2005-09-21 00:00:00 | ** UNSAT ** |
| |
| 1)NOTE: PLEASE SEE 250.66 FOR MIN |
| GROUNDING ELECTRODE CONDUCTOR. 2/0 MIN, |
| A #2 IS SHOWN ON PART OF THE RISER AND |
| 2/0 ON OTHER PART. |
| |
| 2)NOTE: PLEASE INDICATE THE GROUNDING |
| ATTACHMENT FOR TRANSFORMERS PER |
| 250.30,AND GROUNDING ELECTRODE SIZE FOR |
| SEPARATELY DERIVED SYSTEMS. |
| 250.66 |
| |
| 3)NOTE: PLEASE SEE THE "EQUIPMENT |
| GROUNDING CONDUCTORS" ARE ONLY INSTALLED |
| AFTER THE FIRST MEANS OF DISCONNECT. |
| PLEASE REMOVE ALL "EQUIPMENT GRNDS" UP |
| TO THE FIRST MEANS OF DISCONNECT. |
| |
| 4)NOTE: PLEASE SEE LOADS INDICATED ON |
| PANELS "A" ARE THE SAME LOADS SHOWN ON |
| "H-1". PLEASE SEE LOADS ON 277/480V |
| PANEL FOR THESE 120/208V PANELS WOULD |
| NOT BE THE SAME. |
| PLEASE VERIFY LOADS AND ADJUST. |
| |
| 5)NOTE: PLEASE NOTE: ANY COLD |
| WATER/PIPING/SPRINKLER STAND PIPE |
| SYSTEMS IN BLDG SHALL BE BONDED TO THE |
| GROUNDING ELECTRODE SYSTEM. |
| PLEASE SEE WATER PIPE SYSTEM TO SITE |
| SHALL BE PART OF THE GROUNDING ELECTRODE |
| SYSTEM. |
| 250.50,250.104 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| |