Plan Review Details - Permit 05090568
Plan Review Stops For Permit 05090568
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-05-16 Cont ID  
Sent By lursu Date 2006-05-16 Time 14:22 Rev Time 0.00
Received By lursu Date 2006-05-16 Time 14:21 Sent To  
Notes
2006-05-16 00:00:00PERMIT ATTACH TO EXT#0024 FOR 4521
 SALAMANCA WAY
2006-05-14 00:00:00NEEDS !!!!!

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-05 Cont ID  
Sent By rmcdouga Date 2006-06-05 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2006-06-05 Time 15:47 Sent To  
Notes
2006-06-05 00:00:00DENIED
  
 1) THE PLANS MUST BE STAMPED BY PALM
 BEACH COUNTY FOR IMPACT FEES. THE PLAN
 REVIEW NUMBER ON THE PLANS MUST
 CORRESPOND WITH THE P.R. NUMBER ON THE
 IMPACT FEE RECEIPT.
  
 2) SUBMIT FIRE SPRINKLER PLANS FOR THE
 REQUIRED NFPA 13 SYSTEM. THIS IS
 REQUIRED BY FBC 104.3.1.1 OF THE CITY OF
 W.P.B. AMENDMENTS TO THE 2001 FBC.
  
 3) THE GARAGE FLOOR/CEILING ASSEMBLY IN
 DETAIL 17 ON A 10.0.0 DOES NOT
 CORRESPOND TO THE FC 5517 FIRE RATED
 ASSEMBLY LISTED IN THE GYPSUM
 ASSOCIATION MANUAL. PLEASE CORRECT.
  
 4) NUMBER 20 ON THE DOOR SCHEDULE
 SPECIFIES A VENTED GARAGE DOOR. THE
 PRODUCT APPROVAL FOR THE GARAGE DOOR
 DOES NOT INDICATE VENTS IN THE DOOR.
  
 5) REVISE DETAIL 11 ON A 10.0.0 TO
 SPECIFY THE 2001 FBC AND NOT THE CURRENT
 EDITION OF THE STANDARD BUILDING CODE.
  
 6) THE DRAWINGS ATTACHED TO THE STATE
 PRODUCT APPROVAL FOR THE STEEL DOOR FROM
 MASONITE INTERNATIONAL ARE FOR A 6'-8"
 DOOR AND THE PLAN SPECIFIES AN 8'-0"
 DOOR. SEE FL 4940.3 AND DRAWING
 DWG-MA-FLO 133-05.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 TRUSS CONNECTORS. (SIMPSON-HETAL 12 &
 16, USP-USC) THE FL COVERSHEET SUBMITTED
 FOR THE USP HANGERS AND COLUMN BASES &
 CAPS HAS A WINDOW MULLION NOA ATTACHED
 TO IT.
  
 8) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS IS INCOMPLETE. THERE ARE
 SHEETS WITH ANOTHER NOA NUMBER ATTACHED
 AT THE REAR OF THE SH WINDOW NOA.
  
 9) THE DECORATIVE BAHAMA SHUTTERS WILL
 REQUIRE A SEPARATE PERMIT.
  
 10) FS 713.13 IF THE IMPROVEMENT
 DESCRIBED IN THE NOTICE OF COMMENCEMENT
 IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS VOID AND OF NO FURTHER EFFECT.
 (THE NOC WILL NEED TO BE RE-RECORDED
 BEFORE THE PERMIT IS ISSUED.)
  
 11) FBC 13-600.3ABC.1.2 REQUIRES THE
 ENERGY CALCULATION FORMS TO BE SIGNED
 AND SEALED BY AN ARCHITECT OR AN
 ENGINEER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-07 Cont ID  
Sent By rmcdouga Date 2005-12-07 Time 09:41 Rev Time 0.00
Received By rmcdouga Date 2005-12-06 Time 06:45 Sent To Z
Notes
2005-12-07 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED PROJECT APPEARS TO
 COMPRISE MORE THAN ONE PARCEL. PLEASE
 SUBMIT A COPY OF THE REPLAT.
  
 3) IN ORDER TO DETERMINE THE PERCENTAGE
 OF WALL AREA ALLOWED AS OPENINGS BY FBC
 TABLE 600, SUBMIT A SURVEY INDICATING
 THE LOCATIONS OF THE ASSUMED PROPERTY
 LINES BETWEEN THE BUILDINGS.
  
 4) PROVIDE AN AREA CALCULATION TABLE
 LISTING THE FLOOR AREA BREAKDOWNS BY
 FLOOR FOR EACH UNIT AND THE TOTALS FOR
 ALL FOUR UNITS.
  
