Plan Review Details - Permit 05090373
Plan Review Stops For Permit 05090373
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-05 Cont ID  
Sent By jgomez Date 2005-12-05 Time 18:17 Rev Time 0.50
Received By jgomez Date 2005-12-05 Time 18:17 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-07 Cont ID  
Sent By jgomez Date 2005-10-07 Time 13:21 Rev Time 0.33
Received By jgomez Date 2005-10-07 Time 13:21 Sent To PC
Notes
2005-10-07 00:00:00BUILDING REVIEW CHECKLIST:
 1- RECORDED NOTICE OF COMMENCEMENT IS
 MISSING REQUIRED INFORMATION:
 LEGAL DESCRIPTION OF PROPERTY, STREET
 ADDRESS AND THE TAX FOLIO NUMBER. NEED
 TO COMPLETE INFORMATION AND RE-RECORD
 NOTICE OF COMMENCEMENT.
  
 2- PROVIDE ENGINEERED DESIGN PRESSURES
 FOR WINDOWS AND DOORS OPENINGS AS REQ'D
 BY SEC. 1606.1 FBC 2001 AND SEC.
 104.2.1.2 OF CITY AMENDMENTS TO FBC
 2001. ALSO, CLEARLY INDICATE IF
 WINDOW/DOOR IS LOCATED AT THE END OR
 INTERIOR ZONE. PROVIDE KEY PLAN. SEC.
 1606.1 FBC 2001.
  
 3- TO VERIFY THAT DOORS AND WINDOWS
 COMPLY WITH THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER NEED TO
 PROVIDE:
 A) DOORS AND WINDOWS SIZES.
 B) MARK ON DRAWINGS SPECIFIC WINDOWS AND
 DOORS TO BE USED. INCLUDING GLAZING TYPE
 TO BE USED AND REINFORCING IF REQUIRED.
 SEC. 104.2.1.2 CITY AMENDMENTS FBC 2001.
  
 4- IF USING 2X STRUCTURAL BUCKS FOR
 DOORS AND WINDOWS, THEN THEY NEED TO BE
 DESIGN TO RESIST THE LOADS. PROVIDE
 DETAIL/SPECS FOR STRUCTURALBUCK SIZE
 AND ANCHORING FOR DOORS AND WINDOWS.SEC.
 1707.4.4.2 FBC 2001, SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001 AND AS REQUIRED
 ON PRODUCT APPROVALS.
 SEE NOTE: "BUCKS BY OTHERS" ON PRODUCT
 APPROVALS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-20 Cont ID  
Sent By adarroug Date 2005-09-20 Time 08:50 Rev Time 0.00
Received By adarroug Date 2005-09-20 Time 08:50 Sent To B
Notes
2005-09-20 00:00:00TO "MISC" BOX#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-12 Cont ID  
Sent By adarroug Date 2005-09-12 Time 13:32 Rev Time 0.00
Received By adarroug Date 2005-09-12 Time 13:32 Sent To Z
Notes
2005-09-12 00:00:00TO 'Z" BOX

Review Stop Z ZONING
Rev No 1 Status N Date 2005-09-19 Cont ID  
Sent By mmclean Date 2005-09-19 Time 15:23 Rev Time 0.00
Received By mmclean Date 2005-09-19 Time 15:23 Sent To I
Notes
2005-09-19 00:00:00ZONING DOES NOT REVIEW WINDOWS & IMPACT
 SLIDING GLASS DOORS.