Plan Review Details - Permit 05090055
Plan Review Stops For Permit 05090055
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-02-07 Cont ID  
Sent By lmartine Date 2007-02-07 Time 14:17 Rev Time 0.00
Received By lmartine Date 2007-02-07 Time 13:18 Sent To  
Notes
2007-02-07 14:22:05SEE SHEET 2 OF 6 OF PGT FIXED WINDOW REPORT MAX. D.L.O.
 IS 53".

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2006-12-10 Cont ID  
Sent By rnuquist Date 2006-12-10 Time 13:18 Rev Time 0.00
Received By rnuquist Date 2006-12-10 Time 13:18 Sent To  
Notes
2006-12-10 13:19:58ADDED GENERATOR MUST BE ON A SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-09-01 Cont ID  
Sent By alange Date 2006-09-01 Time 14:03 Rev Time 0.75
Received By alange Date 2006-09-01 Time 14:03 Sent To  
Notes
2006-09-01 00:00:00REV OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-08-01 Cont ID  
Sent By alange Date 2006-08-01 Time 14:37 Rev Time 0.00
Received By alange Date 2006-08-01 Time 14:37 Sent To  
Notes
2006-08-01 00:00:00STRUCTURAL REV OK, TRUSS DRAWINGS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-06 Cont ID  
Sent By alange Date 2006-04-06 Time 08:30 Rev Time 1.75
Received By alange Date 2006-04-05 Time 16:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-03-10 Cont ID  
Sent By alange Date 2006-03-10 Time 11:30 Rev Time 0.75
Received By alange Date 2006-03-10 Time 11:29 Sent To  
Notes
2006-03-10 00:00:00DENIED
  
  
 7.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL INFORMATION ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-08 Cont ID  
Sent By alange Date 2006-02-08 Time 13:18 Rev Time 1.50
Received By alange Date 2006-02-08 Time 13:16 Sent To  
Notes
2006-02-08 00:00:00DENIED
  
 1. 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 7.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL INFORMATION ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-29 Cont ID  
Sent By alange Date 2005-09-29 Time 10:40 Rev Time 1.75
Received By alange Date 2005-09-29 Time 09:55 Sent To  
Notes
2005-09-29 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PLEASE SUBMIT 2 ORIGONAL SIGNED AND
 SEALED SURVEYS.FS 472.025
  
 4.SIGN OWNER/AGENT ON ENERGY CALCS.
  
 5.INCLUDE A WINDOW SCHEDULE ON PLANS
 AND INCLUDE SIZE AND TYPES OF BEDROOM
 WINDOWS AND SILL HEIGHT SO THAT
 EMERGENCY ESCAPE OPENING SIZES CAN BE
 CHECKED.FBC 1004.5
  
 6.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS WITH QUALITY ASSURANCE FOR THE
 FOLLOWING:WINDOWS, EXTERIOR DOORS,
 IMPACT PROTECTION, ROOFING AND STRAPS
 AND TIE-DOWNS.
  
 7.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL INFORMATION ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-11-13 Cont ID  
Sent By jleahy Date 2006-11-13 Time 06:46 Rev Time 0.30
Received By jleahy Date 2006-11-13 Time 06:39 Sent To P
Notes
2006-11-13 06:46:50OUTLETS REQUIRED BY 210.52 SHALL BE INSTALLED
  
 GENERATOR REQUIRES A SEPARATE PLAN AND PERMITS.
  
  
 JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-01-22 Cont ID  
Sent By jleahy Date 2006-01-22 Time 12:04 Rev Time 0.45
Received By jleahy Date 2006-01-22 Time 12:03 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-11 Cont ID  
Sent By jleahy Date 2005-09-11 Time 15:52 Rev Time 1.00
Received By jleahy Date 2005-09-11 Time 15:52 Sent To M
Notes
2005-09-11 00:00:00NEED RISER DIAGRAM
  
 NEED PANEL SCHEDULE
  
 LOAD CALCULATION SHOWS 150A WHAT PANEL
 IS IN HOUSE.
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-12-28 Cont ID  
Sent By mperson Date 2006-12-28 Time 11:21 Rev Time 0.00
Received By mperson Date 2006-12-28 Time 11:21 Sent To B
Notes
2006-12-28 13:00:01CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL INSPECTION.
 THE SUBMITTED GAS RISER DIAGRAM CAN'T BE A REVISION
 BECAUSE THERE IS NO GAS PERMIT.
  