 5) THE FBC DOES NOT ALLOW HEIGHT AND
 AREA INCREASES FOR NFPA 13R SPRINKLER
 SYSTEMS. SEE FBC TABLE 500 FOOTNOTE (D).
 SPECIFY THE TYPE OF SPRINKLER SYSTEM ON
 THE PLANS. MUST BE A FULL NFPA 13 SYSTEM
 FOR HEIGHT INCREASE. SUBMIT FIRE
 SPRINKLER PLANS PER FBC 104.3.1.1.
  
 6) FBC 2504.4.1 AND GA 216 REQUIRE WOOD
 FURRING TO BE NOT LESS THAN 3/4" X
 1-1/2" ACTUAL SIZE. ALSO, THE SURFACE
 CAN NOT VARY MORE THAN 1/8" FROM THE
 PLANE OF ADJACENT FURRING MEMBERS.
 DETAIL 1 ON A10.0.0 SHOWS THE FURRING
 ATTACHED OVER 3/4" POLYSTYRENE. PLEASE
 REVISE DETAIL TO COMPLY WITH CODE.
  
 7) SPECIFY THE INSULATION THAT WILL BE
 USED IN THE FLOOR/CEILING ASSEMBLY ABOVE
 THE GARAGE.
  
 8) THE GUTTER DOWNSPOUTS ARE REQUIRED TO
 DISCHARGE ONE FOOT AWAY FROM THE
 STRUCTURE PER FBC 1503.4.4.
  
 9) THE DOOR TO THE EXIT STAIRS AT THE
 SECOND FLOOR MUST PROVIDE A 32" CLEAR
 OPENING FROM THE FACE OF THE DOOR TO THE
 STOP WITH THE DOOR OPEN 90 DEGREES. SEE
 FBC 1003.2.1 AND 1003.2.2
  
 10) SHOW COMPLIANCE WITH FBC MECH. TABLE
 403.3 FOR REQUIRED OUTDOOR AIR
 VENTILATION AT GARAGES OF 100 CFM PER
 CAR.
  
 11) WALL SECTION #4 ON A-7.01 IS
 MISLABELED FOR GENERAL NOTES 4 AND 10.
  
 12) SPECIFY THE EXTERIOR FINISH AT THE
 UNDERSIDE OF THE BAY WINDOW SHOWN ON
 A-7.1.1. SPECIFY THE EXTERIOR SHEATHING,
 LATH AND STUCCO. NOTE: SEE ASTM C 926
 FOR REQUIRED STUCCO THICKNESS.
  
 13) ASTM C 926 REQUIRES 7/8" OF STUCCO
 WHEN APPLIED VERTICALLY ON METAL PLASTER
 BASE OVER SOLID BASE. PLEASE REVISE NOTE
 #46 FOR SECTION 3 ON A-7.0.1.
  
 14) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE. THIS IS THE VERTICAL DISTANCE
 FROM FINISHED GRADE TO THE A POINT AT
 THE AVERAGE HEIGHT OF THE ROOF.
  
 15) PROVIDE A DETAIL OF THE BALCONY
 GUARDRAILS. SPECIFY ATTACHMENTS, SPACING
 OF INTERMEDIATE RAILS, ETC.
  
 16) SPECIFY THE METHOD OF ATTACHMENT FOR
 THE ROOF TILES. THE PRODUCT APPROVAL
 THAT WAS SUBMITTED HAS AN ATTACHMENT
 RESISTANCE MOMENT OF 24.5 FT-LBF FOR
 MORTAR SET TILE. FOR 140 MPH EXPOSURE B
 WITH 40FT MRH, THE REQUIRED MOMENT IS
 28.3 FT-LBF. PLEASE REVISE ROOF TILE
 DETAILS TO COMPLY WITH CODE.
  
 17) UL ASSEMBLY U 906 HAS A 2 HOUR FIRE
 RATING NOT ONE HOUR AS SPECIFIED ON THE
 PLANS FOR WALL TYPES IN DETAILS 2 AND 6
 ON A-10.00.
  
 18) SPECIFY DRAFTSTOPPING IN THE ROOF
 OVERHANGS IN LINE WITH THE TENANT
 SEPARATION WALLS AS REQUIRED BY FBC
 2305.2.3.
  
 19)705.7.1 JOINTS INSTALLED IN OR
 BE- TWEEN FIRE RESISTANT WALLS, FIRE
 RESIS- TANT FLOORS OR FLOOR/ CEILING
 ASSEMBLIES AND FIRE RESISTANT ROOFS OR
 ROOF/ CEILING ASSEMBLIES SHALL BE
 PROTECTED BY AN APPROVED FIRE RESISTANT
 JOINT SYSTEM DESIGNED TO RESIST THE
 PASSAGE OF FIRE FOR A PERIOD NOT LESS
 THAN THE REQUIRED FIRE RESISTANCE RATING
 OF THE WALL, FLOOR OR FLOOR IN OR
 BETWEEN WHICH IT IS INSTALLED. SPECIFY
 THE JOINT SYSTEM AT THE TOP OF THE
 TENANT SEPARATION WALLS.
  
 20) PROVIDE DETAILS FOR MECHANICAL DUCT
 PENETRATIONS THROUGH FIRE RATED
 ASSEMBLIES.
  
 21) DETAIL 17 ON A-10 DOES NOT
 CORRESPOND TO GA ASSEMBLY FC 5517
 SPECIFIED ON SHEET A 10.2.0.
  
 22) TRUSS LAYOUT AND DRAWINGS ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD FOR THE
 STRUCTURE.
  
 23) THE UPLIFT LOAD VALUES LISTED IN THE
 TRUSS ANCHOR SCHEDULE ON S-3 FOR THE
 SIMPSON HETAL 16 & 20 ARE INCORRECT.THE
 ONE THIRD STRESS INCREASE FOR STEEL
 CALCULATIONS IS NO LONGER ALLOWED. SEE
 THE 2005 SIMPSON CATALOG.
  
 24) THE HUGHES "USC" CONNECTORS ALSO
 HAVE INCORRECT UPLIFT VALUES. HUGHES WAS
 PURCHASED BY USP SEVERAL YEARS AGO AND
 IS LONGER IN BUSINESS. SEE THE 2005 USP
 CATALOG FOR VALUES. UPDATE THE TRUSS
 ANCHOR SCHEDULE.
  
 25) UNDER KEY NOTES/ LEGEND ON A-4.0 AND
 OTHER SHEETS REFERENCE IS MADE TO SHEET
 A-13 FOR THE WALL TYPES. HOWEVER, THERE
 IS NO SHEET A-13.
  
 26) THE ENERGY CALCULATIONS CONTAIN
 SEVERAL ERRORS. THESE ARE CONSIDERED
 MULTIFAMILY NOT SINLE FAMILY. THE
 ADJACENT WALL AT THE GARAGE IS METAL
 FRAME AND THE CEILING INSULATION IS
 SPECIFIED AS R-20 ICYENE.
  
 27)PROVIDE MANUFACTURER'S SPECIFICATIONS
 FOR THE ICYENE INSULATION.
  
 28) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 FLORIDA COVER SHEETS FOR ALL PRODUCT
 APPROVALS. IN ADDITION TO THE COVERSHEET
 THE INSTALLATION INSTRUCTIONS OR PRODUCT
 EVALUATION AS LISTED ON THE STATE
 WEBSITE IS ALSO REQUIRED. TWO (2) COPIES
 ARE REQUIRED.
  
 29) SUBMIT STATE PRODUCT APPROVALS FOR
 THE TRUSS CONNECTORS.
  
 30) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS HAS THE INFO FROM THE FIXED
 GLASS WINDOWS ATTACHED TO THE NOA
 COVERSHEET.
  
 31) THE DESIGN PRESSURES LISTED IN THE
 GARAGE DOOR PRODUCT APPROVALS DO NOT
 MEET THE PRESSURES SPECIFIED ON THE
 PLANS. SEE S-6.
  
 32) SUBMIT MANUFACTURER'S SPECS. FOR THE
 DOOR CLOSERS.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 19:52 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 19:45 Sent To  
Notes
2006-05-14 00:00:00************** UNSAT 2ND REVIEW ********
  
 **PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE SOME NEW NOTES DUE TO
 CHANGES IN PLANS.
  
  
 SUB 1)NOTE: OK
  
  
  
 1)NOTE: NOTE #1 OK, HOWEVER SEE NEW
 NOTES DUE TO NEW SERVICE FOR BLDG BEING
 SHOWN. SEE NEW NOTES LISTED SEPARATELY
 BELOW.
  
  
 2)NOTE: NOTE #2 NO:
 ** PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATINGS ARE SHOWN FOR EACH PANEL,
 BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW
 SERVICE).
 PLEASE SEE CALCUALTIONS SUBMITTED ARE
 BASED ON UNIT MAINS, WHICH ARE OK,
 HOWEVER PLEASE SEE THE MAIN IS ALSO
 REQUIRED. THE SEC'S ARE NOT 2/0'S.
  
