Plan Review Stops For Permit 05090826 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
P |
Date |
2007-03-19 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-03-19 |
Time |
10:11 |
Rev Time |
2.00 |
Received By |
jgomez |
Date |
2007-03-19 |
Time |
07:41 |
Sent To |
PC |
|
Notes |
2007-03-19 12:37:23 | BUILDING REVIEW PROVISO: | | 1- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS | | UNDER A SEPARATE PERMIT. INCLUDE COMPLETE STORM | | SHUTTERS INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE. | | | | 2- PROVIDE PRODUCT APPROVAL FOR 8'-0" WIDE SLIDING | | GLASS DOORS AS SHOWN ON PLANS. TWO COPIES. ARCHITECT TO | | REVIEW PRODUCT APPROVAL PRIOR TO SUBMITTAL. | | | | 3- ARCHITECT TO REVIEW AND APPROVE IN WRITING PRODUCT | | APPROVALFOR ROOF SHINGLES AS REQUIRED BY SEC. 108.3 | | CITY AMENDMENTS TO FBC 2004. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
F |
Date |
2007-03-02 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-03-02 |
Time |
17:16 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-03-02 |
Time |
17:16 |
Sent To |
|
|
Notes |
2007-03-02 19:03:50 | BUILDING REVISION THIRD CHECKLIST: | | 1- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS IF | | WORK IS NOT STARTED. NEED RE-RECORDED NOTICE OF | | COMMENCEMENT. | | | | 2- BRING DRAWINGS TO PALM BEACH COUNTY FOR IMPACT FEES | | REVISION. BRING BACK STAMPED DRAWINGS AND PAID RECEIPT | | IF ADDITIONAL FEES ARE DUE. | | | | 3- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS. | | | | 4- OWES $788.35 FOR UPDATED PERMIT VALUATION AND RADON | | FEES. | | ***NOTE: FEES TO BE PAID AT TIME OF NEXT SUBMITTAL. | | PLAN REVIEW WILL NOT BE DONE UNTILALL FEES ARE PAID. | | | | | | 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE | | 9B-72 FOR: | | A) IMPACT SLIDING GLASS DOORS AS SPECIFIED ON | | ARCHITECT'S PLANS. | | | | 6- ARCHITECT TO PROVIDE THE FIRM LICENSE NUMBER AS | | REQUIRED BY SEC. 61G1-16.004 OF FLORIDA ADMINISTRATIVE | | CODE. | | | | 7- CLARIFY WHY IS ARCHITECT APPROVING PRODUCT APPROVAL | | FOR 4", 6" AND 12" CONCRETE LINTELS IF THERE ARE NO | | SUCH TYPE OF LINTELS SPECIFIED ON PLANS. | | | | 8- NEED TO ADDRESS ELECTRICAL COMMENTS ALSO. ***NOTE: | | WHEN RE-SUBMITTING MAKE SURE PROPER PLAN REVIEW TRADES | | ARE INDICATED ON THE RE-SUBMITTTAL FORM TO EXPEDITE THE | | REVIEW PROCESS. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2007-01-22 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-01-22 |
Time |
13:43 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-01-22 |
Time |
07:44 |
Sent To |
|
|
Notes |
2007-01-22 14:04:37 | BUILDING REVISION SECOND CHECKLIST (REVISION DONE UNDER | | FBC 2004 AS SPECIFIED ON PLANS): | | 1- TRUSS DRAWINGS WILL BE REQUIRED FOR REVIEW PRIOR TO | | INSTALLATION. SEE SEC. R802.10 FOR REQUIRED | | INFORMATION. DESIGNER OF RECORD TO REVIEW AND APPROVE | | THEM PRIOR TO SUBMITTAL TO THIS OFFICE. | | | | 2- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF | | BEING RECORDED IF WORK IS NOT STARTED. SEC. 713.13(2) | | FLORIDA STATUTES. NEED RE-RECORDED NOTICE OF | | COMMENCEMENT. | | | | 3- A) REVISE THE ENERGY CALCULATIONS. OVERHANG LENGTH | | AND OVERHANG HEIGHT ARE INCORRECT. | | | | B) COMPLETE ALL INFORMATION ON TOP OF FORM. | | | | 4- BRING DRAWINGS TO PALM BEACH COUNTY FOR IMPACT FEES | | REVISION. BRING BACK STAMPED DRAWINGS AND PAID RECEIPT | | IF ADDITIONAL FEES ARE DUE. | | | | 5- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS | | UNDER A SEPARATE PERMIT