 PLEASE NOTE THAT THE SUBMITTED GAS RISER DIAGRAM IS NOT
 SIZED CORRECTLY PER THE FOLLOWING TABLES.
 A} NFPA (ONLINE) TABLE 6.2(B) SCHEDULE 40 METALLIC PIPE
 BECAUSE FBC-2004 FUEL GAS TABLE, 402.4 (2) ONLY GOES TO
 200'.
 B} NFPA (ONLINE) TABLE 6.2(S) POLYETHYLENE PLASTIC PIPE
 BECAUSE FBC-2004 FUEL GAS TABLE, 402.4 (20) ONLY GOES
 TO 200'.
 C} FBC-2004 FUEL GAS TABLE 402.4 (14) CSST.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-11-30 Cont ID  
Sent By mperson Date 2006-11-30 Time 08:02 Rev Time 0.50
Received By mperson Date 2006-11-30 Time 08:02 Sent To E
Notes
2006-11-30 08:41:19REVISION UNSAT
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE NOTE THAT A SEPERATE GEN/RES PERMIT IS
 REQUIRED FOR THE GENERATOR AND THAT A GAS PERMIT CAN
 NOT BE ISSUED UNTIL ONE HAS BEEN APPLIED FOR AND
 ZONING, ELECTRICAL AND GAS HAS APPROVED THE GENERATOR
 LOCATION. OR YOU CAN INDICATE ON THE DRAWINGS THAT THE
 GENERATOR IS A "FUTURE" GENERATOR.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING
 LENGTHS INDICATED ON THE GAS RISER DIAGRAM ON SHEET
 A-3.
  
 3. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON
 SHEET A-3 GAS RISER DIAGRAM.
  
 4.PLEASE INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI ON SHEET A-3 GAS
 RISER DIAGRAM.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: NEED MANUFACTURER SHEETS OF MP REGULATORS IF GAS
 SYSTEM IS 2PSI. ALSO NEED MANUFACTURER SHEETS AND
 INSTALLATION INSTRUCTIONS ON GENERATOR TO VERIFY BTU
 LOAD AND MINIMUM INSTALLATION CLEARENCES TO
 STRUCTURES.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 11:26 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 11:26 Sent To M
Notes
2006-12-18 11:26:40TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-12-15 Cont ID  
Sent By adarroug Date 2006-12-15 Time 14:50 Rev Time 0.00
Received By adarroug Date 2006-12-15 Time 14:50 Sent To B
Notes
2006-12-15 14:50:40TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-12-04 Cont ID  
Sent By adarroug Date 2006-12-04 Time 10:51 Rev Time 0.00
Received By adarroug Date 2006-12-04 Time 10:50 Sent To B
Notes
2006-12-04 10:51:28TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-11-29 Cont ID  
Sent By spalmer Date 2006-11-29 Time 18:29 Rev Time 0.00
Received By spalmer Date 2006-11-29 Time 18:29 Sent To M
Notes
2006-11-29 18:29:41REV/TO TGORDON'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-11-12 Cont ID  
Sent By adarroug Date 2006-11-12 Time 13:49 Rev Time 0.00
Received By adarroug Date 2006-11-12 Time 13:49 Sent To E
Notes
2006-11-12 13:50:03TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-19 Cont ID  
Sent By adarroug Date 2006-08-19 Time 15:58 Rev Time 0.00
Received By adarroug Date 2006-08-19 Time 15:58 Sent To B
Notes
2006-08-19 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-04-03 Cont ID  
Sent By adarroug Date 2006-04-03 Time 08:58 Rev Time 0.00
Received By adarroug Date 2006-04-03 Time 08:58 Sent To M
Notes
2006-04-03 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-28 Time 17:34 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 17:34 Sent To M
Notes
2006-02-28 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-20 Cont ID  
Sent By adarroug Date 2006-01-20 Time 13:57 Rev Time 0.00
Received By adarroug Date 2006-01-20 Time 13:57 Sent To E
Notes
2006-01-20 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-09 Cont ID  
Sent By adarroug Date 2005-09-09 Time 15:54 Rev Time 0.00
Received By adarroug Date 2005-09-09 Time 15:54 Sent To E
Notes
2005-09-09 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-29 Cont ID  
Sent By alange Date 2005-09-29 Time 11:03 Rev Time 0.00
Received By alange Date 2005-09-01 Time 18:20 Sent To  
Notes
2005-09-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 7 Status N Date 2006-12-19 Cont ID  
Sent By tgordon Date 2006-12-19 Time 08:51 Rev Time 0.20
Received By tgordon Date 2006-12-19 Time 08:51 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2006-11-30 Cont ID  
Sent By tgordon Date 2006-11-30 Time 09:31 Rev Time 0.30
Received By tgordon Date 2006-11-30 Time 09:31 Sent To B
Notes
2006-11-30 09:37:17*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT, PER 2001 FBC 13-600.3.A.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-04-06 Cont ID  
Sent By tgordon Date 2006-04-06 Time 16:21 Rev Time 0.30
Received By tgordon Date 2006-04-06 Time 16:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-04-03 Cont ID  
Sent By tgordon Date 2006-04-03 Time 14:08 Rev Time 0.30
Received By tgordon Date 2006-04-03 Time 14:07 Sent To B
Notes
2006-04-03 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR
 20,400 TOTAL BTU'S, MECHANICAL PLANS ARE
 CALLING FOR 38,000 TOTAL BTU'S, THE
 PLANS CAN NOT CALL FOR MORE TOTAL BTU'S
 THAN THE ENERGY CAL'S. PLEASE CORRECT.
  
