSE THEY STATE THE REQUIREMENT FOR
 ASTM E 136 COMPLIANCE.
  
 3) FBC 202DEFINITION OF "NON-COMBUSTIBLE MATERIAL".
 NON-COMBUSTIBLE MATERIAL IS THAT WHICH HAS PASSED THE
 TEST PROCEDURE SET FORTH IN ASTM E 136.THE SUBMITTED
 PRODUCT TEST REPORT CANNOT BE STAMPED BECAUSE THE TEST
 STANDARD USED TO TEST THE STO CLASSIC NEXT SYSTEM WAS
 NFPA 285 NOT ASTM E 136, SO THE PRODUCT HAS NOT BEEN
 SHOWN TO MEET THE REQUIREMENTS FOR NON-COMBUSTIBLE
 MATERIAL.PROVIDE A TEST REPORT BASED ON THE ASTM E
 136 TEST STANDARD.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 170 Status P Date 2007-10-01 Cont ID  
Sent By rbrown Date 2007-10-01 Time 20:11 Rev Time 0.00
Received By rbrown Date 2007-10-01 Time 20:11 Sent To  
Notes
2007-10-01 20:15:38REVISION SUBMITTED 9/24/07 FOR SHEETS A-6.1, A-6.2,
 A-6.3, A-6.5, A-6.8, A-6.9 AND A-8.3.REVISED
 ARCHITECTURAL SHEETS ARE OK BECAUSE THEY STATE
 REQUIREMENT FOR ASTM E 136 COMPLIANCE.THE SUBMITTED
 PRODUCT TEST REPORT CANNOT BE STAMPED AS THE TEST
 STANDARD USED WAS NFPA 285 NOT ASTM E 136

Review Stop B BUILDING (STRUCTURAL)
Rev No 169 Status P Date 2007-09-23 Cont ID  
Sent By rbrown Date 2007-09-23 Time 17:40 Rev Time 0.00
Received By rbrown Date 2007-09-23 Time 17:40 Sent To  
Notes
2007-09-23 17:41:50REVISION SUBMITTED 7/25/07.SHEET A-7.15 SENT TO
 ZONING FOR REVIEW DUE TO INCREASE IN HEIGHT OF WALL
 ABOVE ARCADE

Review Stop B BUILDING (STRUCTURAL)
Rev No 168 Status F Date 2007-09-23 Cont ID  
Sent By rbrown Date 2007-09-23 Time 16:02 Rev Time 0.00
Received By rbrown Date 2007-09-23 Time 16:02 Sent To  
Notes
2007-09-23 16:18:06BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 7/3/07
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1015.3SHEET A-6.9 HAS BEEN REVISED TO
 INCORPORATE DETAIL F WHICH SHOWS "DECORATIVE RAILING"
 ABOVE THE ARCADE.THE RAILING DESIGN HAS PROPORTIONS
 THAT LEAVE GAPS THAT EXCEED 4 INCHES BETWEEN RAILS.
 SHEET A-6.1, OKEECHOBEE BLVD ELEVATION SHOWS SLIDING
 GLASS DOORS GIVING ACCESS TO THESE RAILINGS.THE
 ORNAMENTAL PATTERN SHALL BE ARRANGED SO THAT A 4 INCH
 SPHERE CANNOT PASS THROUGH ANY OPENING.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 167 Status F Date 2007-09-23 Cont ID  
Sent By rbrown Date 2007-09-23 Time 14:52 Rev Time 0.00
Received By rbrown Date 2007-09-23 Time 14:52 Sent To  
Notes
2007-09-23 15:00:47BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 9/4/07 FOR TRASH CHUTE SHOP DRAWING
 REVISION
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) IT IS NOTED THAT THERE IS A COPY OF A 9/26/06 (2006)
 STAMP FROM ROGER FRY ARCHITECT ON A LETTER FROM
 WILKINSON HI RISE ON SOUND TRANSMISSION, BUT THERE IS
 NO STAMP FROM ROGER FRY ARCHITECT ON THE REVISED SHOP
 DRAWINGS.THE REVISED SHOP DRAWINGS MUST HAVE A SHOP
 DRAWING REVIEW STAMP FROM THE ARCHITECT OF RECORD.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 166 Status P Date 2007-09-23 Cont ID  
Sent By rbrown Date 2007-09-23 Time 14:47 Rev Time 0.00
Received By rbrown Date 2007-09-23 Time 14:47 Sent To  
Notes
2007-09-23 14:48:24SUBMITTAL ON 8/30/07 FOR FPL VAULT LOUVERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 165 Status P Date 2007-09-23 Cont ID  
Sent By rbrown Date 2007-09-23 Time 14:25 Rev Time 0.00
Received By rbrown Date 2007-09-23 Time 14:25 Sent To  
Notes
2007-09-23 14:27:05SUBMITTAL ON 8/24/07 FOR VILLAS ROOF TRUSS SHOP DRAWING
 AND CALCS FOR ALTERNATIVE METAL TRUSS ATTACHMENT

Review Stop B BUILDING (STRUCTURAL)
Rev No 164 Status P Date 2007-09-23 Cont ID  
Sent By rbrown Date 2007-09-23 Time 14:20 Rev Time 0.00
Received By rbrown Date 2007-09-23 Time 14:20 Sent To  
Notes
2007-09-23 14:20:40SUBMITTAL ON 8/21/07 FOR WINDOW WASHING SYSTEM SHOP
 DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 163 Status P Date 2007-09-23 Cont ID  
Sent By rbrown Date 2007-09-23 Time 14:10 Rev Time 0.00
Received By rbrown Date 2007-09-23 Time 14:10 Sent To  
Notes
2007-09-23 14:11:24SUBMITTAL ON 8/10/07 FOR VILLAS ROOF TRUSS SHOP
 DRAWINGS AND CALCS

Review Stop B BUILDING (STRUCTURAL)
Rev No 162 Status F Date 2007-09-23 Cont ID  
Sent By rbrown Date 2007-09-23 Time 12:45 Rev Time 0.00
Received By rbrown Date 2007-09-23 Time 12:45 Sent To  
Notes
2007-09-23 13:26:57BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 7/20/07 FOR CALCULATIONS, SHOP DRAWINGS,
 AND PRODUCT APPROVALS FOR STOREFRONT
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) AS STATED IN THE PREVIOUS REVIEW OF THESE DOCUMENTS
 ON 6/26/07, THE PRODUCT APPROVALS THAT ARE FOR PRODUCTS
 DIFFERENT FROM THE THOSE THAT HAVE ALREADY BEEN
 REVIEWED/STAMPED FOR THIS PROJECT ARE CONSIDERED
 REVISIONS AND A REVISION FEE IS DUE.THE PACKET WAS
 AGAIN INCORRECTLY SUBMITTED AS A ZERO FEE SUBMITTAL.
 IT IS A REVISION AND THE APPROPRIATE REVISION FEE OF
 $50 PLUS $10 FOR EACH NEW PRODUCT HAS NOW BEEN APPLIED
 ONCE FOR THE ORIGINAL REVISION SUBMITTAL AND AGAIN FOR
 THIS RE-SUBMITTAL OF THE REVISION.THE OUTSTANDING FEE
 IS $200 [CALCULATED AS 2X(50 + 5X10)].
  
 2) FBC* 1606.1THE CONTINENTAL GLASS SYSTEM SERIES
 3000 ALUMINUM WINDOW WALL SYSTEM PRODUCT APPROVAL NOA#
 05-1220.18 STATES THAT THE MAXIMUM NEGATIVE DESIGN
 PRESSURE SHALL NOT EXCEED -110 PSF.HOWEVER, SHEET 5
 OF THE THE SUBMITTED ENGINEERING EXPRESS (FRANK
 BENNARDO, P.E.) SHOP DRAWINGS SHOWS THE A REQUIREMENT
 FOR NEGATIVE PRESSURE OF -130 PSF, AND REFERS TO
 RATIONAL ANALYSIS TO JUSTIFY EXCEEDING THE -110 PSF
 NEGATIVE DESIGN PRESSURE LIMIT OF THE PROPOSED PRODUCT.
 NO RATIONAL ANALYSIS WAS SUBMITTED.SUBMIT ORIGINAL
 SIGNED AND SEALED RATIONAL ANALYSIS CALCULATION
 SHEETS.
 BECAUSE THE REVIEW OF THE SHOP DRAWINGS CANNOT BE
 COMPLETED WITHOUT THE REFERENCE ATIONAL ANALYSIS
 CALCULATIONS, ALL COPIES OF THE STAMPED PRODUCT
 APPROVALS HAVE BEEN RETURNED.NO COPIES HAVE BEEN
 RETAINED, SO THEY WILL ALL NEED TO BE RE-SUBMITTED AS A
 COMPLETE PACKAGE WHEN THE RATIONAL ANALYSIS
 CALCULATIONS AND THE SHOP DRAWINGS ARE SUBMITTED.
 BECAUSE THEY HAVE ALL BEEN REVIEWED ALREADY THEY MAY
 ALL BE BROUGHT IN AS ZERO FEE SUBMITTALS.
  
 3) THE PURPOSE OF THE SUBMITTED "TUBE STEEL
 CALCULATIONS" FROM ENGINEERING EXPRESS (FRANK BENNARDO,
 P.E.) COULD NOT BE DETERMINED.HOWEVER IT IS NOTED
 THAT THESE CALCULATIONS MAKE REPEATED REFERENCE TO A
 WIND PRESSURE OF 49 PSF.ACCORDING TO THE RWDI WIND
 TUNNEL TEST REPORT THERE IS NO LOCATION ON THIS
 BUILDING WITH A WIND PRESSURE AS LOW AS 49 PSF.ALL
 SUBMITTED COPIES OF THESE CALCULATIONS ARE BEING
 RETURNED TO THE CONTRACTOR.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 161 Status P Date 2007-09-09 Cont ID  
Sent By rbrown Date 2007-09-09 Time 20:27 Rev Time 0.00
Received By rbrown Date 2007-09-09 Time 20:27 Sent To  
Notes
2007-09-09 20:27:53SUBMITTAL ON 8/17/07 FOR HIGH ROOF AREA 12 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 160 Status P Date 2007-09-09 Cont ID  
Sent By rbrown Date 2007-09-09 Time 20:25 Rev Time 0.00
Received By rbrown Date 2007-09-09 Time 20:25 Sent To  
Notes
2007-09-09 20:25:32SUBMITTAL ON 8/16/07 FOR HIGH ROOF AREA 2 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 159 Status P Date 2007-09-09 Cont ID  
Sent By rbrown Date 2007-09-09 Time 20:21 Rev Time 0.00
Received By rbrown Date 2007-09-09 Time 20:21 Sent To  
Notes
2007-09-09 20:21:53SUBMITTAL ON 8/14/07 FOR HIGH ROOF AREA 7B SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 158 Status P Date 2007-09-09 Cont ID  
Sent By rbrown Date 2007-09-09 Time 20:17 Rev Time 0.00
Received By rbrown Date 2007-09-09 Time 20:17 Sent To  
Notes
2007-09-09 20:18:39SUBMITTAL ON 7/312/07 FOR HIGH ROOF AREA 1 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 157 Status P Date 2007-09-09 Cont ID  
Sent By rbrown Date 2007-09-09 Time 20:11 Rev Time 0.00
Received By rbrown Date 2007-09-09 Time 20:10 Sent To  
Notes
2007-09-09 20:14:56SUBMITTAL ON 7/27/07 FOR VILLAS SE HIGH ROOF SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 156 Status F Date 2007-09-09 Cont ID  
Sent By rbrown Date 2007-09-09 Time 19:56 Rev Time 0.00
Received By rbrown Date 2007-09-09 Time 19:56 Sent To  
Notes
2007-09-09 20:08:41BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 7/10/07 FOR CALCULATIONS AND SHOP DRAWINGS
 FOR EXTERIOR FRAMING AND DROP CEILINGS
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 104.1.5 AND 104.2.1.3THE CALCULATION SHEETS
 AND SHOP DRAWINGS ALL REFER TO A PROJECT LOCATED AT
 2828 CORAL WAY, MIAMI, FL.THE PROJECT LOCATION IS 550
 OKEECHOBEE BLVD, WEST PALM BEACH, FL.ALL SUBMITTED
 DOCUMENTS ARE RETAINED AS PART OF THE RECORD RETENTION
 PROGRAM MANDATED BY STATUTE AND ARE REQUIRED TO STATE
 THE CORRECT PROJECT LOCATION.PLEASE REMOVE ALL
 REFERENCES TO THE INCORRECT LOCATION.
 SUGGESTION: FOR EVERY CALCULATION PAGE, TITLE PAGE,
 CONTENTS PAGE AND DRAWING SHEET, STRIKE OUT ALL
 REFERENCES TO 2828 CORAL WAY, MIAMI, FL AND APPLIY A
 STAMP (OR LABEL) WITH THE CORRECT ADDRESS OF 550
 OKEECHOBEE BLVD, WEST PALM BEACH, FL.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 155 Status P Date 2007-09-09 Cont ID  
Sent By rbrown Date 2007-09-09 Time 19:48 Rev Time 0.00
Received By rbrown Date 2007-09-09 Time 19:48 Sent To  
Notes
2007-09-09 19:50:01SUBMITTAL ON 7/10/07 FOR HIGH ROOF LEVEL SHORING
 CALCULATIONS AND SHOP DRAWING

Review Stop B BUILDING (STRUCTURAL)
Rev No 154 Status P Date 2007-09-09 Cont ID  
Sent By rbrown Date 2007-09-09 Time 19:38 Rev Time 0.00
Received By rbrown Date 2007-09-09 Time 19:38 Sent To  
Notes
2007-09-09 19:39:26SUBMITTAL ON 7/10/07 FOR INTERMEDIATE ROOF LEVEL
 ELEVATION +207'-4" SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 153 Status P Date 2007-09-09 Cont ID  
Sent By rbrown Date 2007-09-09 Time 19:35 Rev Time 0.00
Received By rbrown Date 2007-09-09 Time 19:34 Sent To  
Notes
2007-09-09 19:35:36SUBMITTAL ON 7/10/07 FOR MAIN ROOF LEVEL SLAB POUR 2
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 152 Status P Date 2007-09-09 Cont ID  
Sent By rbrown Date 2007-09-09 Time 18:59 Rev Time 0.00
Received By rbrown Date 2007-09-09 Time 18:59 Sent To  
Notes
2007-09-09 19:01:36SUBMITTAL ON 7/2/07 FOR MAIN ROOF LEVEL SLAB POUR 3
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 151 Status P Date 2007-07-01 Cont ID  
Sent By rbrown Date 2007-07-01 Time 08:49 Rev Time 0.00
Received By rbrown Date 2007-07-01 Time 08:49 Sent To  
Notes
2007-07-01 08:49:46SUBMITTAL ON 6/26/07 FOR MAIN ROOF LEVEL SLAB POUR 1
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 150 Status P Date 2007-07-01 Cont ID  
Sent By rbrown Date 2007-07-01 Time 08:44 Rev Time 0.00
Received By rbrown Date 2007-07-01 Time 08:44 Sent To  
Notes
2007-07-01 08:46:26SUBMITTAL ON 6/22/07 FOR 9TH FLOOR GARAGE SLAB POUR 3
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 149 Status F Date 2007-07-01 Cont ID  
Sent By rbrown Date 2007-07-01 Time 08:34 Rev Time 0.00
Received By rbrown Date 2007-07-01 Time 08:34 Sent To  
Notes
2007-07-01 08:35:57BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 6/20/07 FOR ROOF TRUSS SHOP
 DRAWING
  
 1)THERE IS NO REVIEW STAMP FROM THE DESIGNER OF
 RECORD FOR THE PROJECT.ALL SHOP DRAWINGS AND
 CALCULATIONS MUST BE REVIEWED BY THE DESIGNER OF RECORD
 AND A SHOP DRAWING REVIEW STAMP MUST BE APPLIED TO THEM
 BEFORE SUBMITTAL TO THIS OFFICE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 148 Status P Date 2007-07-01 Cont ID  
Sent By rbrown Date 2007-07-01 Time 08:33 Rev Time 0.00
Received By rbrown Date 2007-07-01 Time 08:33 Sent To  
Notes
2007-07-01 08:34:01SUBMITTAL ON 6/19/07 FOR 20TH FLOOR TOWER SLAB POUR 2
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 147 Status P Date 2007-07-01 Cont ID  
Sent By rbrown Date 2007-07-01 Time 08:29 Rev Time 0.00
Received By rbrown Date 2007-07-01 Time 08:29 Sent To  
Notes
2007-07-01 08:30:46SUBMITTAL ON 6/14/07 FOR 9TH FLOOR GARAGE SLAB POUR 2
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 146 Status P Date 2007-07-01 Cont ID  
Sent By rbrown Date 2007-07-01 Time 08:27 Rev Time 0.00
Received By rbrown Date 2007-07-01 Time 08:27 Sent To  
Notes
2007-07-01 08:27:35SUBMITTAL ON 6/11/07 FOR 20TH FLOOR TOWER SLAB POUR 3
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 145 Status P Date 2007-07-01 Cont ID  
Sent By rbrown Date 2007-07-01 Time 08:23 Rev Time 0.00
Received By rbrown Date 2007-07-01 Time 08:23 Sent To  
Notes
2007-07-01 08:24:21SUBMITTAL ON 6/11/07 FOR 20TH FLOOR TOWER SLAB POUR 1
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 144 Status F Date 2007-07-01 Cont ID  
Sent By rbrown Date 2007-07-01 Time 08:05 Rev Time 0.00
Received By rbrown Date 2007-07-01 Time 08:05 Sent To  
Notes
2007-07-01 08:18:01BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 6/7/07 FOR ROOF TRUSS SHOP
 DRAWING AND CALCULATION
  
 1)THERE IS NO REVIEW STAMP FROM THE DESIGNER OF
 RECORD FOR THE PROJECT.ALL SHOP DRAWINGS AND
 CALCULATIONS MUST BE REVIEWED BY THE DESIGNER OF RECORD
 AND A SHOP DRAWING REVIEW STAMP MUST BE APPLIED TO THEM
 BEFORE SUBMITTAL TO THIS OFFICE.
  
 2) 61G15-23.002(2)FL. ADMIN. CODE.IT IS NOTED THAT
 THE PRINTED NAME AND PRINTED LICENSE NUMBER FOR THE
 ENGINEER, AND CERTIFICATE OF AUTHORIZATION NUMBER FOR
 THE ENGINEERING BUSINESS (MOODY ENGINEERING, INC.) IS
 INCLUDED ON THE SHOP DRAWINGS.HOWEVER THAT
 INFORMATION MUST BE BE PRINTED ON THE CALCULATIONS
 ALSO.CURRENTLY IT IS ONLY THERE IN THE FORM OF THE
 RAISED SEAL, WHICH DOES NOT REPRODUCE WHEN SCANNED FOR
 ARCHIVING.THIS INFORMATION MUST BE MUST BE ADDED TO
 THE FIRST (SIGNED AND SEALED) SHEET OF THE CALCULATION
 REPORT.THE SHEET DOES NOT HAVE TO BE SIGNED AND
 SEALED AGAIN, THE INFORMATION MAY BE ADDED BY HAND.
 (471.025 F.S. AND 471.023 F.S.).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 143 Status P Date 2007-07-01 Cont ID  
Sent By rbrown Date 2007-07-01 Time 08:01 Rev Time 0.00
Received By rbrown Date 2007-07-01 Time 08:01 Sent To  
Notes
2007-07-01 08:02:27SUBMITTAL ON 6/5/07 FOR INTERMEDIATE ROOF SLAB SHORING
 SHOP DRAWINGS AND CALCS

Review Stop B BUILDING (STRUCTURAL)
Rev No 142 Status P Date 2007-07-01 Cont ID  
Sent By rbrown Date 2007-07-01 Time 07:55 Rev Time 0.00
Received By rbrown Date 2007-07-01 Time 07:55 Sent To  
Notes
2007-07-01 08:00:55SUBMITTAL ON 6/5/07 FOR 9TH FLOOR VILLA SLAB POUR 1
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 141 Status P Date 2007-07-01 Cont ID  
Sent By rbrown Date 2007-07-01 Time 07:50 Rev Time 0.00
Received By rbrown Date 2007-07-01 Time 07:50 Sent To  
Notes
2007-07-01 07:52:22SUBMITTAL ON 6/5/07 FOR MAIN ROOF LEVEL SLAB SHORING
 SHOP DRAWING AND CALCS

Review Stop B BUILDING (STRUCTURAL)
Rev No 140 Status P Date 2007-07-01 Cont ID  
Sent By rbrown Date 2007-07-01 Time 07:45 Rev Time 0.00
Received By rbrown Date 2007-07-01 Time 07:45 Sent To  
Notes
2007-07-01 07:48:07SUBMITTAL ON 6/5/07 FOR 19TH FLOOR TOWER SLAB POUR 2
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 139 Status F Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 11:53 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 11:53 Sent To  
Notes
2007-06-30 12:18:48BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 5/31/07 FOR WINDOW WASHING SYSTEM SHOP
 DRAWINGS
  
 1)THERE IS NO REVIEW STAMP FROM THE DESIGNER OF
 RECORD FOR THE PROJECT.ALL SHOP DRAWINGS MUST BE
 REVIEWED BY THE DESIGNER OF RECORD AND A SHOP DRAWING
 REVIEW STAMP MUST BE APPLIED TO THE SHOP DRAWINGS
 BEFORE SUBMITTAL TO THIS OFFICE.
  
 2) THE TITLE BLOCK ON THE PLANS STATE AN INCORRECT
 PROJECT ADDRESS/LOCATION.THE PROJECT STATED IS 2828
 CORAL WAY, MIAMI.THE PLANS MUST IDENTIFY THE CORRECT
 PROJECT LOCATION.
  
 3)THE FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION (DBPR) WEBSITE SHOWS THE LICENSE STATUS OF
 THE WINDOW WASHING SYSTEM ENGINEER AS DELINQUENT.SEE
 ATTACHED PRINTOUT.THE ENGINEER MUST RESOLVE THIS WITH
 THE DBPR/ FLORIDA BOARD OF PROFESSIONAL ENGINEERS, AND
 HAVE THE WEBSITE UPDATED, BEFORE THE PLANS ARE
 RE-SUBMITTED TO THIS OFFICE.
  
 4) FBC* 106.1ENGINEER'S SIGNATURE.ONLY ONE OF THE
 SIX SHEETS SUBMITTED HAS AN ORIGINAL SIGNATURE FROM THE
 ENGINEER.THE OTHER OTHER SHEETS ALL HAVE A RAISED
 SEAL OVER PHOTOCOPIED SIGNATURE.AN ORIGINAL (WET)
 SIGNATURE IS REQUIRED ON ALL DOCUMENTS PREPARED BY A
 PROFESSIONA ENGINEER. (REF: 471.023 F.S.)
  
 5) 61G15-23.002(2)FL. ADMIN. CODE.THE NO PRINTED
 NAME AND PRINTED LICENSE NUMBER FOR THE ENGINEER MUST
 BE ADDED TO EACH SHEET.ALSO, THE ADDRESS OF THE
 ENGINEER (NOT THE COMPANY) IS REQUIRED ON EACH SHEET
 UNLESS PRO-BEL ENTERPRISES IS REGISTERED AS AN
 'ENGINEERING BUSINESS' WITH THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS (FBPE) AND HAS AN ENGINEERING
 BUSINESS NUMBER (CERTIFICATE OF AUTHORIZATION NUMBER)
 ISSUED BY THE FBPE.IF IT IS, THEN PRO-BEL'S
 ENGINEERING BUSINESS NUMBER (CERTIFICATE OF
 AUTHORIZATION NUMBER) MUST BE PRINTED ON THE PLANS.
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 138 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 11:48 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 11:48 Sent To  
Notes
2007-06-30 11:48:52SUBMITTAL ON 5/29/07 FOR 19TH FLOOR TOWER POUR 3
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 137 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 11:44 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 11:44 Sent To  
Notes
2007-06-30 11:45:03SUBMITTAL ON 5/29/07 FOR 19TH FLOOR TOWER POUR 1
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 136 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 11:42 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 11:42 Sent To  
Notes
2007-06-30 11:42:42SUBMITTAL ON 5/22/07 FOR ROOF TRUSS SHOP DRAWINGS AND
 CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 135 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 11:13 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 11:13 Sent To  
Notes
2007-06-30 11:15:54SUBMITTAL ON 5/22/07 FOR 18TH FLOOR TOWER POUR 2
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 134 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 11:07 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 11:07 Sent To  
Notes
2007-06-30 11:09:45SUBMITTAL ON 5/17/07 FOR GARAGE SHORING SHOP DRAWING
 AND CALCULATIONS.SEE RFI # 268 FOR ENGINEER OF RECORD
 REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 133 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 10:53 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 10:53 Sent To  
Notes
2007-06-30 10:53:53SUBMITTAL ON 5/17/07 FOR 18TH FLOOR TOWER POUR 3
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 132 Status N Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 10:51 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 10:51 Sent To  
Notes
2007-06-30 10:52:10SUBMITTAL ON 5/17/07 FOR 18TH FLOOR TOWER POUR 1
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 131 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 10:48 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 10:48 Sent To  
Notes
2007-06-30 10:48:27SUBMITTAL ON 5/10/07 FOR 17TH FLOOR TOWER POUR 2
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 130 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 10:45 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 10:45 Sent To  
Notes
2007-06-30 10:46:00SUBMITTAL ON 5/9/07 FOR 18TH FLOOR TOWER POOL DECK
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 129 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 10:43 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 10:43 Sent To  
Notes
2007-06-30 10:43:52SUBMITTAL ON 5/9/07 FOR 17TH FLOOR TOWER POUR 3 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 128 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 10:39 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 10:39 Sent To  
Notes
2007-06-30 10:40:16SUBMITTAL ON 5/3/07 FOR 17TH FLOOR TOWER POUR 1 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 127 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 10:36 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 10:36 Sent To  
Notes
2007-06-30 10:37:31SUBMITTAL ON 5/3/07 FOR 4TH FLOOR GARAGE POUR 1 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 126 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 10:34 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 10:34 Sent To  
Notes
2007-06-30 10:34:56SUBMITTAL ON 5/2/07 FOR 8TH FLOOR VILLA POUR 3 SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 125 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 10:22 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 10:22 Sent To  
Notes
2007-06-30 10:23:03SUBMITTAL ON 4/30/07 FOR 16TH FLOOR TOWER POUR 3
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 124 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 10:18 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 10:18 Sent To  
Notes
2007-06-30 10:19:59SUBMITTAL ON 4/27/07 FOR 8TH FLOOR GARAGE POUR 2
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 123 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 10:13 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 10:13 Sent To  
Notes
2007-06-30 10:14:10SUBMITTAL ON 4/26/07 FOR 16TH FLOOR TOWER POUR 2
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 122 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 10:09 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 10:09 Sent To  
Notes
2007-06-30 10:10:22SUBMITTAL ON 4/20/07 FOR 8TH FLOOR GARAGE POUR 1
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 121 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 10:04 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 10:04 Sent To  
Notes
2007-06-30 10:06:17SUBMITTAL ON 4/9/07 FOR 9TH FLOOR POST-TENSION SLAB
 SHOP DRAWINGS AND CALCS

Review Stop B BUILDING (STRUCTURAL)
Rev No 120 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 09:57 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 09:56 Sent To  
Notes
2007-06-30 09:58:40SUBMITTAL 4/3/07 FOR EXTERIOR CEILING/SOFFIT METAL
 FRAMING

Review Stop B BUILDING (STRUCTURAL)
Rev No 119 Status P Date 2007-06-30 Cont ID  
Sent By rbrown Date 2007-06-30 Time 09:39 Rev Time 0.00
Received By rbrown Date 2007-06-30 Time 09:39 Sent To  
Notes
2007-06-30 09:41:07SUBMITTAL ON 6/29/07 FOR GUARDRAILS, HANDRAILS, STAIRS
 AND MISC. METALS SHOP DRAWINGS AND CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 118 Status F Date 2007-06-27 Cont ID  
Sent By rbrown Date 2007-06-27 Time 08:11 Rev Time 0.00
Received By rbrown Date 2007-06-27 Time 08:11 Sent To  
Notes
2007-06-27 09:58:44BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 3/30/07 FOR ROOFING PRODUCT APPROVALS AND
 SPECS
  
 1) FBC* 106.3.3ALL PRODUCT APPROVALS, SHOP DRAWINGS
 AND CALCULATIONS SHALL BE REVIEWED BY THE DESIGNER OF
 RECORD AND STAMPED WITH HIS/HER SHOP DRAWING REVIEW
 STAMP PRIOR TO SUBMITTAL FOR BUILDING OFFICIAL REVIEW.
 THERE ARE NO SHOP DRAWING REVIEW STAMPS, FROM THE
 DESIGNER OF RECORD, ON ANY OF THE SUBMITTED DOCUMENTS.
  
 2) THE SUBMITTED SANTAFE SPANISH 'S' CLAY ROOF TILE
 PRODUCT APPROVAL NOA# 05-0921.02 IS A REVISION FROM THE
 CLAY FOREVER, LLC ALTUSA "S" CLAY ROOF TILE PRODUCT
 APPROVAL 05-0901.06 (FL # 5559) THAT WAS REVIEWED AND
 STAMPED ON 9/9/06.REVISED ATTACHMENT CALCULATIONS
 WOULD BE REQUIRED BECAUSE THE ROOF TILE REVISION WAS
 ALSO INTRODUCED UNDER THE ROOFING SUB-PERMIT #
 07060198, AND THE CALCULATIONS SUBMITTED UNDER THAT
 PERMIT NUMBER GENERATED THE FOLLOWING PLAN REVIEW
 COMMENT:
 FBC 1609.1WIND PRESSURES.BASED ON THE RWDI WIND
 TUNNEL TEST REPORT, SHEET S-6.00 OF THE STRUCTURAL
 PLANS FOR THE BUILDING (UNDER PERMIT # 05091425) SHOWS
 NEGATIVE WINDPRESSURES RANGING FROM -70 PSF TO -150
 PSF.THESE DESIGN PRESSURE ARE FAR HIGHER THAN THE
 PRESSURES ASSUMED IN THE SUBMITTED ATLANTIC & CARIBBEAN
 ROOFING CONSULTING, LLC REPORTS 06-1274 L REV. AND
 06-1274 H REV. (BOTH DATED 6/5/07) FOR THE
 DESIGN/SELECTION OF THE TILE AND ATTACHMENT FOR THE
 LOWER AND HIGHER ROOF.SUBMIT CALCULATIONS THAT MEET
 THE DESIGN PRESSURES ON STRUCTURAL PLAN SHEET S-6.00.
 IT IS NOTED THAT THE ATLANTIC & CARIBBEAN ROOFING
 CONSULTING, LLC REPORTS 06-1274 L AND 06-1274 H (BOTH
 DATED 8/15/06, PRIOR TO REVISION) DID MEET THE REQUIRED
 WIND PRESSURES, AND WERE CONSEQUENTLY REVIEWED AND
 STAMPED ON 9/9/06 UNDER PERMIT # 05091425.
  
 3) FLORIDA ADMINISTRATIVE CODE RULE 9B-72EITHER
 STATEWIDE OR LOCAL (CITY OF WEST PALM BEACH) PRODUCT
 APPROVAL IS REQUIRED.WHERE THE FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS (DCA) HAS ISSUED A STATEWIDE PRODUCT
 APPROVAL FL # FOR THE PROPOSED PRODUCT, THE APPROPRIATE
 STATEWIDE PRODUCT APPROVAL COVER SHEET SHALL BE
 ATTACHED TO THE SUBMITTEDMIAMI-DADE NOA.FOR
 REFERENCE, THE ATTACHED EXAMPLE STATEWIDE PRODUCT
 APPROVAL COVER SHEET FL 644, FOR JOHNS MANVILLE
 MODIFIED BITUMEN ROOFING SYSTEM OVER LIGHTWEIGHT
 CONCRETE DECKS, HAS BEEN DOWNLOADED FROM THE DCA
 WEBSITE AT:
 WWW.FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
 PLEASE SUBMIT STATEWIDE COVER SHEETS FOR ALL OF THE
 PROPOSED PRODUCTS THAT HAVE DCA PRODUCT APPROVAL.
  
 4) ROOF TILE PRODUCT APPROVAL.A REVISION FEE, OF $50
 PLUS AN ADDITIONAL $10 FOR EACH PRODUCT APPROVAL THAT
 IS DIFFERENT FROM THOSE THAT HAVE ALREADY BEEN
 REVIEWED/STAMPED FOR THIS PROJECT, IS DUE.THE PRODUCT
 APPROVALS SHALL BE BROUGHT BACK AS A REVISION, NOT A
 (ZERO FEE) SUBMITTAL.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 117 Status F Date 2007-06-26 Cont ID  
Sent By rbrown Date 2007-06-26 Time 18:22 Rev Time 0.00
Received By rbrown Date 2007-06-26 Time 18:22 Sent To  
Notes
2007-06-26 18:40:56BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 4/30/07 FOR STOREFRONT DOOR AND WINDOW
 PRODUCT APPROVALS AND SHOP DRAWINGS
  
 1) FBC* 106.3.3ALL PRODUCT APPROVALS, SHOP DRAWINGS
 AND CALCULATIONS SHALL BE REVIEWED BY THE DESIGNER OF
 RECORD AND STAMPED WITH HIS/HER SHOP DRAWING REVIEW
 STAMP PRIOR TO SUBMITTAL FOR BUILDING OFFICIAL REVIEW.
 THERE ARE NO SHOP DRAWING REVIEW STAMPS ON ANY OF THE
 SUBMITTED DOCUMENTS.
  
 2)FLORIDA ADMINISTRATIVE CODE RULE 9B-72EITHER
 STATEWIDE OR LOCAL (CITY OF WEST PALM BEACH) PRODUCT
 APPROVAL IS REQUIRED.WHERE THE FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS (DCA) HAS ISSUED A STATEWIDE PRODUCT
 APPROVAL FL # FOR THE PROPOSED PRODUCT, THE APPROPRIATE
 STATEWIDE PRODUCT APPROVAL COVER SHEET SHALL BE
 ATTACHED TO THE SUBMITTEDMIAMI-DADE NOA.FOR
 REFERENCE, THE ATTACHED EXAMPLE STATEWIDE PRODUCT
 APPROVAL COVER SHEET FL 5854, FOR YKK SERIES 35H
 ALUMINUM ENTRANCE DOOR, HAS BEEN DOWNLOADED FROM THE
 DCA WEBSITE AT:
 WWW.FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
 PLEASE SUBMIT STATEWIDE COVER SHEETS FOR ALL OF THE
 PROPOSED PRODUCTS THAT HAVE DCA PRODUCT APPROVAL.
  
 3) A REVISION FEE, OF $50 PLUS AN ADDITIONAL $10 FOR
 EACH PRODUCT APPROVAL THAT IS DIFFERENT FROM THOSE THAT
 HAVE ALREADY BEEN REVIEWED/STAMPED FOR THIS PROJECT, IS
 DUE.THE PRODUCT APPROVALS SHALL BE BROUGHT BACK AS A
 REVISION, NOT A (ZERO FEE) SUBMITTAL.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 116 Status F Date 2007-06-25 Cont ID  
Sent By rbrown Date 2007-06-25 Time 19:22 Rev Time 0.00
Received By rbrown Date 2007-06-25 Time 19:22 Sent To  
Notes
2007-06-25 19:38:05BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 5/11/07 FOR DECORAWALL "PROMOULD"
 ARCHITECTURAL DETAILS.
  
 1)FBC 1406.2.2ARCHITECTURAL TRIM.ARCHITECTURAL
 TRIM MORE THAN 40 FEET ABOVE GRADE, ON TYPE I AND II
 BUILDINGS, SHALL BE CONSTRUCTED OF APPROVED
 NON-COMBUSTIBLE MATERIALS AND SHALL BE SECURED WITH
 METAL OR OTHER APPROVED NON-COMBUSTIBLE BRACKETS.THE
 SUBMITTED SHOP DRAWINGS AND SPECIFICATION DO NOT CALL
 OUT MECHANICAL FASTENING FOR THE MOLDINGS ON THIS
 PROJECT.ALSO, THE SUBMITTED SPECIFICATION DOES NOT
 SHOW THAT THE CORE MATERIAL HAS BEEN TESTED IN
 ACCORDANCE WITH ASTM E 136 TO VERIFY THAT IS
 NON-COMBUSTIBLE (REF: FBC 703.4.1).IT IS NOTED THAT
 THE "COATING" HAS BEEN TESTED TO ASTM E 84, BUT NO TEST
 DATA WAS SUBMITTED FOR THE CORE MATERIAL.SUBMIT
 DOCUMENTATION (MARKED UP IF NECESSARY) TO SHOW
 COMPLIANCE WITH THE MECHANICAL FASTENING AND ASTM E 136
 NON-COMBUSTIBILITY REQUIREMENTS.
  
 2) FBC 1609.1WIND LOADS.SUBMIT TEST DATA AND/OR
 ATTACHMENT CALCULATIONS TO JUSTIFY THE MOULDING
 ATTACHMENT RESISTANCE TO WIND LOAD AND SELF WEIGHT.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 115 Status P Date 2007-06-25 Cont ID  
Sent By rbrown Date 2007-06-25 Time 18:46 Rev Time 0.00
Received By rbrown Date 2007-06-25 Time 18:46 Sent To  
Notes
2007-06-25 18:47:28REVISION SUBMITTED ON 4/30/07 FOR DOOR SCHEDULE SHEET
 A-4.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 114 Status P Date 2007-06-24 Cont ID  
Sent By rbrown Date 2007-06-24 Time 18:36 Rev Time 0.00
Received By rbrown Date 2007-06-24 Time 18:36 Sent To  
Notes
2007-06-24 18:39:49SUBMITTAL ON 4/30/07 FOR UL FIRE RATED WALL ASSEMBLY
 (UL LISTING # V452) FOR USE ADJACENT TO WET AREAS

Review Stop B BUILDING (STRUCTURAL)
Rev No 113 Status F Date 2007-06-24 Cont ID  
Sent By rbrown Date 2007-06-24 Time 18:12 Rev Time 0.00
Received By rbrown Date 2007-06-24 Time 18:12 Sent To  
Notes
2007-06-24 18:24:42BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 SUBMITTAL ON 3/15/07 FOR GUARDRAILS, HANDRAILS, STAIRS
 AND MISC. METALS SHOP DRAWINGS.
  
 1) FBC* 106.1ENGINEER'S SIGNATURE AND SEAL, AND
 ENGINEERING BUSINESS CERTIFICATE OF AUTHORIZATION
 NUMBER.THE ENGINEERING LETTER AT THE BEGINNING OF
 EACH SECTION (I.E. AFTER EACH TAB) OF THE SUBMITTED
 BINDER IS A PHOTOCOPY, AND IS MISSING THE ENGINEER'S
 ORIGINAL SIGNATURE AND SEAL, AND THE ENGINEERING
 BUSINESS (OR CERTIFICATE OF AUTHORIZATION) NUMBER FOR
 STRUCTURES INTERNATIONAL, INC.THE ENGINEER SHALL
 APPLY AN ORIGINAL SIGNATURE, RAISED SEAL AND
 CERTIFICATE OF AUTHORIZATION NUMBER (DBPR WEBSITE SHOWS
 IT AS EB 9446, CAN BE ADDED BY HAND) TO EACH LETTER.
 (REF: 471.023 F.S.)**QUOTE PERMIT# ON ALL
 CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 112 Status P Date 2007-06-16 Cont ID  
Sent By rbrown Date 2007-06-16 Time 18:34 Rev Time 0.00
Received By rbrown Date 2007-06-16 Time 18:34 Sent To  
Notes
2007-06-16 18:37:52REVISION SUBMITTED ON 3/15/07 FOR SHEETS A-0.2, A-1.1,
 A-1.5, A-2.1.2, A-2.3.5, A-2.4.4, AND A-4.3
  
 SHEETS A-2.4.5, A-2.4.6, AND A-4.1 RETURNED WITHOUT
 STAMPING BECAUSE LATER REVISIONS OF THESE SHEETS HAVE
 ALREADY BEEN REVIEWED AND STAMPED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 111 Status P Date 2007-06-16 Cont ID  
Sent By rbrown Date 2007-06-16 Time 18:32 Rev Time 0.00
Received By rbrown Date 2007-06-16 Time 18:32 Sent To  
Notes
2007-06-16 18:34:23REVISION SUBMITTED ON 3/15/07 FOR SHEETS A-2.4.2,
 A-2.4.3, A-2.4.5, A-2.4.6, AND A-4.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 110 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:56 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:55 Sent To  
Notes
2007-04-18 22:56:31STRUCTURAL SUBMITTAL ON 4/18/07 FOR TOWER 16TH FLOOR
 SLAB, POUR 1 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 109 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:53 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:53 Sent To  
Notes
2007-04-18 22:53:46STRUCTURAL SUBMITTAL ON 4/13/07 FOR TOWER 15TH FLOOR
 SLAB, POUR 3 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 108 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:50 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:50 Sent To  
Notes
2007-04-18 22:51:07STRUCTURAL SUBMITTAL ON 4/11/07 FOR GARAGE 7TH FLOOR
 SLAB, POUR 3 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 107 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:48 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:48 Sent To  
Notes
2007-04-18 22:48:44STRUCTURAL SUBMITTAL ON 4/11/07 FOR TOWER 15TH FLOOR
 SLAB, POUR 2 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 106 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:45 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:45 Sent To  
Notes
2007-04-18 22:45:55STRUCTURAL SUBMITTAL ON 4/6/07 FOR TOWER 15TH FLOOR
 SLAB, POUR 1 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 105 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:43 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:43 Sent To  
Notes
2007-04-18 22:43:53STRUCTURAL SUBMITTAL ON 4/3/07 FOR TOWER 14TH FLOOR
 SLAB, POUR 3 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 104 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:39 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:39 Sent To  
Notes
2007-04-18 22:40:15STRUCTURAL SUBMITTAL ON 4/2/07 FOR TOWER 14TH FLOOR
 SLAB, POUR 2 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 103 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:36 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:36 Sent To  
Notes
2007-04-18 22:37:30STRUCTURAL SUBMITTAL ON 3/30/07 FOR GARAGE 7TH FLOOR
 SLAB, POUR 1 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 102 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:33 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:33 Sent To  
Notes
2007-04-18 22:34:10STRUCTURAL SUBMITTAL ON 3/27/07 FOR TOWER 14TH FLOOR
 SLAB, POUR 1 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 101 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:29 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:29 Sent To  
Notes
2007-04-18 22:30:05STRUCTURAL SUBMITTAL ON 3/22/07 FOR VILLA 6TH FLOOR
 SLAB SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 100 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:25 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:25 Sent To  
Notes
2007-04-18 22:25:44STRUCTURAL SUBMITTAL ON 3/21/07 FOR TOWER 13TH FLOOR
 SLAB, POUR 3 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 99 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:22 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:22 Sent To  
Notes
2007-04-18 22:22:35STRUCTURAL SUBMITTAL ON 3/21/07 FOR TOWER 13TH FLOOR
 SLAB, POUR 2 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 98 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:18 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:18 Sent To  
Notes
2007-04-18 22:19:35STRUCTURAL SUBMITTAL ON 3/15/07 FOR GARAGE 6TH FLOOR
 SLAB, POUR 2 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 97 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:13 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:13 Sent To  
Notes
2007-04-18 22:15:29STRUCTURAL SUBMITTAL ON 3/14/07 FOR TOWER 13TH FLOOR
 SLAB, POUR 1 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 96 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:11 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:11 Sent To  
Notes
2007-04-18 22:12:06STRUCTURAL SUBMITTAL ON 3/9/07 FOR GARAGE 6TH FLOOR
 SLAB, POUR 1 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 95 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:09 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:09 Sent To  
Notes
2007-04-18 22:09:26STRUCTURAL SUBMITTAL ON 3/8/07 FOR TOWER 12TH FLOOR
 SLAB, POUR 3 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 94 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 22:05 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 22:05 Sent To  
Notes
2007-04-18 22:05:49STRUCTURAL SUBMITTAL ON 3/7/07 FOR TOWER 12TH FLOOR
 SLAB, POUR 2 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 93 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 21:58 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 21:58 Sent To  
Notes
2007-04-18 22:02:48STRUCTURAL SUBMITTAL ON 3/5/07 FOR GARAGE 5TH FLOOR
 SLAB, POUR 3 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 92 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 21:57 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 21:57 Sent To  
Notes
2007-04-18 21:58:01STRUCTURAL SUBMITTAL ON 3/5/07 FOR TOWER 12TH FLOOR
 SLAB, POUR 1 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 91 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 21:50 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 21:50 Sent To  
Notes
2007-04-18 21:51:11STRUCTURAL SUBMITTAL ON 3/5/07 FOR TOWER 11TH FLOOR
 SLAB, POUR 3 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 90 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 21:49 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 21:49 Sent To  
Notes
2007-04-18 21:49:55STRUCTURAL SUBMITTAL ON 3/5/07 FOR TOWER 11TH FLOOR
 SLAB, POUR 2 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 89 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 21:45 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 21:44 Sent To  
Notes
2007-04-18 21:46:22STRUCTURAL SUBMITTAL ON 2/22/07 FOR GARAGE 5TH FLOOR
 SLAB, POUR 2 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 88 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 21:39 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 21:39 Sent To  
Notes
2007-04-18 21:41:20SUBMITTAL ON 2/22/07 FOR ONE TIME PRODUCT APPROVAL
 06-2093 FROM MIAMI-DADE PRODUCT CONTROL DIVISION FOR
 MIAMI WALL SERIES SINGLE HUNG WINDOW TO ADDRESS PROVISO
 OF 9/6/06.

Review Stop B BUILDING (STRUCTURAL)
Rev No 87 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 21:29 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 21:29 Sent To  
Notes
2007-04-18 21:31:52SUBMITTAL ON 2/20/07 FOR ONE TIME PRODUCT APPROVAL
 06-2094 FROM MIAMI-DADE PRODUCT CONTROL DIVISION FOR
 MIAMI WALL SERIES 100 ALUMINUM SLIDING GLASS DOOR TO
 ADDRESS PROVISO OF 9/6/06.

Review Stop B BUILDING (STRUCTURAL)
Rev No 86 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 21:17 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 21:17 Sent To  
Notes
2007-04-18 21:18:33STRUCTURAL SUBMITTAL ON 2/13/07 FOR GARAGE 5TH FLOOR
 SLAB, POUR 1 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 85 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 21:13 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 21:13 Sent To  
Notes
2007-04-18 21:13:59STRUCTURAL SUBMITTAL ON 2/13/07 FOR TOWER 11TH FLOOR
 SLAB, POUR 1 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 84 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 21:09 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 21:09 Sent To  
Notes
2007-04-18 21:10:30STRUCTURAL SUBMITTAL ON 2/13/07 FOR TOWER 10TH FLOOR
 SLAB, POUR 3 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 83 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 21:04 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 21:04 Sent To  
Notes
2007-04-18 21:06:16STRUCTURAL SUBMITTAL ON 2/13/07 FOR TOWER 10TH FLOOR
 SLAB, POUR 2 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 82 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 20:47 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 20:47 Sent To  
Notes
2007-04-18 20:49:20STRUCTURAL SUBMITTAL ON 2/8/07 FOR ROOF, AND
 INTERMEDIATE AND HIGH ROOF SLAB POST-TENSION FRICTION
 LOSS CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 81 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 20:41 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 20:41 Sent To  
Notes
2007-04-18 20:43:30STRUCTURAL SUBMITTAL ON 2/8/07 FOR ADDITIONAL SLAB
 SHORING CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 80 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 20:36 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 20:36 Sent To  
Notes
2007-04-18 20:37:31STRUCTURAL SUBMITTAL ON 2/8/07 FOR VILLA 4TH FLOOR SLAB
 SHORING LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 79 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 20:31 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 20:31 Sent To  
Notes
2007-04-18 20:32:52STRUCTURAL SUBMITTAL ON 2/8/07 FOR VILLA AND GARAGE 9TH
 FLOOR SHORING DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 78 Status P Date 2007-04-18 Cont ID  
Sent By rbrown Date 2007-04-18 Time 20:25 Rev Time 0.00
Received By rbrown Date 2007-04-18 Time 20:25 Sent To  
Notes
2007-04-18 20:26:44STRUCTURAL SUBMITTAL ON 2/8/07 FOR TOWER ROOF SLAB
 POST-TENSION SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 77 Status P Date 2007-04-06 Cont ID  
Sent By rbrown Date 2007-04-06 Time 10:13 Rev Time 0.00
Received By rbrown Date 2007-04-06 Time 10:12 Sent To  
Notes
2007-04-06 10:14:45SUBMITTAL ON 4/5/07 FOR ALUMA SYSTEMS INC. MAIN ROOF
 SHORING CALCULATIONS AND SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 76 Status P Date 2007-04-06 Cont ID  
Sent By rbrown Date 2007-04-06 Time 10:12 Rev Time 0.00
Received By rbrown Date 2007-04-06 Time 10:10 Sent To  
Notes
2007-04-06 10:12:10SUBMITTAL ON 4/5/07 FOR LEVEL 7, POUR 2, SHORING
 LETTERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 75 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 20:11 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 20:11 Sent To  
Notes
2007-02-11 20:18:05SUBMITTAL ON 2/5/07 FOR 4TH FLOOR, POUR 2 SHORING
 INSPECTION LETTERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 74 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 20:09 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 20:09 Sent To  
Notes
2007-02-11 20:11:03SUBMITTAL ON 2/5/07 FOR 4TH FLOOR, POUR 2 SHORING
 INSPECTION LETTERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 73 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 20:04 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 20:04 Sent To  
Notes
2007-02-11 20:06:10SUBMITTAL ON 2/2/07 FOR 8TH FLOOR VILLA AND GARAGE
 SHORING CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 72 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 20:03 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 20:03 Sent To  
Notes
2007-02-11 20:04:33SUBMITTAL ON 2/2/07 FOR 8TH FLOOR VILLA AND GARAGE
 SHORING SHOP DRAWING

Review Stop B BUILDING (STRUCTURAL)
Rev No 71 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 19:57 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 19:57 Sent To  
Notes
2007-02-11 19:57:41SUBMITTAL ON 1/30/07 FOR 9TH FLOOR, POUR 2 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 70 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 19:54 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 19:54 Sent To  
Notes
2007-02-11 19:54:22SUBMITTAL ON 1/30/07 FOR 9TH FLOOR, POUR 3 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 69 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 19:50 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 19:50 Sent To  
Notes
2007-02-11 19:50:54SUBMITTAL ON 1/24/07 FOR 9TH FLOOR, POUR 1 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 68 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 19:46 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 19:46 Sent To  
Notes
2007-02-11 19:47:34SUBMITTAL ON 1/19/07 FOR 8TH FLOOR, POUR 3 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 67 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 19:43 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 19:43 Sent To  
Notes
2007-02-11 19:44:15SUBMITTAL ON 1/16/07 FOR 8TH FLOOR, POUR 2 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 66 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 19:35 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 19:35 Sent To  
Notes
2007-02-11 19:43:23SUBMITTAL ON 1/16/07 FOR 3RD FLOOR SHORING INSPECTION
 LETTER FOR THE VILLAS

Review Stop B BUILDING (STRUCTURAL)
Rev No 65 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 19:32 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 19:32 Sent To  
Notes
2007-02-11 19:35:07SUBMITTAL ON 1/12/07 FOR 3RD FLOOR, POUR 2 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 64 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 19:30 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 19:30 Sent To  
Notes
2007-02-11 19:31:59SUBMITTAL ON 1/11/07 FOR 8TH FLOOR, POUR 1 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 63 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 19:27 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 19:27 Sent To  
Notes
2007-02-11 19:28:29SUBMITTAL ON 1/8/07 FOR 7TH FLOOR, POUR 3 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 62 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 19:25 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 19:25 Sent To  
Notes
2007-02-11 19:26:35SUBMITTTAL ON 1/24/07 FOR WINDOW AND SLIDING GLASS DOOR
 CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 61 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 19:14 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 19:14 Sent To  
Notes
2007-02-11 19:15:09SUBMITTTAL ON 1/24/07 FOR WINDOW AND SLIDING GLASS DOOR
 SHOP DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 60 Status P Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 17:44 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 17:44 Sent To  
Notes
2007-02-11 17:45:52REVISION SUBMITTED ON 12/18/06 FOR GAZEBO SHEET A-9.3

Review Stop B BUILDING (STRUCTURAL)
Rev No 59 Status F Date 2007-02-11 Cont ID  
Sent By rbrown Date 2007-02-11 Time 15:35 Rev Time 0.00
Received By rbrown Date 2007-02-11 Time 15:35 Sent To  
Notes
2007-02-11 17:34:08BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 12/18/06 FOR CLUBROOM AND FITNESS
 CENTER BUILDOUT.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 704.1.2.3OCCUPANCY SEPARATION FOR FITNESS
 CENTER AND CLUB LOUNGE.THE PLANS SHALL STATE THE
 TOTAL AREA OF THE FITNESS CENTER AND TOTAL AREA OF THE
 CLUB LOUNGE.PER FBC 304.1.2 THEY ARE CLASSIFIED AS
 ASSEMBLY OCCUPANCY.IF THE AREA EXCEEDS 2,000 SQ FT,
 THEY SHALL BE SEPARATED FROM THE RESIDENTIAL OCCUPANCY
 BY 2 HOUR FIRE RESISTANT CONSTRUCTION.THE FITNESS
 CENTER AND CLUB LOUNGE BOTH EXCEED 750 SQ FT SO, PER
 FBC 704.1.2.2, THEY CANNOT BE CONSIDERED AS INCIDENTAL
 TO THE RESIDENTIAL OCCPANCY.AMEND THE PLANS TO STATE
 THE AREA OF THE FITNESS CENTER AND CLUB LOUNGE, AND
 INCREASE THE OCCUPANCY SEPARATION FIRE RESISTANCE TO 2
 HOURS IF APPROPRIATE.
  
 2) FBC 1012.1.2FITNESS CENTER DOOR 51.THE DOOR TO
 THE EXIT ACCESS CORRIDOR IS SHOWN SWINGING INTO THE
 FITNESS CENTER.THE DOOR SHALL OPEN IN THE DIRECTION
 OF EGRESS.AMEND THE PLANS.
  
 3) FBC 1012.7FITNESS CENTER EGRESS DOORS.PER FBC
 1004.1.2 NOT LESS THAN TWO EGRESS DOORS ARE REQUIRED.
 THE DOOR SCHEDULE ON SHEET A-4.1 SPECIFIES MAGNETIC
 LOCKS (HARDWARE NOTE 9) FOR DOOR 51 AND DOOR 50
 (LEADING TO THE POOL DECK WHICH GIVES ACCESS TO STAIR
 3).PER FBC 1012.7 MAGNETIC LOCKS ARE NOT PERMISSABLE
 FOR REQUIRED EGRESS SERVING ASSEMBLY OCCUPANCIES.
 SPECIFY PANIC HARDWARE OR FIRE/EXIT HARDWARE FOR DOOR
 51.ALSO, EITHER SPECIFY PANIC HARDWARE OR FIRE/EXIT
 HARDWARE FOR DOOR 50, OR PROVIDE A SECOND DOOR FROM THE
 FITNESS CENTER TO THE EXIT ACCESS CORRIDOR.
  
 4) FBC 1012.1.2CLUB LOUNGE DOOR 66.THE DOOR TO THE
 EXIT ACCESS CORRIDOR IS SHOWN SWINGING INTO THE CLUB
 LOUNGE.THE DOOR SHALL OPEN IN THE DIRECTION OF
 EGRESS.AMEND THE PLANS.
  
 5) FBC 1012.7CLUB LOUNGE EGRESS DOORS.PER FBC
 1004.1.2 NOT LESS THAN TWO EGRESS DOORS ARE REQUIRED.
 THE DOOR SCHEDULE ON SHEET A-4.1 SPECIFIES MAGNETIC
 LOCKS (HARDWARE NOTE 9) FOR DOOR 66 AND DOOR 50
 (LEADING TO THE POOL DECK WHICH GIVES ACCESS TO STAIR
 3).PER FBC 1012.7 MAGNETIC LOCKS ARE NOT PERMISSABLE
 FOR REQUIRED EGRESS SERVING ASSEMBLY OCCUPANCIES.
 SPECIFY PANIC HARDWARE OR FIRE/EXIT HARDWARE FOR DOOR
 66 AND DOOR 50.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 58 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:58 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:58 Sent To  
Notes
2007-01-07 13:00:31SUBMITTAL ON 1/3/07 FOR 7TH FLOOR, POUR 2 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 57 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:57 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:56 Sent To  
Notes
2007-01-07 12:58:08SUBMITTAL ON 1/3/07 FOR 3RD FLOOR, POUR 1 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 56 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:52 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:52 Sent To  
Notes
2007-01-07 12:53:21SUBMITTAL ON 12/27/06 FOR 7TH FLOOR, POUR 1 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 55 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:50 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:50 Sent To  
Notes
2007-01-07 12:51:12SUBMITTAL ON 12/22/06 FOR 6TH FLOOR, POUR 3 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 54 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:48 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:48 Sent To  
Notes
2007-01-07 12:49:12SUBMITTAL ON 12/22/06 FOR VILLA 2ND FLOOR SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 53 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:45 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:45 Sent To  
Notes
2007-01-07 12:45:49SUBMITTAL ON 12/19/06 FOR 6TH FLOOR, POUR 6 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 52 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:42 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:42 Sent To  
Notes
2007-01-07 12:43:00SUBMITTAL ON 12/19/06 FOR 2ND FLOOR, POUR 2 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 51 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:38 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:38 Sent To  
Notes
2007-01-07 12:39:48SUBMITTAL ON 12/14/06 FOR 9TH FLOOR POST-TENSION SLAB
 DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 50 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:27 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:27 Sent To  
Notes
2007-01-07 12:28:46SUBMITTAL ON 12/14/06 FOR 9TH FLOOR POST-TENSION SLAB
 CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 49 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:24 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:24 Sent To  
Notes
2007-01-07 12:25:43SUBMITTAL ON 12/14/06 FOR 8TH FLOOR POST-TENSION SLAB
 DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 48 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:19 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:19 Sent To  
Notes
2007-01-07 12:20:03SUBMITTAL ON 12/14/06 FOR GARAGE 8TH FLOOR POST-TENSION
 SLAB CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 47 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:14 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:14 Sent To  
Notes
2007-01-07 12:15:18SUBMITTAL ON 12/14/06 FOR 6TH FLOOR, POUR 1 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 46 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:10 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:10 Sent To  
Notes
2007-01-07 12:12:19SUBMITTAL ON 12/8/06 FOR 5TH FLOOR, POUR 3 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 45 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:06 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:06 Sent To  
Notes
2007-01-07 12:08:59SUBMITTAL ON 12/8/06 FOR GARAGE 3RD THRU 7TH FLOOR
 POST-TENSION SLAB CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 44 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 12:03 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 12:03 Sent To  
Notes
2007-01-07 12:04:16SUBMITTAL ON 12/8/06 FOR GARAGE 3RD THRU 7TH FLOOR
 POST-TENSION SLAB DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 43 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 11:58 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 11:58 Sent To  
Notes
2007-01-07 11:58:49SUBMITTAL ON 12/6/06 FOR 11TH THRU 20TH FLOOR SHORING
 DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 42 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 11:53 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 11:53 Sent To  
Notes
2007-01-07 11:55:14SUBMITTAL ON 12/6/06 FOR2ND THRU 7TH FLOOR SHORING
 CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 41 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 11:49 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 11:49 Sent To  
Notes
2007-01-07 11:50:42SUBMITTAL ON 12/6/06 FOR VILLA/GARAGE 3RD THRU 7TH
 FLOOR SHORING DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 40 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 11:38 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 11:38 Sent To  
Notes
2007-01-07 11:39:02SUBMITTAL ON 12/4/06 FOR 5TH FLOOR, POUR 2
 SHORING/RE-SHORING INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 39 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 11:35 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 11:35 Sent To  
Notes
2007-01-07 11:36:25REVISION SUBMITTED ON 11/30/06 FOR APPLICATION OF SOUND
 INSULATION ON TRASH CHUTE INSTALLATION

Review Stop B BUILDING (STRUCTURAL)
Rev No 38 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 11:26 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 11:26 Sent To  
Notes
2007-01-07 11:27:44SUBMITTAL ON 11/30/06 FOR 5TH FLOOR, POUR 1
 SHORING/RE-SHORING INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 37 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 11:23 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 11:23 Sent To  
Notes
2007-01-07 11:24:37SUBMITTAL ON 11/21/06 FOR 4TH FLOOR, POUR 3
 SHORING/RE-SHORING INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 36 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 11:20 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 11:20 Sent To  
Notes
2007-01-07 11:21:25SUBMITTAL ON 11/17/06 FOR 4TH THRU 20TH FLOOR
 POST-TENSION SLAB DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 35 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 11:12 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 11:12 Sent To  
Notes
2007-01-07 11:13:38SUBMITTAL ON 11/17/06 FOR 4TH THRU 20TH FLOOR
 POST-TENSION SLAB CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 34 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 11:04 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 11:02 Sent To  
Notes
2007-01-07 11:06:10SUBMITTAL ON 11/17/06 FOR 4TH THRU 20TH FLOOR
 SHORING/RE-SHORING DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 33 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 10:52 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 10:52 Sent To  
Notes
2007-01-07 10:53:21SUBMITTAL ON 11/16/06 FOR 4TH FLOOR, POUR 2 SHORING
 INSPECTION LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 32 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 10:50 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 10:50 Sent To  
Notes
2007-01-07 10:50:58SUBMITTAL ON 11/13/06 FOR ROLLING DOOR SHOP DRAWING

Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 10:44 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 10:44 Sent To  
Notes
2007-01-07 10:45:01SUBMITTAL ON 11/13/06 FOR 4TH THRU 20TH FLOOR SHORING
 CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 10:40 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 10:40 Sent To  
Notes
2007-01-07 10:41:40SUBMITTAL ON 11/13/06 FOR 4TH FLOOR POUR 1 SHORING
 INSPECTION LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 10:34 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 10:34 Sent To  
Notes
2007-01-07 10:36:41SUBMITTAL ON 11/13/06 FOR 4TH, 5TH , 6TH THRU 10TH, AND
 GARAGE 2ND FLOOR SHORING/RE-SHORING DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 10:28 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 10:28 Sent To  
Notes
2007-01-07 10:29:05SUBMITTAL ON 11/13/06 FOR 3RD FLOOR SHORING DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 10:21 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 10:21 Sent To  
Notes
2007-01-07 10:22:11SUBMITTAL ON 11/13/06 FOR 3RD FLOOR SHORING
 CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status P Date 2007-01-07 Cont ID  
Sent By rbrown Date 2007-01-07 Time 10:16 Rev Time 0.00
Received By rbrown Date 2007-01-07 Time 10:16 Sent To  
Notes
2007-01-07 10:17:56SUBMITTAL ON 11/13/06 FOR GARAGE LEVEL 2 AND 3
 SHORING/RE-SHORING CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 11:53 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 11:53 Sent To  
Notes
2006-11-12 11:54:20SUBMITTAL ON 11/3/06 FOR PTE STRAND CO. 2ND LEVEL
 PARKING PT PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 11:44 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 11:44 Sent To  
Notes
2006-11-12 11:45:26SUBMITTAL ON 11/3/06 FOR PTE STRAND CO. 2ND LEVEL
 PARKING PT FRICTION LOSS CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 11:41 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 11:41 Sent To  
Notes
2006-11-12 11:42:16SUBMITTAL ON 11/3/06 FOR UNITED FORMING, INC. LEVEL 3,
 POUR 3 SHORING/RESHORING LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 11:39 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 11:39 Sent To  
Notes
2006-11-12 11:40:23SUBMITTAL ON 10/23/06 FOR UNITED FORMING, INC. LEVEL 3,
 POUR 2 SHORING/RESHORING LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 11:28 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 11:28 Sent To  
Notes
2006-11-12 11:32:30SUBMITTAL ON 10/16/06 FOR ALUMA SYSTEMS INC./UNITED
 FORMING, INC. 2ND FLOOR AND 10TH THRU 20TH FLOOR
 (PARTIAL) SHORING PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 11:25 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 11:25 Sent To  
Notes
2006-11-12 11:25:58SUBMITTAL ON 10/10/06 FOR UNITED FORMING, INC. LEVEL 3,
 POUR 1 SHORING/RESHORING LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 11:22 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 11:22 Sent To  
Notes
2006-11-12 11:22:57SUBMITTAL ON 9/27/06 FOR UNITED FORMING, INC. LEVEL 2,
 POUR 3 SHORING/RESHORING LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 11:19 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 11:19 Sent To  
Notes
2006-11-12 11:20:35SUBMITTAL ON 9/20/06 FOR PTE STRAND CO. 3RD FLOOR PT
 DRAWINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 11:12 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 11:12 Sent To  
Notes
2006-11-12 11:14:07SUBMITTAL ON 9/20/06 FOR PTE STRAND CO. 3RD FLOOR PT
 FRICTION LOSS CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 11:09 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 11:09 Sent To  
Notes
2006-11-12 11:12:37SUBMITTAL ON 9/20/06 FOR UNITED FORMING, INC. 3RD FLOOR
 SHORING PLAN AND DETAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 11:03 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 11:03 Sent To  
Notes
2006-11-12 11:04:57SUBMITTAL ON 9/20/06 FOR UNITED FORMING, INC. LEVEL, 2,
 POUR 2 SHORING/RESHORING LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 11:00 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 11:00 Sent To  
Notes
2006-11-12 11:02:05SUBMITTAL ON 9/20/06 FOR UNITED FORMING, INC.
 CAST-IN-PLACE CONCRETE FRAMING AND SHORING
 CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 10:54 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 10:54 Sent To  
Notes
2006-11-12 10:55:01SUBMITTAL ON 9/8/06 FOR UNITED FORMING, INC. SHORING
 INSPECTION PERSONNEL LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 10:47 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 10:47 Sent To  
Notes
2006-11-12 10:50:12SUBMITTAL ON 9/8/06 FOR UNITED FORMING, INC. LEVEL 2,
 POUR 1 SHORING LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 10:44 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 10:44 Sent To  
Notes
2006-11-12 10:45:31SUBMITTAL ON 9/8/06 FOR CRAVEN THOMPSON FINISH FLOOR
 ELEVATION / FLOOD ELEVATION LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 10:38 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 10:38 Sent To  
Notes
2006-11-12 10:40:27SUBMITTAL ON 9/8/06 FOR ARDAMAN & ASSOCIATES IN-SITU
 SOIL DENSITY TEST LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 10:35 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 10:35 Sent To  
Notes
2006-11-12 10:37:29SUBMITTAL ON 9/8/06 FOR ARDAMAN & ASSOCIATES SPT AND
 POST VIBROFLOTATION TREATMENT PROCEDURE LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 10:27 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 10:27 Sent To  
Notes
2006-11-12 10:35:06SUBMITTAL ON 9/8/06 FOR FORM BOARD SURVEY

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 10:23 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 10:23 Sent To  
Notes
2006-11-12 10:24:47STRUCTURAL SUBMITTAL ON 8/25/06 FOR 2ND FLOOR SHORING
 PLANS AND CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 10:04 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 10:04 Sent To  
Notes
2006-11-12 10:09:31STRUCTURAL SUBMITTAL ON 8/31/06 FOR 2ND AND 3RD LEVEL
 PT DRAWINGS
  
 --IMPORTANT--
 I HAVE WRITTEN THE NAME AND LICENSE NUMBER OF MIAN
 ABDUL HAMID, P.E. ON THE PLANS.THE INFORMATION LISTED
 BELOW SHALL BE INCLUDED ON ALL FUTURE SUBMITTALS OR
 THEY WILL BE DENIED:
 PURSUANT TO 61G15-23.002(2)FL. ADMIN. CODE, PLANS
 SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL
 INCLUDE EITHER THE NAME, ADDRESS AND LICENSE NUMBER OF
 THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS
 THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S.
 AND 471.023 F.S.).
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-11-12 Cont ID  
Sent By rbrown Date 2006-11-12 Time 09:50 Rev Time 0.00
Received By rbrown Date 2006-11-12 Time 09:50 Sent To  
Notes
2006-11-12 09:53:21STRUCTURAL SUBMITTAL ON 8/31/06 FOR 2ND AND 3RD LEVEL
 PT FRICTION LOSS CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-09-06 Cont ID  
Sent By rbrown Date 2006-09-06 Time 22:29 Rev Time 0.00
Received By rbrown Date 2006-09-06 Time 22:29 Sent To  
Notes
2006-09-06 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 -PROVISO-
 SUBMIT STRUCTURAL MULLION SHOP DRAWINGS
 FOR ALL STOREFRONT OVER 144" TALL.THE
 SUBMITTED ARCH ALUMINUM SERIES L-300
 IMPACT WALL STOREFRONT PRODUCT NOA#
 01-0619.01 STATES A MAXIMUM UNIT HEIGHT
 OF 144". THIS IS NOT SUFFICIENT TO COVER
 THE SIZE OF STOREFRONT SPECIFIED ON
 SHEETS A-4.1 AND A-4.2 OF THE PLANS.
 PER THE 8/25/06 MEETING WITH GLASS
 ENGINEERING INC., STRUCTURAL MULLIONS
 WILL BE INCORPORATED AND SHEETS A-4.1
 AND A-4.2 WILL BE AMENDED TO REFLECT
 THIS AND CALL FOR SHOP DRAWINGS 'BY
 OTHERS' TO BE SUBMITTED FOR REVIEW.
  
 -PROVISO-
 SUBMIT ONE-TIME PRODUCT APPROVAL FOR
 SLIDING GLASS DOORS.DOOR SCHEDULE
 SHEET A-4.1 SHOWS A PROPOSED SLIDING
 GLASS DOOR HEIGHT OF 10'-0". PER THE
 8/25/06 MEETING WITH GLASS ENGINEERING
 INC., THEY WILL BE APPLYING FOR A ONE
 TIME PRODUCT APPROVAL FOR THE 10'-0"
 DOOR AND WILL PROVIDE THREE COPIES OF
 THE APPROVAL.ONE-TIME APPROVAL WAS
 PREVIOUSLY GRANTED FOR A DIFFERENT
 PROJECT.
  