AS AGREED ON AT TIME OF | | ORIGINAL PERMIT APPLICATION APPROVAL. | | | | 6- OWES $788.35ADDITIONAL FEES FOR UPDATED BUILDING | | VALUATION,RADON FEES AND REVISION FEES.. | | | | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 | | FOR: | | A) INSWING ENTRY DOOR AS SHOWN ON PLANS. | | B) IMPACT SLIDING GLASS DOORS AS SPECIFIED ON | | PLANS. | | C) PRECAST CONCRETE LINTELS AS SPECIFIED ON PLANS. | | D) ALL SIMPSON OR USP CONNECTORS SPECIFIED ON | | FRAMING PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA | | PRODUCT APPROVAL COVER PAGE AND THE SPECIFIC PAGE | | SHOWING THE CONNECTOR. | | E) SINGLE HUNG WINDOWS. | | | | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITTING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | PRODUCT APPROVAL FOR TIBERLINE SHINGLES IS MISSING THE | | ARCHITECT'S SIGNATURE. | | | | 9- ARCHITECT TO PROVIDE ALL HIS INFORMATION AND FIRM'S | | INFORMATION AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA | | ADMINISTRATIVE CODE. MISSING THE FIRM'S NUMBER. | | | | 10- SHEET A-2.1: | | A) FLOOR PLAN CALLS FOR ONE 16'X7' GARAGE DOOR. | | ELEVATION SHOWS 2 SMALL GARAGE DOORS.PRODUCT APPROVAL | | FOR GARAGE DOORS DON'T SHOW DOOR TO LOOK LIKE 2 DOORS | | IN ONE. HOW IS THIS ACHIEVED. SEC. 106.1.2 CITY | | AMENDMENTS TO FBC 2004 | | | | 11- SHEET S-2: | | A) DETAIL 1/S-2 CALLS FOR (3)2X4 STUDS, WHILE 2ND | | FLOOR FRAMING PLAN CALLS FOR (4)2X4 STUDS. | | CLARIFY/REVISE AS REQUIRED TO MATCH. | | | | 19- SHEET S-3: | | A) REVISE PLYWOOD SHEATHING NAILING SCHEDULE FOR | | ROOF SHEATHING AT ZONE 3. SEE TABLE 2304.9.1 FBC 2004 | | AND REVISE AS REQUIRED. | | | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2006-11-16 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2006-11-15 |
Time |
17:58 |
Rev Time |
3.50 |
Received By |
jgomez |
Date |
2006-11-15 |
Time |
17:52 |
Sent To |
|
|
Notes |
2006-11-16 11:34:34 | BUILDING REVISION CHECKLIST (REVISION DONE UNDER FBC | | 2004 AS SPECIFIED ON PLANS): | | 1- SHEET A-1.0: | | A) REVISE TYPE OF CONSTRUCTION. SEE SEC. 602 FBC | | 2004. TYPE OF CONSTRUCTION SHOWN ON PLANS APPLIES TO | | TYPE IIIB. | | B) ADD 2004 FLORIDA RESIDENTIAL CODE, WHICH IS THE | | ONE THAT APPLIES TO SINGLE FAMILY RESIDENCES. | | C) AREA CALCULATIONS ON SHEET A-1.0 ARE DIFFERENT | | THAN THOSE SHOWN ON SHEET A-1.1. REVISE AS REQUIRED. | | | | 2- TRUSS DRAWINGS WILL BE REQUIRED FOR REVIEW PRIOR TO | | INSTALLATION. SEE SEC. R802.10 FOR REQUIRED | | INFORMATION. | | | | 3- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF | | BEING RECORDED IF WORK IS NOT STARTED. SEC. 713.13(2) | | FLORIDA STATUTES. NEED RE-RECORDED NOTICE OF | | COMMENCEMENT. | | | | 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY CHAPTER | | 13 FBC 2004. | | | | 5- BRING DRAWINGS TO PALM BEACH COUNTY FOR IMPACT FEES | | REVISION. BRING BACK STAMPED DRAWINGS AND PAID RECEIPT | | IF ADDITIONAL FEES ARE DUE. | | | | 6- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS | | UNDER A SEPARATE PERMIT AS AGREED ON AT TIME OF | | ORIGINAL PERMIT APPLICATION APPROVAL. | | | | 7- OWES ADDITIONAL FEES FOR UPDATED BUILDING VALUATION | | AND RADON FEES. FEES WILL BE CALCULATED WHEN ITEM 1(C) | | ABOVE IS CLARIFIED. | | | | 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 | | FOR: | | A) INSWING ENTRY DOOR AS SHOWN ON PLANS. | | B) IMPACT SLIDING GLASS DOORS AS SPECIFIED ON | | PLANS. | | C) PRECAST CONCRETE LINTELS AS SPECIFIED ON PLANS. | | D) ALL SIMPSON OR USP CONNECTORS SPECIFIED ON FRAMING | | PLANS AND DETAILS. | | E) GARAGE DOOR. NEED CLEAR AND LEGIBLE DRAWINGS. | | CLARIFY IF USING THE DADE COUNTY NOA OR FLORIDA PRODUCT | | APPROVAL 4861. PROVIDE COMPLETE PACKAGE FOR EITHER ONE, | | BUT DON'T MISMATCH ONE WITH THE OTHER. | | F) ASPHALT SHINGLES. DOWNLOAD DADE COUNTY NOA | | 04-0305.03 WHICH IS THE CORRECT NOA THAT WAS SUBMITTED | | TO OBTAIN FLORIDA PRODUCT APPROVAL #FL183-R1. GO TO | | WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL INFORMATION. G) | | SINGLE HUNG WINDOWS. | | | | 9- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITTING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | 10-SPECIFY SAFETY GLASS IN WINDOW LOCATED IN MASTER | | BATH TUB. SEC. R308.4 2004 FLORIDA RESIDENTIAL CODE. | | | | 11- 2ND FLOOR ATTIC ACCESS SHALL BE IN HALLWAY OR | | ALREADY ACCESSIBLE LOCATION. REVISE AS REQUIRED. SEC. | | R807.1 2004 FLORIDA RESIDENTIAL CODE. | | | | 12- ENGINEER TO PROVIDE ALL HIS INFORMATION AND FIRM'S | | CERTIFICATE OF AUTHORIZATION AS REQUIRED BY SEC. | | 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. | | | | 13- ARCHITECT TO PROVIDE ALL HIS INFORMATION AND FIRM'S | | INFORMATION AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA | | ADMINISTRATIVE CODE. | | | | 14- SURVEY TO HAVE ORIGINAL SIGNATURE AS REQUIRED BY | | CHAPTER 472 FLORIDA STATUTES. | | | | 15- SHEET A-2.1: | | A) FLOOR PLAN CALLS FOR ONE 16'X7' GARAGE DOOR. | | ELEVATION SHOWS 2 SMALL GARAGE DOORS. CLARIFY/REVISE AS | | REQUIRED TO MATCH. | | B) REVISE ELEVATIONS ORIENTATION. SEE SURVEY FOR | | CORRECT ORIENTATION. | | | | 16- SHEET A-3.1: | | A) PORCH SECTION AND TYP. WALL SECTION CALL FOR | | "ASPHALT TILE ROOF". CLARIFY WHAT IS IT?. REVISE AS | | REQUIRED. | | B) CHANGES DONE BY HAND ARE NOT ACCEPTABLE. EG: | | STUCCO THICKNESS. REVISE ORIGINAL DRAWINGS AS | | REQUIRED. | | | | 17- SHEET A-4.1: | | A) DETAIL #1 IS FOR WINDOW AND DOOR BUCK DETAIL. | | CLARIFY TITLE SAYS WINDOW, WHILE DETAIL SAYS DOOR | | FRAME. | | B) THERE ARE TWO DIFFERENT SPECS FOR BUCK FASTENING. | | SEE DETAIL 1 AND WINDOW/DOOR BUCK NOTES ON SHEET S-2 | | AND REVISE AS REQUIRED. | | C) HURRICANE PANEL DETAIL: EDGE DISTANCE IS | | INCORRECT. STUCCO THICKNESS CAN'T BE CONSIDERED FOR | | EDGE DISTANCE. REVISE AS REQUIRED. SEE ACTUAL STORM | | PANELS PRODUCT APPROVAL. | | ***NOTE: THIS DETAIL IS NOT REQUIRED. IT'S EASIER AND | | WILL AVOID DISCREPANCIES IF ONLY THE PRODUCT APPROVAL | | FOR STORM SHUTTERS IS SUPLLIED WHEN APPROVED BY THE | | DESIGNER OF RECORD. | | D) SECTION AT REAR PORCH: SPECIFY LEDGERS FOR ROOF | | SHEATHING SUPPORT AT MASONRY WALL. SEC. 106.1.2 CITY | | AMENDMENTS TO FBC 2004. | | C) SPECIFY FIREBLOCKING. SEC. R602.8 2004 FLORIDA | | RESIDENTIAL CODE. | | | | 18- SHEET S-2: | | A) REVISE WINDOW NOTES. NEED WINDOWS FOR 140 MPH | | INSTALLATION, NOT 120. REVISE ORIGINAL DRAWING. HAND | | CHANGES ARE NOT ACCEPTABLE. | | B) BEARING WALL CONNECTION TO CBS DETAIL AND DETAIL | | 1/S-2: CLARIFYIF USING SIMPSON OR USP CONNECTORS. C) | | DETAIL 1/S-2 CALLS FOR (3)2X4 STUDS, WHILE 2ND FLOOR | | FRAMING PLAN CALLS FOR (4)2X4 STUDS. CLARIFY/REVISE AS | | REQUIRED TO MATCH. | | D) SPECIFY ROOF TRUSS CONNECTORS FOR REAR PORCH | | ROOF. | | | | 19- SHEET S-3: | | A) REVISE PLYWOOD SHEATHING NAILING SCHEDULE FOR | | ROOF SHEATHING. SEE TABLE 2304.9.1 FBC 2004 AND REVISE | | AS REQUIRED. | | B) SPECIFICATION GIVENON PLYWOOD SHEATHING NAILING | | SCHEDULE AND OVERHANG DETAIL DON'T MATCH. REVISE AS | | REQUIRED. | | C) CONNECTOR SCHEDULE: REVISE UPLIFT AND FASTENERS | | SPECIFIED FOR SIMPSON HETAL 16 AND SP4. SEE CURRENT | | CATALOGUE AND UPDATE AS REQUIRED. OTHERWISE, PROVIDE | | COMPLETE ENGINEERING ANALYSIS FOR VALUES AND NUMBERS | | THAT ARE DIFFERENT FROM THOSE TESTED AND PUBLISHED BY | | MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC | | 2004. | | D) MAXIMUM DESIGN PRESSURES SHOWN ARE LOW COMPARED | | TO TABLE 1609.6B OR TABLES IN ASCE 7-02.PROVIDE | | ACTUAL CALCULATIONS SHOWING HOW THE MAXIMUM POSITIVE | | AND NEGATIVE LOADS ARE DETERMINED. SEC. 106.1.2 CITY | | AMENDMENTS TO FBC 2004. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
N |
Date |
2006-01-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-01-09 |
Time |
10:33 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2006-01-09 |
Time |
10:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-10-03 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-10-03 |
Time |
18:49 |
Rev Time |
0.50 |
Received By |
shill |
Date |
2005-10-03 |
Time |
18:49 |
Sent To |
PC |
|
Notes |
2005-10-03 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2001 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2001 | | | | 1.)ALL INFORMATION REQUIRED BY | | FAC61G15-23.002 IS TO BE ON THE SOILS | | REPORT (CA NUMBER). | | | | 2.)THE SOILS REPORT IS FOR A ONE STORY | | STRUCTURE. | | | | 3.)SHEET 3.1 DOES NOT MATCH THE | | MASTER.NOTES WERE ADDED ON THE NEW | | SHEET PREPARED BY WILLIAM GENZ, PE WHICH | | ARE NOT ON THE MASTER, SEE FLOOR FRAMING | | PLAN, ALTHOUGH THE REVISION NUMBER HAS | | REMAINED THE SAME.THE PLANS SUBMITTED | | TO BE ISSUED FROM A MASTER ARE TO | | EXACTLY MATCH THE MASTER.ANY TIME THAT | | REVISIONS ARE MADE TO ANY PLAN, THE | | DESIGNER IS TO CLEARLY INDICATE ALL | | CHANGES.FOR THE ENGINEER TO MAKE | | REVISIONS WHICH ARE NOT MARKED, | | REPRESENTING THEM AS THE SAME REVISION | | NUMBER AS A PREVIOUSLY APPROVED PLAN, | | DELAYS REVIEW TIME.PLEASE NOTE THAT | | DISCREPANCIES SUCH AS THIS ONE WILL | | RESULT IN THE PLANS BEING ROUTED THROUGH | | ALL TRADES TO ENSURE THAT OTHER CHANGES | | WERE NOT MADE. | | | | 4.)SHEET 5.1 DOES NOT MATCH THE | | MASTER.THE REVISION NUMBERS AND DATES | | ARE NOT THE SAME AS ON THE MASTER. | | | | 5.)IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | AND THE RECEIPT ATTACHED TO THE | | APPLICATION.233-5025 | | | | 6.)PLANS ISSUED FROM A MASTER ARE | | REQUIRED TO INCLUDE ONLY THE FOLLOWING | | SHEETS:FLOOR PLAN (SHEET 4.1) AND | | ELEVATIONS (6.1). | | | | 7.)ADDITIONAL FEES DUE (VALUATION | | ADJUSTMENT), SEE ATTACHED BILL. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
P |
Date |
2007-03-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-03-13 |
Time |
09:58 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-03-13 |
Time |
09:17 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
F |
Date |
2007-02-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-02-25 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-02-25 |
Time |
13:59 |
Sent To |
B |
|
Notes |
2007-02-25 14:16:31 | *** UNSAT *** | | | | | | | | 1) NOTE: PLEASE CLARIFY WHERE THE AIC RATING FOR | | MAIN/SERVICE EQUIPMENT IS STATED ON PLANS. THIS USED TO | | BE ONE PLANS FROM PREVIOUS PROJECTS? | | 110.9 | | PLANS MAY NOT ONLY QUOTE THIS REQUIREMENT. | | | | 2) NOTE: PLEASE SEE NOTE #1 ON RISER USED TO STATE THE | | CONDUIT FROM METER TO PANEL TO BE IN SLAB, HOWEVER THIS | | PART OF THE NOTE HAS BEEN REMOVED. THIS HAS BEEN | | REDLINED ON OTHER SETS OF PLANS WHEN PLANS WERE OK WITH | | OTHER COMMENTS. | | 230.70, 230.71 | | MUST BE IN SLAB OR MUST CONTAIN MAIN WITH OCP OUTSIDE. | | | | 3) NOTE: PLEASE KNOW THAT A MEETING WAS HELD PREVIOUSLY | | WITH DESIGN TEAM REPRESENTATIVES AND INFORMATION WAS | | GIVEN WITH RESPECT TO THE DIFFERENCES OF SD(SMOKE | | DETECTORS) AND SA(SMOKE ALARMS) AND REQUIRED CHANGES | | WHICH WILL NEEDED ON FUTURE PLANS, HOWEVER THIS | | DESIGNATION HAS NOT BEEN CHANGED ON PLANS. | | * | | PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN | | SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY | | INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS | | ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN | | THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS | | OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE | | ALARMS. | | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE | | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. | | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE | | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL | | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY | | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF | | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS | | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS | | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS | | FOR OTHER NEW HOMES. | | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC | | RESIDENTIAL CODE/ FBC AND IN NFPA-72. | | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE*. | | | | 4) NOTE: PLEASE SEE THAT THE FEES OWED PER PREVIOUS | | BUILDING REVIEW COMMENTS HAS NOT BEEN PAID.THIS WAS | | GIVEN AND IS ATTACHED ONCE AGAIN. | | | | ** ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2006-12-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-12-26 |
Time |
12:36 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-12-26 |
Time |
12:31 |
Sent To |
M |
|
Notes |
2006-12-26 12:37:56 | ** UNSAT ** | | | | 1) NOTE: PLEASE SEE HAND DRAWN CHANGES MADE TO | | ELECTRICAL PLANS IN RED PENCIL. PLEASE KNOW THESE ARE | | NOT PERMITTED TO SIGNED AND SEALED PLANS. | | PLEASE SEE ALSO IT APPEARS THESE CHANGES ARE INDICATING | | A RELOCATION OF THE ATTIC ACCESS, LTS, AND SA DEVICE. | | PLEASE BE SURE SHEETS CORRELATE | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2006-08-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-08-10 |
Time |
07:03 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-08-10 |
Time |
06:58 |
Sent To |
P |
|
Notes |
2006-08-10 00:00:00 | **********UNSAT *********** | | | | 1) NOTE: PLEASE CLARIFY UNDERGROUND | | SEC'S TO FPL. IF THESE ARE INSTALLED BY | | FPL , THEN PLEASE DO NOT INDICATE THE | | CONDUCTOR SIZES, AS THESE WILL NOT | | CORRELATE WITH FPL. | | PLEASE ALSO VERIFY THE DOWNSIZING OF THE | | NEURTRAL CONDUCTOR TO A #3. | | PLEASE PROVIDE NEUTRAL LOAD CALCULATION | | OR FULL SIZE NEUTRAL. | | 220.22, 310.15B6 | | | | 2) NOTE: PLEASE SHOW CONDUIT SIZE FOR | | THE UNDERGROUND AND ALSO THE CONDUIT TO | | INSIDE PANEL. UNABLE TO VERIFY AT THIS | | TIME. | | FBC 106.1.2 | | | | 3) NOTE: PLEASE SEE 210.52 AS THERE ARE | | SOME RECEPTS MISSING . SEE REDLINED | | PLANS. | | PLEASE SEE AREA OF WALL OFF KITCHEN AND | | WHAT APPEARS TO BE THE MASTER BEDRM. | | | | 4) NOTE: PLEASE SEE MISSING PENINSULAR | | GFI RECEPT. 210.52C3,210.8A6 | | | | 5) NOTE: PLEASE PROVIDE ALL ROOM AND | | AREA DESIGNATIONS ON PLANS AND CORRELATE | | WITH THE PANEL SCHEDULE. | | PLEASE SEE THAT ALL CIRCUITS ON PANEL | | SCHEDULE SHALL BE SPECIFIC TO ROOMS AND | | AREAS. | | IE; LIVING RM RECEPTS, BEDRM #2 | | LTS/RECEPTS, HALL LTS ETC ETC. | | 408.4 FBC 106.1.2 | | **IT IS KNOWN THAT CIRCUITING DURING | | CONSTRUCTION WILL CHANGE AND THIS CAN EB | | REVISED AT A LATER DATE. | | | | 6) NOTE: PLEASE SEE ONLY TWO CIRCUITS | | ARE BEIGN SHOWNWITH ARC FAULT | | PROTECTION FOR ALL BEDRMS LTS, RECEPTS | | AND SD'S. PLEASE KNOW, THE CODE HAS | | CHANGED FROM PREVIOUSLY SUBMITTED PLANS | | UNDER THIS PROJECT TO REQUIRE ARC FAULT | | PROTECTION FOR ALL OUTLETS IN BEDRMS. | | PLEASE BE SURE TO REVISE AS THE LOAD ON | | THESE ONLY TWO CIRCUITS SEEM TO EXCEED | | RATINGS. | | 210.12B(2002) NEC. 210.52,220 | | | | 7)NOTE: PLEASE SEE MISSING THE REQUIRED | | DEDICATED BATH(S) CIRCUIT(S). | | 210.11C3, SHALL BE 20A AND #12. | | NO BATH(S) LISTED. | | | | 8) NOTE: PLEASE BE SURE HE PLANS PROVIDE | | THE FOLLOWING MINIMUM CODES AS ADOPTED | | FOR DESIGN AND FS/FBC 2004 | | 2002 NFPA-70, 2002 NFPA-72, 2003 | | NFPA-101. | | | | 9) NOTE: PLEASE SEE PLANS INDICATE THE | | PANEL LOCATED IN GARAGE, YET PANEL | | MENTIONS THIS IN HALL/UTILITY. | | | | 10) NOTE: PLEASE SEE MIN EGRESS LIGHTING | | IS REQUIRED FOR WHAT APPEARS TO BE | | DINGIN AND LIV RM FOR EGRESS. SHOWS ONLY | | A JUNCTION BOX FOR FUTURE FAN. PLEASE | | KNOW, THIS CAN BE EITHER PROVIDED BY THE | | SWITCHING OF A RECEPT OR A LT FIXTURE OF | | SOME TYPE WHICH SHALL BE PROIVIDED. | | 210.70, LS101 7.8 | | | | 11) NOTE: PLEASE SEE PLANS SHOWS A METER | | AND A MAIN DISCONNECT ON THE OUTSIDE. IF | | THIS IS THE CASE, PLEASE REVISE RISER TO | | INCLUDE THIS MAIN AND ALSO INCLUDE | | EQUIPMENT GROUNDING CONDUCTORS AS | | REQUIRED. | | 250.24B, 250.122 | | 106.1.2 | | | | 12) NOTE: PLEASE SEE SURVEY PROVIDED IN | | PACKAGE IS REQUIRED TO CONTAIN AN | | ORIGINAL SIAGNAURE IN ORDER FOR SURVEY | | TO BE VALID. PLEASE SEE FAC 61G15-17, FS | | 472.025 | | | | 13) NOTE: PLEASE SEE MISSING THE DINING | | ROOM CIRCUITS ON ONE OR MORE OF THE SM | | APPL CIRCUITS. 210.11C1,220.16 | | | | 14) NOTE: PLEASE SEE 210.4B AS THE | | DISHWASHER/DISPOSAL ARE FROM THE SAME | | RECEPT, HOWEVER THESE ARE ON 1-POLE | | BREAKERS. THIS REQUIRES A 2-POLE BRKR. | | | | 15) NOTE: PLEASE SEE COUNTER SPACE IN | | KTICHEN AS IT SEEMS IT IS MISSING GFI | | RECEPT(S). PLEASE SEE 210.52C1 AND | | REDLINED PLANS. | | | | 16) NOTE: PLEASE SEE "S" SHEETS AS THESE | | ARE MISSING THE REQUIRED CERTIFICATE OF | | AUTHORIZATION NUMBER FOR ENGINEERING | | FIRM. | | FAC 61G15-23.002, FS 471.023 | | | | ** IMPORTANT ** | | BEFORE RESUBMITTING PLANS ONCE ALL | | REVIEWS ARE COMPLETED. PLEASE BE SURE TO | | COMPLETELY REMOVE ALL OLD/VOIDED SHEETS | | AND ONLY INSERT THE NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND | | STAMPING. | | ONLY ONE COPY OF THE OLD SHEETS SHOULD | | BE SUBMITTED FOR REFERENCE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2006-02-06 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-02-06 |
Time |
07:33 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-02-06 |
Time |
07:25 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
N |
Date |
2006-01-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-01-09 |
Time |
10:32 |
Rev Time |
|
Received By |
shill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2007-02-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-22 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-22 |
Time |
13:17 |
Sent To |
E |
|
Notes |
2007-02-22 13:18:17 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2006-12-26 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-26 |
Time |
09:01 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-26 |
Time |
09:01 |
Sent To |
E |
|
Notes |
2006-12-26 09:02:07 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2006-12-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-15 |
Time |
11:15 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-15 |
Time |
11:15 |
Sent To |
Z |
|
Notes |
2006-12-15 11:15:17 | TO "Z" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2006-08-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-08-09 |
Time |
09:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-08-09 |
Time |
09:21 |
Sent To |
E |
|
Notes |
2006-08-09 00:00:00 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2006-08-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-08-01 |
Time |
08:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-08-01 |
Time |
08:50 |
Sent To |
Z |
|
Notes |
2006-08-01 00:00:00 | TO "Z" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2006-01-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-01-30 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-01-30 |
Time |
09:08 |
Sent To |
E |
|
Notes |
2006-01-30 00:00:00 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2006-01-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-01-06 |
Time |
08:55 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-01-06 |
Time |
08:55 |
Sent To |
B |
|
Notes |
2006-01-06 00:00:00 | TO "SHILL" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-12-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-12-27 |
Time |
16:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-12-27 |
Time |
16:14 |
Sent To |
Z |
|
Notes |
2005-12-27 00:00:00 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-09-27 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-09-27 |
Time |
14:40 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-09-27 |
Time |
14:40 |
Sent To |
B |
|
Notes |
2005-09-27 00:00:00 | TO "SHILL" DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-10-03 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-10-03 |
Time |
10:32 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2005-09-21 |
Time |
14:14 |
Sent To |
|
|
Notes |
2005-09-21 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2007-08-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-08-24 |
Time |
14:54 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-08-24 |
Time |
14:53 |
Sent To |
|
|
Notes |
2007-08-24 14:54:31 | REVISION TO MECH. PLANS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-01-18 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2007-01-18 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2007-01-18 |
Time |
10:20 |
Sent To |
B |
|
Notes |
2007-01-18 11:22:31 | PROVISO: | | 1.PER 2004 FRC M1602.4, PRESSURE DIFFERENTIALS ACROSS | | CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL | | BE LIMITEDTO .01 INCH WC (2.5 PASCALS) OR LESS. | | | | 2.FOR PROPER SIZING OF RETURN AIR FROM THE MATER | | SUITE, ALL AIR SUPPLY INTO THE MASTER SUITESHALL BE | | INCLUDED FOR TOTAL SUPPLY AIR (INCLUDE SUPPLY AIR TO | | CLOSETS, BATHROOM, ETC) AND SIZE RETURN ACCORDINGLY. | | 2004 FRC M1602.4 EXCEPTION 1 AND 3.TEST AND BALANCE | | REQUIRED FOR FINAL INSPECTION. | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW PROTECTION | | REQUIRED PER 2004 FRC M1411.3.1. | | | | 4.A MINIMUM OF 4" CLEARANCE AROUND THE AHU IS | | REQUIRED IN ACCORDANCE WITH 2004 FBC CHAPTER 13 | | SUB-CHAPTER 13-610.1.ABC.3.0.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2006-11-02 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-11-02 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-11-02 |
Time |
08:24 |
Sent To |
B |
|
Notes |
2006-11-02 08:25:06 | MECHANICAL REVISION REQUIRED. | | | | NO MECHANICAL PLANS SUBMITTED FOR REVIEW.PLANS | | APPROVED UNDER THE MASTER PERMIT 04031090 DO NOT MATCH | | THE REVISED PLANS. | | | | A MECHANICAL REVISION WILL BE REQUIRED PRIOR TO ROUGH | | INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2006-01-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-01-09 |
Time |
10:33 |
Rev Time |
|
Received By |
shill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2007-01-17 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2007-01-17 |
Time |
09:41 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2007-01-17 |
Time |
09:39 |
Sent To |
|
|
Notes |
2007-01-17 09:41:00 | RE-SUB |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2006-08-19 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-08-19 |
Time |
06:44 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-08-19 |
Time |
06:44 |
Sent To |
M |
|
Notes |
2006-08-19 00:00:00 | PAUL SCHMITZ | | [email protected] | | FBC 2004 PLUMBING CODE PLAN REVIEW | | FBC2004 FUEL GAS CODEPLAN REVIEW | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | UNSAT | | | | SEC 106.3.5.4 RESIDENTAL | | (ONE AND TWO FAMILY) | | (9) PLUMBING. | | SANITARY ISOMETRIC RISER DIAGRAM, | | REUIIRED. | | | | END OF COMMENTS, QUESTIONS 561-805-6692 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2006-01-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2006-01-09 |
Time |
10:33 |
Rev Time |
|
Received By |
shill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2006-12-19 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-12-19 |
Time |
14:27 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-12-19 |
Time |
14:27 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2006-08-08 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-08-07 |
Time |
11:30 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-08-07 |
Time |
11:30 |
Sent To |
I |
|
Notes |
2006-08-08 00:00:00 | DENIED, | | 1. THE PROPOSED DRIVEWAY NEED TO BE | | REDUCE TO MEET THE ZONING GUIDELINES. | | | | NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF | | LANDSCAPE, WHICHEVER IS LESS WITHIN THE | | FIRST 25FT FRONT SETBACK. | | | | 2. NEED TO REDUCE THE DRIVEWAY AND | | PROVIDE TWO COPY OF SURVEY WITH | | MEASUREMENTS (WIDTH & LENGTH) | | | | NOTE: | | THE PROPOSED A/C EQUIPMENT SHALL NOT BE | | CLOSER THAN 1FT FROM SIDE PROPERTY LINE. | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2006-01-05 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-01-05 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-01-05 |
Time |
11:17 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2005-09-26 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-09-26 |
Time |
18:35 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-09-26 |
Time |
18:35 |
Sent To |
I |
|
Notes |
2005-09-26 00:00:00 | DENIED, | | 1. TOO MUCH CONCRETE WITHIN THE FIRST | | 25FT FRONT SETBACK. | | | | NOTE: MUST MAINTAIN 1000SQ FT FOR 75% OF | | LANDSCAPE WHICHEVER IS LESS WITHIN THE | | FIRST 25FT FRONT SETBACK. | | | | MICHELLE MCLEAN | | ZONING TECHNICIAN | | 805-6720 |
|
|