Plan Review Details - Permit 05090527
Plan Review Stops For Permit 05090527
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2005-11-15 Cont ID  
Sent By jleech Date 2005-11-15 Time 17:08 Rev Time 0.25
Received By jleech Date 2005-11-15 Time 17:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-10-04 Cont ID  
Sent By jleech Date 2005-10-04 Time 12:38 Rev Time 0.50
Received By jleech Date 2005-10-04 Time 12:38 Sent To  
Notes
2005-10-04 00:00:00DENIED;
 1. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (TANK), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 4.WHERE IS SECOND STAG REGULATOR?
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-17 Cont ID  
Sent By adarroug Date 2005-10-17 Time 09:26 Rev Time 0.00
Received By adarroug Date 2005-10-17 Time 09:26 Sent To G
Notes
2005-10-17 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-13 Cont ID  
Sent By adarroug Date 2005-09-13 Time 13:20 Rev Time 0.00
Received By adarroug Date 2005-09-13 Time 13:20 Sent To FUEL
Notes
2005-09-13 00:00:00TO "G" BOX