  
 3)NOTE: NOTE #3 OK,
  
 4))NOTE: NOTE #4 OK
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 NO, ??PLEASE SEE THIS
 COULD NOT BE LOCATED ON LOAD CALCS.
 PLEASE SEE 220.3B4.PANEL SCHEDULE
 MENTIONS RECESSED LTS, HOW MANY, AND
 WATTAGE PER FIXTURE NOT SHOWN.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS NEEDS
 TO BE SHOWN ABOVE THE GEN. KT/RECEPT
 LOADS. THIS SHOULD BE ABOVE THE FIGURED
 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 8)NOTE: NOTE #8 NO, PLEASE SEE AN EFFORT
 WAS MADE TO LIST THESE, HOWEVER PLEASE
 SEE LISTING INDICATES "GFI" WHEREAS
 "AFCI" PROTECTION IS REQUIRED.
  
 ** PLEASE LIST ALL THE REQUIRD ARC
 FAULT PROECTED CIRCUITS AS REQUIRED PER
 2002 210.12
 PLEASE KNOW, SD'S ARE BEING SHOWN
 CIRCUITED TO KITCHEN LIGHTING CIRCUIT,
 THIS IS OK, HOWEVER PLEASE KNOW, THIS
 WOULD ALSO REQUIRE ARC FAULT PROTECTION
 FOR THIS ADDITIONAL CIRCUIT.
 THIS IS ONLY A NOTE:
  
 9)NOTE: NOTE #9 OK, NOTE WAS ADDED TO
 PLANS, HOWEVER PLEASE SEE SD'S ARE STILL
 BEING SHOWN WITHIN 20' OF COOKING
 APPLIANCES. THIS IS PERMITTED, HOWEVER
 PLEASE SPECIFY THE SD TO BE INSTALLED IN
 ORDER TO MEET EXCEPTION AS LISTED.
  
 *PLEASE SEE SOME NEW SHEETS WERE ADDED
 WITH COMPLETE NOTE REVISED, HOWEVER NOT
 ALL SHEETS??
  
 **PLEEASE SEE NFPA-72 (2002)
 EDITION,11.8.3.5.
 PLEASE PLACE NOTE ON PLANS WHICH STATES
 LOCATIONS OF SD'S TO BE A MIN OF 3' FROM
 BATH(S) AND KITCHEN DOORS AND 20' FROM
 KITCHEN COOKING APPLIANCES.
 ** PLEASE SEE EXCEPTION TO 20' FROM
 COOKING WITH TYPE OF SD USED.**
 PLEASE SEE PLANS SHOWS A SD IN KITCHEN
 AREA AT THIS TIME.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 NO.
 THIS IS REQUIRED ON ALL SHEETS.
  
 **PLEASE SEE ARCHITECTS TITLE
 BLOCK SHALL ALSO CONTAIN THE PRINTED
 LICENSE NUMBER FOR ARCHITECT OF RECORD.
 FAC 61G1-16.004.
 PLEASE SEE THIS WAS NOT DONE FOR OLD
 SHEETS, ONLY NEW.
 PLEASE SEE THIS COMMENT IS FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
 PLEASE KNOW THIS COMMENT DOES NOT APPLY
 TO KAMM CONSULTING'S TITLE BLOCK.
  
 ********** NEW NOTES *************
  
 1)NOTE: PLEASE SEE 250.66 FOR MIN
 GROUNDING ELECTRODE CONDUCTOR REQUIRED.
 #4 AWG SHOWN, MIN 3/0 AWG REQUIRED
  
 2)NOTE: PLEASE SEE NO SEC'S ARE SHOWN
 FOR SERVICE.??PLEASE SEE 240.4, 310.16
  
 3)NOTE: PLEASE INDICATE THE OCP AT THE
 METER CENTER FOR ALL UNIT BRKRS.215.5
  
 4)NOTE: PLEASE SHOW SERVICE ON PLANS.
 PLEASE SEE ELECTRICAL PLANS DO NOT
 INDICATE THE LOCATION OF SERVICE ON
 EITHER END OF BLDG. PLEASE ALSO NEEDS TO
 BE SHOWN ON THE A-SHEETS, FLR PLANS,
 ELEVATION.
  
 5)NOTE: PLEASE SEE PLANS SHALL CONTAIN
 THE SIGNATURE OF THE ENGINEER OF RECORD.
 PLEASE SEE NEW SHEETS CONTAIN "INITIALS"
 ONLY AND DO NOT CORRELATE WITH THE
 ORIGINAL PLANS.
 FS 471.025, FAC 61G15-23.002
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES. PLEASE SEE
 PLUMB SHEETS WHICH ARE ALSO INITIALED.
 PLEASE SEE "RAISED SEAL" SHALL BE CLEAR
 AND VISABLE WITH ALL INFORMATION ON
 SAID SEAL. PLEASE SEESHEETS,
 INFORMATION ON SEAL IS NOT VISABLE EVEN
 WHEN "SHADOWED WITH PENCIL".
  
 6) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAINS TO PANELS
 IN UNITS. 250.110,250.24,250.122
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-05 Cont ID  
Sent By dpalmer Date 2005-10-05 Time 11:37 Rev Time 0.00
Received By dpalmer Date 2005-10-04 Time 21:43 Sent To  
Notes
2005-10-17 00:00:00**** NOTE ADDED****
  
  
 PLEASE SEE PLANS REFERENC THE WRONG LIFE
 SAFETY CODE.
 PLEASE KNOW, AS OF JAN 1ST 2005 , WE ARE
 UNDER THE 2003 NFPA-101
2005-10-05 00:00:00********* UNSAT *********
  
  
 1)NOTE: PLEASE SEE PROJECT IS SUBMITTED
 AS CONDO'S YET ELECTRICALSERVICES
 PROVIDED IS SHOWN AS EACH WOULD BE A
 TOWNHOUSE (FEE SIMPLE).
 PLEASE SEE WATER SERVICE SHOWS
 MULTI-FAMILY BLDG.
 PLEASE KNOW, IF THESE AS MULTI-FAMILY
 CONDO BLDGS; ONE SERVICE FOR EACH BLDG
 IS PERMITTED,230.2,230.70MAINS WILL BE
 REQUIRED TO BE GROUPED PER 230.72.
 MCB'S SHOWN IN EACH GARAGE PANEL IS
 PERMITTED.
 PLEASE ADJUST SERVICE FOR BLDG.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATINGS ARE SHOWN FOR EACH PANEL,
 BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW
 SERVICE).
  
 3)NOTE: PLEASE CLARIFY LOCATION OF
 DISHWASHER RECEPT. APPEARS TO BE SHOWN
 BEHIND UNIT? THIS IS ONLY A NOTE:
  
 4))NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE PLANS REDLINED FOR SOME
 MISSING W/IN 2' OF THE END OF A COUNTER
 OR 4' SPACING.
 UNIT "A"/STANDARD 2FLR,,,
  
 5)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE THESE HAVE BEEN REDLINED AT
 LOCATIONS OF NOTES.
 UNIT "B",3RD FLR OPT 6 2'OF WALL, UNIT
 "A"2ND FLR, WALL APPEARS TO BE OVER 12'?
 PLEASE SEE A COUPLE OF OTHER LOCATIONS.
  
 6)NOTE: PLEASE SEE LOCATION OF A
 RECESSED LT FIXTURE IN CLOSET
 WASHER/DRYER LOCATION. THESE LOCATIONS
 TYPICALLY CONTAIN SHELVING ABOVE THE
 WASHER/DRYER'S. PLEASE SEE 410.8 FOR MIN
 CLEARENCE FROM LT AND FIXTURE TYPES.
 (WALL MOUNT)? AS SHOWN IN OTHER CLOSETS?
  
 7 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS NEEDS
 TO BE SHOWN ABOVE THE GEN. KT/RECEPT
 LOADS. THIS SHOULD BE ABOVE THE FIGURED
 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 8)NOTE: PLEASE LIST ALL THE REQUIRD ARC
 FAULT PROECTED CIRCUITS AS REQUIRED PER
 2002 210.12
 PLEASE KNOW, SD'S ARE BEING SHOWN
 CIRCUITED TO KITCHEN LIGHTING CIRCUIT,
 THIS IS OK, HOWEVER PLEASE KNOW, THIS
 WOULD ALSO REQUIRE ARC FAULT PROTECTION
 FOR THIS ADDITIONAL CIRCUIT.
 THIS IS ONLY A NOTE:
  
 9)NOTE: PLEEASE SEE NFPA-72 (2002)
 EDITION,11.8.3.5.
 PLEASE PLACE NOTE ON PLANS WHICH STATES
 LOCATIONS OF SD'S TO BE A MIN OF 3' FROM
 BATH(S) AND KITCHEN DOORS AND 20' FROM
 KITCHEN COOKING APPLIANCES.
 ** PLEASE SEE EXCEPTION TO 20' FROM
 COOKING WITH TYPE OF SD USED.**
 PLEASE SEE PLANS SHOWS A SD IN KITCHEN
 AREA AT THIS TIME.
  
