Plan Review Details - Permit 05081425
Plan Review Stops For Permit 05081425
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-08-28 Cont ID  
Sent By jleahy Date 2005-08-28 Time 21:05 Rev Time 0.30
Received By jleahy Date 2005-08-28 Time 21:04 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-23 Cont ID  
Sent By adarroug Date 2005-08-23 Time 19:16 Rev Time 0.00
Received By adarroug Date 2005-08-23 Time 19:16 Sent To E
Notes
2005-08-23 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-08-31 Cont ID  
Sent By tgordon Date 2005-08-31 Time 15:10 Rev Time 0.15
Received By tgordon Date 2005-08-31 Time 15:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-30 Cont ID  
Sent By tgordon Date 2005-08-30 Time 14:24 Rev Time 0.20
Received By tgordon Date 2005-08-30 Time 14:24 Sent To  
Notes
2005-08-30 00:00:00*** DENIED ***
 ENGINEERS SHEET 'CURB SUPPORT
 REINFORCING' NEEDS TO COMPLY TO 2001 FBC
  
 SEC.1606.1.7
 EXAMPLE: BASIC WIND SPEED 140 MPH.
 WIND INPORTANCE FACTOR '1' .
 WIND EXPOSURE 'B' ....
 ALSO WHAT THE CURB IS BEING SCREWED
 INTO.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.