Plan Review Stops For Permit 05082085 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2005-11-17 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-11-17 |
Time |
10:38 |
Rev Time |
0.33 |
Received By |
alange |
Date |
2005-11-17 |
Time |
10:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-09-19 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-09-19 |
Time |
07:01 |
Rev Time |
0.33 |
Received By |
jwitmer |
Date |
2005-09-19 |
Time |
07:00 |
Sent To |
PC |
|
Notes |
2005-09-19 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 05082085 | | ADD: 7113 EAGLE TERRACE | | CONT: DANIEL ELECTRIC | | TEL: (561)718-5324 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1SST REVIEW | | ACTION: DENIED | | 1) THE ENGINEERING FOR THE MOMENT OF | | OVERTURNING IS A COPY NOT THE ORIGINAL. | | PLANS, SPECIFICATIONS,REPORTS OR OTHER | | DOCUMENTS PREPARED BY THE DESIGN | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | RECORD SHALL HAVE THE SIGNATURE AND | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | TO THE DOCUMENT. | | FL STATE STAT: 61G15-23.002 ENGINEERS | | FL ATATE STAT: 61G16.003 ARCHITECTS | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2005-12-16 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-12-16 |
Time |
06:51 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2005-12-16 |
Time |
06:04 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2005-11-07 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-11-07 |
Time |
18:48 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-11-07 |
Time |
18:07 |
Sent To |
M |
|
Notes |
2005-11-07 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIW. | | | | 1} PLEASE INDICATE THE PRIME MOVER (FUEL | | TYPE). THE | | | | 2} PLEASE SEE ARTICLE 445.13, 4/0 IS TOO | | SMALL FOR 75K PLUS 115%. | | | | 3} THE GEC MUST BE LOCATED AT THTE METER | | OR THE FIRST MEANS OF DICONNECTT THE | | RISER HAS IT SHOWN AT THE ATS WHICH | | WOULD BE INCORRECT. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-09-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-09-09 |
Time |
19:28 |
Rev Time |
0.30 |
Received By |
dpalmer |
Date |
2005-09-09 |
Time |
19:28 |
Sent To |
M |
|
Notes |
2005-09-09 00:00:00 | *** UNSAT **** | | | | 1)NOTE: PLEASE SEE MAIN DISCONNECT IS | | REQUIRED TO MANUAL AND LOCATED ON THE | | OUTSIDE OF SERVICE EQUIPMENT. | | 230.76,230.79 | | PLEASE SEE 230.72 FOR GROUPING OF MAINS. | | PLEASE CLARIFY IF EXSITING MCB PANEL IS | | LOCATED IMMEDIATELY AJACENT/CLOSE | | PROXIMITY TO EXISTING PANELS. | | PLEASE SEE 225.31 FOR DISCONNECTING | | MEANS REQUIRED, GROUPED PER 225.34 AND | | RATED FOR SERVICE EQUIPMENT PER 225.36 | | PLEASE SEE NO SPECS/MANUFACTURE CUT | | SHEETS WERE SUBMITTED FOR ATS. | | | | 2)NOTE: PLEASE SEE RISER INDICATES AN | | "EQUIPMENT GROUNDING" CONDUCTOR FROM | | METER TO MAIN. 250.6, 250.24 | | PLEASE SEE AN EQUIPMENT GRND IS ONLY | | INSTALLED AFTER THE FIRST MEANS OF | | DISCONNECT. | | | | 3)NOTE: PLEASE SEE SITE/ EQUIPMENT PLANS | | DOES NOT INDICATE LOCATION OF ATS, | | EXISTING MAINS, OR EXISITNG PANELS. | | ARE EXISTING PANELS MCB? | | | | | | 4)NOTE: PLEASE SEELOAD CALCULATIONS | | SUBMITTED. PLEASE SEE 220.31B, NO | | DERATING MAY BE TAKEN FOR AHU/HEAT. | | PLEASE SEE IS IT PERMITTED TO "LOAD | | SHED" HEAT LOADS FROM A/C SYSTEMS | | THROUGH LV CONTACTORS FROM GEN OR ATS. | | 220.31,702.5, 90.4,700.5 | | | | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | RATED FOR THE AVAILABLE FAULT CURRENT. | | PER 110.9/215.5 | | | | 6)NOTE: PLEASE VERFIY 3 OVENS SHOWN ON | | SERVICE PANELS?? THIS IS OK, JUST A | | NOTE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2005-11-15 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-11-15 |
Time |
16:45 |
Rev Time |
0.33 |
Received By |
jleech |
Date |
2005-11-15 |
Time |
16:45 |
Sent To |
B |
|
Notes |
2005-11-15 00:00:00 | GAS PERMIT REQUIRED. PLANS REQUIRED WITH | | APPLICATION. FINAL GAS INSPECTION | | REQUIRED BEFORE FINAL GEN INSPECTION. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-12-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-12-12 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-12-12 |
Time |
14:52 |
Sent To |
E |
|
Notes |
2005-12-12 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-10-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-10-17 |
Time |
09:01 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-10-17 |
Time |
09:01 |
Sent To |
E |
|
Notes |
2005-10-17 00:00:00 | TO "E" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-09-08 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-09-08 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-09-08 |
Time |
15:48 |
Sent To |
E |
|
Notes |
2005-09-08 00:00:00 | TO "GEN-RES" BOX "E" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2005-09-01 |
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-09-01 |
Time |
14:45 |
Sent To |
|
|
Notes |
2005-09-01 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2005-11-09 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2005-11-09 |
Time |
11:42 |
Rev Time |
0.05 |
Received By |
tgordon |
Date |
2005-11-09 |
Time |
11:42 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2005-09-15 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2005-09-15 |
Time |
16:40 |
Rev Time |
0.15 |
Received By |
tgordon |
Date |
2005-09-15 |
Time |
16:40 |
Sent To |
P |
|
Notes |
2005-09-15 00:00:00 | *** PROVISO *** | | 1) PLANS MUST SHOW ANY BUILDING OPENINGS | | (WINDOWS, DOORS, ROOF & EAVE VENTS). | | 2) GENERATOR EXHAUST MUST BE TEN FEET | | AWAY FROM ANY BUILDING OPENINGS | | (WINDOWS, DOORS, ROOF & EAVE VENTS), AND | | TEN FEET AWAY FROM ADJACENT BUILDING | | OPENINGS. 2001 FBC/M 804.3.3 . | | 3) NATURAL GAS PIPING REQUIRES A GAS | | PERMIT APPLICATION BY A LICENSE PLUMBING | | CONTRACTOR. | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | TOM GORDON 805-6729 OR PATTY KRAUSS | | 805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2005-09-17 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-09-17 |
Time |
06:27 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2005-09-17 |
Time |
06:27 |
Sent To |
B |
|
Notes |
2005-09-17 00:00:00 | GAS PERMIT REQUIRED BY LICENSED PLUMBING | | CONTRACTOR. PERMIT AND WORK TO BE DONE | | BEFORE FINAL GENERATOR INSPECTION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2005-09-07 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-09-07 |
Time |
19:36 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-09-07 |
Time |
19:36 |
Sent To |
I |
|
Notes |
2005-09-07 00:00:00 | GENERATOR CAN ONLY ENCROACH 4FT INTO | | SETBACK. |
|
|