Plan Review Details - Permit 05081635
Plan Review Stops For Permit 05081635
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-31 Cont ID  
Sent By jgomez Date 2005-08-31 Time 12:31 Rev Time 0.33
Received By jgomez Date 2005-08-31 Time 12:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-24 Cont ID  
Sent By jgomez Date 2005-08-24 Time 12:59 Rev Time 0.33
Received By jgomez Date 2005-08-24 Time 12:59 Sent To PC
Notes
2005-08-24 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- FLAT ROOF SYSTEM: CLEARLY IDENTIFY
 WHICHFLAT ROOF SYSTEM IS GOING TO BE
 INSTALLED. THERE ARE SEVERAL SYSTEMS
 THAT ARE APPROVED IN THE SAME PRODUCT
 APPROVAL. NEED TO SUBMIT ONLY THE SYSTEM
 THAT WILL BE USED TO VERIFY FOR THE
 DESIGN PRESSURES COMPLIANCE.
 NOTE: SOME SYSTEMS ARE LIMITATED BY
 LIMITATION #9 WHICH DOESN'T ALLOW
 ADDITIONAL ENHANCING OF FASTENERS TO
 INCREASE THE UPLIFT CAPACITY. WHILE
 OTHERS ARE LIMITED BY LIMITATION #7,
 WHICH ALLOWS FASTENER ENHANCING TO
 INCREASE THE UPLIFT CAPACITY. SEE
 LIMITATIONS PAGE ON THE BACK OF PRODUCT
 APPROVAL.
  
 2- NEED TO RE-RECORD THE NOTICE OF
 COMMENCEMENT. IT EXPIRES AFTER 90 DAYS
 OF RECORDING IF WORK IS NOT STARTED.
  
 3- SPECIFY ON PERMIT APPLICATION HOW
 MUCH SQUARE FOOTAGE IS FOR SHINGLES AND
 HOW MUCH SQUARE FOOTAGE IS FLAT ROOF
 SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.