Plan Review Details - Permit 05090861
Plan Review Stops For Permit 05090861
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-12-10 Cont ID  
Sent By kstevens Date 2005-12-10 Time 11:22 Rev Time 1.00
Received By kstevens Date 2005-12-10 Time 11:22 Sent To  
Notes
2005-12-10 00:00:00.
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.
  
 IF DRYER ROOM IS A CONFINED SPACE,
 OPENINGS REQUIRED PER SECTION 304.3.1 0R
 SECTION 304.3.2 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED. - W/H
 ROOM REQUIRES MINIMUM 2,000 CUBIC FEET
 IF IN A CONFINED SPACE. 2,000 CU REQD.
 FOR FIRE PLACE.
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-10-04 Cont ID  
Sent By jleech Date 2005-10-04 Time 10:13 Rev Time 0.33
Received By jleech Date 2005-10-04 Time 10:13 Sent To  
Notes
2005-10-04 00:00:00DENIED;
 A GEN-RES PERMIT MUST BE APPLIED FOR AND
 APPROVED BY ZONING BEFORE GAS
 APPLICATION CAN BE REVIEW.
 GAS REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2005-09-20 Cont ID  
Sent By dalvarez Date 2005-09-20 Time 10:56 Rev Time 0.00
Received By dalvarez Date 2005-09-20 Time 10:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-30 Cont ID  
Sent By adarroug Date 2005-11-30 Time 09:31 Rev Time 0.00
Received By adarroug Date 2005-11-30 Time 09:31 Sent To G
Notes
2005-11-30 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-20 Cont ID  
Sent By adarroug Date 2005-09-20 Time 16:14 Rev Time 0.00
Received By adarroug Date 2005-09-20 Time 16:14 Sent To G
Notes
2005-09-20 00:00:00TO "G" BOX