 -PROVISO-
 SUBMIT ONE-TIME PRODUCT APPROVAL FOR
 SINGLE HUNG WINDOW.WINDOW SCHEDULE
 SHEET A-4.2 SHOWS SINGLE HUNG WINDOW
 HEIGHTS UP TO 9'-4".PER THE 8/25/06
 MEETING WITH GLASS ENGINEERING INC.,
 THEY WILL BE APPLYING FOR A ONE TIME
 PRODUCT APPROVAL FOR THE 9'-4" HIGH
 WINDOW AND WILL PROVIDE THREE COPIES OF
 THE APPROVAL.ONE-TIME APPROVAL WAS
 PREVIOUSLY GRANTED FOR A DIFFERENT
 PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-27 Cont ID  
Sent By rbrown Date 2006-08-27 Time 19:19 Rev Time 0.00
Received By rbrown Date 2006-08-27 Time 19:18 Sent To  
Notes
2006-08-27 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 7/23/06:
  
 6) PRODUCT APPROVALS.SUBMITTAL OF
 PRODUCT APPROVALS IS NOTED. ONLY ONE
 COPY OF EACH PRODUCT APPROVAL HAS BEEN
 SUBMITTED AT THIS STAGE.THREE COPIES
 WILL BE REQUIRED FOR PERMIT ISSUANCE.
 EACH PRODUCT APPROVAL SHALL HAVE A
 STATEWIDE PRODUCT APPROVAL COVER SHEET.
 ALTERNATIVELY, AN APPLICATION FOR LOCAL
 PRODUCT APPROVAL WILL BE REQUIRED.THE
 FOLLOWING COMMENTS APPLY TO THE
 SUBMITTED PRODUCT APPROVALS:
 (A)MODIFIED BITUMEN ROOFING SYSTEM.
 SUBMITTAL OF THE ENHANCED FASTENER
 DENSITY CALCULATIONS IS NOTED.THE
 CONTENT IS OK BUT THE SIGNATURES ARE
 PHOTOCOPIED AND EACH COPY MUST HAVE THE
 AN ORIGINAL 'WET' SIGNATURE OF DONALD
 FLOOD, P.E.ALSO, PER THE 8/25/06
 MEETING WITH ARTURO PENA, THREE COPIES
 OF THE REFERENCED JOHNS MANVILLE PRODUCT
 APPROVAL NOA# 04-0401.04 WILL BE
 SUBMITTED.THE PRODUCT APPROVAL MUST BE
 MARKED OR SEPARATED TO SHOW WHICH SYSTEM
 IS PROPOSED (THE CALCULATIONS REFERENCE
 THE SYSTEM ON PAGE 30).
 (B)ROOF TILE:SUBMITTAL OF THE
 ALTUSA 'S' PRODUCT APPROVAL NOA#
 05-0901.06 IS NOTED.ALSO, SUBMITTAL OF
 THE TILE ATTACHMENT CALCULATIONS IS
 NOTED.THE CONTENT OF THE CALCULATION
 PACKAGE IS OK BUT THE SIGNATURES ARE
 PHOTOCOPIED AND EACH COPY MUST HAVE THE
 ORIGINAL 'WET' SIGNATURE OF DONALD
 FLOOD, P.E.
 (C)EXTERIOR DOORS. SEE COMMENT 6(J)
 THRU 6(N).
 (D)STOREFRONT.THE SUBMITTED ARCH
 ALUMINUM SERIES L-300 IMPACT WALL
 STOREFRONT PRODUCT NOA# 01-0619.01
 STATES A MAXIMUM UNIT HEIGHT OF 144".
 THIS IS NOT SUFFICIENT TO COVER THE SIZE
 OF STOREFRONT SPECIFIED ON SHEETS A-4.1
 AND A-4.2 OF THE PLANS.PER THE 8/25/06
 MEETING WITH GLASS ENGINEERING INC.,
 STRUCTURAL MULLIONS WILL BE INCORPORATED
 AND SHEETS A-4.1 AND A-4.2 WILL BE
 AMENDED TO REFLECT THIS AND CALL FOR
 SHOP DRAWINGS 'BY OTHERS' TO BE
 SUBMITTED FOR REVIEW.
 (E)SLIDING GLASS DOORS.THE
 SUBMITTED MIAMI WALL SYSTEMS SERIES 100
 SLIDING GLASS DOOR PRODUCT APPROVAL NOA#
 01-0123.02 HAS A MAXIMUM DOOR HEIGHT OF
 102".DOOR SCHEDULE SHEET A-4.1 SHOWS A
 PROPOSED SLIDING GLASS DOOR HEIGHT OF
 10'-0" WHICH EXCEEDS THE MAXIMUM COVERED
 BY THE PRODUCT APPROVAL.PER THE
 8/25/06 MEETING WITH GLASS ENGINEERING
 INC., THEY WILL BE APPLYING FOR A ONE
 TIME PRODUCT APPROVAL FOR THE 10'-0"
 DOOR AND WILL PROVIDE THREE COPIES OF
 THE APPLICATION FORM/LETTER SO THAT A
 PROVISO MAY BE GIVEN.
 (F)SINGLE HUNG WINDOW.THE
 SUBMITTED MIAMI WALL SERIES 122 ALUMINUM
 SINGLE HUNG WINDOW PRODUCT APPROVAL NOA#
 03-1008.03 HAS A MAXIMUM HEIGHT OF 72".
 WINDOW SCHEDULE SHEET A-4.2 SHOWS SINGLE
 HUNG WINDOW HEIGHTS UP TO 9'-4" WHICH
 EXCEED THE MAXIMUM COVERED BY THE
 PRODUCT APPROVAL.PER THE 8/25/06
 MEETING WITH GLASS ENGINEERING INC.,
 THEY WILL BE APPLYING FOR A ONE TIME
 PRODUCT APPROVAL FOR THE 9'-4" HIGH
 WINDOW AND WILL PROVIDE THREE COPIES OF
 THE APPLICATION FORM/LETTER SO THAT A
 PROVISO MAY BE GIVEN.
 (G) FIXED WINDOW.IT IS NOTED THAT
 FIXED WINDOW COVERED BY THE SUBMITTED
 MIAMI WALL PRODUCT APPROVAL NOA#
 04-0322.09 WILL BE USED UNDER THE SINGLE
 HUNG WINDOWS TO FORM THE 'SINGLE HUNG
 WINDOW OVER FIXED WINDOW' CONFIGURATION.
 AN APPROPRIATE MULLION PRODUCT APPROVAL
 MUST BE SUBMITTED OR SHEET A-4.2 SHALL
 BE AMENDED TO SHOW THAT A STRUCTURAL
 MULLION IS TO BE INCORPORATED AND THAT
 SHOP DRAWINGS WILL BE SUBMITTED 'BY
 OTHERS' FOR REVIEW.
 (H)MULLIONS. SEE COMMENTS (D) & (G).
 (I)IF THERE IS A STATEWIDE PRODUCT
 APPROVAL THAT COVERS ANY OF THE
 SUBMITTED PRODUCT APPROVAL NOA'S, THE
 STATEWIDE PRODUCT APPROVAL COVER SHEET
 MUST BE ATTACHED TO THE FRONT OF THE
 NOA.
 (J)STOREFRONT DOOR.PER THE 8/25/06
 MEETING WITH GLASS ENGINEERING INC. THE
 9'-0" STOREFRONT DOOR IS NOT AVAILABLE
 SO SHEET A-4.1 MUST BE AMENDED TO REDUCE
 THE HEIGHT OF THE STOREFRONT DOORS.
 (K)LOUVER DOOR.BOTH THE COVER
 SHEET AND PAGE 41 OF THE SUBMITTED
 INTERTEK TESTING SERVICES REPORT#
 3080611 STATE THAT THE MAXIMUM DESIGN
 PRESSURE FOR THE LOUVER DOOR IS +60 PSF
 AND -60 PSF.THE MINIMUM REQUIRED
 DESIGN PRESSURE REQUIRED FOR THIS
 PROJECT IS +70 PSF AND - 70 PSF.SUBMIT
 AN ALTERNATIVE PRODUCT APPROVAL.
 (L)SINGLE HOLLOW METAL DOOR.THE
 SUBMITTED CURRIES PRODUCT APPROVAL NOA#
 01.1102.02 IS FOR A 7'-0" HIGH DOOR.
 SHEET A-4.1 SHOWS DOOR TYPE 10 AS AN
 8'-0" HIGH DOOR.SUBMIT AN ALTERNATIVE
 PRODUCT APPROVAL.
 (M)DOUBLE HOLLOW METAL DOOR.THE
 SUBMITTED CURRIES PRODUCT APPROVAL NOA#
 02-0924.04 IS OK BUT TWO OF THE
 AVAILABLE OPTIONS HAVE DESIGN PRESSURES
 WHICH ARE LESS THAN THE MINIMUM +70 PSF
 AND - 70 PSF REQUIRED FOR THIS PROJECT.
 THOSE TWO OPTIONS MUST BE STRUCK FROM
 ALL THREE COPIES OF THE PRODUCT APPROVAL
 THAT ARE SUBMITTED FOR PERMITTING.
 (N)ROLL UP DOOR.THE SUBMITTED
 CORNELL IRON WORKS INC. PRODUCT APPROVAL
 NOA# 03-0925.07 IS HARDLY LEGIBLE (POOR
 COPY) BUT APPEARS TO STATE A MAXIMUM
 DESIGN PRESSURE OF +60 PSF AND -60 PSF.
 THE MINIMUM REQUIRED DESIGN PRESSURE
 REQUIRED FOR THIS PROJECT IS +70 PSF AND
 - 70 PSF.SUBMIT AN ALTERNATIVE PRODUCT
 APPROVAL.
  
 16) FBC 411.2.3VEHICLE IMPACT
 WALLS/GUARDRAILS. CONTRARY TO THE
 COMMENT RESPONSE DATED 7/28/06, WALL
 TYPE W-30, SHOWN AT THE NORTH WALL OF
 THE PARKING GARAGE ON 2ND FLOOR FRAMING
 PLAN SHEET S-1.01, SEPARATES AREAS OF
 DIFFERENT FLOOR SLAB LEVEL.ON ONE SIDE
 IS THE 2ND FLOOR PARKING AND ON THE
 OTHER SIDE IS THE VOID ABOVE THE 1ST
 FLOOR COMMMERCIAL SPACE TO THE NORTH.
 IN FACT SHEET S-1.01 STATES "SLAB EDGE"
 AT THIS LOCATION.WALL TYPE W-30 IS A
 PARKING IMPACT WALL AND SHOULD BE SHOWN
 AS SUCH ON THE SHEET S-4-4.1 WALL
 SCHEDULE.
  
 28) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-23 Cont ID  
Sent By rbrown Date 2006-07-23 Time 23:41 Rev Time 0.00
Received By rbrown Date 2006-07-23 Time 19:04 Sent To  
Notes
2006-07-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 2/10/06:
  
 1) 713.13 F.S. NOTICE OF COMMENCEMENT.
 THE RESPONSE IS NOTED.INFORMATIVE: A
 NOTICE OF COMMENCEMENT SHALL BE RECORDED
 AT PALM BEACH COUNTY COURTHOUSE AND A
 COPY SUBMITTED TO THIS OFFICE BEFORE A
 PERMIT CAN BE ISSUED. BLANK FORMS ARE
 AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2) IMPACT FEES. THE RESPONSE IS NOTED.
 INFORMATIVE: THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 5) FBC 13-103.1.1.1 ENERGY CODE
 COMPLIANCE FORMS.EACH COPY OF THE
 SUBMITTED ENERGY CODE COMPLIANCE FORM
 SHALL BE COMPLETED SO THAT SHEET 1 SHOWS
 THE OWNER, PROJECT ADDRESS, ZIP CODE,
 PERMIT NUMBER AND SHEET 2 MUST
 INCORPORATE THE ARCHITECTURAL FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER IN
 THE SPACE PROVIDED.
  
 6) PRODUCT APPROVALS.SUBMITTAL OF
 PRODUCT APPROVALS IS NOTED. EACH PRODUCT
 APPROVAL SHALL HAVE A STATEWIDE PRODUCT
 APPROVAL COVER SHEET.ALTERNATIVELY, AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL
 WILL BE REQUIRED.THE FOLLOWING
 COMMENTS APPLY TO THE SUBMITTED PRODUCT
 APPROVALS:
 (A)MODIFIED BITUMEN ROOFING SYSTEM.
 SUBMITTAL OF GAF RUBERIOD ROOF SYSTEM
 PRODUCT APPROVAL NOA# 03-0501.03 IS
 NOTED.PAGES 9 THROUGH 30 SHALL BE
 MARKED TO SHOW WHICH ONE OUT OF THE MANY
 INCLUDED SYSTEM TYPES IS PROPOSED.THE
 CHOSEN SYSTEM MUST BE APPROPRIATE FOR
 THE CONRETE DECK SPECIFIED ON SHEET
 A-8.3.ALSO, IF ENHANCED FASTENER
 DENSITY IS REQUIRED TO IN ORDER TO MEET
 THE UPLIFT PRESSURES FOR ZONES 2 AND 3
 (PER RWDI WIND LOAD STUDY REPORT),
 CALCULATIONS MUST BE SUBMITTED IN
 COMPLIANCE WITH ROOFING APPLICATION
 STANDARD RAS 117.
 (B)ROOF TILE:THE SUBMITTED PRODUCT
 APPROVAL NOA# 01-0703.04 IS FOR ENTERA
 ESTATE 'S' TILE.THIS DOES NOT
 CORRELATE WITH ROOF DETAIL SHEET A-8.3
 WHICH SPECIFIES ALTUSA SANTA FE 'S'
 TILE. THE PERMIT DOCUMENTS SHALL NOT
 INCORPORATE CONFLICTING PROPOSALS.
 ALSO, THE RWDI WIND LOAD STUDY REPORT
 STATES UPLIFT PRESSURES OF UP TO 170 PSF
 ON THE SLOPED ROOF.SUBMIT TILE
 ATTACHMENT CALCULATIONS TO JUSTIFY THE
 USE OF THE PROPOSED TILE AND ATTACHMENT
 METHOD FOR PRESSURES UPTO 170 PSF.
 (C)EXTERIOR DOORS.SUBMITTAL OF
 PRODUCT APPROVAL FOR GLAZED ALUMINUM
 OUTSWING DOORS IS NOTED, BUT NO EXTERIOR
 DOOR PRODUCT APPROVALS WERE SUBMITTED.
 SUBMIT PRODUCT APPROVALS FOR THE
 STOREFRONT DOORS (9'-0" TALL), LOUVER
 DOORS, HOLLOW METAL DOORS AND ROLL-UP
 DOORS.
 (D)STOREFRONT.THE SUBMITTED ARCH
 ALUMINUM SERIES L-300 IMPACT WALL
 STOREFRONT PRODUCT NOA# 01-0619.01
 STATES A MAXIMUM UNIT HEIGHT OF 144".
 THIS IS NOT SUFFICIENT TO COVER THE SIZE
 OF STOREFRONT SPECIFIED ON SHEETS A-4.1
 AND A-4.2 OF THE PLANS.SUBMIT AN
 ALTERNATIVE PRODUCT APPROVAL.
 (E)SLIDING GLASS DOORS.THE
 SUBMITTED MIAMI WALL SYSTEMS SERIES 100
 SLIDING GLASS DOOR PRODUCT APPROVAL NOA#
 01-0123.02 HAS A MAXIMUM DESIGN PRESSURE
 RATING OF 100 PSF (BOTH POSITIVE AND
 NEGATIVE) AND A MAXIMUM DOOR HEIGHT OF
 102".PER THE SUBMITTED RWDI WIND LOAD
 STUDY REPORT THE SLIDING GLASS DOORS
 WILL BE SUBJECT TO NEGATIVE WIND
 PRESSURE OF -110 PSF WHICH EXCEEDS THAT
 ALLOWED BY THE PRODUCT APPROVAL.ALSO,
 DOOR SCHEDULE SHEET A-4.1 SHOWS A
 PROPOSED SLIDING GLASS DOOR HEIGHT OF
 10'-0" WHICH EXCEEDS THE MAXIMUM COVERED
 BY THE PRODUCT APPROVAL.SUBMIT AN
 ALTERNATIVE PRODUCT APPROVAL.
 (F)SINGLE HUNG WINDOW.THE
 SUBMITTED MIAMI WALL SERIES 122 ALUMINUM
 SINGLE HUNG WINDOW PRODUCT APPROVAL NOA#
 03-1008.03 HAS A MAXIMUM HEIGHT OF 72".
 WINDOW SCHEDULE SHEET A-4.2 SHOWS SINGLE
 HUNG WINDOW HEIGHTS UP TO 9'-4" WHICH
 EXCEED THE MAXIMUM COVERED BY THE
 PRODUCT APPROVAL.ALSO, IS IT THE
 INTENTION TO INSTALL THIS WINDOW ON TOP
 OF THE FIXED WINDOW TO FORM THE 'SINGLE
 HUNG WINDOW OVER FIXED WINDOW'
 CONFIGURATION THAT IS SHOWN ON THE
 WINDOW SCHEDULE SHEET? SUBMIT AN
 ALTERNATIVE PRODUCT APPROVAL THAT COVERS
 WINDOWS OF THE REQUIRED HEIGHT.
 (G) FIXED WINDOW.SUBMITTAL OF THE
 MIAMI WALL SERIES 122 ALUMINUM FIXED
 WINDOW PRODUCT APPROVAL NOA# 04-0322.09
 IS NOTED.FROM THE ELEVATIONS SHOWN ON
 WINDOW SCHEDULE SHEET A-4.2, IT IS NOT
 CLEAR WHERE THIS PRODUCT IS TO BE USED.
 PLEASE CLARIFY.
 (H)MULLIONS.IN ADDRESSING THE
 ABOVE COMMENTS PLEASE NOTE THAT SOME OF
 THE WINDOW CONFIGURATION MAY REQUIRE
 MULLIONS.IF SO PLEASE SUBMIT PRODUCT
 APPROVAL FOR APPROPRIATE MULLIONS.
 (I)IF THERE IS A STATEWIDE PRODUCT
 APPROVAL THAT COVERS ANY OF THE
 SUBMITTED PRODUCT APPROVAL NOA'S, THE
 STATEWIDE PRODUCT APPROVAL COVER SHEET
 MUST BE ATTACHED TO THE FRONT OF THE
 NOA.
  
 11) FBC* 104.2.1FIRE SEPARATION PLANS.
 RECOMMENDATION:THE INCLUSION OF A
 LEGEND ON SHEET A-2.1.2 IS NOTED.
 HOWEVER, THERE IS STILL SOME AMBIGUITY
 IN THE PLANS.FOR EXAMPLE, ON SHEETS
 A-2.1.4 AND A-2.1.5, THE WALLS ADJACENT
 TO THE BREEZEWAY HAVE NO SHADING BUT
 THEY HAVE A NOTE STATING A 2-HOUR FIRE
 RESISTANCE RATING.THE LIFE SAFETY
 PLANS LS-1 TO LS-5 ARE NOT
 OVER-COMPLICATED.PLEASE CONSIDER USING
 THEM TO CLARIFY THE FIRE RESISTANCE
 RATING OF THE WALLS WITH 'DASHED' LINE
 TYPES AND A CORRESPONDING LEGEND.
  
 12) FBC 1012.1.29TH FLOOR CLUBROOM.
 THE DOUBLE DOORS FROM THE CLUBROOM TO
 THE CORRIDOR SHALL SWING IN THE
 DIRECTION OF EGRESS FROM THE CLUBROOM.
 AMEND THE PLAN.
  
 16) FBC 411.2.3VEHICLE IMPACT
 WALLS/GUARDRAILS.IT IS NOTED THAT
 SHEETS A-2.7.1 TO A-2.7.4 NOW REFER TO
 THE STRUCTURAL PLANS.WALL TYPE W-30 IS
 SHOWN AT THE NORTH WALL OF THE PARKING
 GARAGE, ON 2ND FLOOR FRAMING PLAN SHEET
 S-1.01.PLEASE CONFIRM THAT WALL TYPE
 W-30 IS A PARKING IMPACT WALL, ASTHE
 WALL SCHEDUKE ON SHEET S-4.1, DOES NOT
 STATE THAT IT IS.
  
 20) FBC 2603.6.4DYPLAST MOLDINGS,
 SHEET A-6.9.THIS COMMENT HAS NOT BEEN
 PROPERLY ADDRESSED.CONTRARY TO THE
 COMMENT RESPONSE SHEETT, NO DYPLAST
 PRODUCT DATA WAS SUBMITTED.THE
 SUBMITTED URETHANE TECHNOLOGIES TEST
 REPORT# 542317 IS FOR UTD FR SPRAY COAT.
 IN ANY EVENT, THE REPORT SHOWS A FLAME
 SPREAD INDEX OF 30.FBC 2603.6.4
 REQUIRES AFLAME SPREAD INDEX OF 25 OR
 LESS.PLEASE PROVIDE
 MANUFACTURER'S SPECIFICATION FOR THE
 FLAME SPREAD AND COMBUSTIBILITY OF THE
 DYPLAST MOLDINGS.
  
 26) FBC 11-4.1.3SHEETS A-2.1.2 AND
 A-2.1.3 NOW SHOW A 1-3/4" SLAB RECESS.
 THE NOTES REFER TO ID DRAWINGS BUT NO ID
 PLANS WERE SUBMITTED.PLEASE CLARIFY
 THE PROPOSED FINISHED FLOOR LEVEL TO
 MAINTAIN THE ACCESSIBLE ROUTE THROUGH
 THE BUILDING.
  
 27)FBC 1015.2 GUARDRAIL HEIGHT.SHEET
 A-7.6, SECTION C AND SHEET A-7.7,
 SECTION C NOW SHOW A LOW WALL DETAIL
 THAT PROVIDES A 'STEP' WHICH WOULD
 REDUCE THE EFFECTIVE HEIGHT OF THE
 GUARDRAIL.A CHAMFERED EDGE SHOULD BE
 INCORPORATED LIKE THAT WHICH WAS
 INDICATED ON SHEET A-3.5, SECTIONS 2 AND
 3.
  
 28) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-20 Cont ID  
Sent By rbrown Date 2006-02-20 Time 23:30 Rev Time 0.00
Received By rbrown Date 2006-02-10 Time 08:18 Sent To  
Notes
2006-02-10 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 3) INFORMATIVE:
 A SEPARATE PERMIT APPLICATION WILL BE
 REQUIRED FOR THE SWIMMING POOL AND SPA.
 ALSO, A SEPARATE PERMIT APPLICATION WILL
 BE REQUIRED FOR THE CANVAS CANOPIES AND
 FRAMES IF FULL MATERIAL AND DESIGN
 DETAILS ARE NOT PROVIDED AS PART OF THE
 BUILDING PERMIT PLAN SET.
  
 4) FBC 1606.1.1WIND TUNNEL TEST
 REPORT.SUBMIT THREE COPIES OF THE RWDI
 REPORT 05-1427, REFERENCED ON SHEET
 S-0.0 UNDER THE GENERAL NOTES
 SUB-HEADING 'WIND LOADS'
  
 5) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 6) SUBMIT PRODUCT APPROVALS FOR THE
 FIXED WINDOWS, SINGLE HUNG WINDOWS,
 STOREFRONT, SLIDING GLASS DOORS,
 EXTERIOR DOORS AND BUILT-UP ROOFING,
 CONCRETE TILE AND METAL PANEL ROOF
 COVERINGS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE WWW.
 FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
 (IF YOU FIND THAT THE QUOTED WEB PAGE IS
 NO LONGER AVAILABLE, PLEASE INFORM THE
 PLAN REVIEWER)
  
 7) FBC 503.2.6TYPE II CONSTRUCTION,
 SPECIAL UNLIMITED HEIGHT.THIS SECTION
 ALLOWS THE BUILDING HEIGHT TO EXCEED THE
 80' LIMIT STATED IN TABLE 600 FOR TYPE
 II CONSTRUCTION, BUT IT REQUIRES THE
 ROOF AND ITS SUPPORTING STRUCTURE TO
 HAVE A FIRE RESISTANCE OF NOT LESS THAN
 1-1/2 HOURS.THE TABLE ON SHEET A-0.1,
 UNDER GENERAL NOTE 7, STATES THAT THE
 FIRE RESISTANCE OF THE ROOF IS TO BE A
 MINIMUM OF 1 HOUR.AMEND THIS TO 1-1/2
 HOURS.
  
 8) FBC 411.4.1FOR AN ENCLOSED PARKING
 GARAGE (GROUP S) OF TYPE II
 CONSTRUCTION, TABLE 500 LIMITS THE
 MAXIMUM NUMBER OF STORIES TO 6.SHEET
 A-0.1, GENERAL NOTE #5, STATES THE THE
 RESIDENTIAL AND PARKING GARAGE
 OCCUPANCIES ARE CONSIDERED MIXED USE.
 ALTHOUGH FBC 303.2 STATES THAT A MIXED
 OCCUPANCY BUILDING IS GOVERNED BY THE
 HEIGHT AND AREA LIMITATIONS OF IT'S
 PRINCIPAL USE (IN THIS CASE
 RESIDENTIAL), IT GOES ON TO STATE THAT
 ACCESSORY OCCUPANCIES SHALL NOT BE
 LOCATED AT A HEIGHT GREATER THAN THAT
 PERMITTED FOR SUCH AN OCCUPANCY GROUP IN
 THE THE TYPE OF CONSTRUCTION BEING USED.
 IN A TYPE II RESIDENTIAL BUILDING, THE
 PARKING GARAGE OCCUPANCY SHALL NOT
 OCCUPY ANY SPACE ABOVE THE SIXTH STORY.
 AMEND THE CONSTRUCTION TYPE.
  
 9) FBC 11-4.1.2(5)(B)VAN ACCESSIBLE
 PARKING. THE PARKING DATA ON SHEET A-0.1
 STATES THAT 17 ACCESSIBLE SPACES ARE
 BEING PROVIDED.1 IN EVERY 8 ACCESSIBLE
 SPACES SHALL BE VAN ACCESSIBLE.A
 MINIMUM VERTICAL CLEARANCE OF 98 INCHES
 IS REQUIRED AT SUCH SPACES, AND ALONG AT
 LEAST ONE VEHICLE ACCESS ROUTE TO THE
 SPACE FROM THE SITE ENTRANCE.PLEASE
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE.ALSO, THE NOTE ABOUT
 PARKING GARAGE BARRIER HEIGHT, ON SHEET
 A-2.7.1 IS NOT CLEAR. AMEND THE NOTE TO
 DEMONSTRATE COMPLIANCE WITH THE ABOVE
 REQUIREMENT.
  
 10) FBC 412.5SMOKE CONTROL.THE PLANS
 SHALL CLEARLY DESCRIBE THE PROVISION OF
 ONE OF THE FORMS OF SMOKE CONTROL LISTED
 IN THE CODE.ANNOTATE THE PLANS.
  
  
 11) FBC* 104.2.1FIRE SEPARATION PLANS.
 PLEASE ADD CLEAR ANNOTATION TO THE PLANS
 (OR USE LINE TYPES AND A LEGEND) TO
 DEMONSTRATE COMPLIANCE WITH CHAPTER 7,
 FIRE RESISTANT MATERIALS AND
 CONSTRUCTION.THE REFERENCE TO THESE
 REQUIREMENTS ON SHEET A-0.1, GENERAL
 NOTE #5 AND SHEET A-1.1 NOTE #4 IS
 ACKNOWLEDGED, BUT CLEAR DIAGRAMMATIC
 REPRESENTATION IS REQUIRED.FOR
 EXAMPLE, SHEET A-2.1.5 STATES "SHADING
 INDICATES 4 HR FIRE RATED MASONRY WALL &
 COLUMNS" AT THE FPL TRANSFORMER VAULT,
 BUT NO SHADING IS SHOWN.THE WALLS ARE
 SHOWN THE SAME AS THE 2 HR RATED WALLS.
  
 12) FBC* 104.2.1LIFE SAFETY PLANS.SO
 THAT COMPLIANCE WITH CHAPTER 10, MEANS
 OF EGRESS CAN BE DETERMINED, PLEASE
 SUBMIT 1/8"=1'-0" SCALE PLANS, FOR EACH
 STORY, SHOWING OCCUPANCY COUNTS AND
 DISTANCE TO EXIT FOR THE RESIDENTIAL,
 GARAGE, POOL DECK AND OTHER COMMON
 OCCUPANCY AREAS.
  
 13) FBC* 104.2.1ROOM DESIGNATIONS,
 SHEET A-1.5.THE OCCUPANCY FOR THE
 ROOMS TO THE NORTH AND WEST OF THE POOL
 HAVE NOT BEEN STATED.AMEND THE PLAN.
 IT IS NOTED THAT THESE ROOMS ARE
 REFERENCED ON SHEETS A-2.4.2 AND A-2.4.5
 AS FITNESS CENTER AND CLUBROOM UNDER
 SEPARATE PERMIT.FOR CLARITY, A NOTE
 SHOULD BE ADDED TO SHEET A-1.5 ALSO.
  
 14) FBC 1001.1POOL DECK EGRESS.THE
 EXIT DOOR LEADING TO STAIR #4 IS NOTED,
 BUT THE EXIT DOOR LEADING TO STAIR #3 IS
 SHOWN AS A SINGLE DOOR.THE DOORS WITH
 SCHEDULE REFERENCE NUMBER 50, LEAD FROM
 THE POOL DECK INTO THE 'FITNESS CENTER
 AND CLUBROOM' WHICH DO NOT APPEAR TO
 COMMUNICATE WITH THE EXIT ACCESS
 CORRIDOR.PLEASE CLARIFY THE PROVISION
 OF EXITTING FROM THE POOL DECK AREA.
 SEE THE TWO RELATED COMMENTS ABOVE.
  
 15) FBC 1003.3.5WIDTH OF EXIT, SHEET
 A-2.1.1.THE EXIT PASSEGEWAY LEADING TO
 THE EXIT DISCHARGE FROM STAIR NO.1 IS
 SHOWN AS REDUCING IN WIDTH FROM 5'-0" TO
 4'-0".AT NO POINT ALONFG AN EXIT PATH
 MAY THE EXIT WIDTH BE DECREASED.
  
 16) FBC 411.2.3VEHICLE IMPACT
 WALLS/GUARDRAILS, SHEETS A-2.7.1 TO
 A-2.7.4.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE WITH THE
 REQUIREMENT FOR IMPACT GUARDING AT THE
 ENDS OF THE 2ND FLOOR PARKING SPACES
 THAT ARE ADJACENT TO THE VOID OVER THE
 COMMERCIAL TENANT SPACE, AND THE PARKING
 SPACES, ON ALL FLOORS, THAT ARE ADJACENT
 TO THE RAMP, WHERE THE DIFFERENCE IN
 ADJACENT FLOOR ELEVATION IS GREATER THAN
 1'-0".THE SAME APPLIES TO THE 2ND FOOR
 TO 8TH FLOOR PARKING SPACES ADJACENT TO
 THE EAST EXTERIOR WALL.
  
 17) FBC 1608.2.1HANDRAIL STRENGTH,
 SHEET A-3.1 STAIR RAILING NOTE #2 IS
 ACKNOWLEDGED.PLEASE ADD A NOTE TO THE
 PLANS TO STATE THAT THE HANDRAILS SHALL
 BE DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB AND A LINE
 LOAD OF 50 PLF.THESE LOADS SHALL NOT
 BE APPLIED SIMULTANEOUSLY BUT SHALL BE
 APPLIED INDIVIDUALLY AT ANY POINT, AND
 IN ANY DIRECTION, TO PRODUCE MAXIMUM
 STRESS IN EACH OF THE COMPONENTS OR
 SUPPORTS.SEE THE COMMENT BELOW, ALSO,
 WITH RESPECT TO THE GUARDING
 REQUIREMENT FOR THE STAIRS.
  
 18) FBC 1608.2.2GUARDRAIL STRENGTH,
 SHEET A-3.5.ANNOTATE THE PLAN TO STATE
 THAT THE BALCONY RAILINGS (GUARDRAILS)
 SHALL BE DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB APPLIED IN
 ANY DIRECTION AT THE TOP OF THE
 GUARDRAIL, A CONCENTRATED HORIZONTAL
 LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA
 AT ANY POINT, AND A LINE LOAD OF 50 PLF
 APPLIED HORIZONTALLY AT THE REQUIRED
 GUARDRAIL HEIGHT WITH A SIMULTANEOUS
 LINE LOAD OF 100 PLF APPLIED VERTICALLY
 DOWNWARD ON THE TOP OF THE GUARDRAIL.
 THESE LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT
 SHALL BE APPLIED INDIVIDUALLY TO PRODUCE
 MAXIMUM STRESS IN EACH OF THE COMPONENTS
 OR SUPPORTS.
  
 19) FBC 1015.2GUARDRAIL HEIGHT, SHEET
 A-3.5, SECTIONS 2 AND 3.CHAMFER/SLOPE
 THE CONCRETE CAP PROFILE INWARD SO THAT
 IT DOES NOT PROVIDE A 'STEP' WHICH WOULD
 REDUCE THE EFFECTIVE HEIGHT OF THE
 GUARDRAIL.
  
 20) FBC* 104.2.1DYPLAST MOLDINGS,
 SHEET A-6.9.PLEASE PROVIDE
 MANUFACTURER'S SPECIFICATION FOR THE
 FLAME SPREAD AND COMBUSTIBILITY OF THE
 DYPLAST MOLDINGS.
  
 21) FBC 1606.1SOFFITS AND CEILINGS,
 SHEETS A-7.15 AND A-7.16.THE
 BREEZEWAY, ARCADE AND COVERED ENTRY
 DRIVE CEILINGS SHALL BE DESIGNED TO
 RESIST THE WIND PRESSURES FOR COMPONENTS
 AND CLADDING.
  
 22) FAIR HOUSING ACT, SHEET A-0.1.ALL
 OF THE DWELLING UNITS ARE 'COVERED
 UNITS'. IT IS NOTED THAT THERE ARE NO
 TYPICAL PLANS FOR THE UNIT TYPES TO SHOW
 HOW THEY WILL MEET THE REQUIREMENTS OF
 THE FAIR HOUSING ACT.SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 23) FBC 2103MASONRY WALL DETAILS,
 SHEET S0.03.THE VERTICAL REINFORCEMENT
 COLUMN OF THE TABLE ON THE 'TYPICAL
 EXTERIOR REINFORCED MASONRY WALL
 DETAILS' IS INCOMPLETE.
  
 24) FBC* 104.2.1IT IS NOTED THAT THE
 SUBMITTED PLANS ARE NOT COMPLETE.
 ADDITIONAL COMMENTS MAY ARISE WHEN THE
 REQUIRED PLANS ARE SUBMITTED.
  
 25) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 27 Status P Date 2008-04-07 Cont ID  
Sent By jleahy Date 2008-04-07 Time 15:04 Rev Time 0.45
Received By jleahy Date 2008-04-07 Time 15:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 26 Status F Date 2008-03-26 Cont ID  
Sent By jleahy Date 2008-03-26 Time 16:02 Rev Time 2.30
Received By jleahy Date 2008-03-26 Time 15:58 Sent To  
Notes
2008-03-26 16:00:16I WOULD LIKE A LIST IN SEQUENCE OF WHAT IS TO BE TURNED
 ON AND WHEN.
  
 PLEASE LIST SYSTEM BY SYSTEM TO BE TURNED ON.EX.
 ELEVATORS, A/C PUMPS, COMMON AREA POWER, GARAGE ECT
 ECT.
  
 THANKS
  
 JAKE

Review Stop E ELECTRICAL
Rev No 25 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 24 Status P Date 2008-02-11 Cont ID  
Sent By dpalmer Date 2008-02-09 Time 08:11 Rev Time 0.00
Received By dpalmer Date 2008-02-09 Time 08:11 Sent To  
Notes
2008-02-11 08:12:18REVISIONS OK PENDING MECHANICAL, FIRE AND BUILDING
 OFFICIAL RULING ON FUEL TANK.
 SHEETS E-2, E-19A, AND E-20

Review Stop E ELECTRICAL
Rev No 23 Status P Date 2008-02-05 Cont ID  
Sent By dpalmer Date 2008-02-05 Time 19:26 Rev Time 0.00
Received By dpalmer Date 2008-02-05 Time 19:26 Sent To PC
Notes
2008-02-05 19:26:40REV #27 FOR E-6 .

