2005-09-30 00:00:00 | *******DENIED******* |
| MYRON JACOBS(561) 805 6726 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| 1) FBC 1606.2.5THE SYSTEM SELECTED |
| FROM THE SUBMITTED FLAT ROOF PRODUCT |
| APPROVAL NOA HAS A MAXIMUM DESIGN |
| PRESSURE OF LESS THAN -89 PSF AND CITES |
| GENERAL LIMITATION #9 (SEE PAGE 39 OF |
| 45).GENERAL LIMITATION #9 PROHIBITS |
| RATIONAL ANALYSIS OR EXTRAPOLATION TO |
| ENHANCE THE UPLIFT PRESSURE AT PERIMETER |
| AND CORNER AREAS BY REDUCING THE |
| FASTENER SPACING IN THESE AREAS.EITHER |
| SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT |
| APPROVAL) THAT DOES NOT CITE GENERAL |
| LIMITATION #9.ALTERNATIVELY IF THE |
| SELECTED SYSTEM DOES CITE GENERAL |
| LIMITATION #9, IT MUST HAVE A MAXIMUM |
| DESIGN PRESSURE THAT EXCEEDS THE |
| PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 |
| PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR |
| LESS). |
| |
| 2) FL#560-R1 IS NOT APPROVED ON THE |
| STATE WEB-SITE. CHOOSE AN APPROVED |
| PRODUCT AND SUBMIT IT FOR PLAN REVIEW. |
| THE REPORT ON THE WEB-SITE IS A SBCCI |
| REPORT. |
| |
| 3) SEE PREVIOUS NOTES FROM ROB MCDOUGAL |
| |
| BUILDING PLAN REVIEW |
| MYRON JACOBS. |