Plan Review Details - Permit 05090825
Plan Review Stops For Permit 05090825
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-09-21 Cont ID  
Sent By lursu Date 2006-09-21 Time 15:20 Rev Time 0.00
Received By lursu Date 2006-09-21 Time 15:20 Sent To  
Notes
2006-09-21 00:00:00ADDRESS ON THE APPLICATION IS CORRECT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-01-05 Cont ID  
Sent By shill Date 2007-01-05 Time 09:45 Rev Time 0.00
Received By shill Date 2007-01-05 Time 07:35 Sent To  
Notes
2007-01-05 07:36:07****PROVISO****SEPARATE PERMIT SHUTTERS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-02 Cont ID  
Sent By shill Date 2007-01-02 Time 07:10 Rev Time 0.00
Received By shill Date 2007-01-02 Time 07:10 Sent To  
Notes
2007-01-02 07:10:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB
 FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY
 PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL
 561-233-5025 FOR MORE INFORMATION.
  
 2.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 3.)DUE TO VALUATION ADJUSTMENT, FEES HAVE BEEN
 INCREASED.SEE ATTACHED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-16 Cont ID  
Sent By shill Date 2006-09-16 Time 08:04 Rev Time 0.00
Received By shill Date 2006-09-16 Time 08:04 Sent To  
Notes
2006-09-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THIS WAS SUBMITTED AS A RESUB.NO
 FIRST REVIEW WAS DONE.
  
 2.)THE COMPUTER REFERS TO A MASTER,
 YOUR APPLICATION DOES NOT.IF YOU WANT
 THIS ISSUED FROM THE MASTER PERMIT,
 SUBMIT PLANS WHICH ARE IDENTICAL TO THE
 MASTER AND REVISE THE PERMIT
 APPLICATION.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 4.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 5.)PRODUCT APPROVALS REQUIRED FOR ALL
 COMPONENTS AND CLADDING (WINDOWS,
 SHUTTERS, FRENCH DOORS, ETC.).
  
 6.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 7.)DECLARE GOVERNING CODE.IF THIS IS
 ISSUED FROM THE MASTER, PLANS ARE TO BE
 IDENTICAL TO THE MASTER PERMIT (THESE
 PLANS DO NOT MATCH).OTHERWISE DECLARE
 GOVERNING CODE, FBC2001 OR FBC2004.
 NOTE THAT THE STRUCTURAL NOTES REFER TO
 THE WIND PROVISIONS OF FBC2001 1602.IF
 YOU SUBMIT UNDER FBC2004, REVISE ALL
 NOTES TO REFLECT GOVERNING CODE.
  
 8.)ENERGY CALCS REQUIRED, FBC13.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-11-28 Cont ID  
Sent By dpalmer Date 2006-11-28 Time 18:21 Rev Time 0.00
Received By dpalmer Date 2006-11-28 Time 18:21 Sent To M
Notes
2006-11-28 18:22:22PLANS WERE ON HOLD FROM 11/22 NOT TO REVIEW PER
 CONTRACTOR FOR NEW SHEETS.
  
 ** THESE ARE FIRST RESUB NO FEE, NOT SUBMITTIALS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-20 Cont ID  
Sent By dpalmer Date 2006-08-20 Time 12:32 Rev Time 0.00
Received By dpalmer Date 2006-08-20 Time 12:32 Sent To M
Notes
2006-08-20 00:00:00**********UNSAT ***********
  
 1) NOTE: PLEASE CLARIFY UNDERGROUND
 SEC'S TO FPL. IF THESE ARE INSTALLED BY
 FPL , THEN PLEASE DO NOT INDICATE THE
 CONDUCTOR SIZES, AS THESE WILL NOT
 CORRELATE WITH FPL.
 PLEASE ALSO VERIFY THE DOWNSIZING OF THE
 NEURTRAL CONDUCTOR TO A #3.
 PLEASE PROVIDE NEUTRAL LOAD CALCULATION
 OR FULL SIZE NEUTRAL.
 220.22, 310.15B6
  
 2) NOTE: PLEASE SHOW CONDUIT SIZE FOR
 THE UNDERGROUND AND ALSO THE CONDUIT TO
 INSIDE PANEL. UNABLE TO VERIFY AT THIS
 TIME.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE 210.52C1AS THERE
 ARE SOME RECEPTS MISSING . SEE REDLINED
 PLANS.
 PLEASE SEE AREAS OF COUNTER SPACE,
 PLEASE SEE LOCATED NEXT TO STOVE ETC.
  