Review Stop E ELECTRICAL
Rev No 22 Status P Date 2007-12-24 Cont ID  
Sent By dpalmer Date 2007-12-24 Time 15:05 Rev Time 0.00
Received By dpalmer Date 2007-12-24 Time 15:05 Sent To B
Notes
2007-12-24 15:06:13SAUNA SUBMITTALS.
  
 UNIT SHOWS LISTING PER NRTL.

Review Stop E ELECTRICAL
Rev No 21 Status P Date 2007-12-24 Cont ID  
Sent By dpalmer Date 2007-12-24 Time 14:55 Rev Time 0.00
Received By dpalmer Date 2007-12-24 Time 14:55 Sent To PC
Notes
2007-12-24 14:56:07REVS SUBMITTED 12/11
 SHEETS E6, 7, 22, 24

Review Stop E ELECTRICAL
Rev No 20 Status P Date 2007-12-24 Cont ID  
Sent By dpalmer Date 2007-12-24 Time 14:45 Rev Time 0.00
Received By dpalmer Date 2007-12-24 Time 14:45 Sent To PC
Notes
2007-12-24 14:48:03REV'S WHICH WERE ON HOLD FROM 11/2 WERE REVIEWED.
 SHEET 19A WAS NOT STAMPED DUE TO COMMENTS FROM MECH FOR
 LOCATION OF FUEL.
  
 SHEETS 18,22 AND 24 OK

Review Stop E ELECTRICAL
Rev No 19 Status F Date 2007-11-29 Cont ID  
Sent By dpalmer Date 2007-11-29 Time 15:29 Rev Time 0.00
Received By dpalmer Date 2007-11-29 Time 15:29 Sent To  
Notes
2007-11-29 15:29:30** DENIED REVISION FOR E-19A. SUBMITTED 11/7
  
 1) NOTE: PLEASE SEE MECHANICAL REVIEW DATE 11/20/07 AS
 TANKS SHOWN ON ELECTRICAL PLANS IS NOT PERMITTED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 18 Status P Date 2007-11-02 Cont ID  
Sent By dpalmer Date 2007-11-02 Time 14:33 Rev Time 0.00
Received By dpalmer Date 2007-11-02 Time 14:33 Sent To FIRE
Notes
2007-11-02 14:35:07REV FROM 10/22,
 SHEETS E-1- E-6 FOR ACCESS CONTROLS. ELECTRICAL IS OK,
 A SEPARATE LOW VOLTAGE PERMIT IS REQUIRED FOR LOW
 VOLTAGE SYSTEMS.
 PLANS SENT TO FIRE.

Review Stop E ELECTRICAL
Rev No 17 Status P Date 2007-10-30 Cont ID  
Sent By dpalmer Date 2007-10-30 Time 11:43 Rev Time 0.00
Received By dpalmer Date 2007-10-30 Time 11:43 Sent To  
Notes
2007-10-30 11:44:36TEMP PASSED STATUS AS MECH, AND FIRE REVIEW NEEDS TO BE
 DONE FOR NEW FUEL TANK.
 WILL NEED TO KEEP ELECTRICAL SHEETS IF OK AND ONCE ALL
 REVIEWS ARE DONE.
 PREVIOUS REVISION IS STILL ON HOLD.

Review Stop E ELECTRICAL
Rev No 16 Status N Date   Cont ID  
Sent By dpalmer Date   Time 13:11 Rev Time 0.00
Received By dpalmer Date 2007-10-17 Time 13:06 Sent To PC
Notes
2007-10-17 13:14:26SHEETS E-18-19 OUTFRONT UNDER "M" ON HOLD UNTIL FUEL
 AND GENERATOR REVISIONS CAN BE VERIFIED FOR HB 7121 ON
 OTHER REVISIONS.
 THE OTHER REVISIONS SUBMITTED AT THE SAME TIME AHVE NOT
 BEEN REVIEWED AS OF YET.
 PLANS WILL BE UNDER "M" LARGE BINS.

Review Stop E ELECTRICAL
Rev No 15 Status F Date 2007-10-07 Cont ID  
Sent By dpalmer Date 2007-10-07 Time 09:58 Rev Time 0.00
Received By dpalmer Date 2007-10-07 Time 09:58 Sent To PC
Notes
2007-10-07 09:59:51REV FOR E-8, 23 AND 24, LIGHTING REVISIONS.
  
 COMMENTS FROM6/9/07 AND 6/29/07 STILL NEED TO BE
 ADDRESSED.
 EACH REVIEW STOPWILL REMAIN IN A *F* STATUS EVEN IF
 SOME SHEETS ARE OK AND PASSED UNTIL HB 7121 IS
 ADDRESSED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 14 Status F Date 2007-08-26 Cont ID  
Sent By dpalmer Date 2007-08-26 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2007-08-26 Time 15:24 Sent To PC
Notes
2007-08-26 16:17:13REV FOR SHEETS E6 AND 24 ARE OK AND STAMPED.
  
  
 COMMENTS FROM6/9/07 AND 6/29/07 NEED TO BE
 ADDRESSED.
 EACH REVIEW STOPWILL REMAIN IN A *F* STATUS EVEN IF
 SOME SHEETS ARE OK AND PASSED UNTIL HB 7121 IS
 ADDRESSED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 13 Status F Date 2007-08-26 Cont ID  
Sent By dpalmer Date 2007-08-26 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2007-08-26 Time 15:24 Sent To PC
Notes
2007-08-26 16:09:57REV'S FOR E, 2,3,4,5,6,7,8,16,20,21,22,23 AND 24.
 STAMPED OK.
  
  
  
 SHEETS E18, AND 19 WILL NOT BE REVIEWED AND STAMPED
 UNTIL COMMENTS FROM 6/9/07 AND 6/29/07 ARE ADDRESSED.
 EACH REVIEW STOP WILL REMAIN IN A *F* STATUS EVEN IF
 SOME SHEETS ARE OK AND PASSED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2007-06-29 Cont ID  
Sent By dpalmer Date 2007-06-29 Time 08:17 Rev Time 0.00
Received By dpalmer Date 2007-06-29 Time 07:33 Sent To PC
Notes
2007-06-29 08:17:40 
  
 *** UNSAT ***
  
 1) NOTE: PLEASE SEE THE NOTES WHICH WERE GIVEN ON
 6/9/07 WITH RESPECT TO THE NEW FLORIDA LEGISLATIVE
 REQUIREMENTS FOR BACK UP POWER. PLEASE KNOW THAT NO
 FURTHER REVISIONS WILL BE GRANTED FOR THE ELECTRICAL
 SERVICE RISER OR REVISIONS WHICH AFFECT THE SERVICE,
 GENERATOR TO THE BUILDING UNTIL THIS NOTE IS
 ADDRESSED.
 PLEASE SEE THE NOTE BELOW WHICH IS COPIED FROM THE
 REVIEW OF 6/9/07
  
 **
 1) NOTE: PLEASE SEE THE NEW FLORIDA STATE STATUTES WITH
 RESPECT TO THE NEW HOUSE BILL 7121 WHICH WAS SIGNED
 INTO LAW JULY OF 07.
 PLEASE SEE THERE ARE SEVERAL STATUTES WHICH WERE
 AFFECTED. PLEASE SEE THAT AN INDUSTRY BULLETIN IS BEING
 PLACED IN WITH THE REVIEW NOTES AS ADDITIONAL
 INFORMATION.
 *ONCE THIS INFORMATION IS READ AND STATUTES REVIEWED,
 PLEASE PROVIDE ALL INFORMATION AS REQUIRED ON PLANS AND
 DOCUMENTATION FOR REVIEW.
 PLEASE KNOW THAT SOME OF THIS INFORMATION WILL ALSO BE
 NEEDED BY THE FIRE MARSHAL, STATE BOARD FOR ELEVATORS
 ETC.
 **
  
 ** PLEASE SEE THE REVISIONS ON SHEETS E5,10, 11, 21 AND
 22 WERE OK AND STAMPED.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2007-06-09 Cont ID  
Sent By dpalmer Date 2007-06-09 Time 16:37 Rev Time 0.00
Received By dpalmer Date 2007-06-09 Time 14:28 Sent To FIRE
Notes
2007-06-09 16:38:24REVISIONSSUBMITTED 5/17/07 OK, STAMPED FOR ELECTRICAL
 AND ROUTED TO FIRE FOR REVIEW.
  
 SHEETS E,1,2,3,4,5,6,7,8,9,10,11,12,13,23 AND 24.

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2007-06-09 Cont ID  
Sent By dpalmer Date 2007-06-09 Time 15:27 Rev Time 0.00
Received By dpalmer Date 2007-06-09 Time 14:28 Sent To  
Notes
2007-06-09 15:28:34** THIS REVIEW STOP WILL BE PLACED AS *FAILED* EVEN AS
 SOME SHEETS WERE OK.
  
 ** REVIEW OF REVISIONS SUBMITTED 4/30/07
  
  
 ** SEE NOTES BELOW AS SOME SHEETS IN REVISIONS
 SUBMITTED 4/30/07 ARE VOIDED/UNSAT/OK*
  
 ** PLEASE SEE SHEETS E-5,6,8,23 AND 24 WERE VOIDED AS
 THESE SAME SHEETS HAVE ALREADY BEEN SUBMITTED WITH THE
 SAME REVISIONS AND NEW REVISIONS ON MAY 17, 2007. AS
 THESE SHEETS CONTAIN THE SAME INFORMATION THEY WERE
 VOIDED IN SETS.
  
 ** PLEASE SEE SHEET E-18 WAS FAILED, NOTES BELOW WITH
 RESPECT TO NEW FLORIDA STATUTES AND HIGH-RISE
 RESIDENTIAL BUILDINGS.
  
 ** PLEASE SEE SHEETS E-14, 20,21 AND 22 STAMPED OK.
  
 1) NOTE: PLEASE SEE THE NEW FLORIDA STATE STATUTES WITH
 RESPECT TO THE NEW HOUSE BILL 7121 WHICH WAS SIGNED
 INTO LAW JULY OF 07.
 PLEASE SEE THERE ARE SEVERAL STATUTES WHICH WERE
 AFFECTED. PLEASE SEE THAT AN INDUSTRY BULLETIN IS BEING
 PLACED IN WITH THE REVIEW NOTES AS ADDITIONAL
 INFORMATION.
 *ONCE THIS INFORMATION IS READ AND STATUTES REVIEWED,
 PLEASE PROVIDE ALL INFORMATION AS REQUIRED ON PLANS AND
 DOCUMENTATION FOR REVIEW.
 PLEASE KNOW THAT SOME OF THIS INFORMATION WILL ALSO BE
 NEEDED BY THE FIRE MARSHAL, STATE BOARD FOR ELEVATORS
 ETC.
  
 ** PLEASE SUBMIT THE ABOVE FOR REVIEW, IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE OR REVIEWER.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2007-03-22 Cont ID  
Sent By dpalmer Date 2007-03-22 Time 07:10 Rev Time 0.00
Received By dpalmer Date 2007-03-21 Time 19:56 Sent To FIRE
Notes
2007-03-22 07:11:42REV FOR PAGE E-2, OK FOR ELECTRICAL REVIEW.
 SENT TO FIRE

Review Stop E ELECTRICAL
Rev No 8 Status N Date 2007-01-13 Cont ID  
Sent By dpalmer Date 2007-01-13 Time 15:22 Rev Time 0.00
Received By dpalmer Date 2007-01-13 Time 15:22 Sent To  
Notes
2007-01-13 15:26:50REVS , ARE ARCHITECTURAL WHICH ARE DATED SUBMITTED
 12/18,
 PREVIOUS ELEC REV SUBMITTED SAME DATE DONE SEPARATELY/

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-12-31 Cont ID  
Sent By dpalmer Date 2006-12-31 Time 13:29 Rev Time 0.00
Received By dpalmer Date 2006-12-31 Time 12:11 Sent To PC
Notes
2006-12-31 13:29:12** RELDINED **
  
  
 LV ACESS CONTROL SYSTEM TO BE UNDER A SEPARATE PERMIT ,
 INCLUDING SUBMITTING ALL SPECS ON CONTROL /DOOR
 CLOSURE/ CARD READER DEVICES TO BE INSTALLED. THIS WILL
 BE REVIEWED BY FIRE AND ELEC. ANY SYSTEM/DEVICES SHALL
 NOT IMPEDE WITH THE MENAS OF EGRESS IN ANY FASHION
 UNDER NORMAL OR EMERGENCY CONDITIONS. LS 101 7.2.1.5.1
  
 ** REVISION FOR ADDITION OF PANEL LE, SOME OTHER MINOR
 ITEMS INCLUDING NEW ELECTRICLA IN GYM AREA.
  
 SHEETS E-5,-,18,19A,20,21,22 AND 24.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-12-31 Cont ID  
Sent By dpalmer Date 2006-12-31 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2006-12-31 Time 10:28 Sent To PC
Notes
2006-12-31 12:10:59REVISONS DATED 10/16/06FROM ELECTRICLA ENGINEER FOR
 THE FOLLOWING SHEETS.
 MOST SHEETS FOR VALUE ENGINEERING OF FEEDERSFROM
 COPPER TO ALUMINUM. REVISED FEEDERS ON RISER AND PANEL
 SCHEDULES
 GATE CONTROLS,
 DUCT DETECTOR, J-BOXES IN UNITS, AND SPARE CONDUITS AND
 OTHER MINOR MISC ITEMS.
  
 SHEETS
 E-2,9,10,11,12,13,17, 18,20,21,AND 22

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-11-05 Cont ID  
Sent By dpalmer Date 2006-11-05 Time 08:46 Rev Time 0.00
Received By dpalmer Date 2006-11-05 Time 08:34 Sent To  
Notes
2006-11-05 08:47:20STAMPED TWO COPIES OF MANUFACTURES SPECS/CUT SHEETS FOR
 FIRE PUUMP, FIRE PUMP CONTROLLER, GEN, ATS, BUS DUCT
 ETC.
 SENT BACK TOMR BROWN FOR OTHER TRADES TO STAMP.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-01 Cont ID  
Sent By dpalmer Date 2006-09-01 Time 14:45 Rev Time 0.00
Received By dpalmer Date 2006-09-01 Time 14:45 Sent To  
Notes
2006-09-01 00:00:00NEW REVISEDSHEET SP-1 ADDED INTO SETS
 SHOWING THE MIN OF 8HRS FOR FIRE PUMP.
 OK.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-16 Cont ID  
Sent By dpalmer Date 2006-08-16 Time 14:03 Rev Time 0.00
Received By dpalmer Date 2006-08-14 Time 20:10 Sent To  
Notes
2006-08-16 00:00:00REVIEW IN PROGRESS
 *** PASSED PENDING ***
  
  
 CALLED, ENGINEER OF RECORD AND MR PENA,
 FOR INFORMATION ON FIRE PUMP FUEL
 USAGE/CONSUMPTION PER HR. NEED TO HAVE
 IN RECORD SETS, SO THAT A MIN OF 8HRS OF
 ON-SITE FUEL IS PRVOIDED FOR FIRE PUMP.
  
  
 ELECTRICAL PLAN ARE STAMPED.
2006-08-14 00:00:00PLANS IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-18 Cont ID  
Sent By dpalmer Date 2006-06-18 Time 09:49 Rev Time 0.00
Received By dpalmer Date 2006-06-11 Time 20:07 Sent To  
Notes
2006-06-18 00:00:00REVIEW IN PROGRESS.
 ****** UNSAT 2ND REVIEW ******
  
 ** PLEASE SEE SOME COMMENTS FROM FIRST
 REVIEW AND SOME NEW COMMENTS DUE TO
 COMPLETE RISER ETC NOW SUBMITTED.
  
  
 ** IMPORTANT**
 WHEN SUBMITTING MANUFACTURES SPECS/CUT
 SHEETS, PRODUCT APPROVALS, STRUCTURAL
 CALCS ETC,PLEASE PLACE IN A BINDER OF
 SOME TYPE AND LABEL EACH SECTION/PRODUCT
 FOR EASY REFERENCE. THIS WOULD HELP
 GREATLY IN THE PLAN REVIEW PROCESS AND
 KEEPING ALL SUBMITTIALS IN ORDER.
  
 1) NOTE: PLEASE CORRELATE ALL
 SPEC/MANUFACTURES CUT SHEETS SUBMITTED
 WITH PLANS.
 PLEASE SEE TWO DIFFERENT GENERATORS, TWO
 DIFFERENT SIZES, TWO DIFFERENT ATS'S.
 PLEASE SEE RISER AND PLANS.
 215.5
  
 2) NOTE: PLEASE SEE SEE ATS IS STILL
 BEING SHOWN AS 3-POLE ON PLANS/ RISER
 AND SUBMITTIALS.
 PLEASE SEE RISER ALSO INDICATES 4-POLE
 AS REQUIRED IN ONE LOCATION.
 PLEASE SEE E-19 SHOWS 3-POLE ALSO.
 215.5
  
 3) NOTE: PLEASE SEE FIRE PUMP SPECS FOR
 DIESEL FP TANK, INDICATES 300 GALS IN ON
 ONE SHEET AND 270 GALS ON ANOTHER?
 PLEASE SPECIFY THE CORRECT SIZE TANK,
 PLEASE SPECIFY THE GPH CONSUMPTION OF
 THE DIESEL FIRE PUMP.
 ** PLEASE VERIFY MIN 8HRS?
 215.5, UNABLE TO VERIFY. PLEASE SEE
 NFPA-20 CHAPTER 11
  
 4) NOTE: PLEASE SEE NO "JOBSITE SPEC
 BOOKS" WERE SUBMITTED. THIS IS REQUIRED.
  
 5) NOTE: PLEASE SEE RISER NOTE #7A IS
 BEING INDICATED YET THIS COULD NOT BE
 LOCATED ON RISER. THIS IS FOR METER/UNIT
 RISER.
 215.5
  
 6) NOTE: PLEASE SEE NOTE #3 ON HOUSE
 RISER INDICATES GFI PROTECTION. (SHOULD
 BE GFP.)
 215.5
  
 7) NOTE: PLEASE SEE NOTE #5 HOUSE RISER
 NOTES, (3-POLE ATS), SEE NOTES ABOVE AND
 CORRELATE.
 215.5
  
 8) NOTE: PLEASE SEE MAIN FOR "TDP" IS
 SHOWN AS 1000A'S ON E-19, YET THIS IS
 NOTED ON HOUSE RISER NOTES AS BEING
 1200A'S FOR FUTURE>
 THE LOAD ON THIS "TDP" IS NOT KNOWN AT
 THIS TIME>??
 PLEASE VERIFY AS A 1000A DISCONNECT MAY
 FEED A 1200A DISC, AND IS BEING NOTED
 FOR COORDINATION.
 215.5
  
 9) NOTE: PLEASE SEE UNIT C-2 MISSING
 CIRCUITING FOR KITCHEN WALL.
 THIS WAS NOTED AND REDLINED ON PREVIOUS
 PLANS.
 215.5
 ** THIS CAN BE REDLINED**
  
 10) NOTE: PLEASE SEE UNIT C-9 AS
 LOCATION OF SD IN DEN SHOULD BE LOCATED
 WITHIN 12" OF THE HIGHEST POINT OF THE
 CEILING. IN UNIT C-9.1 THE SD WAS
 RELOCATED AND SEEMS TO BE THE SMAE
 LAYOUT.
 NFPA-72 11.8.3.5
 ** THIS CAN BE REDLINED.**
  
 11) NOTE: PLEASE SEE PANEL NOTATIONS ON
 E-20 INDICATE PANELS "TR1", TR2" AND TF
 PANELS BEING LOCATED ON THAT PAGE,
 HOWEVER THESE ARE ON E-22
 215.5
  
 12) NOTE: PLEASE SEE MISPRINT FOR TWO
 PANELS "LP'S" ON LOWER RIGHT HAND CORNER
 OF E-22.
 ** THIS CAN BE REDLINED **
  
 13) NOTE: PLEASE INDICATE THE
 PHOTO-METRICS FOR STAIRS UNDER EM POWER,
 AS ONLY THE TYPICAL DETAILS FOR TWO
 STAIR TOWERS WERE LOCATED FOR LEVELS
 UNDER NORMAL.
 LS 101 7.8.1.3,7.9.2.2
  
 **PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER TRADES WHICH HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 ** WHEN RESUBMITTING PLANS, PLEASE BE
 SURE TO REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-06-11 00:00:00ONE ROLL IN ELECTRICAL FOR REVIEW,

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-13 Cont ID  
Sent By dpalmer Date 2005-12-13 Time 08:01 Rev Time 15.00
Received By dpalmer Date 2005-12-09 Time 16:28 Sent To  
Notes
2005-12-13 00:00:00********** UNSAT ***************
  
 SOUTH TOWER @CITY PLACE
 550 OKEECHOBEE BLVD.
  
 **** PLEASE KNOW, PLANS SUBMITTED ARE
 NOT COMPLETE, THERFORE A COMPLETE REVIEW
 FOR CODE COMPLIANCE CAN NOT BE DONE AT
 THIS TIME.
 PLEASE SEE THE BELOEW ITEMS KNOWN AT
 THIS TIME.
  
 1)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECIFICATION SHEETS/ CUT SHEETS FOR
 FIRE PUMP(DIESEL) FIRE PUMP CONTROLLER,
 GENERATOR, AUTOMATIC TRANSFER SWITCH
 (ATS) AND ANY SUB BASE FUEL TANKS OR
 FUEL TANKS FOR DIESEL FIRE PUMP.
 PLEASE SURE ALL INFORMATION SUBMITTED
 MUST SHOW LISTINGS FROM A NATIONALLY
 RECOGNIZED TESTING LAB. (NRTL).
 PLEASE BE SURE ALL FIRE PUMP CONTROLLERS
 ETC COMPLY WITH NFPA-20 AND OTHER
 APPLICABLE CODES.
  
 2)NOTE: PLEASE SEE PLANS INDICATE 600KW,
 YET RISER DIAGRAM SHOWS 400KW GEN.
 PLEASE ALSO VERIFY IF THE ATS WILLL BE A
 4-POLE AND GEN TO BE SEPARTAELY DERIVED.
  
 PLEASE SEE 700.6DWHICH IN ORDER TO
 INDICATE A GROUND FAULT IN SOLIDLY
 GROUNDED WYE EMERGENCY SYSTEMS OF MORE
 THAN 150 VOLTS TO GROUND AND
 CIRCUIT-PROTECTIVE DEVICES RATED 1000
 AMPERES OR MORE. THE SENSOR FOR THE
 GROUND-FAULT SIGNAL DEVICES SHALL BE
 LOCATED AT, OR AHEAD OF, THE MAIN SYSTEM
 DISCONNECTING MEANS FOR THE EMERGENCY
 SOURCE, AND THE MAXIMUM SETTING OF THE
 SIGNAL DEVICES SHALL BE FOR A
 GROUND-FAULT CURRENT OF 1200 AMPERES.
 INSTRUCTIONS ON THE COURSE OF ACTION TO
 BE TAKEN IN EVENT OF INDICATED GROUND
 FAULT SHALL BE LOCATED AT OR NEAR THE
 SENSOR LOCATION.
 ALTHOUGH 700.26 INDICATES THAT
 GROUND-FAULT PROTECTION OF EQUIPMENT IS
 NOT REQUIRED ON THE ALTERNATE SOURCE FOR
 EMERGENCY SYSTEMS, GROUND FAULTS CAN
 OCCUR ON SUCH SYSTEMS, AND THEY CAN
 RESULT IN EQUIPMENT BURNDOWN. BECAUSE OF
 THE EMERGENCY NATURE OF SUCH SYSTEMS,
 AUTOMATIC DISCONNECT IN THE EVENT OF A
 GROUND FAULT IS INAPPROPRIATE. DETECTION
 OF SUCH A FAULT, HOWEVER, IS DESIRABLE
 SO THAT THE CONDITION CAN BE CORRECTED.
 PLEASE PROVIDE ALL INFORMATION AS NEEDED
 FROM MANUFACTURE TO VERIFY, AS SOME
 MANUFACTURES ALREADY KNOW TO THIS OFFICE
 DO REQUIRE THE SWITCHING OF THE NEUTRAL
 IN ORDER FOR THE GFP SENSING TO WORK
 CORRECTLY.
  
 3)NOTE:PLEASE SEE PLANS E-2 REFERENCE
 TO SEE LAYOUT OF FIRE COMMAND ROOM ON
 E-19, HOWEVER THIS LAYOUT IS "BLANK".
 PLEASE SEE NFPA-72, 101 WITH ALL MIN
 EQUIPMENT REQUIRED IN SUCH ROOM. PLEASE
 INDICATE THESE ITEMS ON PLANS.
 FIRE ALARM CONTROL PANEL, GENERATOR
 ANNUCIATOR PANEL, SHUNTS ETC.
 PLEASE ALSO SEE NOTE FOR EM LTS.
  
 4)NOTE: PLEASE SEE THAT NO PLANS WERE
 SUBMIT TO SHOW POOL AREA LAYOUT ,
 LIGHTING, RECEPTS ETC.
 UNABLE TO VERIFY MIN REQUIRED BY CODE
 FOR THESE AREAS.
  
 5)NOTE: PLEASE PROVIDE REFERENCE TO THE
 2002 NEC ON PLANS.
 PLEASE ALSO REFERENCE 2002 NFPA-72, AND
 THE 2003 NFPA-101.
  
 6)NOTE: PLEASE PROVIDE COMPLETE
 PHOTOMETRICS FOR ALL CORRIDOR, STAIR
 TOWER AND EGRESS PATHS. PLEASE SEE 101
 7.8 WHICH REQUIRES A MIN OF 10FT CANDLES
 MIN FOR STAIR WELLS AND 1FT MIN UNDER EM
 CONDITIONS.
 PLEASE SEE 7.9.2.2 WHICH REQUIRES WIRING
 OF EM LTS TO BE SUCH IN THE EVENT OF THE
 SWITCHING OF A SWITCH, BREAKER ETC OR
 THE TRIPPING OF A SINGLE OCP DEVICE WILL
 IN NO WAY LEAVE ANY ONE AREA OF EGRESS
 IN TOTAL DARKNESS. IN ORDER TO
 ALLEAVIATE THIS , A MIN BATTTERY BACK UP
 FIXTURE OF SOME TYPEWILL BE REQUIRED
 TO POVIDE THE MIN 1FT CANDLE FOR MIN
 TIME.
  
  
 7)NOTE: PLEASE SEE ALL MAIN ELECTRICAL
 ROOMS, FIRE COMMAND ROOM, GEN RM, FIRE
 PUMP RM AND ELEVATOR EQUIPMENT ROOMS ETC
 SHALL A BATTERY BACK UP TYPE OF LIGHTING
 FIXTURE.
 700.16, LS 101 7-9, 90.4
  
 8)NOTE: PLEASE SEE 620.23 AND 620.24
 WHICH REQUIRES EQUIPMENT ROOMS/AREAS TO
 HAVE A DEDICATED BRANCH CIRCUIT FOR
 RECEPTS AND LIGHTING.PLEASE SEE A
 DEDICATE CIRCUIT WAS LOCATED FOR RECEPT,
 HOWEVER LIGHTING COULD NOT BE VERIFIED.
  
 9)NOTE: PLEASE SEE FIRE REVIEW FOR EXACT
 LOCATIONS OF ANY "KNOX BOX" LOCATION(S)
 WHICH MAY BE REQUIRED. ONE OR MORE
 LOCATIONS SHALL BE PLACED/NOTED ON
 PLANS.
  
 10)NOTE: PLEASE SHOW ALL ROOM/AREA
 DESIGNATIONS ON PLANS. PLEASE SEE AREAS
 IN UNITS. PLEASE SEE AREAS WHICH NOW
 INDICATE THE 15A, #14 CIRCUITS IN AREAS
 WHICH APPEAR TO BE DINING AREAS.
 PLEASE SEE 210.52B1,210.11C1
  
 11)NOTE: : PLEASE SEE 210.63 FOR
 REQUIMENTS OF GFI RECEPTS FOR ALL A/C
 EQUIPMENT. PLEASE SEE THESE COULD NOT BE
 LOCATED ON ROOF PLANS ETC.
  
 12)NOTE: PLEASE PROVIDE SPECIFIC NOTES
 ON SHEETS CONTAINING A LARGER SCALE OF
 ELECTRICAL ROMMS. THE NOTE FOR 110.26
 WAS FOUND ON RISER SHEET, HOWEVER PLEASE
 INCLUDE THIS ON ABOVE SHEETS.
  
 13)NOTE: PLEASE SEE SOME AREAS, WHICH
 ARE LABELED AS ELEVATORS RMS ARE SHOWN
 BLANK?
 E-7
  
 14)NOTE: PLEASE PROVIDE DETAIL FOR ALL
 FLOOR PENETRATIONS AND PENETRATIONS FOR
 BUC-DUCT INDICATION THE MIN 4" CURBING.
 368.6B2
  
 15)NOTE: PLEASE INDICATE THE EQUIPMENT
 GROUNDING METHOD OF BUS-DUCT. PLEASE
 PROVIDE CUT SHEET FROM MANUFACTURE.
 PLEASE SEE LOCAL AMENDMENTS WHICH REUIRE
 THE EQUIPMENT GROUNDING TO BE
 COPPER.250.62
  
 16)NOTE: PLEASE PROVIDE COLOR CODING OF
 ELECTRICAL WIRING PER 215.8 OFLOCAL
 AMENDMENTS. 120/208 BLK,RED, BLUE,
 WHITE.
 277/480V BROWN, PURPLE, YELLOW, GREY.
 SEE OTHERS IF ANY OTHER ELECTRICAL
 VOLTAGES ARE TO BE USED.
  
  
 17)NOTE: PLEASE SEE SOME CIRCUTING
 MISSING ON UNITS PLANS. THESE HAVE BEEN
 REDLINED FOR AREAS OF COMMENT.
  
 18)NOTE: PLEASE SEE SOME UNITS MISSING
 RECEPTS PER 210.52.
 PLEASE SEE REDLINED SET, ONLY A COUPLE.
  
 19)NOTE: PLEASE SEE C 2.2 WHICH MENTIONS
 TO SEE ENLARGE AREA TO SHOW DETAIL,
 HOWEVER THIS SEEMS TO BE BLANK ON PLANS.
  
 20)NOTE:PLEASE SEE THAT ALL RECEPTS
 SHOWN IN CLOSETS FOR LV TRNSFORMERS TO
 BE "PLUGGED IN" SHALL BE LOCATED ATLEAST
 12" MIN FROM SHELVING. THESE MAY BE
 LOCATED ABOVE DOOR WAYS.
 PLEASE SEE PLUG-IN TYPE TRANSFORMERS
 CREATE VERY HIGH TEMPS AND SOME IN THIS
 JURISTICTION HAVE HEATED TO THE POINT OF
 MELTING, AND CUSE OF FIRE IN CLOSETS AND
 CLOSE PROIMITY TO COMBUSTIBLES. PLEASE
 SEE THIS CREATES A LIFE-SAFETY SITUATION
 AND ANY UNITS CONTAININGOCP, THERMAL
 CUT-OUT DEVICES WILL BE REQUIRED TO BE
 LOCATED AS ABOVE. 110.26,240.24D
  
 21)NOTE: PLEASE SEE SOME UNITS IN WHICH
 THERE SEEMS TO BE TWO DIFFERENT HEIGHTS
 IN BEDRM CEILINGS. PLEASE SEE NFPA-72
 11.8.3.5 WHICH REQUIRES THESE SD'S TO BE
 LOCATED WITHIN 12" OF THE HIGHESRT POINT
 OF THE FLAT CEILING AREA.
 PLEASE SEE REDLINED PLANS FOR LOCATIONS.
  
 22)NOTE: PLEASE SEE SOME UNITS WHICH
 INDICATE A HIGHER LOAD OF 122.5A'S ON A
 125A BREAKER. PLEASE VERIFY AS THIS DOES
 NOT SEEM TO LEAVE ANY ALLOTMENT FOR
 FURTURE WIRING EXPANTION OF LOADS.
 THIS IS THE LOAD AFTER ALL PERMITTED
 DE-RATING BY NEC.
 PLEASE ALSO SEE ANY ARE VERYCLOSE TO
 THE 100A'S PROVIDED.
 90.8
  
 23)NOTE: PLEASE SEE AREAS OF PLANS WHICH
 CONTAIN "WHITE-OUT" AND HAND-DRAWN
 CHNAGES MADE. (RISER SHEET).
 PLEASE SEE FS 471.025 ETC WHICH DOES NOT
 PERMIT ANY HAND DRAWN CHANGES TO PLANS,
 UNLESS EACH INDIVIDUAL CHANGE IS SIGNED
 AND DATED BY THE SAID ENGINEER OF
 RECORD.
  
 24)NOTE:PLEASE PROVIDE COMPLETE NOTES
 WITH RESPECT TO THE LOCATIONS OF SMOKE
 DETECTORS. 11.8.3.5
 SMOKE ALARMS AND SMOKE DETECTORS
 INSTALLED WITHIN A 6.1-M (20-FT)
 HORIZONTAL PATH OF A COOKING APPLIANCE
 SHALL BE EQUIPPED WITH AN
 ALARM-SILENCING MEANS OR BE OF THE
 PHOTOELECTRIC TYPE.
 SMOKE ALARMS AND SMOKE DETECTORS SHALL
 NOT BE INSTALLED WITHIN A 914-MM
 (36-IN.) HORIZONTAL PATH FROM A DOOR TO
 A KITCHEN OR A BATHROOM CONTAINING A
 SHOWER OR TUB.
 SMOKE ALARMS AND SMOKE DETECTORS SHALL
 NOT BE INSTALLED WITHIN A 914-MM
 (36-IN.) HORIZONTAL PATH FROM THE SUPPLY
 REGISTERS OF A FORCED AIR HEATING OR
 COOLING SYSTEM AND SHALL BE INSTALLED
 OUTSIDE OF THE DIRECT AIRFLOW FROM THOSE
 REGISTERS AND 5' MIN FROM RETURN AIR
 GRILLES.
 SMOKE ALARMS AND SMOKE DETECTORS SHALL
 NOT BE INSTALLED WITHIN A 914-MM
 (36-IN.) HORIZONTAL PATH FROM THE TIP OF
 THE BLADE OF A CEILING-SUSPENDED
 (PADDLE) FAN.
  
 25)NOTE:PLEASE SHOW GROUNDING SYSTEM
 FOR ALL TRANSFORMER. PLEASE INCLUDE
 GROUNDING OF THESE TRANSFOMERS ON RISER
 DIAGRAM IN NOTES/LINE DIAGRAM.
 250.30, 250.50 ETC.
 PLEASE PROVIDE THIS LINE DIAGRAM ON
 RISER SHEET.
  
 26)NOTE:PLEASE SEE NO GFP INDICATED FOR
 HDP. 230.95. 240.13 ETC.
  
 27)NOTE: PLEASE SEE ANY PROPOSED
 LIGHTNING PROTECTION SYSTEM SHALL BE
 INSTALLED AND ACCEPTABLE PER NFPA-780.
 ALTHOUGH A LIGHTNING PROTECTION SYSTEM
 IS NOT SHOWN ON ANY PLANS, PLEASE BE
 SURE A NOTE IS PLACED ON "ROOF-TOP"
 SHEET WITH REFERENCE TO NFPA-780.
 AS NOTED IN MEETING , "LIGHTNING
 PREVENTION" SYSTEMS ARE NOT PERMITTED OR
 ACCEPTABLE IN THIS JURISTICTION.
  
