2005-09-01 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- PROVIDE FLORIDA LOCAL PRODUCT |
| APPROVAL OR APPLY FOR LOCAL PRODUCT |
| APPROVAL AS REQUIRED BY RULE 9B-72 OF |
| DCA. SEE WWW.FLORIDABUILDING.ORG. |
| |
| DADE COUNTY NOA ALONE IS NOT |
| AUTOMATICALLY AN STATEWIDE PRODUCT |
| APPROVAL. IF MANUFACTURER DOESN'T HAVE |
| THE FLORIDA PRODUCT APPROVAL, THEN, |
| MANUFACTURER MAY APPLY FOR LOCAL PRODUCT |
| APPROVAL USING THE DADE COUNTY NOA AND |
| BY COMPLETING THE LOCAL PRODUCT APPROVAL |
| FORM DOWNLOADED FROM THE FLORIDA WEBSITE |
| WWW.FLORIDABUILDING.ORG. |
| |
| 2- CLEARLY SPECIFY HOW IS CLAY TILE |
| GOING TO BE ATTACHED TO VERIFY |
| COMPLIANCE WITH THE UPLIFT LOADS. IF |
| USING NAILS OR SCREWS, THEN, SPECIFY |
| NUMBER OF FASTENERS PER TILE. |
| |
| 3- OWES $8.78 FOR UPDATED VALUATION IN |
| THE PERMIT APPLICATION. VALUATION WAS |
| UPDATED TO $10,160. |
| |
| 4- SPECIFY EXISTING TYPE OF ROOFING TO |
| BE REMOVED. IF EXISTING ROOF WERE |
| SHINGLES, THEN, ENGINEER'S CERTIFICATION |
| WILL BE REQUIRED TO VERIFY THAT EXISTING |
| ROOF TRUSSES WILL RESIST THE PROPOSED |
| LOAD OF CLAY TILES. |
| |