Plan Review Details - Permit 05081909
Plan Review Stops For Permit 05081909
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-09-08 Cont ID  
Sent By alange Date 2005-09-08 Time 12:37 Rev Time 0.50
Received By alange Date 2005-09-08 Time 12:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-29 Cont ID  
Sent By btrobaug Date 2005-09-29 Time 13:26 Rev Time 0.50
Received By btrobaug Date 2005-09-29 Time 13:15 Sent To B
Notes
2005-09-29 00:00:00TO LUIS, EC WORKERS COMP EXPIRED./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-09-02 Cont ID  
Sent By jleahy Date 2005-09-02 Time 11:00 Rev Time 0.30
Received By jleahy Date 2005-09-02 Time 11:00 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-20 Cont ID  
Sent By adarroug Date 2005-09-20 Time 14:15 Rev Time 0.00
Received By adarroug Date 2005-09-20 Time 14:15 Sent To P
Notes
2005-09-20 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 10:32 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 10:32 Sent To E
Notes
2005-09-01 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-20 Cont ID  
Sent By adarroug Date 2005-09-08 Time 14:12 Rev Time 0.00
Received By adarroug Date 2005-08-30 Time 14:51 Sent To  
Notes
2005-08-30 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-29 Cont ID  
Sent By jleech Date 2005-09-29 Time 11:00 Rev Time 0.50
Received By jleech Date 2005-09-29 Time 11:00 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-09-08 Cont ID  
Sent By jleech Date 2005-09-08 Time 12:57 Rev Time 0.75
Received By jleech Date 2005-09-08 Time 12:57 Sent To  
Notes
2005-09-08 00:00:00DENIED;
 1. FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 2. FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 3.) FBC-2001424.2.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPER- ATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.
 4. FBC-2001 424.2.8.1 VALVES SHALL BE
 MADE OF MATERIALS THAT ARE APPROVED IN
 THE FLA BLDG CODE, PLUMBING.THEY WILL
 BE READILY ACCESSIBLE FOR MAINT. AND
 REMOVAL.SEC 424.2.8.2 FULL WAY VALVES
 SHALL BE INSTALLED TO INSURE PROPER
 FUNCTION OF THE FILTRATION AND PIPING
 SYSTEMS.SEC 424.2.8.3 WHERE CHECK
 VALVES ARE INSTALLED THEY SHALL BE OF
 THE SWING OR VERTICAL CHECK PATTERNS.
 SEC 424.2.8.4 COMBINATION VALVES SHALL
 REQUIRE APPROVAL OF THE ADMINISTRATIVE
 AUTHORITY PRIOR TO THEIR INSTALLATION.
 5. FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 6)424.2.9 WATER SUPPLY, LOCAL ORD
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE. (ADD TO NOTES)
 7)424.2.13.2 JOINTS AND CONNECTIONS, FBC
 PLUMBING SEC 605.21, PERPLE PRIMER
 REQUIRED ON PVC PIPING. (ADD TO NOTES)
 8)424.2.14.2 WATER RETENTION, PROVIDE A
 POSITIVE MEANS OF RETAINING WATER IN
 HEATER WHEN PUMP IS SHUT OFF. ( ADD TO
 NOTES)
 PLUMBING PLAN REVEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-31 Cont ID  
Sent By mmclean Date 2005-08-31 Time 15:37 Rev Time 0.00
Received By mmclean Date 2005-08-31 Time 15:36 Sent To I
Notes
***NONE***