 28)NOTE: PLEASE SEE THIS NOTE IS ALL
 ENCOMPASSING OF ELECTRICAL RISER,
 EQUIPMENT SCHEDULE, LOAD CALCULATIONS,
 PANEL SCHEDULES AND CALCUALTIONS ETC.
  
 ** PLEASE COMPLETE ALL OF THE ABOVE AND
 SUBMIT FOR REVIEW.
 PLEASE CORRELATE ALL PANEL SCHEDULS ,
 EQUIPMENT WITH RISER
 PLEASE COMPLETE RISER WITH INFORMATION
 FOR EQUIPMENT, FEEDERS ETC.
 PLEASE SEE MANY AREAS OF LOAD
 CALCULATIONS WHICH ONLY INDICATE
 XXXXXXX'S.
 PLEASE SEE 2002 NEC.
  
 ** PLEASE KNOW THERE MAY BE OTHER
 COMMENTS DUE TO THE INCOMPLETE PLANS AT
 THIS TIME.
  
 ** PLEASE SEE REDLINED PLANS FOR
 POSSIBLE LOCATIONS.
  
 PLEASE SUBMITTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE TO GO OVER COMMENTS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
2005-12-09 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-07-26 Cont ID  
Sent By rchokshi Date 2006-07-26 Time 13:08 Rev Time 0.00
Received By rchokshi Date 2006-07-26 Time 13:06 Sent To  
Notes
2006-07-26 00:00:00PASS 7-26-06,RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-10-06 Cont ID  
Sent By mamini Date 2005-10-06 Time 13:21 Rev Time 1.00
Received By mamini Date 2005-10-06 Time 13:21 Sent To  
Notes
2005-10-06 00:00:00FAILED:
 1. AT THE PRESENT TIME, THE DEPARTMENT
 OF PUBLIC UTILITIES AND ENGENEERING
 SERVICES IS IN PROCESS OF DOING CAPACITY
 STUDIES FOR WATER AND SEWER CONNECTIONS
 IN SURROUNDING AREA.THE CIVIL
 ENGINEERING PLAN REVIEW CAN NOT PROCEED
 UNTIL SUCH STUDIES ARE COMPLETED AND
 CONNECTION TO THE SERVICES ARE APPROVED.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 22 Status P Date 2008-09-09 Cont ID  
Sent By mcarsill Date 2008-09-09 Time 11:39 Rev Time 0.00
Received By mcarsill Date 2008-09-09 Time 11:27 Sent To  
Notes
2008-09-09 11:39:06GRAPHIC DISPLAY SHOP DRAWING FOR THE SMOKE CONTROL
 PANEL.
  
 1. THE NEW PANEL IS TO BE TESTED AND THE PROPER
 DOCUMENTATION IS TO BE PROVIDED TO THE MEHCANICAL
 DIVISION AND THE FIRE RESCUE DEPARTMENT INDICATING THAT
 THE PANEL OPERATES CORRECTLY.
  
 2. THE EXISTING SMOKE CONTROL EQUIPMENT LOCATED IN THE
 FIELD HAD BEEN PREVIOUSLY TESTED WHEN SMOKE CONTROL
 COMPONENTS WERE CONNECTED TO THE FIRE ALARM CONTROL
 PANEL.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 21 Status F Date 2008-08-12 Cont ID  
Sent By mawillia Date 2008-08-12 Time 09:22 Rev Time 0.00
Received By mawillia Date 2008-08-11 Time 17:16 Sent To  
Notes
2008-08-11 17:25:24*****SUBMITTAL (FOR FIREMAN'S OVERRIDE PANEL)
 DENIED*****
  
  
 1.THE PLANS SHALL BE SUBMITTED WITH NO INK, PENCIL,
 OR DARKENED/WHITE-OUTED MARKINGS.
  
 2.THE SCOPE OF WORK ADDRESS SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
  
 CAPT. MICHAEL A, WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 20 Status P Date 2008-05-12 Cont ID  
Sent By mawillia Date 2008-05-12 Time 12:02 Rev Time 0.00
Received By mawillia Date 2008-05-12 Time 11:54 Sent To  
Notes
2008-05-12 12:00:42*****APPROVED*****
  
  
 REVIEWED REVISED PLAN SHEETS A-8.5, A-9.2.1, AND
 A-9.2.2;NO FIRE STAMP NEEDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 19 Status P Date 2008-02-21 Cont ID  
Sent By mawillia Date 2008-02-21 Time 14:43 Rev Time 0.00
Received By mawillia Date 2008-02-21 Time 14:38 Sent To M
Notes
2008-02-21 14:42:51*****TCO PLAN APPROVED*****
  
  
 THE TCO PLAN OUTLINE SUBMITTED BY THE RELATED
 GROUP/MOSS & ASSOCIATES WAS REVIEWED AND APPROVED FOR
 LIFE SAFETY COMPLIANCE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 18 Status P Date 2008-02-21 Cont ID  
Sent By mawillia Date 2008-02-21 Time 14:37 Rev Time 0.00
Received By mawillia Date 2008-02-21 Time 13:03 Sent To  
Notes
2008-02-21 13:45:18*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEETS A1.1,A-1.5, A-2.1.6,A-2.4.2,
 A-2.4.5, AND A-6.5 WERE REVIEWED;PLAN SHEETS A1.1AND
 A-2.1.6 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 17 Status P Date 2008-02-21 Cont ID  
Sent By mawillia Date 2008-02-21 Time 11:30 Rev Time 0.00
Received By mawillia Date 2008-02-21 Time 11:15 Sent To  
Notes
2008-02-21 11:25:03*****REVISION APPROVED*****
  
 THE COMMENT FROM FIRE REVIEW STOP #16 HAS BEEN
 ADDRESSED;REVISED PLAN SHEET E-2 STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 16 Status F Date 2007-12-20 Cont ID  
Sent By mawillia Date 2007-12-20 Time 12:43 Rev Time 0.00
Received By mawillia Date 2007-12-20 Time 12:35 Sent To  
Notes
2007-12-20 12:43:25*****UNSAT*****
  
  
 PLEASE ADDRESS ELECTRICAL AND PLUMBING COMMENTS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 15 Status P Date 2007-11-27 Cont ID  
Sent By mawillia Date 2007-11-27 Time 11:18 Rev Time 0.00
Received By mawillia Date 2007-11-27 Time 10:33 Sent To  
Notes
2007-11-27 11:12:54*****APPROVED REVISION*****
  
  
 REVIEWED REVISED PLAN SHEET A-8.1 (8/27/07), A-8.4
 (10/3/07), AND A-9.3.1 (8/9/07) ;NO FIRE-STAMPING
 NEEDED FOR THESE SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 14 Status P Date 2007-11-13 Cont ID  
Sent By mawillia Date 2007-11-13 Time 13:37 Rev Time 0.00
Received By mawillia Date 2007-11-13 Time 13:07 Sent To  
Notes
2007-11-13 13:31:11*****APPROVED REVISION DATED 10/04/07*****
  
  
 REVISED PLAN SHEET E-19A STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status P Date 2007-11-07 Cont ID  
Sent By mwennerg Date 2007-11-07 Time 15:53 Rev Time 0.00
Received By mwennerg Date 2007-11-07 Time 15:53 Sent To  
Notes
2007-11-07 15:55:10REVISED SHEETS E-1, E-2, E-3, E-4, E-5, AND E-6. ACCESS
 CONTROL TO COMPLY WITH NFPA 101, SEC. 7.2.1.6.2.

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2007-11-06 Cont ID  
Sent By mawillia Date 2007-11-06 Time 17:54 Rev Time 0.00
Received By mawillia Date 2007-11-06 Time 17:32 Sent To  
Notes
2007-11-06 17:54:49*****APPROVED, REVISION DATED 09/07/07*****
  
  
 REVISED PLAN SHEETS A-1.1, A-2.14,A-2.15, A-2.3.6,
 A-2.7.1, A-6.1, A-6.5, AND A-6.9 WERE REVIEWED AND
 APPROVED;PLAN SHEET A-6.1 WAS STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2007-09-18 Cont ID  
Sent By mawillia Date 2007-09-18 Time 15:44 Rev Time 0.00
Received By mawillia Date 2007-09-18 Time 15:28 Sent To  
Notes
2007-09-18 15:38:48*****APPROVED*****
  
  
 REVISED PLAN SHEET SP-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status N Date 2007-07-02 Cont ID  
Sent By mwennerg Date 2007-07-02 Time 10:25 Rev Time 0.00
Received By mwennerg Date 2007-07-02 Time 10:25 Sent To  
Notes
2007-07-02 10:27:34REVISIONS DATED 4/27/07 TO MECHANICAL AND PLUMBING
 SHEETS. IT DOES NOT APPEAR THAT THERE ARE ANY CHANGES
 THAT EFFECT LIFE SAFETY. ANY REVISIONS MADE TO FIRE
 PROTECTION SYSTEMS ARE TO BE SUBMITTED UNDER THAT
 SPECIFIC PERMIT AND ILLUSTRATED ON SPECIFIC PLANS.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2007-06-29 Cont ID  
Sent By mawillia Date 2007-06-29 Time 14:49 Rev Time 0.00
Received By mawillia Date 2007-06-29 Time 14:35 Sent To E
Notes
2007-06-29 14:48:35*****REVISIONS (RE LIGHTS)APPROVED*****
  
  
 THE SCOPE OF WORK ON THESE REVISED ELECTRICAL PLAN
 SHEETS HAVE NO BEARING UPON LIFE SAFETY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2007-04-30 Cont ID  
Sent By mawillia Date 2007-04-30 Time 14:18 Rev Time 0.00
Received By mawillia Date 2007-04-30 Time 13:47 Sent To  
Notes
2007-04-30 14:02:08*****REVISION #9[2/02/07]APPROVED******
  
  
 REVISED PLAN SHEETS SP-8 THRU SP-12 SHOWING FIRE
 SPRINKLERS IN DRYER SHAFT TO BE INSTALLED AT TOP AND
 BOTTOM FLOOR ONLU WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status F Date 2007-04-09 Cont ID  
Sent By mawillia Date 2007-04-09 Time 12:13 Rev Time 0.00
Received By mawillia Date 2007-04-09 Time 11:54 Sent To  
Notes
2007-04-09 12:13:07*****UNSAT*****
  
  
 UNABLE TO LOCATE REVISION #12 ON THE SUBMITTED PLAN
 SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2007-03-26 Cont ID  
Sent By mawillia Date 2007-03-26 Time 19:15 Rev Time 0.00
Received By mawillia Date 2007-03-26 Time 19:06 Sent To  
Notes
2007-03-26 19:14:56*****REVISION APPROVED*****
  
  
 SHEET NUMBER E-2 (REVISED DATE 03/01/07) STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-01-30 Cont ID  
Sent By mwennerg Date 2007-01-30 Time 11:45 Rev Time 0.00
Received By mwennerg Date 2007-01-30 Time 11:45 Sent To  
Notes
2007-01-30 11:47:00REVISED ARCHITECTURAL SHEETS ONLY DATED 11/17/06.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-08-29 Cont ID  
Sent By mwennerg Date 2006-08-29 Time 07:23 Rev Time 0.00
Received By mwennerg Date 2006-08-29 Time 07:23 Sent To  
Notes
2006-08-29 00:00:00***PROVISO***
  
 1) THESE PLANS APPEARED TO HAVE BEEN
 REVISED ON SHEET LS.2 AT STAIR #(2) EXIT
 DOORS CONVERGE AT ONE ANOTHER. EXITING
 FROM THE GARAGE AND CORRIDOR COULD
 POSSIBLY BECOME UNUSEABLE DUE TO PERSONS
 EXITING FROM BOTH THESE AREAS. PLEASE
 REVISE THIS AREA WHERE EXIT CONVERGENCE
 OCCURS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FOR MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-07-17 Cont ID  
Sent By mcarsill Date 2006-07-17 Time 11:40 Rev Time 0.00
Received By mcarsill Date 2006-07-17 Time 10:26 Sent To  
Notes
2006-07-17 00:00:001. IT APPEARS THAT ON LS-3 TRAVEL
 DISTANCE ROUTES ARE TRAVELING OVER A
 PARKING SPACE WHERE A VEHICLE WOULD BE
 PARKED. THIS OCCURS IN THE VICINITY OF
 STAIR # 4. THIS ROUTE IS INDICATED FOR
 THREE DIFFERENT PLACES.
  
 2. PLEASE EXPLAIN HOW THE TWO DOORS WORK
 SINCE THEY ARE IN CLOSE PROXIMITY TO ONE
 ANOTHER ON LS-2. THE GARAGE AREA DOOR
 AND STAIR # 4 DOOR.
  
 3. SHOULD THE TWO 184 FEET TRAVEL
 DISTANCE ROUTES SHOWN ON PAGE LS-1
 TRAVEL PAST THE PUMP ROOM AND JANITORS
 CLOSET INTO THE HALLWAY TO REACH THE
 EXIT WHICH IS CLOSER.
  
 4. NO DOOR (S) SHOWN AT 58 OCCUPANT
 ARROW FROM CLUBROOM SHOWN ON LS-4.
 PLEASE ADVISE.
  
 5. PLEASE EXPLAIN IN SWINGING DOORS FROM
 THE CLUBROOM NEAR THE 33 FEET TRAVEL
 DISTANCE ROUTE. IS THIS THE CORRECT
 DIRECTION FOR THESE DOORS TO SWING.
  
 6. COULD NOT LOCATE BUILDING ADDRESS ON
 THE ELEVATIONS THAT FACE OKEECHOBEE
 BOULEVARD. INFORMATION LOCATED ON PAGE
 A-10.1. OKAY.
  
 7. IT APPEARS THAT THE PREVIOUS COMMENTS
 HAVE BEEN ADDRESSES.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-11-18 Cont ID  
Sent By mcarsill Date 2005-11-18 Time 16:58 Rev Time 0.00
Received By mcarsill Date 2005-11-18 Time 16:31 Sent To  
Notes
2006-01-04 00:00:00******DENIED******
  
 PLAN REVIEW WAS STARTED BY F.M. M.
 CARSILLO AND STOPPED AFTER 32 COMMENTS.
 THE FOLLOWING IS A CONTINUATION OF THE
 SAME PLAN REVIEW:
  
 33) A MINIMUM OF (2) FIRE DEPARTMENT
 CONNECTIONS REQUIRED FOR HIGHRISE
 BUILDINGS.
  
 34) THE FIRE ALARM SYSTEM SHALL BE UL
 CERTIFIED FOR CENTRAL STATION SERVICE.
  
 35) LOCKING KNOX BOX CAPS REQUIRED FOR
 FIRE DEPARTMENT CONNECTIONS.
  
 36) THE FIRE ALRM SYSTEM SHALL MEET THE
 SURVIVABILITY REQUIREMENTS OF NFPA 72.
  
 37) THE BUILDING IS TO MEET ALL HIGHRISE
 REQUIREMENTS IN ACCORDANCE WITH
 APPLICABLE BUILDING AND FIRE CODES.
  
 38) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 39) SEPARATE SHOP DRAWINGS AND
 MANUFACTURER SPEC SHEETS REQUIRED FOR
 FIRE PUMP AND ASSOCIATED EQUIPMENT.
  
 40) PLEASE NOTE THAT VARIOUS CODE
 EDITIONS ON SHT SP-14 ARE INCORRECT.
 NFPA 101 AND NFPA 1, 2003 EDITION, NFPA
 13, 2002 EDITION, NFPA 14, 2003 EDITION,
 AND NFPA 20, 2003 EDITION.
  
 41) IN ADDITION TO ELECTRONIC SWITCHES,
 THE DOUBLE CHECK DETECTOR ASSEMBLY SHALL
 BE SECURED WITH A LOCK AND CHAIN.
  
 42) ALL ELEVATORS TO COMPLY WITH ASME
 A17.1.
  
 43) PARKING GARAGE TO COMPLY WITH THE
 APPLICABLE BUILDING CODES AND NFPA 88A.
  
 44) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS IN
 TERMS OF CLASS A,B, OR C.
  
 45) AN ADDRESS IS REQUIRED ON BUILDING
 AND SHALL BE A MINIMUM OF 6" IN HEIGHT
 AND CONTRASTING WITH BACKGROUND.
  
 46) ALL SMOKE DETECTORS SHALL BE LOCATED
 A MINIMUM OF (3) FEET FROM AC DIFFUSERS.
  
 47) FIRE ALARM SYSTEM SHALL BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPFR
 FIRE PLANS REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2005-11-18 00:00:001. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. EXIT STAIRS ARE TO BE KEPT UP
 WITH CONSTRUCTION.
  
 3. TEMPORTARY STANDPIPES ARE
 REQUIRED WHEN THE BUILDING REACHES
 THREE STORIES OR THIRTY FEET IN HEIGHT.
  
 4. DEBRIS REMOVAL SHALL OCCUR
 DAILY.
  
 5. NO CUTTING OR WELDING IS TO BE
 PERFORMED WITHOUT APPROVAL FROM
 THE BUREAU OF FIRE PREVENTION AND
 COMPLIANCE WITH NFPA 51B.
  
 6. WHAT WILL BE THE NAME OF THE NEW
 STREET.
  
 7. WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING ,AND AFTER CONSTRUCTION.
  
 8. SUITABLE ROADS REQUIRED FOR FIRE
 AND PARAMEDICAL EQUIPMENT.
  
 9. COULD ONLY LOCATE ONLY TWO FIRE
 HYDRANTS ON PAGE C-13. NOT ENOUGH
 FIRE HYDRANTS.
  
 10. PLEASE REVIEW CODE TAB BOX TO
 ENSURE PROPER INFORMATION.
  
 11. KNOX-BOXES WILL BE REQUIRED.
  
 12. ALL COMMERCIAL SPACES MUST BE FIRE
 SPRINKLER PROTECTED PRIOR TO
 RECEIVING A C OF O.
  
 13. COULD NOT LOCATE EXIT SIGNS GARAGE,
 GROUND FLOOR.
  
 14. NO EXIT SIGNS SECOND FLOOR, PAGE
 E-3.
  
 15. EXIT SIGNS APPEAR TO BE MISSING
 ON PAGE E-4. WHERE ARE THE ARE THE
 EXIT SIGNS LOCATED FOR THE GARAGE.
 CORRIDOR NEAR ELECTRICAL ROOM # 3
 DISPLAYS NO EQUIPMENT.
  
 16. SAME PROBLEM ON PAGE E-5.
  
 17. EXIT SIGNS SHALL NOT EXCEED 100
 FEET APART.
  
 18. ELECTRICAL PLANS DO NOT APPEAR TO
 BE COMPLETE.
  
 19. PLEASE INDICATE FIRE RATINGS OF
 SHAFTS SHWON ON PAGE AC-14.
  
 20. MECHANICAL EQUIPMENT SHOWN IN
 SOME STAIRWELLS. ONLY CERTAIN
 EQUIPMENT IS ALLOWED IN STAIRWELLS.
  
 21. PLEASE XPLAIN GATE IN PARKING GARAGE
 ON PAGE A-1.1.
  
 22. PLEASE SUBMIT A LIFE SAFETY PLAN
 FOR REVIEW.
  
 23. DOORS FOR THE POOL DECK ON THE 9TH
 FLOOR APPEAR TO SWING IN THE WRONG
 DIRECTION.
  
 24. PLEASE INDICATE OCCUPANT LOAD
 FOR POOL AND POOL DECK.
  
 25. PLEASE EXPLAIN CARD READERS AND HOW
 THEY WILL EFFECT EXITING.
  
 26. SOFFITS ARE NOT TO INTERFERE WITH
 ANY OPERATION OF REQUIRED FIRE
 SPRINKLERS.
  
 27. PLEASE PROVIDE PRESCRIPTVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 28. PLEASE INDICATE WHICH ELEVATORS
 WILL BE STRETCHER ACCESSIBLE. SIGNS WILL
 BE REQUIRED.
  
 29. ELEVATOR WARNING SIGNS WILL BE
 REQUIRED.
  
 30. STAIRWELL SIGNS WILL BE REQUIRED.
  
 31. TACTILE SIGNAGE REQUIRED AT STAIRS.
  
 32. WHAT SIZE IS THE RISER AND TREADS
 SHOWN ON PAGE A-2.1.3.
  
 ACCORDING TO DEWEY PALMER, NEW SHEETS
 ARE TO BE SUBMITTED BY THE ARCHITECT.
 THE REVIEW WAS STOPPED BECAUSE THE PLANS
 WERE NOT COMPLETE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2007-11-20 Cont ID  
Sent By rregueir Date 2007-11-20 Time 08:58 Rev Time 0.00
Received By rregueir Date 2007-11-20 Time 08:55 Sent To  
Notes
2007-11-20 08:58:16REVIEW: 1ST
 ACTION: DENIED
  
 FBC 2001 W/ 2003 SUPPLEMENTS
 NFPA 37-94
  
 1. P-1A AND P-1B: INSTALLATIONS OF ABOVE GROUND FUEL
 TANKS IN EXCESS OF 550 GALLONS ARE REQUIRED TO BE
 APPROVED BY THE PALM BEACH COUNTY DEPARTMENT OF
 ENVIRONMENTAL RESOURCE MANAGEMENT. PLANS SHALL BE
 SUBMITTED AND APPROVED BY DERM PRIOR TO BEING REVIEWED
 FOR CODE COMPLIANCE AND MADE PART OF THE PERMIT RECORD.
 FOR MORE INFORMATION PLEASE CONTACT DERM AT
 561-233-2400 OR VISIT
 HTTP://WWW.CO.PALM-BEACH.FL.US/ERM/INDEX.ASP.
  
 2. P-1A AND P-1B: FUEL STORAGE FOR STATIONARY
 COMBUSTION ENGINES SHALL COMPLY WITH NFPA 37-94 IN
 ACCORDANCE WITH FBC, M 915.1. THE FOLLOWING CONDITIONS
 WHICH ARE SHOWN ON PLANS ARE IN VIOLATION OF NFPA 37-94
 SEC. 6-3.2.3.1:
  
 A) UNENCLOSED DAY TANKS (I.E., TANKS NOT IN A ROOM BY
 THEMSELVES) WHICH ARE USED FOR EMERGENCY PURPOSES SHALL
 NOT EXCEED 660 GALLONS.
 B) TWO OR MORE TANKS WITH AN AGGREGATE CAPACITY MORE
 THAN 660 GALLONS SHALL NOT BE CONNECTED TO ONE ENGINE.
 C) THE AGGREGATE CAPACITY OF ALL UNENCLOSED DAY AND
 SUPPLY TANKS IN A BUILDING SHALL NOT EXCEED 1,320
 GALLONS.
 D) DAY AND SUPPLY TANKS WITH INDIVIDUAL CAPACITIES
 LARGER THAN 660 GALLONS OR THOSE TANKS WHICH CAUSE THE
 AGGREGATE CAPACITY TO EXCEED 1,320 GALLONS IN A
 BUILDING SHALL BE ENCLOSED IN ACCORDANCE WITH SEC.
 6-3.5. ROOMS CONTAINING ONLY TANKS SHALL BE CONSTRUCTED
 OF WALLS, FLOOR AND TOP HAVING A FIRE RESISTANCE RATING
 OF NOT LESS THAN 3 HOURS WITH THE WALLS BONDED TO THE
 FLOOR IN ACCORDANCE WITH 6-3.5.1. PLEASE SEE THIS
 SECTION FOR ADDITIONAL REQUIREMENTS.
  
 3. IF THE 1500 GALLON DAY TANK IS ENCLOSED IN A 3-HOUR
 ROOM AS REQUIRED BY 6-3.2.3.1 AND 6-3.5, THEN THE
 AGGREGATE TOTAL OF THE SUPPLY TANKS FOR THE GENERATOR
 AND THE FIRE PUMP WILL BE LESS THAN THE MAXIMUM
 AGGREGATE 1,320 GALLONS ALLOWED FOR UNENCLOSED TANKS
 AND NO ADDITIONAL 3-HOUR ENCLOSURES WILL BE REQUIRED BY
 THIS SECTION.
  
 4. PLEASE VERIFY COMPLIANCE WITH SECTIONS 6-4 THROUGH
 6-8 REGARDING FUEL FLOW CONTROL, FILLING, PIPING AND
 TRANSFER OF LIQUID FUEL TO ENGINES.
  
 NOTE: A SEPARATE FUEL PERMIT IS REQUIRED FOR FUEL
 STORAGE SYSTEMS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-08-26 Cont ID  
Sent By kstevens Date 2006-08-26 Time 16:01 Rev Time 0.00
Received By kstevens Date 2006-08-26 Time 16:01 Sent To  
Notes
2006-08-26 00:00:00 
  
 PASSED/PROVISO
  
  
  
 GAS APPLIANCE VENTING SHALL BE FIELD
 INSPECTED AND APPROVED.
 MANUF. SPECIFICATION SHEETS SHALL BE
 SUBMITTED AT THE TIME OF GAS PERMIT
 APPLICATION. MANUF. SPECIFICATIONS
 SHEETS REQUIRED FOR THE GAS REGULATORS.
 VENTS FOR REGULATORS SHALL BE MADE OF
 NON COMBUSTABLE MATERIAL. GAS RISER - A
 SHUT OFF VALVE SHALL BE INSTALLED PRIOR
 TO THE REGULATORS WITH A UNION BETWEEN
 OR AFTER REGULATOR. (SHT P-6). SECTION
 410.2(5). REVISIONS REQUIRED FOR THESE
 SHEETS.

Review Stop I INCOMING/PROCESSING
Rev No 163 Status N Date 2008-09-10 Cont ID  
Sent By adarroug Date 2008-09-10 Time 12:49 Rev Time 0.00
Received By adarroug Date 2008-09-10 Time 12:49 Sent To Z
Notes
2008-09-10 12:50:03TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 162 Status N Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 08:50 Rev Time 0.00
Received By tgordon Date 2008-08-26 Time 08:50 Sent To FIRE
Notes
2008-08-26 08:50:54TO "FIRE" BOX

Review Stop I INCOMING/PROCESSING
Rev No 161 Status N Date 2008-08-25 Cont ID  
Sent By tgordon Date 2008-08-25 Time 14:49 Rev Time 0.00
Received By tgordon Date 2008-08-25 Time 14:49 Sent To FIRE
Notes
2008-08-25 14:50:21TO "FIRE" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 160 Status N Date 2008-08-05 Cont ID  
Sent By adarroug Date 2008-08-05 Time 16:05 Rev Time 0.00
Received By rregueir Date 2008-08-05 Time 16:05 Sent To FIRE
Notes
2008-08-06 14:23:47SENT TO MECHANICAL IN ERROR. RE-ROUTED TO FIRE INBOX.
2008-08-05 16:05:24TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 159 Status N Date 2008-07-17 Cont ID  
Sent By adarroug Date 2008-07-17 Time 13:24 Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 13:24 Sent To P
Notes
2008-07-17 13:24:59TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 158 Status N Date 2008-05-27 Cont ID  
Sent By adarroug Date 2008-05-27 Time 09:01 Rev Time 0.00
Received By adarroug Date 2008-05-27 Time 09:01 Sent To B
Notes
2008-05-27 09:01:50TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 157 Status N Date 2008-05-01 Cont ID  
Sent By adarroug Date 2008-05-01 Time 15:14 Rev Time 0.00
Received By adarroug Date 2008-05-01 Time 15:14 Sent To B
Notes
2008-05-01 15:14:31TO "RBROWN "DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 156 Status N Date 2008-04-17 Cont ID  
Sent By adarroug Date 2008-04-17 Time 16:58 Rev Time 0.00
Received By adarroug Date 2008-04-17 Time 16:58 Sent To B
Notes
2008-04-17 16:59:22TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 155 Status N Date 2008-04-14 Cont ID  
Sent By adarroug Date 2008-04-14 Time 14:50 Rev Time 0.00
Received By adarroug Date 2008-04-14 Time 14:50 Sent To FIRE
Notes
2008-04-14 14:51:17TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 154 Status N Date 2008-04-11 Cont ID  
Sent By adarroug Date 2008-04-11 Time 13:11 Rev Time 0.00
Received By adarroug Date 2008-04-11 Time 13:11 Sent To  
Notes
2008-04-11 13:13:41TO "COMM" BD#26

Review Stop I INCOMING/PROCESSING
Rev No 153 Status N Date 2008-03-28 Cont ID  
Sent By adarroug Date 2008-03-28 Time 10:16 Rev Time 0.00
Received By adarroug Date 2008-03-28 Time 10:16 Sent To M
Notes
2008-03-28 10:16:27TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 152 Status N Date 2008-03-17 Cont ID  
Sent By adarroug Date 2008-03-17 Time 15:00 Rev Time 0.00
Received By adarroug Date 2008-03-17 Time 15:00 Sent To M
Notes
2008-03-17 15:01:11TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 151 Status N Date 2008-03-06 Cont ID  
Sent By adarroug Date 2008-03-06 Time 15:06 Rev Time 0.00
Received By adarroug Date 2008-03-06 Time 15:06 Sent To P
Notes
2008-03-06 15:06:59TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 150 Status N Date 2008-03-06 Cont ID  
Sent By adarroug Date 2008-03-06 Time 14:53 Rev Time 0.00
Received By adarroug Date 2008-03-06 Time 14:53 Sent To M
Notes
2008-03-06 14:54:08TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 149 Status N Date 2008-03-03 Cont ID  
Sent By adarroug Date 2008-03-03 Time 12:39 Rev Time 0.00
Received By adarroug Date 2008-03-03 Time 12:39 Sent To B
Notes
2008-03-03 12:39:41TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 148 Status N Date 2008-02-08 Cont ID  
Sent By adarroug Date 2008-02-08 Time 09:55 Rev Time 0.00
Received By adarroug Date 2008-02-08 Time 09:55 Sent To M
Notes
2008-02-08 09:55:47TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 147 Status N Date 2008-02-06 Cont ID  
Sent By adarroug Date 2008-02-06 Time 10:30 Rev Time 0.00
Received By adarroug Date 2008-02-06 Time 10:30 Sent To B
Notes
2008-02-06 10:30:33TO "KCONRAD" DESK/SUBMITTAL(TCO PLANS)

Review Stop I INCOMING/PROCESSING
Rev No 146 Status N Date 2008-02-06 Cont ID  
Sent By adarroug Date 2008-02-06 Time 10:28 Rev Time 0.00
Received By adarroug Date 2008-02-06 Time 10:28 Sent To P
Notes
2008-02-06 10:29:09TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 145 Status N Date 2008-02-06 Cont ID  
Sent By adarroug Date 2008-02-06 Time 10:28 Rev Time 0.00
Received By adarroug Date 2008-02-06 Time 10:28 Sent To M
Notes
2008-02-06 10:28:44TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 144 Status N Date 2008-01-31 Cont ID  
Sent By adarroug Date 2008-01-31 Time 11:46 Rev Time 0.00
Received By adarroug Date 2008-01-31 Time 11:45 Sent To  
Notes
2008-01-31 11:46:26TO "COMM" BD#12

Review Stop I INCOMING/PROCESSING
Rev No 143 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 11:54 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 11:54 Sent To  
Notes
2008-01-29 12:01:08TO "COMM" BD#2

Review Stop I INCOMING/PROCESSING
Rev No 142 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 11:54 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 11:54 Sent To M
Notes
2008-01-29 11:54:18TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 141 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 11:51 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 11:51 Sent To E
Notes
2008-01-29 11:51:44TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 140 Status N Date 2008-01-11 Cont ID  
Sent By spalmer Date 2008-01-11 Time 10:34 Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 10:34 Sent To B
Notes
2008-01-11 10:34:47TO ROBERT BROWNS DESK

Review Stop I INCOMING/PROCESSING
Rev No 139 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 14:57 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 14:57 Sent To B
Notes
2007-12-13 14:57:39TO "RBROWN' DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 138 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 09:09 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 09:09 Sent To E
Notes
2007-12-13 09:10:08TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 137 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 15:09 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 15:09 Sent To M
Notes
2007-11-27 15:09:37TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 136 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 14:24 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 14:24 Sent To B
Notes
2007-11-15 14:25:14TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 135 Status N Date 2007-11-14 Cont ID  
Sent By adarroug Date 2007-11-14 Time 12:21 Rev Time 0.00
Received By adarroug Date 2007-11-14 Time 12:21 Sent To B
Notes
2007-11-14 12:22:17TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 134 Status N Date 2007-11-09 Cont ID  
Sent By adarroug Date 2007-11-09 Time 15:36 Rev Time 0.00
Received By adarroug Date 2007-11-09 Time 15:36 Sent To B
Notes
2007-11-09 15:36:49TO "RBROWN" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 133 Status N Date 2007-11-08 Cont ID  
Sent By adarroug Date 2007-11-08 Time 10:41 Rev Time 0.00
Received By adarroug Date 2007-11-08 Time 10:41 Sent To  
Notes
2007-11-21 14:28:58TO "COMM" BD#31
2007-11-08 10:41:22WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 132 Status N Date 2007-11-05 Cont ID  
Sent By adarroug Date 2007-11-05 Time 14:32 Rev Time 0.00
Received By adarroug Date 2007-11-05 Time 14:32 Sent To E
Notes
2007-11-05 14:32:32TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 131 Status N Date 2007-11-05 Cont ID  
Sent By adarroug Date 2007-11-05 Time 12:55 Rev Time 0.00
Received By adarroug Date 2007-11-05 Time 12:55 Sent To B
Notes
2007-11-05 12:55:39TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 130 Status N Date 2007-10-30 Cont ID  
Sent By adarroug Date 2007-10-30 Time 11:03 Rev Time 0.00
Received By adarroug Date 2007-10-30 Time 11:03 Sent To B
Notes
2007-10-30 11:04:01TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 129 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 10:35 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 10:35 Sent To B
Notes
2007-10-24 10:35:41TO "RBROWN" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 128 Status N Date 2007-10-22 Cont ID  
Sent By adarroug Date 2007-10-22 Time 10:31 Rev Time 0.00
Received By adarroug Date 2007-10-22 Time 10:31 Sent To E
Notes
2007-10-22 10:31:52TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 127 Status N Date 2007-10-16 Cont ID  
Sent By adarroug Date 2007-10-16 Time 10:19 Rev Time 0.00
Received By adarroug Date 2007-10-16 Time 10:19 Sent To  
Notes
2007-11-05 09:53:58TO "COMM" BD#61
2007-10-16 10:19:50WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 126 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 15:30 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 15:29 Sent To FIRE
Notes
2007-10-15 15:30:21TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 125 Status N Date 2007-10-15 Cont ID  
Sent By adarroug Date 2007-10-15 Time 10:10 Rev Time 0.00
Received By adarroug Date 2007-10-15 Time 10:10 Sent To B
Notes
2007-10-15 10:10:54TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 124 Status N Date 2007-10-11 Cont ID  
Sent By rbrown Date 2007-10-11 Time 17:45 Rev Time 0.00
Received By rbrown Date 2007-10-11 Time 17:45 Sent To  
Notes
2007-10-11 17:49:35BUILDING SUBMITTAL SENT TO R BROWN FOR REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 123 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 14:29 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 14:29 Sent To M
Notes
2007-10-10 14:29:33TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 122 Status N Date 2007-10-09 Cont ID  
Sent By adarroug Date 2007-10-09 Time 13:15 Rev Time 0.00
Received By adarroug Date 2007-10-09 Time 13:15 Sent To E
Notes
2007-10-25 15:50:02TO "COMM" BD#4
2007-10-09 13:16:54WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 121 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 15:21 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 15:21 Sent To B
Notes
2007-09-28 15:21:20TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 120 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 13:08 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 13:08 Sent To E
Notes
2007-09-28 13:09:02TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 119 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 11:49 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 11:49 Sent To B
Notes
2007-09-28 11:51:58TO "RBROWN' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 118 Status N Date 2007-09-27 Cont ID  
Sent By adarroug Date 2007-09-27 Time 16:30 Rev Time 0.00
Received By adarroug Date 2007-09-27 Time 16:30 Sent To  
Notes
2007-09-27 16:31:19TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 117 Status N Date 2007-09-27 Cont ID  
Sent By adarroug Date 2007-09-27 Time 12:28 Rev Time 0.00
Received By adarroug Date 2007-09-27 Time 12:28 Sent To  
Notes
2007-10-19 08:29:49TO "COMM" BD#25
2007-09-27 12:28:41WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 116 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 11:19 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 11:19 Sent To B
Notes
2007-09-24 11:19:28TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 115 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 12:40 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 12:40 Sent To M
Notes
2007-09-06 12:41:04TO "M" BOX#REV

