Plan Review Stops For Permit 05090280 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2005-11-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-11-18 |
Time |
18:31 |
Rev Time |
0.50 |
Received By |
jgomez |
Date |
2005-11-18 |
Time |
18:31 |
Sent To |
PC |
|
Notes |
2005-11-18 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO | | (PROVIDE INFO. PRIOR TO INSTALLATION TO | | AVOID DELAYS OR CONFLICTS): | | | | 1- PROVIDE COMPLETE INFORMATION FOR | | STORM SHUTTERS, 12'-0" WIDE SLIDING | | GLASS DOORS AND 8'-0" HIGH 1HR FIRE | | RATED INSWING DOOR AS SHOWN IN PLANS AT | | ATRIUM UNDER A SEPARATE PERMIT AS AGREED | | WITH CONTRACTOR. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2005-11-18 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-11-15 |
Time |
18:59 |
Rev Time |
1.00 |
Received By |
jgomez |
Date |
2005-11-15 |
Time |
18:59 |
Sent To |
|
|
Notes |
2005-11-15 00:00:00 | CALLED ANDY TO GET CORRECT ENERGY CALCS. | | PLANS ON JULIO'S DESK WAITING TO GET THE | | ENERGY CALCULATIONS TO PROCEED WITH | | PERMIT PROCESS. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-09-30 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-09-29 |
Time |
17:55 |
Rev Time |
2.00 |
Received By |
jgomez |
Date |
2005-09-29 |
Time |
17:51 |
Sent To |
PC |
|
Notes |
2005-09-29 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- ROOF FRAMING PLAN: REVISE CONNECTORS | | SPECIFIED FOR TRUSSES RESTING ON GIRDER | | TRUSS AT ENTRY ROOF. CONNECTOR SPECIFIED | | IS FOR MASONRY APPLICATION. NEED TO | | SPECIFY WOOD TO WOOD CONNECTORS. | | | | 2- TRUSS ANCHOR SCHEDULE: REVISE NUMBER | | OF NAILS SPECIFIED FOR HUS26. SEE 2005 | | CATALOGUE. | | | | 3- PROVIDE FLORIDA OR LOCAL PRODUCT | | APPROVAL FOR: | | A) ATRIUM 1 HR FIRE RATED DOOR WITH | | INSWING AS SPECIFIED ON PLANS. | | B) ROOF TILE (MISSING FLORIDA APPROVAL) | | C) FIXED WINDOW (MISSING FL. APPROVAL) | | D) FRENCH DOORS AT GREAT ROOM. | | | | 4- WINDOW MULLION SIZE SPECIFIED FOR | | FIXED WINDOWS AT GREAT ROOM DOESN'T | | RESIST THE DESIGN PRESSURES. REVISE AS | | REQUIRED AND SPECIFY ANCHORS. SECTION | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | | 5- NEED RECORDED NOC. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2006-02-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2006-02-02 |
Time |
14:53 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2006-02-02 |
Time |
12:52 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2005-09-19 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-09-19 |
Time |
07:40 |
Rev Time |
0.75 |
Received By |
btrobaug |
Date |
2005-09-19 |
Time |
06:56 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2006-02-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-02-01 |
Time |
18:04 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-02-01 |
Time |
18:04 |
Sent To |
E |
|
Notes |
2006-02-01 00:00:00 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-11-08 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-11-08 |
Time |
14:30 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-11-08 |
Time |
14:30 |
Sent To |
B |
|
Notes |
2005-11-08 00:00:00 | TO "JGOMEZ" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-09-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-09-16 |
Time |
15:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-09-16 |
Time |
15:59 |
Sent To |
E |
|
Notes |
2005-09-16 00:00:00 | TO "SFR" "E" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-09-30 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2005-09-30 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2005-09-12 |
Time |
13:55 |
Sent To |
|
|
Notes |
2005-09-12 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2005-09-22 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2005-09-22 |
Time |
16:30 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2005-09-22 |
Time |
16:30 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2005-09-26 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-09-26 |
Time |
13:37 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2005-09-26 |
Time |
13:37 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2005-09-16 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-09-16 |
Time |
15:01 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-09-16 |
Time |
15:01 |
Sent To |
I |
|
Notes |
|
|