Plan Review Details - Permit 05091161
Plan Review Stops For Permit 05091161
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-15 Cont ID  
Sent By jgomez Date 2005-12-15 Time 18:37 Rev Time 0.33
Received By jgomez Date 2005-12-15 Time 18:37 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-22 Cont ID  
Sent By jgomez Date 2005-11-22 Time 17:00 Rev Time 0.33
Received By jgomez Date 2005-11-22 Time 17:00 Sent To PC
Notes
2005-11-22 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
  
 2- DESIGN PRESSURES INDICATED ON THE
 WIND LOAD CHART TAKEN FROM THE FBC 2001
 ARE INCORRECT. THE EFFECTIVE AREA
 (TRIBUTARY AREA FOR THE ANCHORS) SHALL
 BE 10PSF NOT 100PSF. REVISE AS REQUIRED.
 OR PROVIDE COMPLETE ENGINEERING ANALYSIS
 STATING WHY USING THE 100PSF AS THE
 EFFECTIVE WIND AREA. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 3- ANCHOR SCHEDULE IN STORM PANELS
 ENGINEERED DRAWINGS: A) REVISE MARKED
 ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE REVISED DESIGN
 PRESSURES REQUESTED ON ITEM #2 ABOVE.
 B) CIRCLE ONLY THE ANCHOR TYPE AND
 SPACING THAT APPLY TO THIS JOB.
  
 4- CONTRACTOR TO UPDATE LICENSE WITH THE
 FRONT COUNTER PERMIT SPECIALISTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-10 Cont ID  
Sent By adarroug Date 2005-12-10 Time 14:45 Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 14:45 Sent To B
Notes
2005-12-10 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 17:42 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 17:42 Sent To B
Notes
2005-09-23 00:00:00TO "MISC" BOX#1