Review Stop I INCOMING/PROCESSING
Rev No 114 Status N Date 2007-09-06 Cont ID  
Sent By adarroug Date 2007-09-06 Time 08:35 Rev Time 0.00
Received By adarroug Date 2007-09-06 Time 08:35 Sent To B
Notes
2007-09-06 08:35:44TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 113 Status N Date 2007-08-31 Cont ID  
Sent By adarroug Date 2007-08-31 Time 09:59 Rev Time 0.00
Received By adarroug Date 2007-08-31 Time 09:59 Sent To B
Notes
2007-08-31 09:59:44TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 112 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 14:44 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 14:44 Sent To  
Notes
2007-08-29 14:45:07TO "COMM" BD#33--REV DATED FOR 8/3/07 THAT WAS WAITING
 FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 111 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 15:51 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 15:51 Sent To B
Notes
2007-08-27 15:52:33TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 110 Status N Date 2007-08-23 Cont ID  
Sent By adarroug Date 2007-08-23 Time 15:52 Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 15:52 Sent To B
Notes
2007-08-23 15:52:50TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 109 Status N Date 2007-08-23 Cont ID  
Sent By adarroug Date 2007-08-23 Time 11:29 Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 11:29 Sent To M
Notes
2007-08-23 11:30:17TO "RREQUIERO" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 108 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 14:11 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 14:11 Sent To B
Notes
2007-08-21 14:11:37TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 107 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 10:33 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 10:33 Sent To B
Notes
2007-08-16 10:34:08TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 106 Status N Date 2007-08-14 Cont ID  
Sent By adarroug Date 2007-08-14 Time 13:17 Rev Time 0.00
Received By adarroug Date 2007-08-14 Time 13:17 Sent To B
Notes
2007-08-14 13:18:18TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 105 Status N Date 2007-08-13 Cont ID  
Sent By adarroug Date 2007-08-13 Time 10:52 Rev Time 0.00
Received By adarroug Date 2007-08-13 Time 10:52 Sent To B
Notes
2007-08-13 10:52:40TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 104 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 14:10 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 14:10 Sent To  
Notes
2007-08-16 15:44:18TO "COMM" BD#61
2007-08-07 19:36:18A SHEETS, ROUTED TO RB INCOMING BOX.
2007-08-06 14:11:33WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 103 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 11:45 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 11:45 Sent To B
Notes
2007-08-02 11:46:17TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 102 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 11:38 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 11:38 Sent To  
Notes
2007-08-14 14:53:30TO "COMM" BD#19
2007-08-02 11:38:31WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 101 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 13:58 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 13:58 Sent To  
Notes
2007-07-30 13:59:07WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 100 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 13:36 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 13:36 Sent To E
Notes
2007-07-30 13:36:24TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 99 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 10:43 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 10:43 Sent To B
Notes
2007-07-30 10:44:16TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 98 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-27 Time 11:32 Rev Time 0.00
Received By adarroug Date 2007-07-27 Time 11:32 Sent To  
Notes
2007-07-27 11:33:10WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 97 Status N Date 2007-07-24 Cont ID  
Sent By adarroug Date 2007-07-24 Time 16:44 Rev Time 0.00
Received By adarroug Date 2007-07-24 Time 16:43 Sent To B
Notes
2007-07-24 16:44:23TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 96 Status N Date 2007-07-19 Cont ID  
Sent By adarroug Date 2007-07-19 Time 08:25 Rev Time 0.00
Received By adarroug Date 2007-07-19 Time 08:25 Sent To M
Notes
2007-07-19 08:25:45TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 95 Status N Date 2007-07-12 Cont ID  
Sent By adarroug Date 2007-07-12 Time 08:57 Rev Time 0.00
Received By adarroug Date 2007-07-12 Time 08:57 Sent To B
Notes
2007-07-12 08:57:34TO "RBROWN" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 94 Status N Date 2007-07-11 Cont ID  
Sent By adarroug Date 2007-07-11 Time 11:41 Rev Time 0.00
Received By adarroug Date 2007-07-11 Time 11:40 Sent To B
Notes
2007-07-11 11:42:22TO "RBROWN" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 93 Status N Date 2007-07-05 Cont ID  
Sent By adarroug Date 2007-07-05 Time 11:16 Rev Time 0.00
Received By adarroug Date 2007-07-05 Time 11:16 Sent To  
Notes
2007-07-17 15:49:16TO "COMM" BD#23
2007-07-05 11:16:33WAITING FOR "COMM"BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 92 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 16:36 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 16:36 Sent To B
Notes
2007-07-03 16:36:56TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 91 Status N Date 2007-06-29 Cont ID  
Sent By adarroug Date 2007-06-29 Time 10:21 Rev Time 0.00
Received By adarroug Date 2007-06-29 Time 10:21 Sent To B
Notes
2007-06-29 10:21:45TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 90 Status N Date 2007-06-27 Cont ID  
Sent By adarroug Date 2007-06-27 Time 10:55 Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 10:55 Sent To B
Notes
2007-06-27 10:55:46TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 89 Status N Date 2007-06-25 Cont ID  
Sent By adarroug Date 2007-06-25 Time 14:38 Rev Time 0.00
Received By adarroug Date 2007-06-25 Time 14:38 Sent To B
Notes
2007-06-25 14:38:29TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 88 Status N Date 2007-06-24 Cont ID  
Sent By adarroug Date 2007-06-24 Time 17:44 Rev Time 0.00
Received By adarroug Date 2007-06-24 Time 17:44 Sent To E
Notes
2007-06-24 17:44:59TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 87 Status N Date 2007-06-22 Cont ID  
Sent By adarroug Date 2007-06-22 Time 11:19 Rev Time 0.00
Received By adarroug Date 2007-06-22 Time 11:19 Sent To B
Notes
2007-06-22 11:20:18TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 86 Status N Date 2007-06-21 Cont ID  
Sent By adarroug Date 2007-06-21 Time 10:35 Rev Time 0.00
Received By adarroug Date 2007-06-21 Time 10:35 Sent To B
Notes
2007-06-21 10:35:30TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 85 Status N Date 2007-06-18 Cont ID  
Sent By adarroug Date 2007-06-18 Time 11:21 Rev Time 0.00
Received By adarroug Date 2007-06-18 Time 11:21 Sent To B
Notes
2007-06-18 11:21:29TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 84 Status N Date 2007-06-11 Cont ID  
Sent By adarroug Date 2007-06-11 Time 08:29 Rev Time 0.00
Received By adarroug Date 2007-06-11 Time 08:29 Sent To B
Notes
2007-06-11 08:29:40TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 83 Status N Date 2007-06-06 Cont ID  
Sent By adarroug Date 2007-06-06 Time 16:17 Rev Time 0.00
Received By adarroug Date 2007-06-06 Time 16:17 Sent To B
Notes
2007-06-06 16:17:38TO "RBROWN" DESK/ 4 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 82 Status N Date 2007-06-04 Cont ID  
Sent By adarroug Date 2007-06-04 Time 09:23 Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 09:23 Sent To B
Notes
2007-06-04 09:24:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 81 Status N Date 2007-05-29 Cont ID  
Sent By adarroug Date 2007-05-29 Time 16:50 Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 16:50 Sent To B
Notes
2007-05-29 16:51:04TO "RBROWN" DESK/ 2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 80 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 10:12 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 10:12 Sent To B
Notes
2007-05-23 10:12:33TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 79 Status N Date 2007-05-22 Cont ID  
Sent By adarroug Date 2007-05-22 Time 16:38 Rev Time 0.00
Received By adarroug Date 2007-05-22 Time 16:38 Sent To B
Notes
2007-05-22 16:39:12TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 78 Status N Date 2007-05-18 Cont ID  
Sent By adarroug Date 2007-05-18 Time 15:32 Rev Time 0.00
Received By adarroug Date 2007-05-18 Time 15:32 Sent To E
Notes
2007-05-18 15:32:53TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 77 Status N Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 10:27 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 10:27 Sent To B
Notes
2007-05-15 10:27:44TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 76 Status N Date 2007-05-04 Cont ID  
Sent By adarroug Date 2007-05-04 Time 10:25 Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 10:25 Sent To B
Notes
2007-05-04 10:25:34TO "RBROWN" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 75 Status N Date 2007-05-03 Cont ID  
Sent By adarroug Date 2007-05-03 Time 15:45 Rev Time 0.00
Received By adarroug Date 2007-05-03 Time 15:45 Sent To B
Notes
2007-05-03 15:45:31TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 74 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 15:48 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 15:48 Sent To  
Notes
2007-05-14 14:29:42TO "COMM" BD#57
2007-05-02 15:49:07WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 73 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 09:38 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 09:38 Sent To B
Notes
2007-05-02 09:39:04TO "RBROWN" DESK/4 SUBMITTALS AND 1 REV

Review Stop I INCOMING/PROCESSING
Rev No 72 Status N Date 2007-04-27 Cont ID  
Sent By adarroug Date 2007-04-27 Time 09:04 Rev Time 0.00
Received By adarroug Date 2007-04-27 Time 09:04 Sent To  
Notes
2007-04-27 09:08:09TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 71 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 11:41 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 11:41 Sent To B
Notes
2007-04-23 11:41:33TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 70 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 16:12 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 16:12 Sent To P
Notes
2007-04-19 16:12:27TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 69 Status N Date 2007-04-18 Cont ID  
Sent By adarroug Date 2007-04-18 Time 16:41 Rev Time 0.00
Received By adarroug Date 2007-04-18 Time 16:41 Sent To B
Notes
2007-04-18 16:41:29TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 68 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 10:02 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 10:02 Sent To B
Notes
2007-04-16 10:02:38TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 67 Status N Date 2007-04-11 Cont ID  
Sent By adarroug Date 2007-04-11 Time 11:00 Rev Time 0.00
Received By adarroug Date 2007-04-11 Time 11:00 Sent To B
Notes
2007-04-11 11:01:28TO "RBROWN" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 66 Status N Date 2007-04-09 Cont ID  
Sent By adarroug Date 2007-04-09 Time 09:43 Rev Time 0.00
Received By adarroug Date 2007-04-09 Time 09:43 Sent To B
Notes
2007-04-09 09:43:54TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 65 Status N Date 2007-04-06 Cont ID  
Sent By spalmer Date 2007-04-06 Time 17:21 Rev Time 0.00
Received By spalmer Date 2007-04-06 Time 17:21 Sent To B
Notes
2007-04-06 17:21:12TO ROBERT BROWN

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2007-04-03 Cont ID  
Sent By spalmer Date 2007-04-03 Time 17:18 Rev Time 0.00
Received By spalmer Date 2007-04-03 Time 17:18 Sent To B
Notes
2007-04-03 17:18:44TWO SUBMITTALS TO ROBERT BROWN

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2007-03-27 Cont ID  
Sent By dpolen Date 2007-03-27 Time 10:31 Rev Time 0.00
Received By dpolen Date 2007-03-27 Time 10:29 Sent To  
Notes
2007-03-27 10:30:12TO ROBERT B. DESK

Review Stop I INCOMING/PROCESSING
Rev No 62 Status N Date 2007-03-26 Cont ID  
Sent By spalmer Date 2007-03-26 Time 18:30 Rev Time 0.00
Received By spalmer Date 2007-03-26 Time 18:30 Sent To P
Notes
2007-03-26 18:30:58TO KEN STEVENS

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 15:11 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 15:11 Sent To B
Notes
2007-03-24 15:11:53TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2007-03-23 Cont ID  
Sent By adarroug Date 2007-03-23 Time 11:53 Rev Time 0.00
Received By adarroug Date 2007-03-23 Time 11:53 Sent To B
Notes
2007-03-23 11:54:16TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2007-03-23 Cont ID  
Sent By adarroug Date 2007-03-23 Time 09:14 Rev Time 0.00
Received By adarroug Date 2007-03-23 Time 09:14 Sent To B
Notes
2007-03-23 09:14:38TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 14:47 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 14:47 Sent To B
Notes
2007-03-16 14:47:30TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 11:55 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 11:55 Sent To M
Notes
2007-03-16 11:55:41TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 11:51 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 11:51 Sent To P
Notes
2007-03-16 11:51:44TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 55 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 11:24 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 11:24 Sent To B
Notes
2007-03-16 11:24:55TO "RBROWN" DESK/2 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 11:20 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 11:20 Sent To B
Notes
2007-03-16 11:20:47TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 11:17 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 11:17 Sent To M
Notes
2007-03-16 11:18:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 11:08 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 11:08 Sent To E
Notes
2007-03-16 11:08:28TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2007-03-16 Cont ID  
Sent By adarroug Date 2007-03-16 Time 10:48 Rev Time 0.00
Received By adarroug Date 2007-03-16 Time 10:48 Sent To P
Notes
2007-03-16 10:48:59TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2007-03-15 Cont ID  
Sent By adarroug Date 2007-03-15 Time 13:44 Rev Time 0.00
Received By adarroug Date 2007-03-15 Time 13:44 Sent To B
Notes
2007-03-15 13:45:10TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2007-03-10 Cont ID  
Sent By adarroug Date 2007-03-10 Time 15:00 Rev Time 0.00
Received By adarroug Date 2007-03-10 Time 15:00 Sent To B
Notes
2007-03-10 15:00:22TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2007-03-09 Cont ID  
Sent By adarroug Date 2007-03-09 Time 13:27 Rev Time 0.00
Received By adarroug Date 2007-03-09 Time 13:27 Sent To B
Notes
2007-03-09 13:27:55TO "RBROWN" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 16:19 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 16:19 Sent To B
Notes
2007-03-06 16:20:11TO "RBROWN" DESK/4 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2007-02-27 Cont ID  
Sent By adarroug Date 2007-02-27 Time 11:36 Rev Time 0.00
Received By adarroug Date 2007-02-27 Time 11:36 Sent To B
Notes
2007-02-27 11:36:45TO "RBROWN" BOX/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 11:35 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 11:35 Sent To B
Notes
2007-02-22 11:36:32TO "RBROWN" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2007-02-14 Cont ID  
Sent By adarroug Date 2007-02-14 Time 14:56 Rev Time 0.00
Received By adarroug Date 2007-02-14 Time 14:56 Sent To B
Notes
2007-02-14 14:57:05TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2007-02-12 Cont ID  
Sent By adarroug Date 2007-02-12 Time 09:22 Rev Time 0.00
Received By adarroug Date 2007-02-12 Time 09:22 Sent To B
Notes
2007-02-12 09:22:33TO "RBROWN" DESK/6SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 42 Status F Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 08:16 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 08:16 Sent To B
Notes
2007-02-08 08:17:08TO "RBROWN" DESK/ 2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2007-02-06 Cont ID  
Sent By adarroug Date 2007-02-06 Time 11:13 Rev Time 0.00
Received By adarroug Date 2007-02-06 Time 11:12 Sent To B
Notes
2007-02-06 11:13:24TO "RBROWN" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 15:15 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 15:15 Sent To B
Notes
2007-02-01 15:15:22TO "RBROWN" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2007-01-29 Cont ID  
Sent By adarroug Date 2007-01-29 Time 16:34 Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 16:34 Sent To B
Notes
2007-01-29 16:35:22TO "RBROWN" DESK/ 3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2007-01-18 Cont ID  
Sent By adarroug Date 2007-01-18 Time 16:34 Rev Time 0.00
Received By adarroug Date 2007-01-18 Time 16:34 Sent To B
Notes
2007-01-18 16:35:00TO "RBROWN" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2007-01-17 Cont ID  
Sent By adarroug Date 2007-01-17 Time 16:21 Rev Time 0.00
Received By adarroug Date 2007-01-17 Time 16:20 Sent To B
Notes
2007-01-17 16:21:05TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2007-01-17 Cont ID  
Sent By adarroug Date 2007-01-17 Time 16:16 Rev Time 0.00
Received By adarroug Date 2007-01-17 Time 16:16 Sent To P
Notes
2007-01-17 16:16:36TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2007-01-17 Cont ID  
Sent By adarroug Date 2007-01-17 Time 10:04 Rev Time 0.00
Received By adarroug Date 2007-01-17 Time 10:04 Sent To B
Notes
2007-01-17 10:05:15TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 19:10 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 19:10 Sent To B
Notes
2007-01-09 19:10:33TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2007-01-04 Cont ID  
Sent By adarroug Date 2007-01-04 Time 11:40 Rev Time 0.00
Received By adarroug Date 2007-01-04 Time 11:40 Sent To B
Notes
2007-01-04 11:40:33TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2007-01-03 Cont ID  
Sent By adarroug Date 2007-01-03 Time 17:37 Rev Time 0.00
Received By adarroug Date 2007-01-03 Time 17:37 Sent To B
Notes
2007-01-03 17:38:16TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 15:53 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 15:53 Sent To B
Notes
2006-12-27 15:53:30TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2006-12-26 Cont ID  
Sent By adarroug Date 2006-12-26 Time 14:30 Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 14:30 Sent To B
Notes
2006-12-26 14:31:24TO "RBROWN" DESK/ 2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2006-12-20 Cont ID  
Sent By adarroug Date 2006-12-20 Time 11:33 Rev Time 0.00
Received By adarroug Date 2006-12-20 Time 11:33 Sent To B
Notes
2006-12-20 11:33:53TO "RBROWN" DESK/ 2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2006-12-19 Cont ID  
Sent By adarroug Date 2006-12-19 Time 09:07 Rev Time 0.00
Received By adarroug Date 2006-12-19 Time 09:07 Sent To P
Notes
2006-12-19 09:07:24TO"P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2006-12-19 Cont ID  
Sent By adarroug Date 2006-12-19 Time 08:59 Rev Time 0.00
Received By adarroug Date 2006-12-19 Time 08:59 Sent To E
Notes
2006-12-19 09:00:50TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2006-12-19 Cont ID  
Sent By adarroug Date 2006-12-19 Time 08:58 Rev Time 0.00
Received By adarroug Date 2006-12-19 Time 08:58 Sent To M
Notes
2006-12-19 08:58:37TO "M" BOX/2 REV

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2006-12-19 Cont ID  
Sent By adarroug Date 2006-12-19 Time 08:53 Rev Time 0.00
Received By adarroug Date 2006-12-19 Time 08:53 Sent To  
Notes
2007-01-11 10:02:58TO "COMM" BD#30
2006-12-19 08:54:20WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 17:41 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 17:41 Sent To E
Notes
2006-12-17 17:41:30TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 14:26 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 14:26 Sent To B
Notes
2006-12-17 14:26:44TO "RBROWN" DESK/5 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2006-12-12 Cont ID  
Sent By adarroug Date 2006-12-12 Time 15:18 Rev Time 0.00
Received By adarroug Date 2006-12-12 Time 15:18 Sent To B
Notes
2006-12-12 15:19:07TO "RBROWN" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2006-12-07 Cont ID  
Sent By adarroug Date 2006-12-07 Time 11:45 Rev Time 0.00
Received By adarroug Date 2006-12-07 Time 11:44 Sent To B
Notes
2006-12-07 11:45:24TO "RBROWN' DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2006-12-06 Cont ID  
Sent By adarroug Date 2006-12-06 Time 13:05 Rev Time 0.00
Received By adarroug Date 2006-12-06 Time 13:05 Sent To B
Notes
2006-12-06 13:06:16TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 10:31 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 10:31 Sent To B
Notes
2006-12-05 10:31:52TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 11:16 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 11:16 Sent To B
Notes
2006-12-01 11:16:31TO "RBROWN" DESK/REV-TRASH CHUTE

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 11:13 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 11:13 Sent To B
Notes
2006-12-01 11:14:09TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2006-11-27 Cont ID  
Sent By adarroug Date 2006-11-21 Time 16:07 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 16:08 Sent To B
Notes
2006-11-20 14:22:59TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 11:42 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 11:42 Sent To B
Notes
2006-11-17 11:42:28TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-11-15 Cont ID  
Sent By adarroug Date 2006-11-15 Time 11:10 Rev Time 0.00
Received By adarroug Date 2006-11-15 Time 11:10 Sent To B
Notes
2006-11-15 11:10:59TO "RBROWN" DESK/7 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-11-06 Cont ID  
Sent By adarroug Date 2006-11-06 Time 10:22 Rev Time 0.00
Received By adarroug Date 2006-11-06 Time 10:22 Sent To B
Notes
2006-11-06 10:22:28TO "RBROWN" DESK/ 2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-10-25 Cont ID  
Sent By adarroug Date 2006-10-25 Time 09:07 Rev Time 0.00
Received By adarroug Date 2006-10-25 Time 09:07 Sent To B
Notes
2006-10-25 09:07:43TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-10-17 Cont ID  
Sent By adarroug Date 2006-10-17 Time 09:53 Rev Time 0.00
Received By adarroug Date 2006-10-17 Time 09:53 Sent To B
Notes
2006-10-17 09:54:44TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-10-12 Cont ID  
Sent By adarroug Date 2006-10-12 Time 15:26 Rev Time 0.00
Received By adarroug Date 2006-10-12 Time 15:26 Sent To B
Notes
2006-10-12 15:26:38TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-09-29 Cont ID  
Sent By adarroug Date 2006-09-29 Time 09:34 Rev Time 0.00
Received By adarroug Date 2006-09-29 Time 09:34 Sent To B
Notes
2006-09-29 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-09-22 Cont ID  
Sent By adarroug Date 2006-09-22 Time 15:27 Rev Time 0.00
Received By adarroug Date 2006-09-22 Time 15:27 Sent To B
Notes
2006-09-22 00:00:00TO "RBROWN" DESK/5 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-22 Cont ID  
Sent By adarroug Date 2006-09-22 Time 09:06 Rev Time 0.00
Received By adarroug Date 2006-09-22 Time 09:06 Sent To B
Notes
2006-09-22 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-09 Cont ID  
Sent By adarroug Date 2006-09-09 Time 16:17 Rev Time 0.00
Received By adarroug Date 2006-09-09 Time 16:17 Sent To B
Notes
2006-09-09 00:00:00TO "RBROWN" DESK/ 6 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-28 Cont ID  
Sent By adarroug Date 2006-08-28 Time 08:43 Rev Time 0.00
Received By adarroug Date 2006-08-28 Time 08:40 Sent To B
Notes
2006-08-28 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-18 Cont ID  
Sent By adarroug Date 2006-08-18 Time 09:30 Rev Time 0.00
Received By adarroug Date 2006-08-18 Time 09:30 Sent To B
Notes
2006-08-18 00:00:00SUBMITTAL TO "COMM" BD#47 W/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 11:05 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 11:05 Sent To  
Notes
2006-08-11 00:00:00TO "COMM" BD#47
2006-08-08 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-27 Cont ID  
Sent By adarroug Date 2006-04-27 Time 15:25 Rev Time 0.00
Received By adarroug Date 2006-04-27 Time 15:25 Sent To  
Notes
2006-05-22 00:00:00TO "COMM" BD#13/ROLLED PLANS BY
 "LMARTINEZ" OFFICE
2006-04-27 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-20 Cont ID  
Sent By rbrown Date 2006-02-20 Time 23:30 Rev Time 0.00
Received By rbrown Date 2005-09-28 Time 18:42 Sent To  
Notes
2005-10-03 00:00:00TO "COMM" BD#14/PLANS ON RACK
2005-09-28 00:00:00WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-09-10 Cont ID  
Sent By rkussner Date 2008-09-10 Time 16:52 Rev Time 0.00
Received By rkussner Date 2008-09-10 Time 16:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 24 Status P Date 2008-03-31 Cont ID  
Sent By rregueir Date 2008-03-31 Time 16:22 Rev Time 0.00
Received By rregueir Date 2008-03-31 Time 13:13 Sent To PC
Notes
2008-03-31 16:26:38ADDED NEW PAGE AC-30 WITH DERM APPROVAL FOR 1500 GALLON
 FUEL TANK.

Review Stop M MECHANICAL (A/C)
Rev No 23 Status P Date 2008-03-25 Cont ID  
Sent By rregueir Date 2008-03-25 Time 13:33 Rev Time 0.00
Received By rregueir Date 2008-03-25 Time 13:33 Sent To PC
Notes
2008-03-25 13:33:53PG AC-11 REV.14 OK

Review Stop M MECHANICAL (A/C)
Rev No 22 Status F Date 2008-03-25 Cont ID  
Sent By rregueir Date 2008-03-25 Time 13:33 Rev Time 0.00
Received By rregueir Date 2008-03-25 Time 13:30 Sent To PC
Notes
2008-03-25 13:32:59PG AC-30 NEW 1500 GALLON DIESEL STORAGE TANK FOR
 EMERGENCY GENERATOR WITH ALLL RELATED FUEL PIPING. ALL
 ABOVE-GROUND FUEL STORAGE TANKS >550 GALLONS SHALL BE
 SUBMITTED TO PALM BEACH COUNTY DERM FOR PRIOR APPROVAL.
 FOR MORE INFORMATION PLEASE CONTACT DERM AT
 561-233-2400.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 21 Status P Date 2008-03-25 Cont ID  
Sent By rregueir Date 2008-03-25 Time 13:28 Rev Time 0.00
Received By rregueir Date 2008-03-25 Time 10:32 Sent To PC
Notes
2008-03-25 13:28:14PG AC-5 REV.17 RESTAMP. 3 COPIES RETURNED TO
 CONTRACTOR
 PG AC-19 REV.2 RESTAMP. 3 COPIES RETURNED TO CONTRACTOR

Review Stop M MECHANICAL (A/C)
Rev No 20 Status P Date 2008-02-16 Cont ID  
Sent By rregueir Date 2008-02-16 Time 15:20 Rev Time 0.00
Received By rregueir Date 2008-02-16 Time 15:18 Sent To PC
Notes
2008-02-16 15:20:40REVISED PAGES AS FOLLOWS:
 AC-1 REV.12
 AC-4 REV.15
 AC-5 REV.17
 AC-6 REV.9
 AC-7 REV.21
 AC-8 REV.2
 AC-19 REV.2
  

Review Stop M MECHANICAL (A/C)
Rev No 19 Status P Date 2008-02-16 Cont ID  
Sent By rregueir Date 2008-02-16 Time 13:57 Rev Time 0.00
Received By rregueir Date 2008-02-16 Time 13:53 Sent To  
Notes
2008-02-16 13:57:47PG AC-5 REVISION 16

Review Stop M MECHANICAL (A/C)
Rev No 18 Status P Date 2007-12-24 Cont ID  
Sent By tgordon Date 2007-12-24 Time 08:51 Rev Time 0.30
Received By tgordon Date 2007-12-24 Time 08:51 Sent To E
Notes
2007-12-24 08:58:23** SUBMITTAL FOR SAUNA **
 *** PROVISO ***
 1) A VENTILATION OPENING INTO THE SAUNA ROOM SHALL BE
 PROVIDED. THE OPENING SHALL BE NOT LESS THAN 4 INCHES
 BY 8 INCHES (102 MM BY 203 MM) LOCATED NEAR THE TOP OF
 THE DOOR INTO THE SAUNA ROOM. PER 2004 FBC/M 914.5.
  
 2)WARNING NOTICE.
 THE FOLLOWING PERMANENT NOTICE, CONSTRUCTED OF APPROVED
 MATERIAL, SHALL BE MECHANICALLY ATTACHED TO THE SAUNA
 ROOM ON THE OUTSIDE:
 WARNING: DO NOT EXCEED 30 MINUTES IN SAUNA. EXCESSIVE
 EXPOSURE CAN BE HARMFUL TO HEALTH. ANY PERSON WITH POOR
 HEALTH SHOULD CONSULT A PHYSICIAN BEFORE USING SAUNA.
 THE WORDS SHALL CONTRAST WITH THE BACKGROUND AND THE
 WORDING SHALL BE IN LETTERS NOT LESS THAN 0.25-INCH
 (6.4 MM) HIGH. PER 2004 FBC/M 914.5.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
  
 ** 4-30-08UPDATE TO PROVISO. IF THE SAUNA HEATER IS
 ELECTRIC AND NOT FUEL BURNING THEN VENTILATION WILL NOT
 BE REQUIRED AND SAUNA SHALL BE INSTALLED PER
 MANUFACTURES INSTRUCTIONS, PER 2004 FBC/M 304.1. **
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 17 Status P Date 2007-12-07 Cont ID  
Sent By rregueir Date 2007-12-07 Time 08:21 Rev Time 0.00
Received By rregueir Date 2007-12-06 Time 16:20 Sent To PC
Notes
2007-12-07 08:24:18REVISED MECHANICAL AS FOLLOWS:
 AC-1 REV.11
 AC-2 REV.8
 AC-3 REV.7
 AC-4 REV.15
 AC-13 REV.5
 AC-24 REV.3

Review Stop M MECHANICAL (A/C)
Rev No 16 Status P Date 2007-10-20 Cont ID  
Sent By rregueir Date 2007-10-20 Time 19:28 Rev Time 0.00
Received By rregueir Date 2007-10-20 Time 19:21 Sent To  
Notes
2007-10-20 19:29:38PG AC-13 REV.4
 PROVISO CONDITION HAS BEEN SATISFIED.

Review Stop M MECHANICAL (A/C)
Rev No 15 Status   Date 2007-10-06 Cont ID  
Sent By rregueir Date 2007-10-06 Time 09:23 Rev Time 0.00
Received By rregueir Date 2007-10-06 Time 09:20 Sent To  
Notes
2007-10-06 09:24:17NO REVIEW THIS STOP. CHECK-IN WAS AN ERROR. THIS REVIEW
 CHECKED IN ON 10/5/07.RJR

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date 2007-10-06 Cont ID  
Sent By rregueir Date 2007-10-06 Time 14:50 Rev Time 0.00
Received By rregueir Date 2007-10-05 Time 09:00 Sent To PC
Notes
2007-10-06 14:50:17AC-1 REV.10
 AC-7 REV.18,19
 AC-9 REV.5
 AC-12 REV.2
 AC-13 REV.3 W/ PROVISO
 AC-14 REV.14
 AC-15 REV.3
 AC-16 REV.5
 AC-17 REV.2
 AC-23 REV.15,16,17
 AC-24 REV.3
  
 **************PROVISO*****************
 AC-13 UNIT B-1: 6X6 DROP IN BATHROOM IS NO LONGER SHOWN
 TAPPING INTO SUPPLY TRUNK LINE. CORRECT AND RESUBMIT.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2007-08-24 Cont ID  
Sent By rregueir Date 2007-08-24 Time 13:48 Rev Time 0.00
Received By rregueir Date 2007-08-24 Time 09:12 Sent To  
Notes
2007-08-24 13:54:19MECH REVS PAGES: AC-1, AC-5, AC-6, AC-7, AC-8, AC-9,
 AC-10, AC-18, AC-19, AC-21, AC-22, AC-23, AC-24, AC-25,
 AC-29

Review Stop M MECHANICAL (A/C)
Rev No 12 Status F Date 2007-08-18 Cont ID  
Sent By rregueir Date 2007-08-18 Time 13:41 Rev Time 0.00
Received By rregueir Date 2007-08-18 Time 13:40 Sent To E
Notes
2007-08-18 13:40:57AN ATTEMPT WAS MADE TO REVIEW ALL MECHANICAL REVISIONS
 CURRENTY IN THIS OFFICE. A REVIEW COULD NOT BE
 COMPLETED AT THIS TIME. THERE ARE SOME PAGES WHICH
 APPEAR 3 TIMES IN 3 DIFFERENT SUBMITTALS AND IN 3
 DIFFERENT STAGES OF BEING REVISED WITH CHANGES THAT ARE
 NOT IN DATED ORDER. THESE MECHANICAL REVISIONS WERE
 SUBMITTED ON THE FOLLOWING DATES:
  
 7/17/07, 7/27/07 AND 7/31/07
  
 PLEASE TAKE ALL THREE OF THESE AND CONSOLIDATE THEM
 INTO A CONCISE, UP-TO-DATE SET OF REVISIONS TO BE
 REVIEWED AND INCORPORATED INTO THE PERMIT SET OF
 PLANS.
  
 THE 7/27 SUBMITTAL HAS ACCOMPANYING PLUMBING PLANS. THE
 MECHANICAL PLANS HAVE BEEN REMOVED AND THE PLUMBING
 PLANS ARE ROUTED TO THE PLUMBING REVIEWER'S INBOX.
  
 THE 7/31 SUBMITTAL HAS ACCOMPANYING ELECTRICAL PLANS.
 THE MECHANICAL PLANS HAVE BEEN REMOVED AND THE PLUMBING
 PLANS ARE ROUTED TO THE ELECTRICAL REVIEWER'S INBOX.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 11 Status F Date 2007-08-18 Cont ID  
Sent By rregueir Date 2007-08-18 Time 13:39 Rev Time 0.00
Received By rregueir Date 2007-08-18 Time 10:18 Sent To P
Notes
2007-08-18 13:38:59AN ATTEMPT WAS MADE TO REVIEW ALL MECHANICAL REVISIONS
 CURRENTY IN THIS OFFICE. A REVIEW COULD NOT BE
 COMPLETED AT THIS TIME. THERE ARE SOME PAGES WHICH
 APPEAR 3 TIMES IN 3 DIFFERENT SUBMITTALS AND IN 3
 DIFFERENT STAGES OF BEING REVISED WITH CHANGES THAT ARE
 NOT IN DATED ORDER. THESE MECHANICAL REVISIONS WERE
 SUBMITTED ON THE FOLLOWING DATES:
  
 7/17/07, 7/27/07 AND 7/31/07
  
 PLEASE TAKE ALL THREE OF THESE AND CONSOLIDATE THEM
 INTO A CONCISE, UP-TO-DATE SET OF REVISIONS TO BE
 REVIEWED AND INCORPORATED INTO THE PERMIT SET OF
 PLANS.
  
 THE 7/27 SUBMITTAL HAS ACCOMPANYING PLUMBING PLANS. THE
 MECHANICAL PLANS HAVE BEEN REMOVED AND THE PLUMBING
 PLANS ARE ROUTED TO THE PLUMBING REVIEWER'S INBOX.
  
 THE 7/31 SUBMITTAL HAS ACCOMPANYING ELECTRICAL PLANS.
 THE MECHANICAL PLANS HAVE BEEN REMOVED AND THE PLUMBING
 PLANS ARE ROUTED TO THE ELECTRICAL REVIEWER'S INBOX.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2007-06-13 Cont ID  
Sent By rregueir Date 2007-06-13 Time 13:14 Rev Time 0.00
Received By rregueir Date 2007-06-13 Time 13:11 Sent To  
Notes
2007-06-13 13:14:50RECEIVED REPLACEMENT LETTERS WHICH WERE PREVIOUSLY
 REVIEWED ON 6/5/07. LETTER IS NOTICE OF ACCEPTANCE BY
 THE ENGINEER OF RECORD FOR THE TERMINATION OF RETURN
 AIR DUCT IN THE A/C CLOSET WITH A MINIMUM OF 3 INCHES
 CLEARANCE FROM THE SUPPLY DUCT TO ALLOW PROPER RETURN
 AIR FLOW.
  