 10)NOTE: PLEASE SEE MECHANICAL NOTES
 PERTAINING TO "DRYER BOOSTER FANS".
 AS PER MECHANICAL THESE MAY NOT BE
 PERMITTED AND ANY COMMENT THEY MAY HAVE
 WILL DIRECTLY AFFECT ELECTRICAL PLANS.
 THIS IS A NOTE, AS IT IS NOT AN NEC
 ISSUE.
 PLEASE SEE ALL SYSTEMS DO HAVE BE
 LISTED.110.3,90.7
  
 11)NOTE: PLEASE SEE ARCHITECTS TITLE
 BLOCK SHALL ALSO CONTAIN THE PRINTED
 LICENSE NUMBER FOR ARCHITECT OF RECORD.
 FAC 61G1-16.004.
 PLEASE SEE THIS COMMENT IS FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
 PLEASE KNOW THIS COMMENT DOES NOT APPLY
 TO KAMM CONSULTING'S TITLE BLOCK.
  
 12)NOTE: PLEASE SEE "SHIFT" IN PLANS FOR
 ELECTRICAL DEVICES IN UNIT "A"-1 FST
 FLR(REV).
 PLEASE ALSO SEE SOME OTHER UNITS MISSING
 LAYOUT OF BATH RM AREA.
 3RD FLR, OPT 7 (REV).
  
 13)NOTE: PLEASE SEE PLANS DO NOT
 INDICATE ANY ACCESIBLITY TO GFI RECEPTS
 SHOWN FOR JACUZZI/WHIRLPOOL TUB.
  
 14)NOTE: PLEASE SEE 406.2B,210.21B3&4
 WHICH REQUIRES THE MAX OCP FOR A 50A
 RANGE RECEPT TO BE 50A'S. PLEASE SEE A
 2P-60A BRKR IS SHOWN.
  
 15)NOTE: PLEASE PROVIDE AREA AND ROOM
 DESIGNATIONS ON PLANS. PLEASE SEE SOME
 ARE MISSING.
 THIS WILL ALSO BE REQUIRED TO DETERMINE
 CIRCUITING FOR DINING AREAS.
  
 16)NOTE: PLEASE SEE PLANS REFERENCE THE
 2000 NFPA 101, WHEN AS OF JAN 1ST 2005,
 THE 2003 NFPA-101 IS IN EFFECT.
  
 ** PLEASE KNOW, MANY ITEMS HAVE BEEN
 REDLINED ON PLANS FOR LOCATIONS OF
 NOTES.
  
 ** PLEASE KNOW, A REVIEW OF MAIN
 ELECTRICAL SERVICECAN NOT BE DONE AT
 THIS TIME, AS SERVICE WILL BE CHANGING.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLF/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 ** PLEASE SEE THIS MAY BE CONSIDERED A
 "THRESHOLD" PROJECT. IF SO, THREE SETS
 OF PLANS WILL BE REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
2005-10-04 00:00:00IN ELECTRIC FOR REVIEW.
 NOTES TO FOLLOW

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-09-20 Cont ID  
Sent By mamini Date 2005-09-20 Time 11:18 Rev Time 0.50
Received By mamini Date 2005-09-20 Time 11:18 Sent To  
Notes
2005-09-20 00:00:00PASSED:
  
 1. SEE PERMIT # 04120439 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-06-23 Cont ID  
Sent By mwennerg Date 2006-06-23 Time 10:24 Rev Time 0.00
Received By mwennerg Date 2006-06-23 Time 10:24 Sent To  
Notes
2006-06-23 00:00:00***PROVISO***
  
 1) FLORIDA FIRE PREVENTION CODE, 2004
 EDITION SHALL BE REFERENCED. 2001
 EDITION IS CALLED OUT ON A-0.0.0.
  
 2) PLEASE SEE BUILDING REVIEW COMMENT
 (2) REGARDING THE SUBMITTAL OF FIRE
 PROTECTION SHEETS FOR REVIEW. THE
 SEPARATE SHOP DRAWINGS AND PERMIT WILL
 ALSO BE REQUIRED PRIOR TO SYSTEM
 INSTALLATION.
  
 PLANS NOT STAMPED UNTIL COMPLIANCE IS
 MET.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-10-06 Cont ID  
Sent By mwennerg Date 2005-10-06 Time 11:08 Rev Time 0.00
Received By mwennerg Date 2005-10-06 Time 11:08 Sent To  
Notes
2005-10-06 00:00:00******OK******
  
 1) INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILINGS SHALL BE CLASS A,
 CLASS B, OR CLASS C AND SHOULD BE NOTED
 ON PLANS.
  
