Plan Review Details - Permit 05081889
Plan Review Stops For Permit 05081889
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 13:36 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 13:36 Sent To M
Notes
2005-09-01 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-09-02 Cont ID  
Sent By tgordon Date 2005-09-02 Time 08:11 Rev Time 0.15
Received By tgordon Date 2005-09-02 Time 08:11 Sent To  
Notes
2005-09-02 00:00:00*** PROVISO ***
 1) IF SUPPLY AIR IS GREATER THAN 2000
 CFM A SMOKE DETECTOR IS REQUIRED
 2001 FBC/M 606.2.1.
 2) PROVIDE FOR AUX. DRAIN PAN UNDER
 A.H.U. WITH DRAIN PROTECTION 2001
 FBC/M 307.2.3.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.