2005-10-31 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05091394 |
| ADD: 1801 S FLAGLER DR # 1209 |
| CONT: AAA ALUMINUM DOORS & WINDOWS |
| TEL: (561)533-9869 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PLANS, SPECIFICATIONS,REPORTS OR |
| OTHER DOCUMENTS PREPARED BY THE DESIGN |
| PROFESSIONAL AND BEING FILED FOR PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND |
| SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| TO THE DOCUMENT. |
| FL STATE STAT: 61G15-23.002 ENGINEERS |
| FL ATATE STAT: 61G16.003 ARCHITECTS |
| *** BOTH SEETS OF ENGINEERING MUST BE |
| SIGNED & SEALED BY THE ENGINEER OF |
| RECORD.61G15-23.002 / 471.025(1) |
| |
| 2)THE MIAMI-DADE REPORT SUBMITTED, PGT |
| SLIDING GLASS DOOR REPORT WILL REQUIRE |
| THE CONTRACTOR TO SELECT AND HIGHLIGHT |
| WHICH GLASS TYPE WILL BE INSTALLED, |
| PANEL WIDTH AND HEIGHT WITH THE |
| ASSOCIATED POSITIVE & NEGATIVE PRESSURE. |
| |
| 3) THE FLORIDA COVERSHEET FL 239-R2 TIES |
| TO A MIAMI-DADE REPORT, SHEET 2 OF THE |
| FL REPORT LIST (6) MIAMI NOAS THAT ARE |
| ASSOCIATED WITH THE COVER SHEET BUT NONE |
| WERE SUBMITTED. A FENESTRATION TESTING |
| REPORT WAS SUBMITTED. |
| EITHER SUBMIT THE MIAMI NOA THAT |
| TIES TO THE FLORIDA COVERSHEET OR SUBMIT |
| THE FENESTRATION REPORT FOR LOCAL |
| PRODUCT APPROVAL WITH THE REQUIRED THIRD |
| PARTY QUALITY ASSURANCE ENTITY LISTED |
| WITH THE STATE. |
| WITHOUT THE PROPER REPORTS THE DESIGN |
| PRESSURES CAN NOT BE DETERMINED, ONCE |
| THE CORRECT PRODUCT APPROVAL ARE |
| SUBMITTED THEY WILL BE REVIEWED FOR CODE |
| COMPLIANCE. |
| |
| 4) THE SAME HOLDS TRUE FOR MULLIONS, NO |
| REPORT (NOA) WAS SUBMITTED, ONLY THE FL |
| COVERSHEET. |
| 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |