Plan Review Details - Permit 05082085
Plan Review Stops For Permit 05082085
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-11-17 Cont ID  
Sent By alange Date 2005-11-17 Time 10:38 Rev Time 0.33
Received By alange Date 2005-11-17 Time 10:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-19 Cont ID  
Sent By jwitmer Date 2005-09-19 Time 07:01 Rev Time 0.33
Received By jwitmer Date 2005-09-19 Time 07:00 Sent To PC
Notes
2005-09-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05082085
 ADD: 7113 EAGLE TERRACE
 CONT: DANIEL ELECTRIC
 TEL: (561)718-5324
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1SST REVIEW
 ACTION: DENIED
 1) THE ENGINEERING FOR THE MOMENT OF
 OVERTURNING IS A COPY NOT THE ORIGINAL.
 PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-16 Cont ID  
Sent By btrobaug Date 2005-12-16 Time 06:51 Rev Time 1.00
Received By btrobaug Date 2005-12-16 Time 06:04 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-11-07 Cont ID  
Sent By btrobaug Date 2005-11-07 Time 18:48 Rev Time 0.50
Received By btrobaug Date 2005-11-07 Time 18:07 Sent To M
Notes
2005-11-07 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIW.
  
 1} PLEASE INDICATE THE PRIME MOVER (FUEL
 TYPE). THE
  
 2} PLEASE SEE ARTICLE 445.13, 4/0 IS TOO
 SMALL FOR 75K PLUS 115%.
  
 3} THE GEC MUST BE LOCATED AT THTE METER
 OR THE FIRST MEANS OF DICONNECTT THE
 RISER HAS IT SHOWN AT THE ATS WHICH
 WOULD BE INCORRECT.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-09 Cont ID  
Sent By dpalmer Date 2005-09-09 Time 19:28 Rev Time 0.30
Received By dpalmer Date 2005-09-09 Time 19:28 Sent To M
Notes
2005-09-09 00:00:00*** UNSAT ****
  
 1)NOTE: PLEASE SEE MAIN DISCONNECT IS
 REQUIRED TO MANUAL AND LOCATED ON THE
 OUTSIDE OF SERVICE EQUIPMENT.
 230.76,230.79
 PLEASE SEE 230.72 FOR GROUPING OF MAINS.
 PLEASE CLARIFY IF EXSITING MCB PANEL IS
 LOCATED IMMEDIATELY AJACENT/CLOSE
 PROXIMITY TO EXISTING PANELS.
 PLEASE SEE 225.31 FOR DISCONNECTING
 MEANS REQUIRED, GROUPED PER 225.34 AND
 RATED FOR SERVICE EQUIPMENT PER 225.36
 PLEASE SEE NO SPECS/MANUFACTURE CUT
 SHEETS WERE SUBMITTED FOR ATS.
  
 2)NOTE: PLEASE SEE RISER INDICATES AN
 "EQUIPMENT GROUNDING" CONDUCTOR FROM
 METER TO MAIN. 250.6, 250.24
 PLEASE SEE AN EQUIPMENT GRND IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 3)NOTE: PLEASE SEE SITE/ EQUIPMENT PLANS
 DOES NOT INDICATE LOCATION OF ATS,
 EXISTING MAINS, OR EXISITNG PANELS.
 ARE EXISTING PANELS MCB?
  
  
 4)NOTE: PLEASE SEELOAD CALCULATIONS
 SUBMITTED. PLEASE SEE 220.31B, NO
 DERATING MAY BE TAKEN FOR AHU/HEAT.
 PLEASE SEE IS IT PERMITTED TO "LOAD
 SHED" HEAT LOADS FROM A/C SYSTEMS
 THROUGH LV CONTACTORS FROM GEN OR ATS.
 220.31,702.5, 90.4,700.5
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 6)NOTE: PLEASE VERFIY 3 OVENS SHOWN ON
 SERVICE PANELS?? THIS IS OK, JUST A
 NOTE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2005-11-15 Cont ID  
Sent By jleech Date 2005-11-15 Time 16:45 Rev Time 0.33
Received By jleech Date 2005-11-15 Time 16:45 Sent To B
Notes
2005-11-15 00:00:00GAS PERMIT REQUIRED. PLANS REQUIRED WITH
 APPLICATION. FINAL GAS INSPECTION
 REQUIRED BEFORE FINAL GEN INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-12 Cont ID  
Sent By adarroug Date 2005-12-12 Time 14:52 Rev Time 0.00
Received By adarroug Date 2005-12-12 Time 14:52 Sent To E
Notes
2005-12-12 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-17 Cont ID  
Sent By adarroug Date 2005-10-17 Time 09:01 Rev Time 0.00
Received By adarroug Date 2005-10-17 Time 09:01 Sent To E
Notes
2005-10-17 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 15:48 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 15:48 Sent To E
Notes
2005-09-08 00:00:00TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-09-01 Time   Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 14:45 Sent To  
Notes
2005-09-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-11-09 Cont ID  
Sent By tgordon Date 2005-11-09 Time 11:42 Rev Time 0.05
Received By tgordon Date 2005-11-09 Time 11:42 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-15 Cont ID  
Sent By tgordon Date 2005-09-15 Time 16:40 Rev Time 0.15
Received By tgordon Date 2005-09-15 Time 16:40 Sent To P
Notes
2005-09-15 00:00:00*** PROVISO ***
 1) PLANS MUST SHOW ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS).
 2) GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJACENT BUILDING
 OPENINGS. 2001 FBC/M 804.3.3 .
 3) NATURAL GAS PIPING REQUIRES A GAS
 PERMIT APPLICATION BY A LICENSE PLUMBING
 CONTRACTOR.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-09-17 Cont ID  
Sent By jleech Date 2005-09-17 Time 06:27 Rev Time 0.25
Received By jleech Date 2005-09-17 Time 06:27 Sent To B
Notes
2005-09-17 00:00:00GAS PERMIT REQUIRED BY LICENSED PLUMBING
 CONTRACTOR. PERMIT AND WORK TO BE DONE
 BEFORE FINAL GENERATOR INSPECTION.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-07 Cont ID  
Sent By mmclean Date 2005-09-07 Time 19:36 Rev Time 0.00
Received By mmclean Date 2005-09-07 Time 19:36 Sent To I
Notes
2005-09-07 00:00:00GENERATOR CAN ONLY ENCROACH 4FT INTO
 SETBACK.