 4) NOTE: PLEASE SEE MISSING ISLAND
 GFI RECEPT. 210.52C1-5,210.8A6
  
 5) NOTE: PLEASE SEE THAT ALL ROOM AND
 AREA DESIGNATIONS ON PLANS CORRELATE
 WITH THE PANEL SCHEDULE.
 PLEASE SEE THAT ALL CIRCUITS ON PANEL
 SCHEDULE SHALL BE SPECIFIC TO ROOMS AND
 AREAS.
 IE; LIVING RM RECEPTS, BEDRM #2
 LTS/RECEPTS, HALL LTS ETC ETC.
 408.4 FBC 106.1.2
 **IT IS KNOWN THAT CIRCUITING DURING
 CONSTRUCTION WILL CHANGE AND THIS CAN EB
 REVISED AT A LATER DATE.
  
 6) NOTE: PLEASE SEE ONLY TWO CIRCUITS
 ARE BEIGN SHOWNWITH ARC FAULT
 PROTECTION FOR ALL BEDRMS LTS, RECEPTS
 AND SD'S. PLEASE KNOW, THE CODE HAS
 CHANGED FROM PREVIOUSLY SUBMITTED PLANS
 UNDER THIS PROJECT TO REQUIRE ARC FAULT
 PROTECTION FOR ALL OUTLETS IN BEDRMS.
 PLEASE BE SURE TO REVISE AS THE LOAD ON
 THESE ONLY TWO CIRCUITS SEEM TO EXCEED
 RATINGS.
 210.12B(2002) NEC. 210.52,220
  
 7)NOTE: PLEASE SEE MISSING NEW GDO
 DEDICATED CIRCUIT ON PANEL
 SCHEDULE/LOADS ETC.
  
 8) NOTE: PLEASE BE SURE HE PLANS PROVIDE
 THE FOLLOWING MINIMUM CODES AS ADOPTED
 FOR DESIGN AND FS/FBC 2004
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101.
  
 9) NOTE: PLEASE SEE PLANS INDICATE THE
 PANEL LOCATED INHALL ON PLANS AND
 PANEL SCHEDULE SAY HALL/UTILITY.??
 PLEASE SEE ELECTRICAL PLANS DO NOT SHOW
 THE SAME WALL AS SHOWN ON BUILDING
 PLANS.
 PLEASE ALSO CLARIFY THE MISSING CONTROL
 FOR LT(S) IN THE UTILITY RM. 210.70
  
 10) NOTE: PLEASE SEE "J-BOXES" SHOWN ON
 PLANS NEED TO BE NOTED FOR "FUTURE FAN
 BOXES' IF INDEED FOR FANS. PLEASE SEE
 314.47D
  
 11) NOTE: PLEASE SEE PLANS DO NOT SHOWN
 LOCATION OF SERVICE ON THE OUTSIDE OF
 HOUSE.
 106.1.2
  
 12) NOTE: PLEASE SEE SURVEY PROVIDED IN
 PACKAGE IS REQUIRED TO CONTAIN AN
 ORIGINAL SIAGNAURE IN ORDER FOR SURVEY
 TO BE VALID. PLEASE SEE FAC 61G15-17, FS
 472.025
  
 13) NOTE: PLEASE SEE MISSING THE DINING
 ROOM CIRCUITS ON ONE OR MORE OF THE SM
 APPL CIRCUITS. 210.11C1,220.16
  
 14) NOTE: PLEASE SEE DISHWASHER AND
 DISPOSAL SEEM TO BE SHARED TO THE SAME
 RECEPT, HOWEVER PLEASE SEE PANEL DOES
 NOT INDICATE A 2-POLE BREAKER. PLEASE
 SEE 210.4B
  
 15) NOTE:PLEASE SEE SW FOR LT OUTSIDE
 REAR OF DWELLING IS BEING SHOWN AS A
 3WAY YET PLANS DO NOT SHOW THIS BEING
 CONNECTED TO ANY OTHER LOCATTION?
 PLEASE ALSO SEE EGRESS, AND INGRESS
 LIGHTING CONTROLS REQUIRED. (FROM
 OUTSIDE INTO DWELLING/DINING AREA) NO
 MEANS TO TURN ON LTS/LIGHTING OUTLET.
 210.70
 PLEASE SEE LOCATION OF SWITCH LEGS FOR
 GARAGE LTS AND LOCATIONS OF SWITCHES.
 210.70 (MISPRINT)
  