 2) FIRE SPRINKLER MONITORING TO BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 20:27 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 20:27 Sent To  
Notes
2006-04-11 00:00:00TO "COMM" BD#4
2006-03-21 00:00:00WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-05 Cont ID  
Sent By adarroug Date 2005-12-05 Time 09:44 Rev Time 0.00
Received By adarroug Date 2005-12-05 Time 09:44 Sent To Z
Notes
2005-12-05 00:00:00TAKEN FROM "COMM" BD#56/TO "RMCDOUGAL"
 DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-08 Cont ID  
Sent By rmcdouga Date 2005-12-08 Time 08:38 Rev Time 0.00
Received By rmcdouga Date 2005-09-14 Time 14:14 Sent To  
Notes
2005-09-19 00:00:00TO "COMM" BD#56
2005-09-14 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-19 Cont ID  
Sent By pkrauss Date 2006-06-19 Time 21:22 Rev Time 0.00
Received By pkrauss Date 2006-06-19 Time 21:22 Sent To FIRE
Notes
2006-06-19 00:00:00PROVISO: 2001 FBC/BUILDING 1/4 UNITS
 RESPONSE TO COMMENTS DATED 11-21-06
  
 COMMENT #3:BOOSTER FANS ARE TO BE
 REMOVED AND SPECIFIC DRYERS ARE TO BE
 INSTALLED.PLEASE NOTE, SPECIFIC DRYERS
 ARE TO BE INSTALLED AT FINAL INSPECTION.
  
 COMMENT #5:PLAN SHEET M0.1. O.A.
 CALCULATIONS ARE BASED ON "INFILTRATION
 RATES".THESE ARE MAXIMUM RATES ALLOWED
 BY THE CODE & MAY NOT BE "ACTUAL/TRUE"
 RATES.THE ACTUAL RATE IS NOT KNOWN
 UNLESS TESTED.O.A. CALCS ARE TO BE IN
 ACCORDANCE WITH 2001 FMC 402.2, 402.2.1
 OR TABLE 403.3.PLAN SHEET M2 INDICATES
 A 6" O.A. DUCT, PLEASE REMOVE IF THIS IS
 NOT GOING TO BE UTILIZED.
  
 COMMENT #8:PLAN SHEET M0.1 THE AHU
 MOUNTING DETAIL KEYNOTE DETAIL 15 STATES
 NO COMBUSTIBLES ALLOWED IN THE RETURN
 AIR PLENUM.THE ARCHITECURAL PLANS
 (A-4.0.2) THE DOOR SCHEDULE INDICATES
 "WOOD LOUVERD DOOR".PLEASE VERIFY WITH
 THE DOOR MANUFACTURE THAT THIS DOOR &
 FRAME WILL MEET THE 25 FLAME/50 SMOKE
 INDEX WHEN TESTED UNDER ASTM 84.
  
 PLEASE REVISE PLANS TO REFLECT THE
 IMPLEMENTATION OF THE PROVISO'S.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-22 Cont ID  
Sent By pkrauss Date 2005-11-22 Time 10:06 Rev Time 0.00
Received By pkrauss Date 2005-11-21 Time 16:37 Sent To  
Notes
2005-11-22 00:00:00DENIED:
 1.PLAN SHEET 1-0.0.0 PROJECT
 INFORMATION INDICATES TYPE VI,
 UNPROTECTETED SPRINKLERED.PLEASE
 INDICATE FULL SPRINKLERED, 13R OR 13D
 TYPE SYSTEM.PLEASE NOTE, ADDTIONAL
 COMMENTS MAY BE GENERATED BY THE
 RESPONSES GIVEN.
  
 2.PLEASE CLARIFY DUCT PENETRATION
 THROUGH THE SEPARATION WALL BETWEEN THE
 GARAGE AND THE FIRST FLOOR OF THE
 RESIDENCE.PLAN SHEET A-4.0.2 &
 A-10.0.0, INDICATES THIS SEPARATION AS 1
 HR. PLAN M1 ONLY INDICATES A FIRE DAMPER
 AT THE CEILING PENETRATION.DUCTS LESS
 THAN 100 SQ INCHES SHALL COMPLY WITH
 2001 FMC 607.1.3 #3 ITEMS 1 THROUGH 4.
  