 RJR

Review Stop M MECHANICAL (A/C)
Rev No 9 Status F Date 2007-06-05 Cont ID  
Sent By rregueir Date 2007-06-05 Time 13:13 Rev Time 0.00
Received By rregueir Date 2007-06-05 Time 13:13 Sent To PC
Notes
2007-06-05 13:15:28SUBMITTAL LETTER FROM ENGINEER REGARDING RETURN AIR
 CLEARANCE IN APARTMENT A/C CLOSETS.
  
 THIS LETTER IS NOT ACCEPTED. PLEASE SUBMIT 3 COPIES OF
 THE LETTER EACH SIGNED AND SEALED BY THE ENGINEER OF
 RECORD WITH THE ENGINEER'S ORIGINAL SIGNATURE, NOT
 PHOTOCOPIED SIGNATURES.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2007-06-01 Cont ID  
Sent By rregueir Date 2007-06-01 Time 15:49 Rev Time 0.00
Received By rregueir Date 2007-05-30 Time 09:56 Sent To  
Notes
2007-06-01 11:42:15PAGES AC-4 AND AC-10 OK, REMAINING PAGES DENIED WITH
 COMMENTS. SEE BELOW:
  
 1. AC-5: ONLY ONE OF THE TWO DUCTS PENETRATING JANITOR
 CLOSET WALL IS PROTECTED WITH FIRE DAMPER. PLEASE SHOW
 BOTH TO BE PROTECTED IN ACCORDANCE WITH FBC,M 607.1.2.
  
 2. AC-9: WHAT IS THE DESIGNTION FOR THE ROOFTOP EXHAUST
 FAN ABOVE RISER TX-14? THIS INFORMATION WAS REMOVED
 FROM PREVIOUS PLANS.
  
 3. AC-18: REVISION 21 REMOVED THE NOTE FOR 2 HOUR RATED
 DUCT, BUT EACH RISER STILL HAS A NOTE CALLING FOR FIRE
 RATED DUCT. PLEASE CLARIFY. IS THE DUCT TO BE RATED OR
 NOT?
  
 4. AC-18: REVISION 20, PLEASE SHOW HOW HORIZONTAL
 ASSEMBLY PENETRATION AT BOTTOM OF TX-22 IS TO BE
 PROTECTED PER FBC CH.705.
  
 5. AC-19: EQUIPMENT DESIGNATION ON THIS PAGE DOES NOT
 MATCH WITH RISERS BEING SERVED. EXAMPLE: REVISION SHOWS
 PAC 1 AND 2 FEEDING RISER P/A 1. HOWEVER, REVISED PG
 AC-10 SHOWS PAC-1 FEEDING RISER P/A 1 AND PAC-2 FEEDING
 RISER P/A 4. PLEASE COORDINATE DRAWINGS ACCORDINGLY.
  
 6. AC-7: PLEASE CHANGE PAC-9 REFERENCES TO PAC-5 IN
 CONJUNCTION WITH REVISION 17.
  
 7. AC-21 AND 22: ISO-PADS, IF LOCATED IN RETURN AIR
 PLENUMS, SHALL BE NON COMBUSTIBLE OR MEET THE 25/50
 FLAME SPREAD/SMOKE DEVELOPMENT INDEX PER FBC,M
 602.2.1.
  
 8. AC-22: RISER 31 SHOWS PAC-9 ON ROOF. PAC-9 WAS
 RENAMED PAC-5 IN REVISION 17 ON PAGE AC-7. PLEASE
 COORDINATE DRAWINGS.
  
 9. AC-23: EF-13,14,15,28 ARE ALL MARKED AS PART OF
 REVISION 11, BUT THEY DO NOT APPEAR AS PART OF REVISION
 11 ON THE PREVIOUS AC-23 WHICH WAS REVIEWED ON SEPT 6,
 2006. PLEASE MARK ALL REVISIONS CORRECTLY BASED ON WHEN
 THEY ARE FIRST ADDED TO PLANS.
  
 10. AC-23: EF-28 ON SCHEDULE SHOWS 400 CFM, BUT FLOOR
 PLAN SHOWS 450. WHICH IS CORRECT? EF-29 ON SCHEDULE
 SHOWS 900 CFM, BUT FLOOR PLAN SHOWS 800. WHICH IS
 CORRECT?
  
 11. AC-24: WHY ARE AC-12,13,14 CROSSED OUT ON HEAT PUMP
 SCHEDULE? SIZES AND OTHER RATINGS HAVE ALSO CHANGED FOR
 THESE UNITS, BUT THEY ARE NOT SHOWN AS HAVING BEEN
 REVISED. PLEASE CLARIFY.
  
 12. AC-25: DETAIL FOR CONDENSATE OVERFLOW PROTECTION: A
 FLOAT SWITCH MAY BE INSTALLED INSIDE THE UNIT, BUT A
 FLOATSWITCH IS STILL REQUIRED IN THE AUXILIARY DRAIN
 PAN UNDER THE UNIT PER FBC,M 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2007-03-27 Cont ID  
Sent By rregueir Date 2007-03-27 Time 09:32 Rev Time 0.00
Received By rregueir Date 2007-03-27 Time 08:17 Sent To PC
Notes
2007-03-27 09:31:57REVISED PAGE AC-5
  
 -------------------PROVISO------------------
  
 DUCTS PENETRATING RATED ASSEMBLIES IN HVAC PUMP ROOM
 AND JANITOR'S CLOSET APPEAR TO BE MISSING FIRE DAMPERS.
 PLEASE CORRECT AND RESUBMIT PRIOR TO INSPECTION.
  
 RONALD J REGUEIRO
 561-805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2007-03-22 Cont ID  
Sent By rregueir Date 2007-03-22 Time 18:51 Rev Time 0.00
Received By rregueir Date 2007-03-19 Time 15:09 Sent To  
Notes
2007-03-22 18:51:38DENIED
  
 PAGES AC-4 AND AC-7
  
 COMMENTS FOR THIS REVIEW ARE NUMBERED TO CORRELATE WITH
 PREVIOUS PLAN REVIEW COMMENTS FOR CONTINUITY.
  
 1. OK
  
 2. RESPONSE TO THIS COMMENT STATES "NO CHANGE. NOT PART
 OF THIS REV." IF THAT IS THE CASE, PLEASE REMOVE THE
 CLOUD AND THE DELTA-12 DESIGNATION. FBC 106.1.3.
  
 3. AC-13 WAS MISTAKENLY OMITTED FROM THIS COMMENT.
 THERE ARE FOUR UNPROTECTED OPENINGS RESULTING FROM DUCT
 PENETRATIONS RELATED TO THIS SYSTEM. PLEASE SEE REVISED
 ARCHITECTURAL DRAWING A-2.4.5 REV. 6 FOR LOCATIONS OF
 ALL RATED WALLS WHICH MAY BE AFFECTED BY BY THESE DUCT
 SYSTEMS. ALL SUCH OPENINGS ARE TO BE PROTECTED PER
 FBC,M 607.1.2.
  
 4. THIS AREA IS PART OF THE REVISION AS EF 28 AND
 RELATED DUCTS DO NOT APPEAR ON THE PREVIOUSLY REVIEWED
 PLAN (SEE REVISION 11 DATED 2/24/06). THE ADDED WORK ON
 THIS PAGE MAKES IT PART OF THIS REVISION EVEN IF IT IS
 INCORRECTLY DESIGNATED AS BEING PART OF A PREVIOUS
 REVISION. PLEASE CORRECT AND RESUBMIT. FBC 106.1.3.
  
 5. OK
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2007-02-09 Cont ID  
Sent By rregueir Date 2007-02-09 Time 08:40 Rev Time 0.00
Received By rregueir Date 2007-02-07 Time 09:58 Sent To  
Notes
2007-02-09 08:56:54-----------------DENIED----------------
  
 1. PG AC-4: EF-29 MAY NOT DISCHARGE INTO SHAFT GE3.
 THIS SHOULD BE AN INDIPENDENT SYSTEM DISCHARGING
 DIRECTLY TO THE OUTDOORS PER FBC,M 501.2 AND 501.3.
  
 2. PG AC-4: REVISION DELTA12 DATED 9/22/06 - I AM
 UNABLE TO DETERMINE ANY CHANGE FROM PREVIOUS PLAN.
 PLEASE CLARIFY.
  
 3. PG AC-7: BASED ON REVISED ARCHITECTURAL PAGE A-2.4.5
 DATED 11/17/06, THE DUCT SYSTEM FOR AC-14 HAS SEVERAL
 UNPROTECTED OPENINGS IN RATED WALLS. PLEASE SHOW HOW
 THESE OPENINGS WILL BE PROTECTED IN THE RATED
 ASSEMBLIES PER FBC,M 607.1.2.
  
 4. PG AC-7: ELEVATOR LOBBY AND STORAGE HVAC PLAN - THIS
 AREA IS MARKED AS REVISION DELTA11 BUT IT DOES NOT
 APPERAR ON PG AC-7 DATED 2/24/06 WHERE DELTA 11
 ORIGINATED. PLEASE CLARIFY. SAME CONDITION OCCURS ON PG
 AC-23 REGARDING THE ADDITION OF EF 13,14,15 TO
 SCHEDULE.
  
 5. AC-7: ELEVATOR LOBBY SYSTEM AC-15 HAS SEVERAL
 UNPROTECTED OPENINGS WHERE DUCTS PENETRATE RATED WALLS
 AS SHOWN ON REVISED PAGE A-2.4.3. PLEASE SHOW HOW HESE
 OPENINGS WILL BE PROTECTED PER FBC,M 607.1.2.
  
 RONALD J REGUEIRO
 561-805-6734
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-11-16 Cont ID  
Sent By pkrauss Date 2006-11-16 Time 07:30 Rev Time 0.00
Received By pkrauss Date 2006-11-16 Time 07:30 Sent To  
Notes
2006-11-16 07:47:24PROVISO:
 DRYER EXHAUST SHALL NOT EXCEED THE MANUFACTURER'S
 MAXIMUM LENGTH AS INDICATED IN THE INSTALLATION
 INSTRUCTIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-23 Cont ID  
Sent By pkrauss Date 2006-08-23 Time 10:06 Rev Time 0.00
Received By pkrauss Date 2006-08-21 Time 15:31 Sent To  
Notes
2006-08-23 00:00:00PROVISO:
 RESPONSE TO COMMENT #3:ELEVATION
 PROVIDED ON PLAN SHEET AC-5.PLEASE
 NOTE, EXHAUST FROM EF-23 SHALL NOT
 TERMINATE IN A MANNER THAT NOXIOUS
 CONTAMINANTS MY BE DRAWN BACK INTO THE
 FRESH AIR INTAKE (INTAKE LOUVER).
 PLEASE PROVIDE CO SENSOR IN THIS ROOM.
  
 RESPONSE TO COMMENT #11: PLAN SHEET AC-4
 VENTLATION FOR THE POOL EQUIPMENT ROOM
 #1 MAKE-UP AIR AND THE EXHAUST AIR WILL
 BE INTO THE GARAGE.PLEASE PROVIDE CO
 SENSOR IN THIS ROOM.
  
 PLAN SHEET AC-7 TERMINATION OF EF-12 IS
 WITHIN 3FT THE POOL EQUIPMENT ROOM #2.
 PER 2001 FMC 401.5 OPENING LOCATION FOR
 EXHAUST AND INTAKES SHALL BE LOCATED A
 MINIMUM OF 10 FT FROM BUILDINGS ON THE
 SAME LOT.
  
 RESPONSE TO COMMENT #19:INIDCATES
 GYPSUM BOARD OVER EXPOSED SURFACES OF
 THE DOOR.THIS IS NOT ACCEPTABLE.
 PLEASE PROVIDE SOLUTION / SUBMITTAL
 WITHIN 60 DAYS OF THE PERMIT ISSUANCE.
  
 COMMENT 20:THE FOLLOWING RESIDENTIAL
 HEAT PUMPS AC-7 & AC-8 ARE REQUIRED TO
 HAVE FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 OR BY AREA SMOKE DETECTORS PER 2001 FMC
 606.2.1 & 606.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-11 Cont ID  
Sent By pkrauss Date 2006-07-06 Time 13:36 Rev Time 0.00
Received By pkrauss Date 2006-07-06 Time 09:44 Sent To  
Notes
2006-07-06 00:00:00 
 RESPONSE TO COMMENTS FROM REVIEW DATED
 12/28/05
  
 COMMENT #1 - OK
 COMMENT #2 - OK (SEE COMMENT #3)
  
 COMMENT #3 - REPONSE INDICATES SHEET
 AC-5 PROVIDES MUFFLER ELEVATION.PLAN
 ONLY INDICATES MUFFLER EXHAUST TO
 TERMINATE A MINIMUM OF 10 FT FROM O/A
 INTAKES.PLEASE PROVIDE ELEVATION FROM
 THE ADJOINGING GRADE LEVEL.PLEASE
 NOTE, MUFFLER AND EF-23 EXHAUST
 TERMINATIONS ARE WITHIN 10 FT OF THE
 FRESH AIR INTAKE TO THE GENERATOR ROOM.
  
 COMMENT #4 - OK - PLEASE PROVIDE
 INFORMATION ON WHAT WILL BE STORED IN
 THE JANITOR CLOSET #1.
  
 COMMENT #5 - OK FOR THE COMMON AREAS
 ONLY.PLEASE PROVIDE O/A CALCULATIONS
 FOR THE RESIDENCE IN ACCORDANCE WITH
 2001 FBC 403.3, VENTILATION SYSTEMS FOR
 OTHER THAN R-E (ONE & TWO FAMILY
 DWELLINGS), SHALL BE DESIGNED TO HAVE
 THE CAPACITY TO SUPPLY THE MINIMUM
 OUTDOOR AIR FLOW RATE DETERMINED IN
 ACCORDANCE WITH TABLE 403.3.
  
 COMMENT #6 - OK
 COMMENT #7 - OK
 COMMENT #8 - OK
 COMMENT #9 - OK
 COMMENT #10 - PLAN SHEET AC-14 UNIT C-5,
 PLEASE NOTE, RETURN AIR TO BE EQUAL TO
 SUPPLY INTO THAT AREA.R/A SHALL BE A
 MINIMUM OF 8".
  
 COMMENT #11 - PLAN SHEET AC-4
 VENTILATION FOR THE POOL EXHAUST AND AIR
 MAKE-UP ARE TERMINATING IN THE ENCLOSED
 GARAGE.GARAGE VENTILATION IS NOT
 CONTINUOUS, THEREFORE HOW WILL THIS
 APPLICATION PROVIDE FRESH AIR INTO THIS
 ROOM.PLAN SHEET AC-7 THE POOL
 EQUIPMENT ROOM LOUVERED DOOR APPEARS TO
 BE WITHIN 3FT OF THE TERMINATION OF
 EF-12.PLEASE INDICATE WHAT CHEMICALS &
 THE AMOUNT THAT WILL BE STORED IN WHICH
 EQUIPMENT ROOM.
  
 COMMENT #12 - OK, PLEASE NOTE, RESPONSE
 INDICATES COMBUSTION AIR CALCULATIONS
 ARE INDICATED ON PLAN SHEET AC-9 &
 AC-11.THERE ARE NO COMBUSTION AIR
 CALCS ON AC-9 BUT AC-7 INSTEAD.
  
 COMMENT #13 - OK, SEE COMMENT 12.
  
 COMMENT #14 - OK
 COMMENT #15 - PLAN SHEET AC-29, PROPOSED
 SMOKE CONTROL SYSTEM.PLEASE INDICATE
 WHICH METHOD IS INTEND TO BE UTILIZED
 UNDER 2001 FBC 412.5 ITEMS 1, 2, 3 OR 4.
 SHOULD SUBMITTAL BE UNDER ITEM 4, THIS
 MUST BE SUBMITTED TO THE BUILDING
 OFFICAL, NEIL MELICK.PLEASE PROVIDE
 ALL SUPPORTING DOCUMENTATION.
  
 COMMENT #16 - OK
 COMMENT #17 - OK
 COMMENT #18 - OK
 ****************************************
 NEW COMMENT
 19. PLAN SHEET A-4.1 - THE DOOR SCHEDULE
 INDICATES THE A/C CLOSET DOOR IN THE
 APARTMENTS ARE TO BE WOOD.PLEASE
 VERIFY WITH THE DOOR MANUFACTURER IF
 THIS MEETS THE CRITERIA FOR A NON
 COMBUSTIBLE DOOR AS REQUIRED IN 2001 FMC
 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By pkrauss Date 2005-12-28 Time 16:58 Rev Time 0.00
Received By pkrauss Date 2005-12-28 Time 16:58 Sent To  
Notes
2005-12-28 00:00:00DENIED:2001 FLORIDA BUILDING CODE
  
 1.PLAN SHEET AC-1 EMERGENCY GENERATOR
 NOTE STATES 'SEE 1/4" SCALE DRAWING ON
 THIS SHEET FOR LAYOUT.DETAIL FOR THE
 LAYOUT IS NOT SHOWN.
  
 2.PLEASE PROVIDE DISTANCE TO SIDEWALK
 FROM THE GENERATOR EXHAUST TERMINATION.
  
 3.PLEASE PROVIDE DETAIL FOR THE
 GENERATOR WITH THE ELEVATION FOR MUFFLER
 EXHAUST.PLAN SHEET A-2.1.6 INDICATES
 LOUVERS, PLEASE SPECIFY INTAKES &
 EXHAUST.
  
 4.PLAN SHEET AC-1 VENTILATION FOR
 VARIOUS ROOMS ARE NOT INDICATED
 (TELEPHONE, ELECTRICAL, PUMP ROOM,
 OFFICE AREAS, ETC).
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001 FBC
 TABLE 403.3.
  
 6.PROVIDE CALCULATIONS FOR THE GARAGE
 VENTILATION IN ACCORDANCE WITH 2001 FBC
 411.4.2.
  
 7.PLEASE NOTE, PLAN SHEET AC-1 FUTURE
 COMMERCIAL/RETAIL SPACE.SHOULD A
 RESTAURANT BE IN THE FUTURE PLANS
 CONSIDER LAYOUT FOR GREASE DUCT AND
 EXHAUST TERMINATION.
  
 8.PLAN SHEETS AC-8 & 9 MECHANICAL
 ROOMS.PLANS DO NOT INDICATE
 VENTILATION FOR THE ROOMS.
  
 9.PROVIDE LAYOUT FOR CONDENSER WATER
 PIPING.INDICATE PIPE SIZE & MATERIAL.
  
  
 10. AC-12 UNIT C-5 DEN AREA WEST OF THE
 KITCHEN AREA, RETURN AIR IN NOT
 INDICATED.PLAN SHEET A1.1 SHOWS DOOR
 SEPARATING DEN.SHOW COMPLIANCE WITH
 2001 FMC 601.4.PLEASE NOTE, RETURN AIR
 JUMPERS SHALL COMPLY WITH 2001 FMC 601.4
 EXCEPTION 1 & 3.
  
 11. PROVIDE INFORMATION & DETAILS FOR
 THE VENTILATION OF THE POOL EQUIPMENT
 ROOM.
  
 12. PLAN SHEET P-1 ITEM #2 INDICATES GAS
 LINE.PLEASE INDICATE ALL GAS
 APPLIANCES.
  
 13. PLAN SHEET P-7 INDICATES A BOILER
 ROOM.PLEASE PROVIDE VENTILATION &
 COMBUSTION AIR CALCULATIONS.
  
 14. PLEASE PROVIDE SEQUENCE OF
 OPERATION.
  
 15. PLEASE INDICATE METHOD OF SMOKE
 CONTROL PER 2001 FBC 412.5.
  
 16. DRYER SHAFT & TRASH CHUTE SHALL BE
 EQUIPPED WITH FIRE SPRINKLERS IN
 ACCORDANCE WITH 2001 FBC 705.2.4.6 &
 NFPA 13 SECTION 8.14.2.2.1 & 13.15.2.1.1
  
 17. PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE GENERATOR, DRYER,
 PUMPS, ETC.
  
 18. PLEASE PROVIDE ENERGY CALCULATIONS
 PER CHAPTER 13 OF THE 2001 FBC.
  
 PLEASE NOTE, PLANS APPEAR TO BE
 INCOMPLETE WHICH MAY GENERATE ADDITIONAL
 COMMENTS ON SUBSEQUENT REVIEWS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 19 Status P Date 2008-03-29 Cont ID  
Sent By kstevens Date 2008-03-29 Time 13:09 Rev Time 0.00
Received By kstevens Date 2008-03-29 Time 13:09 Sent To  
Notes
2008-03-29 13:10:02REVISIONS APPROVED--SHTS P-1, P-2, P-3, P-4 & P-5

Review Stop P PLUMBING
Rev No 18 Status F Date 2008-02-23 Cont ID  
Sent By kstevens Date 2008-02-23 Time 15:02 Rev Time 0.00
Received By kstevens Date 2008-02-23 Time 15:02 Sent To  
Notes
2008-02-23 15:14:46REVISIONS DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P-1 PREVIOUS REVISION SIGNED, SEALED & DATED
 4/18/07 SHOWED UP TO REVISION NUMBER 18. THIS REVISION
 SUBMITTED 2/5/08, SIGNED, SEALED & DATED 1/31/07 HAS
 NEW INFORMATION INDICATED ON REVISION NUMBER 18. ALSO
 MANY PREVIOUSLY APPROVED REVISIONS ARE STILL INDICATED
 ON THE PLANS AS CLOUDS AND REVISION NUMBERS. THESE
 REVISIONS THAT HAVE BEEN PREVIOUSLY APPROVED IF NOT
 SHUT OFF CREATE MANY EXTRA HOURS OF REVIEW. TURN OFF
 ALL PREVIOUSLY APPROVED REVISIONS, (CLOUDS/NUMBERS) AND
 ONLY INDICATE THE REVISION BEING SUBMITTED FOR REVIEW.
 IF THIS IS NOT DONE THEN THE REVISION WILL BE DENIED
 AND SENT BACK BECAUSE IT IS TOO TIME CONSUMING TO
 REVIEW THE TOTAL SHEET LOOKING FOR A FEW REVISIONS WHEN
 REVISIONS ARE SHOWN ALL OVER THE SHEET. SECTION
 104.2.1.3.
  
 2. SHT P-2PREVIOUS REVISION SIGNED, SEALED & DATED
 4/27/07 SHOWED UP TO REVISION NUMBER 18. THIS REVISION
 SUBMITTED 2/5/08, SIGNED, SEALED & DATED 1/31/07 HAS
 NEW INFORMATION INDICATED ON REVISION NUMBER 18. ALSO
 MANY PREVIOUSLY APPROVED REVISIONS ARE STILL INDICATED
 ON THE PLANS AS CLOUDS AND REVISION NUMBERS. THESE
 REVISIONS THAT HAVE BEEN PREVIOUSLY APPROVED IF NOT
 SHUT OFF CREATE MANY EXTRA HOURS OF REVIEW. TURN OFF
 ALL PREVIOUSLY APPROVED REVISIONS, (CLOUDS/NUMBERS) AND
 ONLY INDICATE THE REVISION BEING SUBMITTED FOR REVIEW.
 IF THIS IS NOT DONE THEN THE REVISION WILL BE DENIED
 AND SENT BACK BECAUSE IT IS TOO TIME CONSUMING TO
 REVIEW THE TOTAL SHEET LOOKING FOR A FEW REVISIONS WHEN
 REVISIONS ARE SHOWN ALL OVER THE SHEET. SECTION
 104.2.1.3.
  
 3. SHT P-3 PREVIOUS REVISION SIGNED, SEALED & DATED
 4/27/07 SHOWED UP TO REVISION NUMBER 18. THIS REVISION
 SUBMITTED 2/5/08, SIGNED, SEALED & DATED 1/31/07 HAS
 NEW INFORMATION INDICATED ON REVISION NUMBER 18. ALSO
 MANY PREVIOUSLY APPROVED REVISIONS ARE STILL INDICATED
 ON THE PLANS AS CLOUDS AND REVISION NUMBERS. THESE
 REVISIONS THAT HAVE BEEN PREVIOUSLY APPROVED IF NOT
 SHUT OFF CREATE MANY EXTRA HOURS OF REVIEW. TURN OFF
 ALL PREVIOUSLY APPROVED REVISIONS, (CLOUDS/NUMBERS) AND
 ONLY INDICATE THE REVISION BEING SUBMITTED FOR REVIEW.
 IF THIS IS NOT DONE THEN THE REVISION WILL BE DENIED
 AND SENT BACK BECAUSE IT IS TOO TIME CONSUMING TO
 REVIEW THE TOTAL SHEET LOOKING FOR A FEW REVISIONS WHEN
 REVISIONS ARE SHOWN ALL OVER THE SHEET. SECTION
 104.2.1.3.
  
 4. SHT P-5 MANY REVISIONS ARE NOT CLOUDED/NUMBERED ON
 THIS SHEET. ALSO MANY PREVIOUSLY APPROVED REVISIONS ARE
 STILL INDICATED ON THE PLANS AS CLOUDS AND REVISION
 NUMBERS. THESE REVISIONS THAT HAVE BEEN PREVIOUSLY
 APPROVED IF NOT SHUT OFF CREATE MANY EXTRA HOURS OF
 REVIEW. TURN OFF ALL PREVIOUSLY APPROVED REVISIONS,
 (CLOUDS/NUMBERS) AND ONLY INDICATE THE REVISION BEING
 SUBMITTED FOR REVIEW. IF THIS IS NOT DONE THEN THE
 REVISION WILL BE DENIED AND SENT BACK BECAUSE IT IS TOO
 TIME CONSUMING TO REVIEW THE TOTAL SHEET LOOKING FOR A
 FEW REVISIONS WHEN REVISIONS ARE SHOWN ALL OVER THE
 SHEET. SECTION 104.2.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 17 Status P Date 2008-02-23 Cont ID  
Sent By kstevens Date 2008-02-23 Time 15:01 Rev Time 0.00
Received By kstevens Date 2008-02-23 Time 15:01 Sent To  
Notes
2008-02-23 15:02:22REVISIONS OK--SHTS P-4, P-23 & P-23A

Review Stop P PLUMBING
Rev No 16 Status F Date 2008-02-23 Cont ID  
Sent By kstevens Date 2008-02-23 Time 10:51 Rev Time 0.00
Received By kstevens Date 2008-02-23 Time 10:51 Sent To  
Notes
2008-02-23 10:51:51 
  
  
 REVISIONS DENIED
  
 SHTS P-1A & P-1B SHOW REVISIONS FOR DIESEL FUEL FOR THE
 GENERATOR. FUEL GAS IS A MECHANICAL PLAN REVIEW AND AS
 SUCH SHALL BE SUBMITTED UNDER THE MECHANICAL SHEETS AND
 TO THE MECHANICAL PLAN REVIEWER.
  
 THIS HAS BEEN INDICATED IN THE PREVIOUS REVISION
 REVIEWS DATED 12-04-07 & 12-13-07
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 15 Status F Date 2007-12-13 Cont ID  
Sent By kstevens Date 2007-12-13 Time 08:12 Rev Time 0.00
Received By kstevens Date 2007-12-13 Time 08:12 Sent To  
Notes
2007-12-13 08:12:46 
  
  
 REVISIONS DENIED
 SHTS P-1A & P-1B SHOW REVISIONS FOR DIESEL FUEL FOR
 THE GENERATOR. FUEL GAS IS A MECHANICAL PLAN REVIEW AND
 AS SUCH SHALL BE SUBMITTED UNDER THE MECHANICAL SHEETS
 AND TO THE MECHANICAL PLAN REVIEWER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 14 Status F Date 2007-12-04 Cont ID  
Sent By kstevens Date 2007-12-04 Time 12:18 Rev Time 0.00
Received By kstevens Date 2007-12-04 Time 12:18 Sent To  
Notes
2007-12-04 12:21:49 
  
  
 REVISIONS DENIED
 SHTS P-1A & P-1B SHOW REVISIONS FOR DIESEL FUEL FOR
 THE GENERATOR. FUEL GAS IS A MECHANICAL PLAN REVIEW AND
 AS SUCH SHALL BE SUBMITTED UNDER THE MECHANICAL SHEETS
 AND TO THE MECHANICAL PLAN REVIEWER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 13 Status N Date 2007-10-18 Cont ID  
Sent By kstevens Date 2007-10-18 Time 15:51 Rev Time 0.00
Received By kstevens Date 2007-10-18 Time 15:51 Sent To  
Notes
2007-10-18 15:52:59 
  
  
  
  
  
 SHTS A2.7.5 & A2.7.6 DELETED A PLANTER DRAIN AND A DECK
 DRAIN. THESE CHANGES SHALL BE INDICATED ON THE PLUMBING
 PLANS AND THE STORM ISOMETRIC RISER DIAGRAM
  
  
  
  
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 12 Status P Date 2007-09-15 Cont ID  
Sent By kstevens Date 2007-09-15 Time 09:56 Rev Time 0.00
Received By kstevens Date 2007-09-15 Time 09:56 Sent To  
Notes
2007-09-15 09:59:17REVISIONS APPROVED, SHTS P-4 & P-22
  
  
  
  
  
 SHT P-4 REVISION REQUIRED FOR THE STORM RISER DIAGRAMS
 TO REFLECT THE CHANGES TO THE PRIMARY AND SECONDARY
 ROOF DRAINS AND PIPING REVISEDBY REVISION 11.
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 11 Status P Date 2007-06-09 Cont ID  
Sent By kstevens Date 2007-06-09 Time 12:02 Rev Time 0.00
Received By kstevens Date 2007-06-09 Time 12:02 Sent To  
Notes
2007-06-09 12:03:42REVISIONS OK--SHTS P-2, P-3, P-5, P-20, P-23 &
 P-23A

Review Stop P PLUMBING
Rev No 10 Status F Date 2007-06-09 Cont ID  
Sent By kstevens Date 2007-06-09 Time 11:58 Rev Time 0.00
Received By kstevens Date 2007-06-09 Time 11:58 Sent To  
Notes
2007-06-09 12:02:20REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P-1 NO CHANGES FROM LAST REVISION. (REVISION
 18). SEE SHEET SIGNED, SEALED, DATED 4-18-2007.
  
 2. SHT P-4 8TH FLOOR HUB DRAINS, (SAFE WASTE), NOT
 APPROVED. SECTION 1002.1 EACH FIXTURE SHALL HAVE ITS
 OWN TRAP. NO DOUBLE TRAPING. CONNECT EACH HUB DRAIN TO
 THE VENTED LINE. (COMBINATION WASTE & VENT).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 9 Status P Date 2007-06-04 Cont ID  
Sent By kstevens Date 2007-06-04 Time 14:42 Rev Time 0.00
Received By kstevens Date 2007-06-04 Time 14:42 Sent To  
Notes
2007-06-04 14:42:44REVISION OK - SHT P-1

Review Stop P PLUMBING
Rev No 8 Status F Date 2007-04-04 Cont ID  
Sent By kstevens Date 2007-04-04 Time 07:55 Rev Time 0.00
Received By kstevens Date 2007-04-04 Time 07:55 Sent To  
Notes
2007-04-04 10:59:13REVISION/DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHT A-1 SHOW ALL PIPE SIZES DOWNSTREAM OF THE 6" HUB
 DRAINS. TABLE 710.1(1). THESE PIPES SHALL NOT REDUCE IN
 THE DIRECTION OF FLOW PER SECTION 704.2.
  
 2. SHT A-1 SHOW ALL CLEANOUTS REQUIRED BY SECTIONS
 708.3.1 & 708.3.3 IN LINES TO NEW 6" HUB DRAINS.
  
 3. SHT A-1 REVISIONS 10 THRU 15 NOT INDICATED WITH
 CLOUDS OR NUMBERED TRIANGLES. THESE REVISIONS ARE NOT
 APPROVED. SECTION 104.2.1.
  
 4. ALL CHANGES TO THE SANITARY ON THEFLOOR PLAN SHALL
 BE REFLECTED ON THE SANITARY RISER DIAGRAM. REVISIONS
 WILL BE REQUIRED FOR THE RISER DIAGRAM. SECTION
 104.2.1.
  
 5. SHT P-20 DETAIL FOR THE SPRINKLER DRAIN DOES NOT
 REFLECT WHAT IS SHOWN ON THE FLOOR PLAN SHEET P-1. NO
 TRAP IS SHOWN, NO HUB IS SHOWN, NO VENT IS SHOWN AND
 PIPE SIZE WILL BE REQUIRED TO BE 6". SECTIONS 704.2,
 901.2.1, 1002.1 & 104.2.1.
  
 6. SHT P-20 NOTESSTATES PROVIDE FLEXIBLE CONNECTION
 TO SITE DRAINAGE. PLEASE PROVIDE A DETAIL SHOWING THE
 CONNECTION AND INDICATING THE MATERIAL TO BE USED.
 SECTIONS 104.2.1, 301.2 & 301.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status F Date 2007-04-03 Cont ID  
Sent By kstevens Date 2007-04-03 Time 11:47 Rev Time 0.00
Received By kstevens Date 2007-04-03 Time 11:47 Sent To  
Notes
2007-04-03 12:16:05REVISION/ DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P-5 PIPE ROUTING IN AREAS 53, 55, 57, 75, 76
 ALSO CHANGE THE WAY THE SQUARE FOOTAGE ACCUMULATED IN
 THE SYSTEM. THIS WILL CHANGE THE PIPE SIZE IN SOME
 INSTANCES. SEE ALL SECTIONS OF PIPE DOWNSTREAM OF THE
 CHANGES AND MAKE SURE THE SQUARE FOOTAGE IS RECHECKED.
 SECTION 104.2.1 AND TABLE 1106.3.
  
 2. SHT P-5 NEW DECK DRAINS ADDED AROUND THE GAS HEATER
 SPA SHALL REFLECT THE SQUARE FOOTAGE BEING DRAINED AND
 INDICATE THE PIPE SIZE PER TABLE 1106.3.
  
 3. SHT P-5 ALL CHANGES TO THE STORM SYSTEM, (DECK
 DRAINS, PLANTER DRAINS OR TRENCH DRAINS), SHALL BE
 REFLECTED IN THE STORM RISER DIAGRAMS. SECTION
 104.2.1.
  
 4. SHT P-5 THERE IS CONCERN THAT IF THERE IS BLOCKAGE
 IN THE PRIMARY SYSTEM IN SOME AREAS, THE WATER WILL
 ENTER THE OCCUPIED SPACES BEFORE THE SECONDARY DRAIN,
 OR OVERFLOW SCUPPER. (EXAMPLE AREAS 1 THRU 4, 15, 17,
 19, 21, 22, 45). SECTIONS 1107.1 & 1107.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-04-03 Cont ID  
Sent By kstevens Date 2007-04-03 Time 11:46 Rev Time 0.00
Received By kstevens Date 2007-04-03 Time 11:46 Sent To  
Notes
2007-04-03 11:47:14REVISIONS OK - SHTS P-1A REV. #2 & P-5A REV. #3.