 ** IMPORTANT **
 BEFORE RESUBMITTING PLANS ONCE ALL
 REVIEWS ARE COMPLETED. PLEASE BE SURE TO
 COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT THE NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONLY ONE COPY OF THE OLD SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By dpalmer Date 2006-08-10 Time 07:40 Rev Time 0.00
Received By dpalmer Date 2006-08-10 Time 07:40 Sent To PC
Notes
2006-08-10 00:00:00***** THIS IS AN EXPIRED APPLICATION,
 CAME IN FOR PERMIT AND NEVER CAME
 THROUGH PLAN REVIEW AND WAS NEVE ISSUED
 FOR PERMIT.
 THERE HAS NO BEEN NO ACTIVITY.\
 CALLED, CONTRACTOR'S REP AND PLANS ARE
 BEING PALCE UNDER "S' FOR PU.
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 10:11 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 10:11 Sent To P
Notes
2007-08-03 10:12:02TO "JLEECH" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-28 Cont ID  
Sent By adarroug Date 2007-06-28 Time 15:49 Rev Time 0.00
Received By adarroug Date 2007-06-28 Time 15:49 Sent To M
Notes
2007-06-28 15:50:35TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-04 Cont ID  
Sent By adarroug Date 2007-01-04 Time 12:14 Rev Time 0.00
Received By adarroug Date 2007-01-04 Time 12:14 Sent To B
Notes
2007-01-04 12:14:49TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 11:46 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 11:46 Sent To E
Notes
2006-11-21 11:46:25TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-18 Cont ID  
Sent By adarroug Date 2006-08-18 Time 10:16 Rev Time 0.00
Received By adarroug Date 2006-08-18 Time 10:16 Sent To E
Notes
2006-08-18 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-09 Cont ID  
Sent By adarroug Date 2006-08-09 Time 09:29 Rev Time 0.00
Received By adarroug Date 2006-08-09 Time 09:29 Sent To E
Notes
2006-08-09 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-16 Cont ID  
Sent By shill Date 2006-09-16 Time 08:47 Rev Time 0.00
Received By shill Date 2006-08-02 Time 15:59 Sent To  
Notes
2006-08-02 00:00:00TO "Z" BOX/REV

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-03 Cont ID  
Sent By tgordon Date 2007-07-03 Time 14:48 Rev Time 0.20
Received By tgordon Date 2007-07-03 Time 14:48 Sent To  
Notes
2007-07-03 14:48:53REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-11-29 Cont ID  
Sent By tgordon Date 2006-11-29 Time 09:26 Rev Time 0.30
Received By tgordon Date 2006-11-29 Time 14:19 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-21 Cont ID  
Sent By tgordon Date 2006-08-21 Time 08:17 Rev Time 0.25
Received By tgordon Date 2006-08-21 Time 08:17 Sent To P
Notes
2006-08-21 00:00:00*** DENIED ***
 1) JOB ADDRESS MUST APPEAR ON ALL PAGES
 OF PLANS.
  
 2) MECHANICAL PLANS EQUIPMENT LIST SHOWS
 AHU IS A 10 SEER AND CONDENSER UNIT IS A
 12 SEER, PLEASE SHOW THE SEER OF THE
 SYSTEM ONLY. AND SHOW THE TOTAL BTU'S.
 AND SENSIBLE BTU'S. OF THE A/C SYSTEM.
  
 3) PLEASE SHOW ON MECH. PLANS THE SIZE
 OF THE RETURN AIR GRILL TO THE AIR
 HANDLER.
  
 4) RETURN AIR TRANSFER DUCTS TO
 BEDROOMS, THE GRILLS ARE TO SMALL FOR
 THE DUCTS.
  
 5) SUPPLY AIR DUCT TO SECOND FLOOR
 CLOSET #2 NEEDS TO BE SIZED.
  
 6) PLEASE EXPLAIN WHY A 7" SUPPLY AIR
 DUCT IS GOING TO THE SMALL CLOSET IN THE
 HALL.
  
 7) PLEASE SUBMIT MANUAL D CALCULATIONS
 FOR RESIDENTIAL DUCT DESIGN, PER 2004
 FBC/R M1601.1 AND FBC 13-610.1.ABC.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-08-07 Cont ID  
Sent By jleech Date 2007-08-07 Time 08:06 Rev Time 0.00
Received By jleech Date 2007-08-07 Time 08:06 Sent To  
Notes
2007-08-07 08:06:31REVISED RISER DIAGRAM OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-12-11 Cont ID  
Sent By jleech Date 2006-12-11 Time 07:18 Rev Time 0.00
Received By jleech Date 2006-12-11 Time 07:18 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-13 Cont ID  
Sent By tgordon Date 2006-11-29 Time 14:19 Rev Time 0.00
Received By jleech Date 2006-09-13 Time 07:26 Sent To B
Notes
2006-09-13 00:00:00DENIED;
 1.AUTOMATIC CLOTHES WASHER BRANCH DRAIN
 IS REQUIRED TO BE 3" SEE FBC-2004
 PLUMBING SECTION 406.3.
 2.CLOTHES DRIER VENT NOT SHOWN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2006-08-07 Cont ID  
Sent By mmclean Date 2006-08-07 Time 11:27 Rev Time 0.00
Received By mmclean Date 2006-08-07 Time 11:27 Sent To I
Notes
2006-08-08 00:00:00REV - ADD ATTACHED GARAGE & COVERED
 PORCH.


Account Summary | Usage Policy | Privacy Policy