 3.PLAN SHEET M2 DRYER EXHAUST EXCEEDS
 25 FT REQUIREMNET WITH REDUCTIONS FOR
 90'S PER 2001 FMC 504.6.PLAN SHEET
 E2.2.4 INDICATES "BF" (BOOSTER FANS?).
 PLEASE NOTE INSTALLATION OF BOOSTER FANS
 WILL BE REVIEWED BY THE BUILDING OFFICAL
 UNDER "ALTERNATE MATERIALS & METHODS"
 2001 FMC 103.7.1.PLEASE PROVIDE THE
 FOLLOWING INFORMATION FOR REVIEW: 1) A
 LETTER FROM AN ENGINEER EMPLOYED BY THE
 DRYER MANUFACTURER STATING THE
 INSTALLATION OF THE DRYER BOOSTER FAN IS
 ACCEPTABLE AND WILL NOT VOID THE
 WARRANTY OF THE DRYER. 2) MEANS OF
 NOTIFYING THE OWNER SHOULD THE BOOSTER
 FAN FAIL. 3) MANUFACTURER'S SUBMITTAL &
 INSTALLATION DATA FOR THE BOOSTER FANS.
 4) PROVIDE ALL PERTINENT INFORMATION FOR
 ALL TRADES MECHANICAL, ELECTRICAL, FIRE,
 ETC. FOR THE INSTALLATION OF BOOSTER
 FANS.
  
 4.PLAN SHEET M2 THE O.A. INTAKE IS
 WITHIN 10 FT OF THE TOILET & DRYER
 EXHAUST TERMINATIONS.EXHAUST
 CONTAMINANTES SHALL NOT BE RECIRCULATED
 PER 2001 FMC 501.3.
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH TABLE
 403.3.
  
 6.PLEASE NOTE R/A TRANSFER GRILLES
 LOCATED ON THE 3RD FLOOR ARE NOT SIZED
 PROPERLY, SEE 2001 FMC 601.4 EXCEPTION 2
 & 3.TRANSFER SHALL BE A MINIMUM OF 50
 SQ INCHES PER 100 CFM OF SUPPLY AIR INTO
 THAT AREA.
  
 7.PLEASE PROVIDE DETAIL FOR THE AHU
 LOCATED IN THE CLOSET.PLEASE NOTE,
 MECHANICAL CLOSET SHALL BE CONSTRUCTED
 PER 2001 FMC 603.9 & 610.1.ABC.3.7 OF
 CHAPTER 13 OF THE 2001 FBC.
  
 8.NO COMBUSTIBLES ALLOWED IN THE
 MECHANICAL CLOSET PER 2001 FMC 602.2.1.
  
 9.CONDENSATE DRAIN SHALL TERMINATE A
 MINIMUM OF 12" FROM THE BUILDING
 STUCTURE PER 2001 FBC 1503.4.4.
  
 10. AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FMC
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-05-17 Cont ID  
Sent By kstevens Date 2006-05-17 Time 17:50 Rev Time 0.00
Received By kstevens Date 2006-05-17 Time 17:49 Sent To  
Notes
2006-05-17 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P2.1.1, P2.2.4, P3.1.1, P3.2, &
 P3.2.4 SEAL DOES NOT IMPART INFORMATION
 REQUIRED FOR THE IMPRESSION TYPE SEAL.
 SIGNATURE REQUIRED ON THE SEAL, INITIALS
 DO NOT MATCH SIGNATURE ON OTHER PLUMBING
 SHEETS. 61G15-23.002(1) & FS R71.025.
 ALSO SEE 61G15-23.001, AND ATTACHED
 SHEET CONCERNING SEAL MANDATE FROM THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
  
 2. SHTS P2.1.1, P3.1.1 THE SANITARY
 BUILDING DRAIN SHALL BE A MINIMUM OF 4
 FT. OFF THE FOOTER PER SECTION 307.4.
  
 3. SHTS P2.2.4, & P3.2.4 FLOOR PLAN AND
 RISER DIAGRAM SHOW THE KITCHEN SINK ARMS
 RUNNING ABOVE THE FLOOR AND IN FRON OF
 THE RANGE. PLEASE CLARIFY. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-12 Cont ID  
Sent By kstevens Date 2005-11-12 Time 18:41 Rev Time 0.00
Received By kstevens Date 2005-11-12 Time 18:41 Sent To  
Notes
2005-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHTS P2.1.1, P-2.2.4, P-3.1.1, P-3.2
 AND P-3.2.4 WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASH MACHINES OF ALL
 UNITS. PER SECTION 604.9. - ALL WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE",
 NOT IN THE CEILING AS SHOWN IN SOME
 CASES. PDI-WH 201 AND MANUF INSTALLATION
 INSTRUCTIONS.
 2. IF INDIVIDUAL METERS NO BACKFLOW
 DEVISE IS REQUIRED, BUT IF SINGLE METER
 AN RPZV BACKFLOW WILL BE REQUIRED ON THE
 WATER SERVICE. PLEASE CLARIFY. SECTION
 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-12-14 Cont ID  
Sent By gjoyce Date 2005-12-14 Time   Rev Time  
Received By gjoyce Date 2005-12-14 Time   Sent To R
Notes
***NONE***