Plan Review Details - Permit 05091007
Plan Review Stops For Permit 05091007
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-11 Cont ID  
Sent By jgomez Date 2005-10-11 Time 16:58 Rev Time 0.00
Received By jgomez Date 2005-10-11 Time 17:36 Sent To  
Notes
2005-10-11 00:00:00BUILDING REVIEW CHECKLIST:
 1-A) ENGINEER CALCULATIONS: CLARIFY WHY
 THE EXTERIOR PARTITION DESIGN LOADS
 CHART SHOWS INTERNAL PRESSURE OF 0.00.
 IT'S NOT CLEAR IF THE DESIGN ASSUMPTION
 IS THAT BUILDING IS ENCLOSED OR
 PARTIALLY ENCLOSED SINCE NO VALUE WAS
 ENTERED. ENGINEER TO REVISE/CLARIFY AS
 REQUIRED. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 B) ENGINEER TO CLARIFY IF DOOR WILL BE
 USED AS PART OF THE BUILDING ENVELOPE OR
 NOT. SEE NOTE REGARDING THE DESIGN
 PRESSURES ON ITEM #3 OF THIS WIND
 CALCULATIONS SHEET WHICH SAYS THAT
 "THESE LOADS ARE NOT INTENDED FOR USE
 WITH COMPONENTS THAT PROTECT OR CREATE A
 BUILDING ENVELOPE".
  
 2- CLEARLY SPECIFY ON SHEET 2 OF 4
 SPECIFIC DOOR MODULE AND GLASS TYPE TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER.
  
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-11 Cont ID  
Sent By jgomez Date 2005-10-11 Time 17:36 Rev Time 0.00
Received By jgomez Date 2005-09-21 Time 19:57 Sent To  
Notes
2005-09-21 00:00:00TO "MISC" BOX#1