Plan Review Details - Permit 05081648
Plan Review Stops For Permit 05081648
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-11-21 Cont ID  
Sent By jgomez Date 2005-11-21 Time 12:20 Rev Time 0.75
Received By jgomez Date 2005-11-21 Time 12:20 Sent To PC
Notes
2005-11-21 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS AND ATRIUM FIRE RATED
 DOOR AS SHOWN ON PLANS UNDER A SEPARATE
 PERMIT AS AGREED WITH ANDY FROM KENCO
 COMMUNITIES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-21 Cont ID  
Sent By jgomez Date 2005-11-15 Time 17:05 Rev Time 1.00
Received By jgomez Date 2005-11-15 Time 17:05 Sent To PC
Notes
2005-11-15 00:00:00BUILDING REVIEW
 1- CALLED ANDY FROM THE RIF GROUP. NEED
 TO USE FBC 2001 ENERGY CALCS FORMS, NOT
 FBC 2004 FORMS. (CALLED ANDY TO HIS CELL
 PHONE AROUND 5:10PM ON 11-15-05).
 WAITING FOR CONTRACTORS RESPONSE TO
 SUBMIT CORRECT ENERGY CALCULATIONS TO
 PROCESS PERMIT. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-16 Cont ID  
Sent By jgomez Date 2005-09-16 Time 12:28 Rev Time 2.00
Received By jgomez Date 2005-09-16 Time 12:28 Sent To PC
Notes
2005-09-16 00:00:00BUILDING REVIEW CHECKLIST:
 1- BRING PLANS BACK TO PALM BEACH COUNTY
 TO CORRECT PR NUMBERS. I TALKED TO MRS.
 GIL FROM THE COUNTY SHE SAYS THAT THIS
 IMPACT FEES RECEIPT (PR#: 05042803)
 DOESN'T MATCH THIS PROPERTY. REVISE AS
 REQUIRED. BRING BACK CORRECT PAID
 RECEIPT AND PLANS STAMPED WITH
 CORRESPONDING PR NUMBER.
  
 2- NEED RECORDED N.O.C.
  
 3- ENERGY CALCS ARE GETTING THE CEILING
 FANS CREDIT. REVISE ELECTRICAL PLAN TO
 SPECIFY CEILING FAN SIZE IN EACH ROOM
 INCLUDING CEILINGS FANS REQUIRED IN THE
 GREAT ROOM. SEE TABLE 6-6 CHAPTER 13 FBC
  
 4- REVISE ROOF FRAMING PLAN AT ENTRY
 PORCH ROOF. CONCRETE BEAM DOESN'T EXTEND
 TO THE FOYER AREA. REVISE FRAMING AROUND
 KNEEWALL ON THE LEFT HAND SIDE. THERE IS
 NOT CONCRETE BEAM. REVISE ROOF FRAMING
 PLAN AS REQ'D AND SPECIFY CORRESPONDING
 CONNECTORS. SEC. 104.2.1.2 CITY
 AMENDEMNTS TO FBC 2001.
  
 5- MULLION SIZE SPECIFIED FOR FIXED
 WINDOWS AT GREAT ROOM AREA DOESN'T
 RESIST THE DESIGN PRESSURES. REVISE AS
 REQ'D. SEC. 104.2.1.2 CITY AMENDMENTS TO
 FBC.
  
 6- TRUSS ANCHOR SCHEDULE: REVISE NUMBER
 OF NAILS FOR HUS26. SEE 2005 CATALOGUE.
  
 7- PROVIDE PRODUCT APPROVAL FOR:
 A) "INSWING" 1HR FIRE RATED DOOR AT
 ATRIUM AS SHOWN ON PLANS.
  
 B) MULLION SIZE SPECIFIED FOR FIXED
 WINDOWS AT GREAT ROOM AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-02-03 Cont ID  
Sent By dpalmer Date 2006-02-03 Time 18:18 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 18:18 Sent To PC
Notes
2006-02-03 00:00:00REDLINED 8' MIN GRND ROD 250.52A5

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-09-02 Cont ID  
Sent By dpalmer Date 2005-09-02 Time 15:49 Rev Time 0.33
Received By dpalmer Date 2005-09-02 Time 15:49 Sent To M
Notes
2005-09-02 00:00:00210.52C1?

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 13:08 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 13:08 Sent To E
Notes
2006-01-27 00:00:00TO "DPALMER' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-22 Cont ID  
Sent By jgomez Date 2005-11-15 Time 16:23 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 11:49 Sent To B
Notes
2005-10-22 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-10-22 Time 11:48 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 10:53 Sent To E
Notes
2005-09-02 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-16 Cont ID  
Sent By jgomez Date 2005-09-16 Time 13:42 Rev Time 0.00
Received By jgomez Date 2005-08-29 Time 11:33 Sent To  
Notes
2005-08-29 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-09-07 Cont ID  
Sent By prafter Date 2005-09-07 Time 08:51 Rev Time 1.00
Received By prafter Date 2005-09-07 Time 08:51 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-09-08 Cont ID  
Sent By jleech Date 2005-09-08 Time 10:25 Rev Time 0.00
Received By jgomez Date 2005-11-15 Time 17:04 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-11-15 Cont ID  
Sent By mmclean Date 2005-09-01 Time 17:34 Rev Time 0.00
Received By jgomez Date 2005-09-01 Time 17:34 Sent To I
Notes
2005-11-15 00:00:00APPROVED BY MICHELLE ON 9-1-05. SEE
 SURVEY