2005-09-09 00:00:00 | *** UNSAT **** |
| |
| 1)NOTE: PLEASE SEE 225.34, 230.72 WHICH |
| REQUIRES ALL MAINS TO BE GROUPED. |
| |
| PLEASE CLARIFY IF EXSITING MCB PANELS |
| ARE LOCATED IMMEDIATELY AJACENT/CLOSE |
| PROXIMITY TO EXISTING PANELS. |
| PLEASE SEE 225.31 FOR DISCONNECTING |
| MEANS REQUIRED, GROUPED PER 225.34 AND |
| RATED FOR SERVICE EQUIPMENT PER 225.36 |
| |
| 2)NOTE: PLEASE CORRELATE PANELS SHOWN ON |
| RISER WITH PANEL SCHEDULES SUBMITTED. |
| 215.5 |
| |
| 3)NOTE: PLEASE SEE SITE/ EQUIPMENT PLANS |
| DOES NOT INDICATE LOCATION OF ATS, |
| EXISTING MAINS, OR EXISITNG PANELS. |
| ARE EXISTING PANELS MCB? |
| UNABLE TO VERIFY NOTES ABOVE. |
| |
| |
| 4)NOTE: PLEASE SEELOAD CALCULATIONS |
| SUBMITTED. PLEASE SEE 220.31B, NO |
| DERATING MAY BE TAKEN FOR AHU/HEAT. |
| PLEASE SEE IS IT PERMITTED TO "LOAD |
| SHED" HEAT LOADS FROM A/C SYSTEMS |
| THROUGH LV CONTACTORS FROM GEN OR ATS. |
| 220.31,702.5, 90.4,700.5 |
| IF SHEDDING LOADS, SHOW DETAIL IN DOING |
| SO. |
| PLEASE CORRELATE LOADS ON PANELS AND SUB |
| PANELS. |
| PLEASE SHOW ALL CONTINUOUS LOADS AT |
| 125%, |
| PLEASE SEE SOME PANELS SHOWS 100% FIG |
| FOR HEAT AND OTHERS SHOW A 65% FIG. |
| 230.42,215.3, ETC. |
| |
| 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 6)NOTE: PLEASE SEE AN APPROPRIATE VALUE |
| SHALL BE PLACED ON PERMIT APPLICATION. |
| FBC 104.6.5, ALL LABOR AND MATERIALS. |
| PLEASE SEE PERMIT FROM THIS COMPANY FOR |
| SMALLER UNITS HAVE COME IN WITH A VALUE |
| IN EXCESS OF $11,000 MORE THAN THIS |
| PERMIT APPL.????? |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |