Plan Review Details - Permit 05091241
Plan Review Stops For Permit 05091241
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-17 Cont ID  
Sent By jgomez Date 2006-02-17 Time 11:16 Rev Time 0.40
Received By jgomez Date 2006-02-17 Time 07:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-01-25 Cont ID  
Sent By jgomez Date 2006-01-25 Time 15:37 Rev Time 0.50
Received By jgomez Date 2006-01-25 Time 15:37 Sent To PC
Notes
2006-01-25 00:00:00BUILDING REVIEW 3RD CHECKLIST:
 1- DETAIL G: SOFFIT CONNECTION
 DETAIL ON SHEET 3 OF 5 OF DRAWING 05-417
 IS LIMITED TO 84" MAX. PANEL SPAN FOR
 57PSF DESIGN PRESSURES. ACCORDION
 SHUTTERS FOR OPENINGS #1, #2, #5, #9,
 #10, #15, #17, #18 DON'T WORK.
  
 ***NOTE:
 MAKE SURE SHUTTER SPAN IS MEASURED
 PROPERLY.
  
 2- INSTALLATION SCHEDULE AND KEY PLAN
 DON'T MATCH.DIMENSIONS ARE DIFFERENT.
 DON'T KNOW WHICH ONE HAS THE CORRECT
 DIMENSIONS.
  
 3- INSTALLATION SCHEDULE IS INCOMPLETE.
 SOME OPENINGS ARE MISSING THE
 DIMENSIONS. SOME OPENINGS ARE MISSING
 THE DESIGN PRESSURES. REVISE AS
 REQUIRED. USE ATTACHED COPY OF
 INSTALLATION SCHEDULE THAT WAS REVISED
 TO FACILITATE PLAN REVIEW, INSPECTIONS
 AND EVEN INSTALLATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-21 Cont ID  
Sent By jgomez Date 2005-12-21 Time 12:15 Rev Time 0.50
Received By jgomez Date 2005-12-21 Time 12:15 Sent To PC
Notes
2005-12-21 00:00:00BUILDING REVIEW CHECKLIST:
 1- FLORIDA PRODUCT APPROVALS COVER PAGES
 SUBMITTED AND DRAWINGS SUBMITTED DON'T
 MATCH. NEED TO PROVIDE THE EXACT SAME
 DRAWINGS THAT WERE SUBMITTED TO OBTAIN
 THE FLORIDA PRODUCT APPROVAL.
  
 2- ACCORDING TO THE KEY PLAN THERE ARE
 20 ACCORDION SHUTTERS, 4 ALUMINUM PANELS
 AND 1 STEEL PANEL. NEED PRODUCT APPROVAL
 FOR A)STEEL PANELS,B)ALUMINUM PANELS
 ANDC) ACCORDION SHUTTERS. PACKAGE
 SUBMITTED ON ITEM #1 WAS MISSING THE
 STEEL PANELS PRODUCT APPROVALS.
  
 3- A) WHEN SUBMITTING DRAWINGS THAT
 MATCH FLORIDA PRODUCT APPROVAL, PLEASE
 MAKE SURE THAT ANCHOR SPACING SPECIFIED
 IS IN CONFORMANCE WITH ANCHOR SCHEDULE
 SHOWNON DRAWINGS. ANCHOR SCHEDULE
 SUBMITTED NOW DOESN'T WORK.
  
 B) INSTALLATION SCHEDULE IS MISSING
 ANCHOR SPACING FOR OPENINGS #10, #11.
  
 C) CLEARLY INDICATE WHICH SHUTTERS
 ARESTEEL AND WHICH ARE ALUMINUM. ALSO,
 CLEARLY INDICATE IN DRAWINGS ANCHOR
 SCHEDULE SPECIFIC MOUNTING CONDITIONS
 AND ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURE, EDGE
 DISTANCE, CONNECTION TYPE ANC STRUCTURE
 TO BE ATTACHED TO (CONCRETE, CONCRETE
 BLOCK OR WOOD) TO VERIFY COMPLIANCE WITH
 THE PROPOSED INSTALLATION. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 **NOTE: ATTACHED IS A REVISED SAMPLE OF
 INSTALLATION SCHEDULEWHICH SUMMARIZES
 ALLREQUIRED INFORMATION FOR PLAN
 REVIEW AND IS VERY HELPFUL FOR
 INSPECTORS, PLAN REVIEWERS AND EVEN
 INSTALLERS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-22 Cont ID  
Sent By jgomez Date 2005-11-22 Time 09:29 Rev Time 0.50
Received By jgomez Date 2005-11-22 Time 09:28 Sent To PC
Notes
2005-11-22 00:00:00BUILDING REVIEW CHECKLIST:
 1- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS IF WORK IS NOT STARTED.
 NEED RE-RECORDED NOC.
  
 2- PROVIDE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL FOR:
 A) ACCORDION SHUTTERS, B) ALUMINUM
 PANELS AND C) STEEL PANELS AS REQUIRED
 BY RULE 9B-72 OF DCA. SEE THE WEBSITE
 WWW.FLORIDABUILDING.ORG FOR REQUIRED
 INFORMATION. DADE COUNTY NOA ALONE IS
 NOT AUTOMATICALLY AN STATE WIDE FLORIDA
 PRODUCT APPROVAL.
  
 3- KEY PLAN AND INSTALLATION SCHEDULE
 DON'T MATCH. REVISE AS REQUIRED.
  
 4- INSTALLATION SCHEDULE: CLEARLY
 INDICATE WHICH OPENINGS WILL HAVE STEEL
 PANELS, ALUMINUM PANELS OR ACCORDION
 SHUTTERS AND CLEARLY SPECIFY ANCHOR TYPE
 FOR EACH OPENING. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 5- CONTRACTOR TO UPDATE WORKER'S COMP.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-16 Cont ID  
Sent By adarroug Date 2006-02-16 Time 11:18 Rev Time 0.00
Received By adarroug Date 2006-02-16 Time 11:18 Sent To B
Notes
2006-02-16 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 13:13 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 13:13 Sent To B
Notes
2006-01-22 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-15 Cont ID  
Sent By adarroug Date 2005-12-15 Time 16:38 Rev Time 0.00
Received By adarroug Date 2005-12-15 Time 16:38 Sent To B
Notes
2005-12-15 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-26 Cont ID  
Sent By adarroug Date 2005-09-26 Time 18:55 Rev Time 0.00
Received By adarroug Date 2005-09-26 Time 18:55 Sent To B
Notes
2005-09-26 00:00:00TO "MISC" BOX#1