Plan Review Stops For Permit 05081889 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-09-01 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-09-01 |
Time |
13:36 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-09-01 |
Time |
13:36 |
Sent To |
M |
|
Notes |
2005-09-01 00:00:00 | TO "M" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2005-09-02 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2005-09-02 |
Time |
08:11 |
Rev Time |
0.15 |
Received By |
tgordon |
Date |
2005-09-02 |
Time |
08:11 |
Sent To |
|
|
Notes |
2005-09-02 00:00:00 | *** PROVISO *** | | 1) IF SUPPLY AIR IS GREATER THAN 2000 | | CFM A SMOKE DETECTOR IS REQUIRED | | 2001 FBC/M 606.2.1. | | 2) PROVIDE FOR AUX. DRAIN PAN UNDER | | A.H.U. WITH DRAIN PROTECTION 2001 | | FBC/M 307.2.3. | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | TOM GORDON 805-6729 OR PATTY KRAUSS | | 805-6719. |
|
|
|