2005-10-06 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- ROLLAFLEX SHADE: |
| A) EVEN THOUGH THIS PRODUCT IS NOT USED |
| FOR HURRICANE MISSILE IMPACT PROTECTION, |
| STILL IT NEEDS TO MEET THE DESIGN |
| CRITERIA OF SEC. 1606 FBC 2001. PRODUCT |
| WAS DESIGNED FOR 90MPH. NEED TO COMPLY |
| WITH THE 140MPH WIND LOAD DESIGN |
| PRESSURES. |
| |
| B) WIND LOAD TABLE 3.44 IS NOT PREPARED |
| BY THE SAME ENGINEER WHO DESIGNED THE |
| ROLLAFLEX SHADE. NEED TO BE SIGNED AND |
| SEALED BY THE CONSULTING ENGINEER SHOWN |
| ON THE TITLE BLOCK AT BOTTOM OF PAGE AS |
| REQUIRED BY CHAPTER 471 FLORIDA |
| STATUTES. |
| |
| C) WIND LOAD TABLE 3.44: CLARIFY WHY |
| USING TRIBUTARY AREA OF 100S.F.SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| D) PROVIDE DETAILS AND SPECIFICATION FOR |
| ANCHORING OF UPPER BOX SUPPORTING THE |
| ROLLAFLEX SHADE WHEN IT'S IN OPEN |
| POSITION. MUST RESIST WIND LOADS OF |
| CHAPTER 16 FBC 2001. |
| |
| E) NUMBER OF SPANS ARE TWOACCORDING TO |
| 90MPH WIND LOAD. REVISE NUMBER OF SPAN |
| REQUIRED ACCORDING TO THE REVISED |
| ENGINEER CALCULATIONS FOR 140MPH. SEE |
| SHEET 2 OF 2.SECTION 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| F) ENGINEER TO PROVIDE ALL HIS |
| INFORMATION ON SIGNED AND SEALED |
| DRAWINGS AS REQUIRED BY CHAPTER 471 FL. |
| STATUTES & FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.002. |
| |
| G) PROVIDE SPECS/DETAILS OF HOW IS THE |
| SHADE OPENED/CLOSED. IS IT DONE MANUALLY |
| OR POWERED?. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. (ELECTRIC PERMIT |
| REQUIRED FOR POWERED OPERATION) |
| |
| H) PROVIDE 2 ORIGINAL SIGNED AND SEALED |
| DRAWINGS. NOT COPIES. CHAPTER 471 |
| FLORIDA STATUTES. |
| |
| 3- IF THE INTENTION IS TO PROTECT ALL |
| DWELLING OPENINGS, THEN CLARIFY WHY |
| OPENING #1 IS NOT GOING TO BE PROTECTED. |
| LEAVING OPENINGS WITHOUT PROTECTION |
| (SPECIALLY A LARGE OPENING) DECEIVES THE |
| PURPOSE OF PROTECTING THE DWELLING. |
| DWELLING WILL BE PARTIALLY OPEN AND IF |
| GLASS BRAKES IN OPENING #1, THEN THE |
| OTHER SHUTTERS WILL PROVIDE NOT |
| PROTECTION BECAUSE THEY MAY BE BLOWN |
| AWAY BY THE THE INTERNAL PRESSURES. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712. |