2005-10-04 00:00:00 | |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} ALL DRAWINGS SHALL BEAR THE NAME AND |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| THE DESIGN. 104.2.1 FBC. |
| IF A ARCHITECT OR THE ENGINEER WHO'S |
| TITLE BLOCK APPEARS ON THE PLAN, COMPLY |
| WITH ARTICLES 481 AND 471 RESPECTIVELY. |
| |
| 2} SUBMIT THE AIC CALCULATIONS FOR THE |
| SERVICE AND INDICATE THE AIC RATING OF |
| THE EQUIPMENT PER 110.9 & 10. |
| |
| 3}THE GROUNDING ELECTRODE SYSTEM NEEDS |
| TO ORIGINATE FROM ONE POINT. THE RISER |
| HAS TWO, ONE FROM THE METER AND ONE FROM |
| THE PANEL. SEE 250.36(F) FOR LOCATION |
| PERMITTED. |
| |
| 4} THE DINING ROOM CIRCUIT MUST COMPLY |
| WITH 210.52(B)(1), 20 AMP #12 WIRE, SEE |
| CIRCUIT #1 ON THE PANEL SCHEDULE. |
| |
| 5} THE "JACUZZI TUB" MUST BE GFI |
| PROTECTED PER 680.71. PLEASE INDICATE |
| SAME ON PLANS. |
| |
| 6} PLEASE VERIFY THE WATER HEATER AT |
| 2500 WATTS. SEE LOAD CALC. |
| |
| 7} THE PENINSULA RECEPTACLE(S) MUST |
| COMPLY WITH 210.52(C)(3). |
| |
| 8} SMOKE DETECTORS ARE REQUIRED PER |
| NFPA-72, AND 905.2 FBC. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |
| [email protected] |
| FAX/:561/659-8026 |
| |
| |