Plan Review Details - Permit 05090882
Plan Review Stops For Permit 05090882
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-09-01 Cont ID  
Sent By mjacobs Date 2006-09-01 Time 07:23 Rev Time 0.00
Received By mjacobs Date 2006-09-01 Time 06:58 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-07-13 Cont ID  
Sent By mjacobs Date 2006-07-13 Time 14:41 Rev Time 0.00
Received By mjacobs Date 2006-07-13 Time 14:24 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-04-07 Cont ID  
Sent By mjacobs Date 2006-04-07 Time 16:49 Rev Time 0.00
Received By mjacobs Date 2006-04-07 Time 14:46 Sent To Z
Notes
2006-04-07 00:00:00 
  
 1) AWNINGS SHALL BE DESIGNED SO THAT
 FABRIC OR MEMBRANE COVER CAN BE QUICKLY
 AND EASILY REMOVED PER 3105.4.2.1.
 TIGHTLY WRAPED OR WOVEN CORDS ARE NOT
 ACCEPTABLE. PLEASE SUBMIT A DETAIL
 DRAWING OF COVER ATTATCHMENT METHOD.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-27 Cont ID  
Sent By mjacobs Date 2006-02-27 Time 14:51 Rev Time 1.00
Received By mjacobs Date 2006-02-27 Time 14:51 Sent To PC
Notes
2006-02-27 00:00:001) PLEASE SEE PREVIOUS NOTES ABOUT
 WHITE-OUT ON PLANS. AGAIN NO WHITE-OUT
 OR HAND WRITING ARE ALLOWED ON PLANS.
 THE BUILDING OFFICIAL MAY SET STANDARDS
 THROUGH DEPARTMENTAL POLICY STANDARDS
 FOR PLANS AND CONFORMITY TO ITS RECORD
 RETENTION PROGRAM."NO WHITE OUT OR HAND
 WRITING ON PLANS".THE ONLY PERSON
 ALLOWED TO MAKE CHANGES ON THE PLANS IS
 THE DESIGNER OF RECORD. ALL CHANGES
 SHALL BE INITIAL AND DATED BY THAT
 PERSON.SEE THE CITY OF
 W.P.B.AMENMENDMENTS 106.1.3.
  
 2) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-08 Cont ID  
Sent By mjacobs Date 2006-02-08 Time 15:11 Rev Time 1.50
Received By mjacobs Date 2006-02-08 Time 13:38 Sent To PC
Notes
2006-02-08 00:00:001)106.1.3 THE BUILDING OFFICIAL MAY
 SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND
 SPRCIFICATIONS IN ORDER TO PRIVIDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. "NO WHITE OUT". THE ONLY PERSON
 WHO CAN MAKE CHANGES ON THE DRAWINGS IS
 THE DESIGNER OF SUCH DRAWINGS.ALL
 CHANGES SHALL BE INITIAL AND DATED BY
 THAT PERSON.
  
 2) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-14 Cont ID  
Sent By mjacobs Date 2005-11-14 Time 16:15 Rev Time 2.00
Received By mjacobs Date 2005-11-14 Time 13:04 Sent To PC
Notes
2005-11-14 00:00:00 
 1) 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2) THE AWNING SHALL BE DESIGNED TO THE
 140MPH BASIC WIND SPEED WITH THE COVER
 IN PLACE.SEE F.B.C SEC.1606.1.6 AND
 1606.1.7.
  
 3) WHAT TYPE OF STRUCTURE WILL THE
 AWNING BE ANCHORED INTO? IS IT
 CONCRETE/BLOCK/WOOD OR HOLLOW CLAY TILE?
  
 4)SUBMIT THE CERTIFICATE SHOWING THE
 FLAME SPREAD RATING OF THE AWNING
 MATERIAL.SEE F.B.C SEC.3204.2.
  
 5) SUBMIT A SURVEY OR SITE PLAN SHOWING
 THE SIDEWALK WIDTH. THE FIXED AWNING
 SHALL NOT EXTEND OR OCCUPY NOR THAN
 TWO-THIRDS OF THE SIDEWALK. FBC 3204.3.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX(561)659-8026
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-08-31 Cont ID  
Sent By adarroug Date 2006-08-31 Time 15:14 Rev Time 0.00
Received By adarroug Date 2006-08-31 Time 15:14 Sent To B
Notes
2006-08-31 00:00:00TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 13:36 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 13:36 Sent To Z
Notes
2006-08-12 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-16 Cont ID  
Sent By adarroug Date 2006-06-16 Time 10:56 Rev Time 0.00
Received By adarroug Date 2006-06-16 Time 10:56 Sent To B
Notes
2006-06-16 00:00:00TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-06 Cont ID  
Sent By adarroug Date 2006-04-06 Time 10:28 Rev Time 0.00
Received By adarroug Date 2006-04-06 Time 10:28 Sent To B
Notes
2006-04-06 00:00:00TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-08 Cont ID  
Sent By adarroug Date 2006-03-08 Time 16:35 Rev Time 0.00
Received By adarroug Date 2006-03-08 Time 16:35 Sent To Z
Notes
2006-03-08 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-27 Cont ID  
Sent By adarroug Date 2006-02-27 Time 09:22 Rev Time 0.00
Received By adarroug Date 2006-02-27 Time 09:22 Sent To B
Notes
2006-02-27 00:00:00TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-07 Cont ID  
Sent By adarroug Date 2006-02-07 Time 12:18 Rev Time 0.00
Received By adarroug Date 2006-02-07 Time 12:18 Sent To B
Notes
2006-02-07 00:00:00TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-04 Cont ID  
Sent By adarroug Date 2005-10-04 Time 15:36 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 15:36 Sent To B
Notes
2005-10-04 00:00:00TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 10:59 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 10:59 Sent To Z
Notes
2005-09-21 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 4 Status P Date 2006-08-28 Cont ID  
Sent By astelly Date 2006-08-28 Time 09:10 Rev Time 0.00
Received By astelly Date 2006-08-28 Time 09:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-05-09 Cont ID  
Sent By astelly Date 2006-05-09 Time 10:36 Rev Time 0.00
Received By astelly Date 2006-05-09 Time 10:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-04-04 Cont ID  
Sent By astelly Date 2006-04-04 Time 14:54 Rev Time 0.00
Received By astelly Date 2006-04-04 Time 14:54 Sent To  
Notes
2006-04-04 00:00:00PLANS WITH WITE-OUT CANNOT BE REVIEWED.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-10-03 Cont ID  
Sent By astelly Date 2005-10-03 Time 11:44 Rev Time 0.00
Received By astelly Date 2005-10-03 Time 11:43 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved