2005-10-08 00:00:00 | ******** UNSAT ********** |
| |
| 1)NOTE: PLEASE SEE TWO INDIVIDUAL TH |
| UNITS ARE BEING CONVERTED INTO ONE. |
| PLEASE SEE ELECTRICAL SERVICE SHALL |
| CONTAIN ONLY ONE MAIN AND ONE SERVICE. |
| PLEASE SUBMIT RISER DIAGRAM WITH REVISED |
| ELECTRICAL FOR NEW WORK TO BE DONE. |
| 230.2. |
| |
| |
| 2)NOTE: PLEASE SEE RECEPTS AT KITCHEN |
| COUNTERSPACE, BATH RM AND GARAGE ARE ALL |
| TO BE GFI / GFI PROTECTED. |
| 210.8A6,210.8A1, 210.8A2 |
| |
| 3)NOTE: PLEASE PROVIDE A REVISED PANEL |
| SCHEDULE FOR NEW ELECTRICAL WORK. |
| WASHER, DRYER, DEDICATED BRANCH CIRCUITS |
| REQUIRED UNDER 210.52D, 210.52B1, |
| 210.11C1,C3 ETC. |
| 215.5 |
| |
| 4)NOTE: PLEASE PROVIDE ALL ROOM/AREA |
| DESIGNATIONS ON PLANS. |
| PLEASE ALSO IDENTIFY FLRS. |
| 215.5 |
| |
| 5)NOTE: PLEASE SEE WATER HEATER SHOWN |
| MAY NOT BE LOCATED IN A CLOSET |
| CONTAINING COMBUSTIBLES. 422.17 |
| |
| 6)NOTE: PLANS SHALL CONTAIN THE PRINTED |
| NAME AND THE SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR PLANS/DESIGN. |
| FBC 104.2.1, CITY WIDE ADMINISTRATIVE |
| CODE. |
| |
| 7)NOTE: PLEASE SEE SWITCHES CONTROLING |
| LITGHTING ETC FROM TWO OR MORE LOCATIONS |
| ARE 3-WAY SWITCHES. PLEASE SEE MISPRINT |
| ON PLANS WHICH INDICATE A SWITCH WITH 2? |
| AND LISTED ON SYMBOL SCHEDULE AS 2-WAY? |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |