Plan Review Details - Permit 05090602
Plan Review Stops For Permit 05090602
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-02-03 Cont ID  
Sent By mwennerg Date 2006-02-03 Time 16:00 Rev Time 0.00
Received By mwennerg Date 2006-02-03 Time 16:00 Sent To  
Notes
2006-02-03 00:00:00REVISION DATED 2/3/06 REF: RAINPROOF
 ENCLOSURES

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-10-13 Cont ID  
Sent By nmccray Date 2005-10-13 Time 13:34 Rev Time 0.00
Received By nmccray Date 2005-10-13 Time 13:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-23 Cont ID  
Sent By mwennerg Date 2005-09-23 Time 09:57 Rev Time 0.00
Received By mwennerg Date 2005-09-23 Time 09:57 Sent To  
Notes
2005-09-23 00:00:00******DENIED******
  
 1) PLANS ONLY SHOW ONE PIV. TAMPER
 SWITCHES ARE REQUIRED FOR EACH BUILDING.
  
 2) ELECTRONIC SWITCHES WITH CHAIN AND
 LOCK WILL BE REQUIRED FOR DOUBLE CHECK
 DETECTOR ASSEMBLY.
  
 3) FIRE ALARM PANELS THAT MONITOR
 SPRINKLER SYSTEMS SHALL BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 4) FIRE ALARM TO BE CLASS A, STYLE D OR
 FULLY ADDRESSABLE.
  
 5) PLEASE PROVIDE A COPY OF THE CONTRACT
 TO VERIFY VALUE FOR ENTIRE PROJECT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-28 Cont ID  
Sent By adarroug Date 2005-09-28 Time 18:47 Rev Time 0.00
Received By adarroug Date 2005-09-28 Time 18:47 Sent To FIRE
Notes
2005-09-28 00:00:00TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-14 Cont ID  
Sent By adarroug Date 2005-09-14 Time 13:22 Rev Time 0.00
Received By adarroug Date 2005-09-14 Time 13:22 Sent To FIRE
Notes
2005-09-14 00:00:00TO "F" BOX