 2) MANUAL J CALCULATIONS ARE CALLING FOR
 15,125 SENSIBLE BTU'S AND THE MECHANICAL
 PLANS ARE CALLING FOR 29,000 SENSIBLE
 BTU'S, THE PLANS CAN ONLY CALL FOR 20%
 MORE THAN THE MANUAL J CAL'S. PER 2004
 FBC CH. 13 607.1.ABC.1.1 PLEASE CORRECT.
  
 3) ENERGY CALCULATIONS ARE CALLING FOR 5
 KW HEAT AND THE MECHANICAL PLANS ARE
 CALLING FOR 10 KW HEAT, THE PLANS CAN
 NOT CALL FOR MORE THAN THE ENERGY CAL'S.
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-03-01 Cont ID  
Sent By tgordon Date 2006-03-01 Time 11:30 Rev Time 0.45
Received By tgordon Date 2006-03-01 Time 11:30 Sent To B
Notes
2006-03-01 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW ALL RETURN
 AIR DUCTS AND GRILLS NEED TO SHOW SIZES.
  
 2) RETURN AIR TRANSFER DUCT FROM STUDY
 TO AHU CLOSET IS NOT SIZED.
  
 3) RETURN AIR GRILL IN STUDY IS NOT
 SIZED.
  
 4) RETURN AIR OPEN DUCT IN AHU CLOSET IS
 NOT SIZED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-01-23 Cont ID  
Sent By tgordon Date 2006-01-23 Time 16:05 Rev Time 0.30
Received By tgordon Date 2006-01-23 Time 16:05 Sent To B
Notes
2006-01-23 00:00:00*** DENIED ***
 1)NEED DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS FOR NEW VENTLESS FIREPLACE.
  
 2) NEED TO SUPPLY COMBUSTION AIR, OR
 COMBUSTION AIR CALCULATIONS FOR VENTLESS
 FIREPLACE, PER 2001 FBC/M 701.1 .
  
 3) NEED ALL RETURN AIR DUCTS SIZED AND
 ALL RETURN AIR GRILLS SIZED.
  
 4) NEED MECHANICAL PLANS SIGNED AND NAME
 PRINTED.ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-12 Cont ID  
Sent By tgordon Date 2005-09-12 Time 08:23 Rev Time 0.15
Received By tgordon Date 2005-09-12 Time 08:23 Sent To P
Notes
2005-09-12 00:00:00NOT APPLYING FOR MECH. PERMIT AT THIS
 TIME, NO MECH. CONTRACTOR OR MECH. PLANS
 SUBMITTED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-12-28 Cont ID  
Sent By mperson Date 2006-12-28 Time 11:20 Rev Time 0.33
Received By mperson Date 2006-12-28 Time 11:20 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-11-29 Cont ID  
Sent By mperson Date 2006-11-29 Time 16:39 Rev Time 0.45
Received By mperson Date 2006-11-29 Time 16:39 Sent To G
Notes
2006-11-29 16:49:44REVISION UNSAT
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTION ARE REQUIRED FOR PLUMBING PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE NEW SINK INDICATED ON SHEET A-1 MUST BE ADDED TO
 THE SANITARY RISER DIAGRAM ON SHEET A-3 AND ALSO BE
 NOTED AS A REVISION.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-09-20 Cont ID  
Sent By jleech Date 2005-09-20 Time 10:21 Rev Time 0.50
Received By jleech Date 2005-09-20 Time 10:21 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-09 Cont ID  
Sent By mmclean Date 2005-09-09 Time 15:16 Rev Time 0.00
Received By mmclean Date 2005-09-08 Time 18:00 Sent To I
Notes
***NONE***