Plan Review Details - Permit 05082087
Plan Review Stops For Permit 05082087
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-20 Cont ID  
Sent By alange Date 2005-09-20 Time 14:52 Rev Time 0.66
Received By alange Date 2005-09-20 Time 13:40 Sent To  
Notes
2005-09-20 00:00:00 
  1ST REVIEW
  ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE
 ISSUED.
  
 2) PROVIDE INFORMATION FOR THE SLAB
 AND
 ANCHORING OF GENERATOR, SEE1606.1.3
 ANCHORAGE AGAINST OVERTURNING, UPLIFT
 AND SLIDING. STRUCTURAL MEMBERS AND
 SYSTEMS, AND COMPONENTS AND CLADDING
 IN
 A BUILDING OR STRUCTURE SHALL BE
 ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR
 THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN
 PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 3) SURVEY: FL S S472.025 REQUIRES
 SURVEYS TO BE ORIGINALS, SIGNED,
 SEALED
 AND DATED.
  
 4 ) FBC 104.2.1ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-09 Cont ID  
Sent By dpalmer Date 2005-09-09 Time 19:43 Rev Time 0.30
Received By dpalmer Date 2005-09-09 Time 19:43 Sent To M
Notes
2005-09-09 00:00:00*** UNSAT ****
  
 1)NOTE: PLEASE SEE 225.34, 230.72 WHICH
 REQUIRES ALL MAINS TO BE GROUPED.
  
 PLEASE CLARIFY IF EXSITING MCB PANELS
 ARE LOCATED IMMEDIATELY AJACENT/CLOSE
 PROXIMITY TO EXISTING PANELS.
 PLEASE SEE 225.31 FOR DISCONNECTING
 MEANS REQUIRED, GROUPED PER 225.34 AND
 RATED FOR SERVICE EQUIPMENT PER 225.36
  
 2)NOTE: PLEASE CORRELATE PANELS SHOWN ON
 RISER WITH PANEL SCHEDULES SUBMITTED.
 215.5
  
 3)NOTE: PLEASE SEE SITE/ EQUIPMENT PLANS
 DOES NOT INDICATE LOCATION OF ATS,
 EXISTING MAINS, OR EXISITNG PANELS.
 ARE EXISTING PANELS MCB?
 UNABLE TO VERIFY NOTES ABOVE.
  
  
 4)NOTE: PLEASE SEELOAD CALCULATIONS
 SUBMITTED. PLEASE SEE 220.31B, NO
 DERATING MAY BE TAKEN FOR AHU/HEAT.
 PLEASE SEE IS IT PERMITTED TO "LOAD
 SHED" HEAT LOADS FROM A/C SYSTEMS
 THROUGH LV CONTACTORS FROM GEN OR ATS.
 220.31,702.5, 90.4,700.5
 IF SHEDDING LOADS, SHOW DETAIL IN DOING
 SO.
 PLEASE CORRELATE LOADS ON PANELS AND SUB
 PANELS.
 PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%,
 PLEASE SEE SOME PANELS SHOWS 100% FIG
 FOR HEAT AND OTHERS SHOW A 65% FIG.
 230.42,215.3, ETC.
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 6)NOTE: PLEASE SEE AN APPROPRIATE VALUE
 SHALL BE PLACED ON PERMIT APPLICATION.
 FBC 104.6.5, ALL LABOR AND MATERIALS.
 PLEASE SEE PERMIT FROM THIS COMPANY FOR
 SMALLER UNITS HAVE COME IN WITH A VALUE
 IN EXCESS OF $11,000 MORE THAN THIS
 PERMIT APPL.?????
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 15:46 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 15:46 Sent To E
Notes
2005-09-08 00:00:00TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 14:46 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 14:46 Sent To Z
Notes
2005-09-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-15 Cont ID  
Sent By tgordon Date 2005-09-15 Time 08:03 Rev Time 0.20
Received By tgordon Date 2005-09-15 Time 08:03 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-09-17 Cont ID  
Sent By jleech Date 2005-09-17 Time 13:25 Rev Time 0.25
Received By jleech Date 2005-09-17 Time 13:25 Sent To B
Notes
2005-09-17 00:00:00GAS PERMIT REQUIRED BY GAS CONTRACTOR
 DRAWINGS REQUIRED WITH APPLICATION. GAS
 PERMIT IS REQUIRED TO BE ON THE JOB AND
 MUST BE SIGNED OFF BEFORE FINAL
 INSPECTION ON GENERATOR.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-07 Cont ID  
Sent By mmclean Date 2005-09-07 Time 19:47 Rev Time 0.00
Received By mmclean Date 2005-09-07 Time 19:47 Sent To I
Notes
2005-09-07 00:00:00GENERATOR CAN ONLY ENCROACH 4FT INTO
 SETBACK.