Review Stop P PLUMBING
Rev No 5 Status F Date 2007-01-23 Cont ID  
Sent By kstevens Date 2007-01-23 Time 09:56 Rev Time 0.00
Received By kstevens Date 2007-01-23 Time 09:56 Sent To  
Notes
2007-01-23 14:20:27 
 REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P1 THE DRAINS FROM THE FIRE SPRINKLER SHALL BE
 INDIRECT WASTED AND REQUIRES A TRAP. SECTIONS 802.1.4 &
 901.2.1. A FLOOR SINK OR HUB DRAIN IS REQUIRED. (SEE
 REVISION 13 - REVISION STATES BLDG DEPT COMMENT. I
 BELIEVE THE COMMENT WAS THAT INDIRECT WASTE RECEPTORS
 ARE NOT ALLOWED IN THE STAIRWELL, NOT THAT THE WASTE
 RECEPTORS ARE NOT NEEDED. SEE PROVISO ON PLANS). PLEASE
 CLARIFY.
  
 2. SHT P-1 PLEASE TURN OFF ALL PREVIOUS REVISIONS AS
 THIS SLOWS THE REVISION PROCESS DOWN. ONLY INDICATE THE
 REVISIONS BE SUBMITTED AT THIS TIME ON THE PLANS.
 SECTION 104.2.1.-- THERE ARE CHANGES TO THE ROUTING
 OF THEWATER SUPPLY TO THE FIRE PUMP AS WELL AS A
 BYPASS THAT HAS NOT BEEN CLOUDED, NOR INDICATED AS A
 REVISION. CLOUD AND NUMBER ALL REVISIONS. - - MANY
 REVISIONS SHOWN HAVE NO CHANGES TO STAMPED SET OF
 PLANS. PLEASE CLARIFY. (SEE REVISIONS 10 & 12).
  
 3. SHT P-22REVISION #4 NOT APPROVED. SEE COMMENT #1.
  
  
 **********APPROVED SHEETS**********
 P-5, &P-5A.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-01-23 Cont ID  
Sent By kstevens Date 2007-01-23 Time 06:50 Rev Time 0.00
Received By kstevens Date 2007-01-22 Time 06:50 Sent To  
Notes
2007-01-23 07:21:32 
 REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P1 THE DRAINS FROM THE FIRE SPRINKLER SHALL BE
 INDIRECT WASTED AND REQUIRES A TRAP. SECTIONS 802.1.4 &
 901.2.1. A FLOOR SINK OR HUB DRAIN IS REQUIRED. (SEE
 REVISION 13 - REVISION STATES BLDG DEPT COMMENT. I
 BELIEVE THE COMMENT WAS THAT INDIRECT WASTE RECEPTORS
 ARE NOT ALLOWED IN THE STAIRWELL, NOT THAT THE WASTE
 RECEPTORS ARE NOT NEEDED. SEE PROVISO ON PLANS). PLEASE
 CLARIFY.
  
 2. SHT P-1 PLEASE TURN OFF ALL PREVIOUS REVISIONS AS
 THIS SLOWS THE REVISION PROCESS DOWN. ONLY INDICATE THE
 REVISIONS BE SUBMITTED AT THIS TIME ON THE PLANS.
 SECTION 104.2.1.-- THERE ARE CHANGES TO THE ROUTING
 OF THEWATER SUPPLY TO THE FIRE PUMP AS WELL AS A
 BYPASS THAT HAS NOT BEEN CLOUDED, NOR INDICATED AS A
 REVISION. CLOUD AND NUMBER ALL REVISIONS. - - MANY
 REVISIONS SHOWN HAVE NO CHANGES TO STAMPED SET OF
 PLANS. PLEASE CLARIFY. (SEE REVISIONS 10 & 12).
  
  
 **********APPROVED SHEETS**********
 P-2, P-3, P-4, P-5, AND NEW SHEET P-5A.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-08-26 Cont ID  
Sent By kstevens Date 2006-08-26 Time 15:10 Rev Time 0.00
Received By kstevens Date 2006-08-24 Time 17:26 Sent To  
Notes
2006-08-26 00:00:00 
  
  
  
 PASSED/PROVISO
  
 SHTS P-1 & P-22 FLOOR DRAINS ARE NOT
 APPROVED IN THE STAIRWELLS. POSITIVE
 PRESSURES CAUSED BY THE STAIRWELL
 PRESSURIZATION MAY CONFLICT WITH SECTION
 901.2. ALSO PENETRATIONS IN AN EXIT
 ENCLOSUER ASSEMBLY OTHER THAN THOSE
 LIMITED TO NFPA 101 SECTION 7.1.3.2.1(5)
 ARE NOT ALLOWED. - REVISIONS REQUIRED
 FOR THESE SHEETS
  
  
  
  
 GAS APPLIANCE VENTING SHALL BE FIELD
 INSPECTED AND APPROVED.
 MANUF. SPECIFICATION SHEETS SHALL BE
 SUBMITTED AT THE TIME OF GAS PERMIT
 APPLICATION. MANUF. SPECIFICATIONS
 SHEETS REQUIRED FOR THE GAS REGULATORS.
 VENTS FOR REGULATORS SHALL BE MADE OF
 NON COMBUSTABLE MATERIAL. GAS RISER - A
 SHUT OFF VALVE SHALL BE INSTALLED PRIOR
 TO THE REGULATORS WITH A UNION BETWEEN
 OR AFTER REGULATOR. (SHT P-6). SECTION
 410.2(5). REVISIONS REQUIRED FOR THESE
 SHEETS.
  
  
  
  
 SHTS P-4 & P-21A COOLING TOWER WATER
 RISER DIAGRAM. THE CHECK VALVES TO THE
 FOUNTAINS AND THE TRASH CHUTES ARE NOT
 APPROVED. INSTALL N-36 VACUUM BREAKERS
 FOR THIS APPLICATION. - THE IRRIGATION
 SYSTEM REQUIRES A PRESSURE VACUUM
 BREAKER TO THAT LINE SEPARATE FROM THE
 REST OF THE SYSTEM. - CLARIFY WATER
 PIPING TO POOL HEATERS AS THERE IS MAKE
 UP WATER TO THE COLLECTING TANKS. -
 REVISION REQUIRED FOR THESE SHEETS.
  
  
  
  
 SEE PROVISO REQUIREMENTS FOR SHEETS P-1,
 P-4, P-6, P-21A, & P-22.
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-06-28 Cont ID  
Sent By kstevens Date 2006-06-28 Time 14:30 Rev Time 0.00
Received By kstevens Date 2006-06-22 Time 10:13 Sent To  
Notes
2006-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB CITY CODE
  
 FROM PREVIOUS REVIEW. COMMENT NUMBER
 SHALL REMAIN THE SAME AS FIRST REVIEW:
  
 4. SHTS A-1.7, A-1.8, A-2.6.1 THRU
 A-2.6.6, SUBMIT CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS FOR ALL ROOFS.
 SHOW THE LOCATION OF ALL SECONDARY ROOF
 DRAINS FOR ALL ROOFS/DECKS.
 ***RESPONSE NOTED, BUT SCUPPER SCHEDULE
 CALCULATIONS & ROOF DRAIN SF ARE
 DIFFERENT. PLEASE CORRELATE INFORMATION.
 SECTION 104.2.1.
 5. ALL UNIT TYPES SHALL COMPLY WITH
 FHA-98 DESIGN MANUAL REQUIREMENTS ONE
 THRU SEVEN. SUBMIT DETAILS.
 ***RESPONSE NOTED, BUT BATH #2 IN UNITS
 B-1, C-1, C-2, C-2.1, C-2.2, C-3, C-4,
 C-5, C-6, C-7, C-8, & D-1, AS WELL AS
 THE M/B OF UNITS C-9 & C-9.1. SHOW THE
 OPENING FOR THE W/C'S. OPENINGS SHALL BE
 A MINIMUM 33" WIDE WITH THE W/C BEING
 18" OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE & 15" TO ADJACENT FIXTURE OR
 VANITY CABINET. W/C'S BETWEEN FIXTURES
 SHALL BE 18" OFF ONE FIXTURE AND 15" OFF
 THE OTHER WITH A MINIMUM 33" OPENING.
 SEE PAGES 7.43, 7.44 & 7.45. -
 REINFORCING FOR FOLDING GRAB BARS MUST
 BE SUBSTANTIAL BECAUSE OF THEIR
 CANTILEVERED DESIGN. 20 GAUGE SHEET
 METAL BACKING DOES NOT APPEAR TO BE
 SUBSTANTIAL. PLEASE INDICATE WITH
 CALCULATIONS HOW THIS WILL BE CONSIDERED
 SUBSTANTIAL. (SEE PAGE 28).
  
 9. SHTS A-2.7.5 & A-10.1 MORE
 INFORMATION IS REQUIRED FOR THE
 FOUNTAINS. PLEASE INDICATE IF THERE WILL
 BE WATER SUPPLY LINES AND OR DRAINAGE
 LINES FOR FOUNTAINS. IF WATER SUPPLY
 LINES ARE INSTALLED, BACKFLOW PREVENTION
 IS REQUIRED. IF DRAINS ARE INSTALLED,
 THEY SHALL CONNECT TO THE SANT. SYSTEM
 AND THE OVERFLOW SHALL DRAIN TO STORM.
 PLEASE CLARIFY. SECTIONS 104.2.1 & 608.
 ***RESPONSE NOTED, BUT NO BACKFLOW
 PREVENTORS ARE SHOWN ON PLANS. PLEASE
 INDICATE WHERE THESE CAN BE FOUND AS
 THERE IS NO WATER RISER DIAGRAM FOR THE
 COOLING TOWER WATER. PLEASE SUBMIT A
 WATER RISER DIAGRAM SHOWING ALL PIPE
 SIZE, VALVES, BACKFLOWS ETC. FOR THE
 COOLING TOWER SYSTEM. SECTION 104.3.1.1.
 - FOUNTAIN AT PORTE-COCHERE PLAZA TO BE
 BY SEPARATE PERMIT, BUT WILL THE DRAIN
 LINE, OVERFLOW LINE AND WATER SUPPLY TO
 THE FOUNTAIN BE RUN TO FOUNTAIN AT THAT
 TIME? SECTION 104.2.1.
  
 18. SHT P-4 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SF OF EACH DRAINED AREA PLUS 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS,
 PLUS THE AREA OF ROOFS THAT DRAIN ONTO
 THE ROOF/DECK AREA FROM ABOVE.
 ***RESPONSE NOTED, BUT P-6 SCUPPER
 SCHEDULE CALCULATIONS TOTAL AREA SERVED
 BY DRAIN ON SCHEDULE DOES NOT REFLECT
 THE TOTAL SHOWN ON SHT P-5 DECK DRAINS &
 PLANTER DRAINS. MANY TOTAL AREAS ARE NOT
 CORRECT. PLEASE RECHECK THE ADDITION.
 SECTION 104.2.1 AND TABLE 1106.3.
  
 22. SHT P-7 SUBMIT CALCULATION FOR
 PRIMARY AND SECONDARY ROOF DRAINS. (SEE
 COMMENT #18). SECTIONS 1106 & 1107.
 ***RESPONSE NOTED, BUT SCUPPER SCHEDULE
 CALCULATIONS TOTAL AREA SERVED BY DRAIN
 DOES NOT REFLECT SF ON ROOF PLAN. PLEASE
 CORRELATE INFORMATION. SECTION 104.2.1.
  
 33. SHT P-18 RISERS 86, 87, 81, 80 LOWER
 OFFSET VENTS REQUIRED. (SHOW AT LOWEST
 OFFSET) SECTION 915.3.
 ***RESPONSE NOTED, BUT THE LOWER OFFSET
 VENTS ARE STILL NOT SHOWN ON RISERS 80,
 81, AND 87A.
  
 36. THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PERMIT APPLICATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 ***RESPONSE NOTED, BUT THE ISOMETRIC
 INDICATES THE POOL/SPA HEATERS ARE ON
 THE 8TH FLOOR, BUT THE FLOOR PLAN SHOWS
 THE HEATERS ON THE 9TH FLOOR. PLEASE
 CORRELATE RISER WITH FLOOR PLAN. - SOME
 CUT SECTIONS SHOW NO LENGTH AS REQUIRED.
 SEE FROM THE METER TO THE FIRST RISER,
 THE OFFSET ON THE RUN TO THE WATER
 HEATERS, AND THE DROP TO THE WATER
 HEATERS IS NOT SHOWN.
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3)
 ***RESPONSE NOTED, BUT NOT ALL CUT
 SECTIONS ARE GIVEN TO VERIFY DEVELOPED
 LENGTH.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 ***RESPONSE NOTED, BUT NO VENTING
 INFORMATION INDICATED.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 ***RESPONSE NOTED, BUT MANUF.
 SPECIFICATION SHEETS FOR ALL GAS
 EQUIPMENT SHALL BE SUBMITTED FOR REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 **************NEW COMMENTS**************
  
 1B. SHT A-2.7.5 MORE INFORMATION IS
 REQUIRED FOR THE SCUPPERS. SUBMIT A
 DETAIL INDICATING WHERE THE SCUPPER WILL
 BE PIPED TO. SHOW SCUPPER HEIGHT &
 WIDTH, AND INDICATE THE DISTANCE FROM
 THE DECK TO THE FLOW LINE. SHOW THE AREA
 TO BE DRAINED BY EACH EOS AND INDICATE
 THE SQUARE FOOTAGE BEING DRAINED BY EACH
 EOS. - INDICATE THE TERMINATION POINT
 FOR EACH EOS. SECTION 104.2.1.
  
 2B. EMERGENCY OVERFLOW SCUPPERS SHALL BE
 LOCATED AS CLOSE AS PRACTICABLE TO THE
 REQUIRED VERT LEADERS, AND SHALL BE A
 MINIMUM 4" IN HEIGHT. SECTION 1503.4.2.
  
 3B. SUBMIT A EMERGENCY OVERFLOW SCUPPER
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES. SECTION 1O3.1.1.
  
 3B. SHT P-1 RELIEF VENT REQUIRED FOR
 AAV'S, (STUDOR VENTS). SECTION 917.3.2.
  
 4B. SHT P-1 SANITARY RISERS 44A, & 51A
 ARE NOT SHOWN ON THE FLOOR PLAN. PLEASE
 CLARIFY. SECTION 104.2.1.
  
 5B. SHT P-1 CONDENSATE LINE IS CONNECTED
 TO THE SANITARY BUILDING DRAIN BETWEEN
 RISERS 43 & 39. THIS IS NOT APPROVED.
 MUNICIPAL CODE SECTION 90-125(5).
  
 6B. SHT P-1 10 DD'S SHOWN AS RWL'S.
 PLEASE CORRELATE INFORMATION. SECTION
 104.2.1.
  
 7B. SHT P-2 RWL DESIGNATIONS COVERED UP
 BY RECTANGLE GRID REFERANCES AT COL.
 LINES 57.1-R.1, 57.1-N.1, 57.1-C.1 AND
 OVER A SANT. RISER DESIGNATION AT COL.
 LINE 57.1-B.2. PLEASE MOVE REFERENCES.
 SECTION 104.2.1.
  
 8B. SHT P-2 10 3" DD'S ARE SHOWN AS
 RWL'S. PLEASE CORRELATE INFORMATION.
 SECTION 104.2.1.
  
 9B. SHT P-2 6"RWL 3500SF UP & DOWN IS
 SHOWN AS 3200SF AT ROOF DRAIN. PLEASE
 CORRELATE INFORMATION. SECTION 104.2.1.
  
 10B. SHT P-3 3RD FLOOR AND 7TH FLOOR ARE
 DIFFERENT FROM FLOORS 4, 5, & 6 AND EACH
 OTHER, SO HOW CAN ALL FLOORS BE TYPICAL?
 PLEASE CLARIFY. SECTION 104.2.1.
  
 11B. SHT P-3 PLEASE INDICATE THE SQUARE
 FOOTAGE FOR ALL DECK DRAINS. SECTION
 104.2.1 AND TABLE 1106.3.
  
 12B. SHT P-36"RWL 3500SF UP & DOWN IS
 SHOWN AS 3200SF @ THE ROOF DRAIN. PLEASE
 CORRELATE INFORMATION. SECTION 104.2.1.
  
 13B. SHT P-4RWL'S INDICATED AS PD'S OR
 DD'S ON STORM RISERS. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 14B. SHT P-6 SCUPPER SCHEDULE
 CALCULATIONS, CHECK ADDITION OF SF ON
 AREAS 22, 62, 79, & 106. SECTION
 102.1.1.
  
 15B. SHT P-7 WHITE-OUT IS NOT APPROVED
 ON SIGNED/SEALED SETS OF PLANS SUBMITTED
 FOR RECORD. SECTION 104.2.1.3.
  
 16B. SHT P-7 SUBMIT A WATER RISER
 DIAGRAM ISOMETRIC FOR PIPING IN BOILER
 ROOM THAT REFLECTS THE LAYOUT ON THE
 FLOOR PLAN. SHOW ALL PIPE SIZES, VALVES,
 VACUUM RELIEF VALVES, CIRCULATION PUMPS,
 THERMAL EXPANSION CONTROL, THERMOMETERS,
 ETC. FOR THE DOMESTIC WATER HEATER &
 STORAGE TANK. SECTION 104.3.1.1.
  
 17B. SHT P-7 BOILER ROOM DETAIL THE COLD
 WATER SUPPLY APPEARS TO BE PASSING THRU
 THE HOT WATER STORAGE TANK. PLEASE
 CLARIFY. SECTION 104.2.1.
  
 18B. SHT P-13 PLEASE INDICATE WHAT IS AT
 THE TOP OF ALL COLD WATER RISERS. NO
 REFERENCE SYMBOL IS SHOWN ON SHT P-2
 PLUMBING LEGEND. IF THEY ARE AIR
 CHAMBERS, THEY ARE NOT APPROVED.
 SECTIONS 104.2.1, 604.9, & PDI-WH 201.
  
 19B. SHT P-16 RISER 44A/51A MAXIMUM 20
 FIXTURE UNITS ON 4" STACK PER TABLE
 912.3.
  
 20B. SHT P-17 RISERS 52A, & 84AARE NOT
 FOUND ON THE HORIZONTAL BUILDING
 SANITARY DRAIN ISOMETRIC RISER DIAGRAM.
 SHTP-22. PLEASE CLARIFY. SECTION
 104.2.1.
  
 21B. SHT P-18 RISER 87A NOT FOUND ON THE
 HORIZONTAL BUILDING SANITARY DRAIN
 ISOMETRIC RISER DIAGRAM. SHT P-22 PLEASE
 CLARIFY. SECTION 104.2.1.
  
 22B. SHT P-19 RISER 34/57 SHOWS NO
 CONNECTION TO STACK FOR FLOORS 15, 17, &
 19. PLEASE CLARIFY. SECTION 104.2.1.
  
 23B. SHT P-20 SPRINKLER DRAIN DETAIL. A
 TRAP AND A VENT ARE REQUIRED FOR THIS
 LINE. SECTIONS 901.2.1. & 1002.1.
  
 24B. SHT P-22 HORIZONTAL SANITARY RISER
 DOES NOT REFLECT THE FLOOR PLAN. NO
 DRAIN LINES FOR THE FIRE SPRINKLER
 DRAINS. - FUTURE LINE, (4" 20FU),
 UPSTREAM OF RISER 68,69,70,72,73,74 NOT
 SHOWN. - FLOOR DRAIN UPSTREAM OF RISER
 59-67 & 71 NOT SHOWN. - OFFSET FOR RISER
 6 NOT SHOWN. - 2ND FLOOR OFFSET FOR
 RISER 22-26, 33-36, & 41 NOT SHOWN.
 SECTION 104.2.1.
  
 25B. SHT P-22 RELIEF VENTS REQUIRED FOR
 ALL AAV'S, (STUDOR VENTS). SECTION
 917.3.2.
  
 26B. SHT P-22 SHOW THE VENT PIPING FOR
 ALL FUTURE LINES SHOWING ALL PIPE SIZES,
 AND INDICATE WHICH STACK THE VENTS
 CONNECT INTO. SECTION 104.2.1 AND TABLE
 916.1.
  
 27B. SHT P-22 RECHECK ALL DFU'S ADDITION
 IN SANITARY RISER. SOME ADDITION IS NOT
 CORRECT AND THIS AFFECT THE PIPE SIZING
 IN SOME CASES. (SEE RED LINE CORRECTIONS
 ON ONE SET OF PLANS. SECTION 104.2.1 AND
 TABLE 710.1(1). (NOTE: BATHROOM GROUP
 CONSISTING OF W/C, LAV, BIDET, AND TUB
 OR SHOWER IS 5FU, AND WITH AN EXTRA LAV
 AND SHOWER IS 8FU. - SOME RISERS APPEAR
 TO INDICATE MORE FIXTURE UNITS THAN ARE
 ACTUALLY SHOWN. - TRAPS FOR FIXTURES
 OVER 2" SHALL BE SIZED PER TABLE 709.2.
 (EXAMPLE: 3" FLOOR DRAIN IS 5FU).
  
 28B. SHT P-22 RISER 22,23,24 DOES NOT
 SHOW PIPING FROM POOL EQUIPMENT ROOM,
 NOR FROM THE 2 FOUNTAINS AS INDICATED ON
 SHT P-3. PLEASE CORRELATE. SECTION
 104.2.1.
  
 29B. SHT P-22 SHOW THE CLEANOUTS WHERE
 REQUIRED PER SECTIONS 708.3.1, 708.3.3 &
 708.3.5. (ALSO SHOW ON SHT P-1).
  
 30B. SHT P-22 SHOW TRAPS AND VENTING FOR
 THE FIRE SPRINKLER DRAIN LINES AS
 REQUIRED IN SECTIONS 901.2.1 & 1002.1.
  
 31B. SHT P-23 STORM RISER DIAGRAM, SHOW
 SF DRAINED BY EACH DD. - 4" RD(2000SF)
 DOES NOT REFLECT THE ROOF PLAN, NOR
 CALCULATIONS (1900SF). - 6" DD (4350SF)
 DOES NOT REFLECT 9TH FLOOR PLAN. (SHTS
 P-1 & P-3 4450SF) PLEASE CORRELATE
 SECTION 104.2.1. - CLEANOUTS REQUIRED
 PER SECTION 1101.8. (ALSO SHOW ON SHT
 P-1.
  
 32B. SHT P-23A STORM RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. FOUNTAIN
 OVERFLOWS ARE NOT SHOWN. - OFFSET ON THE
 9TH FLOOR FOR ROOF DRAIN 3200SF IS SHOWN
 ON THE 8TH FLOOR ON THE FLOOR PLAN. -
 SHOME SF FOR SOME DRAINS DO NOT REFLECT
 THE FLOOR PLAN AND/OR CALCULATIONS.
 PLEASE CORRELATE. - NO SF SHOWN FOR MANY
 DD'S AND CAN NOT VERIFY PIPE SIZE UNTIL
 SF FOR ALL DD'S IS SHOWN. SECTION
 104.2.1 AND TABLE 1106.3.
  
 33B. SHT P-32A CLEANOUTS REQUIRED PER
 SECTION 1101.8 SHALL BE SHOWN. (ALSO ON
 SHT P-1).
  
 34B. BACKFLOW PREVENTION REQUIRED FOR
 IRRIGATION ON THE 9TH FLOOR. SECTION
 608.13.
  
 35B. A SEPARATE RPZV BACKFLOW IS
 REQUIRED FOR THE COOLING TOWER WATER
 SUPPLY LINE. (NOT SHOWN ON CIVIL SHEETS)
  
 36B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONALS AND FS 53.80(2)(B).
 THIS IS GIVEN AS A NOTICE ONLY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-17 Cont ID  
Sent By kstevens Date 2005-12-17 Time 11:57 Rev Time 0.00
Received By kstevens Date 2005-12-15 Time 17:44 Sent To  
Notes
2005-12-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB CITY CODE
  
 1. PLANS APPEAR TO BE INCOMPLETE AS
 SUBMITTED. MORE COMMENTS MAY BE
 FORTHCOMING NEXT REVIEW.
 2. SHT L-6 MISSING. (SEE INDEX ON SHT
 L-1). SECTION 104.2.1.
 3. SHT A-0.1 INDEX INDICATES THAT SHTS
 A-5.1 THRU A-5.6 HAVE KITCHEN AND
 BATHROOM ELEVATIONS, NOTES & DETAILS.
 THESE SHEETS WERE NOT SUBMITTED. SECTION
 104.2.1.
 4. SHTS A-1.7, A-1.8, A-2.6.1 THRU
 A-2.6.6, SUBMIT CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS FOR ALL ROOFS.
 SHOW THE LOCATION OF ALL SECONDARY ROOF
 DRAINS FOR ALL ROOFS/DECKS.
 5. ALL UNIT TYPES SHALL COMPLY WITH
 FHA-98 DESIGN MANUAL REQUIREMENTS ONE
 THRU SEVEN. SUBMIT DETAILS.
 6. NOT USED
 7. ALL ARCHITECT SHEETS. SEAL OF THE
 ARCHITECT SHALL IMPART INFORMATION
 REQUIRED BY FAC/FS. LITTLE OR NO
 INFORMATION CAN BE GLEANED FROM THE SEAL
 ON SOME SHEETS. PLEASE BE SURE EACH
 SHEET IS SEALED CORRECTLY & INFORMATION
 REQUIRED IS IMPARTED ON EACH SHEET. FAC
 61G1-16.004 & FS 481.2055.
 8. SHT A-2.7.5 SHOW THE LOCATION OF ALL
 SECONDARY DRAINS REQUIRED BY SECTION
 1107.
 9. SHTS A-2.7.5 & A-10.1 MORE
 INFORMATION IS REQUIRED FOR THE
 FOUNTAINS. PLEASE INDICATE IF THERE WILL
 BE WATER SUPPLY LINES AND OR DRAINAGE
 LINES FOR FOUNTAINS. IF WATER SUPPLY
 LINES ARE INSTALLED, BACKFLOW PREVENTION
 IS REQUIRED. IF DRAINS ARE INSTALLED,
 THEY SHALL CONNECT TO THE SANT. SYSTEM
 AND THE OVERFLOW SHALL DRAIN TO STORM.
 PLEASE CLARIFY. SECTIONS 104.2.1 & 608.
 10. SHT A-2.7.5 SEPARATE PERMITS
 REQUIRED FOR THE POOL & SPA POOL.
 (INFORMATIONAL).
 11. SHT P-1 NO PIPING SHOWN TO FLOOR
 DRAINS IN THE TRASH ROOM AND IN THE PUMP
 ROOMS. SECTION 104.2.1.
 12. SHT P-1 NO PIPING SHOWN TO RISERS
 29, 30, & 44 THRU 51. SECTION 104.2.1.
 13. SHT P-1 RISERS 10 & 26 NOT SHOWN ON
 FLOOR PLAN. SECTION 104.2.1.
 14. SHT P-2 NO FLOOR PLANS FOUND FOR THE
 FLOOR PLAN A-1.2. PLEASE CLARIFY.
 SECTION 104.2.1.
 15. SHT P-2 4"-180FU DOWNSTREAM OF RISER
 S/51A IS NOT CORRECT. PLEASE CHECK
 FIGURES. SECTION 104.2.1.
 16. SHT P-2 RECALCULATE FU'S DOWNSTREAM
 OF RISERS 64 & 65. SECTION 104.2.1.
 17. SHT P-2 INDICATE FU VALUE FOR RISERS
 75 & 82. SECTION 104.2.1.
 18. SHT P-4 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SF OF EACH DRAINED AREA PLUS 1/2 AREA OF
 ALL VERTICAL WALLS INCLUDING PARAPETS,
 PLUS THE AREA OF ROOFS THAT DRAIN ONTO
 THE ROOF/DECK AREA FROM ABOVE.
 19. SHT P-4 NUMEROUS RWL'S & DECK DRAINS
 ARE SHOWN FOR DD & PLANTER DRAINS ON THE
 9TH FLOOR, BUT NO PIPING IS SHOWN
 INDICATING WHERE THE DRAINS ARE DRAINING
 TO. PLEASE CLARIFY. SHOW PIPING ON RWL
 RISER DIAGRAMS. ALSO NO RWL'S FOR THESE
 DRAINS ARE SHOWN ON SUBSEQUENT SHEETS.
 SECTION 104.2.1.
 20. SHT P-5 SHOW THE LOCATION OF ALL
 SECONDARY DRAINS REQUIRED IN SECTION
 1107.
 21. SHT P-5 RWL 3200SF NOT SHOWN ON THE
 FLOOR PLAN. (NEAR RISER 79) 104.2.1.
 22. SHT P-7 SUBMIT CALCULATION FOR
 PRIMARY AND SECONDARY ROOF DRAINS. (SEE
 COMMENT #18). SECTIONS 1106 & 1107.
 23. SHT P-7 SUBMIT A DETAIL FOR THE
 BOILER ROOM. SHOW THE PIPING LAYOUT
 INCLUDING ALL PIPE SIZES, VALVES, VACUUM
 RELIEF VALVES, CIRCULATION PUMPS, P&T
 VALVES, PAN DRAINS, THERMAL EXPANSION
 CONTROL ECT. INDICATE ALL PIPE
 MATERIALS. SECTION 104.2.1.
 24. SHTS P-8 THRU P-12 ALL UNITS WATER
 RISER DIAGRAMS. WATER HAMMER ARRESTOR
 REQUIRED AT THE REFRIGERATOR ICE MAKER
 IN AN "EFFECTIVE RANGE". PDI-WH 201 AND
 MANUF. INSTALLATION REQUIREMENTS.
 25. SHT P-13 FLUSH RING RISER FOR THE
 TRASH CHUTE REQUIRES BACKFLOW
 PROTECTION. PLEASE INDICATE THE METHOD
 OF PROTECTION. SECTION 608.
 26. SHT P-13 WATER RISER 13 INDICATES 1"
 COLD WATER SUPPLY TO WATER HEATERS, BUT
 HOT WATER RISERS SHOW 2". PLEASE
 CLARIFY. SECTION 104.2.1.
 27. SHT P-14 PLEASE INDICATE MATERIAL
 USED AND TYPE OF SYSTEM. SECTION
 104.2.1.
 28. P-16 SANT. RISERS 44A 7 51A. PER
 SECTION 914.1 A RELIEF VENT IS REQUIRED
 AT EACH 10TH INTERVAL BEGINING WITH THE
 TOP FLOOR.
 29. SUBMIT A SANITARY HORIZONTAL RISER
 DIAGRAM IN ISOMETRIC FORM FOR THE
 BUILDING DRAIN. INDICATE ALL PIPE SIZES
 AND SHOW THE LOCATION OF ALL RISERS.
 SHOW DRAINAGE FIXTURE UNITS AS IT
 ACCUMULATES IN THE SYSTEM. SECTION
 104.3.1.1.
 30. SUBMIT A STORM ISOMETRIC RISER
 DIAGRAM FOR THE HORIZONTAL PIPING OF THE
 BUILDING STORM DRAIN. SHOW ALL PIPE
 SIZES, RISER LOCATIONS, AND THE SQUARE
 FOOTAGE AS IT ACCUMULATES IN THE SYSTEM.
 SECTION 104.3.1.1.
 31. SUBMIT STORM RWL RISER DIAGRAMS.
 SHOW ALL PIPE SIZES, OFFSETS & SQUARE
 FEET.
 32. SHT P-15 RISER 7 FIRST FLOOR TUB
 MISLABLED AS A SHOWER. SECTION 104.2.1.
 33. SHT P-18 RISERS 86, 87, 81, 80 LOWER
 OFFSET VENTS REQUIRED. (SHOW AT LOWEST
 OFFSET) SECTION 915.3
 34. SHT P-19 RISER 41 RELIEF VENT
 REQUIRED. SECTION 914.
 35. P-20 SPRINKLER DRAIN DETAIL, DRAIN
 TO CONNECT TO THE SANITARY SYSTEM, NOT
 THE STORM AS SHOWN. CITY CODE 90-203.
 36. THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PERMIT APPLICATION:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 37. ALL PLUMBING SHEETS. ENGINEERS SEAL
 SHALL SHOW ALL INFORMATION REQUIRED BY
 FAC 61G15-23.001 & FS 481.025
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 10 Status P Date 2008-09-10 Cont ID  
Sent By rkussner Date 2008-09-10 Time 16:54 Rev Time 0.00
Received By rkussner Date 2008-09-10 Time 16:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 9 Status P Date 2008-01-31 Cont ID  
Sent By eschneid Date 2008-01-31 Time 16:18 Rev Time 0.00
Received By eschneid Date 2008-01-31 Time 16:18 Sent To  
Notes
2008-01-31 16:19:39REVISION TO ADD DOOR TO THE FUEL TANK ROOM.

Review Stop Z ZONING
Rev No 8 Status P Date 2007-11-08 Cont ID  
Sent By eschneid Date 2007-11-08 Time 17:38 Rev Time 0.00
Received By eschneid Date 2007-11-08 Time 17:38 Sent To  
Notes
2007-11-08 17:39:10AIRCRAFT WARNING LIGHT

Review Stop Z ZONING
Rev No 7 Status P Date 2007-10-23 Cont ID  
Sent By eschneid Date 2007-10-23 Time 11:15 Rev Time 0.00
Received By eschneid Date 2007-10-23 Time 11:15 Sent To  
Notes
2007-10-23 11:16:43FOR REVISION #37 - CHANGING THE RAILING ABOVE ARCADE
 AND ADDING/REVISING DOORS TO COMMERCIAL UNITS.

Review Stop Z ZONING
Rev No 6 Status P Date 2007-09-26 Cont ID  
Sent By eschneid Date 2007-09-26 Time 17:39 Rev Time 0.00
Received By eschneid Date 2007-09-26 Time 17:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2007-07-23 Cont ID  
Sent By eschneid Date 2007-07-23 Time 17:05 Rev Time 0.00
Received By eschneid Date 2007-07-23 Time 17:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2007-01-22 Cont ID  
Sent By eschneid Date 2007-01-22 Time 10:44 Rev Time 0.00
Received By eschneid Date 2007-01-22 Time 10:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-08-22 Cont ID  
Sent By eschneid Date 2006-08-22 Time 15:50 Rev Time 0.00
Received By eschneid Date 2006-08-22 Time 15:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-18 Cont ID  
Sent By eschneid Date 2006-05-23 Time 16:15 Rev Time 0.00
Received By eschneid Date 2006-05-23 Time 16:15 Sent To  
Notes
2006-07-18 00:00:001) MINOR AMENDMENT REQUIRED TO MODIFY
 THE PLAZA AREA, INCLUDING THE
 LANDSCAPING, AND THE CHANGED LANDSCAPE
 ON THE EAST FACADE.
  
 2) THE COLUMN/WALL ELEMENT MAY NOT BE
 16'6" TALL (PG A-10.1)DISCUSSED WITH
 JOE VERDONE ON THE ACCEPTIBLE HEIGHT.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-03-26 Cont ID  
Sent By eschneid Date 2005-10-05 Time 10:00 Rev Time 0.50
Received By eschneid Date 2005-10-05 Time 9:30 Sent To  
Notes
2005-10-05 00:00:001) REQUIRE MINOR AMENDMENT REFLECTING
 THE MOVEMENT AND CHANGE IN BUILDING
 FOORPRINT ON BOTH THE SITE AND LANDSCAPE
 PLANS.PLEAE PROVIDE UPDATED PARKING
 COUNTS AS INTERIOR PARKING CONFIGURATION
 HAS CHANGED.
 2) METAL ROOF WOOD REQUIRE CRA APPROVAL.
 PLANNING STAFF DOES NOT SUPPORT THE
 PAINTED ALUMINUM.
 3) THE PROPOSED 12 FOOT TALL OBELISK IN
 THE FOUNTAIN IS NOT APPROVED BY PLANNING
 STAFF.
  
 CONTACT ERIC SCHNEDER (561) 822-1435.