Plan Review Details - Permit 05090802
Plan Review Stops For Permit 05090802
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-30 Cont ID  
Sent By dpalmer Date 2005-09-30 Time 11:48 Rev Time 0.00
Received By dpalmer Date 2005-09-30 Time 11:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-21 Cont ID  
Sent By dpalmer Date 2005-09-21 Time 18:07 Rev Time 0.40
Received By dpalmer Date 2005-09-21 Time 18:07 Sent To  
Notes
2005-09-21 00:00:00** UNSAT **
  
 1)NOTE: PLEASE SEE 250.66 FOR MIN
 GROUNDING ELECTRODE CONDUCTOR. 2/0 MIN,
 A #2 IS SHOWN ON PART OF THE RISER AND
 2/0 ON OTHER PART.
  
 2)NOTE: PLEASE INDICATE THE GROUNDING
 ATTACHMENT FOR TRANSFORMERS PER
 250.30,AND GROUNDING ELECTRODE SIZE FOR
 SEPARATELY DERIVED SYSTEMS.
 250.66
  
 3)NOTE: PLEASE SEE THE "EQUIPMENT
 GROUNDING CONDUCTORS" ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE REMOVE ALL "EQUIPMENT GRNDS" UP
 TO THE FIRST MEANS OF DISCONNECT.
  
 4)NOTE: PLEASE SEE LOADS INDICATED ON
 PANELS "A" ARE THE SAME LOADS SHOWN ON
 "H-1". PLEASE SEE LOADS ON 277/480V
 PANEL FOR THESE 120/208V PANELS WOULD
 NOT BE THE SAME.
 PLEASE VERIFY LOADS AND ADJUST.
  
 5)NOTE: PLEASE NOTE: ANY COLD
 WATER/PIPING/SPRINKLER STAND PIPE
 SYSTEMS IN BLDG SHALL BE BONDED TO THE
 GROUNDING ELECTRODE SYSTEM.
 PLEASE SEE WATER PIPE SYSTEM TO SITE
 SHALL BE PART OF THE GROUNDING ELECTRODE
 SYSTEM.
 250.50,250.104
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-20 Cont ID  
Sent By adarroug Date 2005-09-20 Time 14:26 Rev Time 0.00
Received By adarroug Date 2005-09-20 Time 14:26 Sent To E
Notes
2005-09-20 00:00:00TO "DPALMER" DESK