Plan Review Details - Permit 05081350
Plan Review Stops For Permit 05081350
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-05-16 Cont ID  
Sent By lursu Date 2006-05-16 Time 15:15 Rev Time 0.00
Received By lursu Date 2006-05-16 Time 15:15 Sent To  
Notes
2006-05-16 00:00:00PERMIT ATTACHED TO EXT#0009 FOR BLDG 6 :
 4502 MERCEDES WAY.
2006-05-14 00:00:00NEEDS!!!

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-08-23 Cont ID  
Sent By jhiggins Date 2005-08-23 Time 10:56 Rev Time 0.00
Received By jhiggins Date 2005-08-23 Time 10:56 Sent To  
Notes
2005-08-23 00:00:00SITE ADDRESS OF 3700 N MILITARY TRL
 APPLIES UNTIL INTERIOR STREETS ARE
 FORMALLY ASSIGNED.
  
 AS PROJECT IS BEING CONSTRUCTED ON TWO
 SEPARATE PARCELS, UNITY OF TITLE MAY BE
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-09 Cont ID  
Sent By rmcdouga Date 2006-06-09 Time 16:09 Rev Time 0.00
Received By rmcdouga Date 2006-06-09 Time 16:09 Sent To  
Notes
2006-06-09 00:00:00DENIED
  
 1) THE PLANS MUST BE STAMPED BY PALM
 BEACH COUNTY FOR IMPACT FEES. THE PLAN
 REVIEW NUMBER ON THE PLANS MUST
 CORRESPOND WITH THE P.R. NUMBER ON THE
 IMPACT FEE RECEIPT.
  
 2) SUBMIT FIRE SPRINKLER PLANS FOR THE
 REQUIRED NFPA 13 SYSTEM. THIS IS
 REQUIRED BY FBC 104.3.1.1 OF THE CITY OF
 W.P.B. AMENDMENTS TO THE 2001 FBC.
  
 3) THE GARAGE FLOOR/CEILING ASSEMBLY IN
 DETAIL 17 ON A 10.0.0 DOES NOT
 CORRESPOND TO THE FC 5517 FIRE RATED
 ASSEMBLY LISTED IN THE GYPSUM
 ASSOCIATION MANUAL. PLEASE CORRECT.
  
 4) NUMBER 20 ON THE DOOR SCHEDULE
 SPECIFIES A VENTED GARAGE DOOR. THE
 PRODUCT APPROVAL FOR THE GARAGE DOOR
 DOES NOT INDICATE VENTS IN THE DOOR.
  
 5) REVISE DETAIL 11 ON A 10.0.0 TO
 SPECIFY THE 2001 FBC AND NOT THE CURRENT
 EDITION OF THE STANDARD BUILDING CODE.
  
 6) THE DRAWINGS ATTACHED TO THE STATE
 PRODUCT APPROVAL FOR THE STEEL DOOR FROM
 MASONITE INTERNATIONAL ARE FOR A 6'-8"
 DOOR AND THE PLAN SPECIFIES AN 8'-0"
 DOOR. SEE FL 4940.3 AND DRAWING
 DWG-MA-FLO 133-05.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 TRUSS CONNECTORS. (SIMPSON-HETAL 12 &
 16, USP-USC) THE FL COVERSHEET SUBMITTED
 FOR THE USP HANGERS AND COLUMN BASES &
 CAPS HAS A WINDOW MULLION NOA ATTACHED
 TO IT.
  
 8) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS IS INCOMPLETE. THERE ARE
 SHEETS WITH ANOTHER NOA NUMBER ATTACHED
 AT THE REAR OF THE SH WINDOW NOA.
  
 9) THE DECORATIVE BAHAMA SHUTTERS WILL
 REQUIRE A SEPARATE PERMIT.
  
 10) FS 713.13 IF THE IMPROVEMENT
 DESCRIBED IN THE NOTICE OF COMMENCEMENT
 IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS VOID AND OF NO FURTHER EFFECT.
 (THE NOC WILL NEED TO BE RE-RECORDED
 BEFORE THE PERMIT IS ISSUED.)
  
 11) FBC 13-600.3ABC.1.2 REQUIRES THE
 ENERGY CALCULATION FORMS TO BE SIGNED
 AND SEALED BY AN ARCHITECT OR AN
 ENGINEER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-28 Cont ID  
Sent By rmcdouga Date 2006-02-28 Time 08:04 Rev Time 0.00
Received By rmcdouga Date 2006-02-27 Time 15:53 Sent To  
Notes
2006-02-28 00:00:00DENIED
  
 1) THE 2001 FBC DOES NOT ALLOW HEIGHT OR
 AREA INCREASES FOR NFPA 13R SPRINKLER
 SYSTEMS. SEE FBC TABLE 500 FOOTNOTE (D).
 FBC 903.2 REQUIRES A NFPA 13 SPRINKLER
 SYSTEM.
  
 2) THE DOOR TO THE EXIT STAIRS AT THE
 SECOND FLOOR MUST PROVIDE A 32" CLEAR
 OPENING FROM THE FACE OF THE DOOR TO THE
 STOP WITH THE DOOR OPEN 90 DEGREES. SEE
 FBC 1003.2.1 AND 1003.2.2. THE 2-8 DOOR
 SPECIFIED DOES NOT COMPLY.
  
 3) SHOW COMPLIANCE WITH FBC MECH. TABLE
 403.3 FOR THE REQUIRED OUTDOOR AIR
 VENTILATION AT GARAGES OF 100 CFM PER
 CAR.
  
 4) SEE MECHANICAL COMMENTS FOR DUCT
 PENETRATIONS THROUGH FIRE RATED
 ASSEMBLIES.
  
 5) THE TRUSS LAYOUT AND DRAWINGS ARE ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD FOR THE
 STRUCTURE. IF ACCEPTABLE, THE STRUCTURAL
 ENGINEER SHOULD STAMP AND SIGN THE TRUSS
 LAYOUT AS SUCH.
  
 6) THE TRUSS DRAWING INDEX SHEET IS
 INCOMPLETE. SEE FAC 61G15-31.003. THE
 NAME OF THE AUTHORITY HAVING
 JURISDICTION, THE LOADS AND NAME & DATE
 OF THE APPLICABLE BUILDING CODE IS
 REQUIRED.
  
 7) THE UPLIFT PRESSURES IN THE TRUSS
 ANCHOR SCHEDULE ARE INCORRECT FOR THE
 SIMPSONHETAL 12 AND THE USP USC. THE
 CORRECT UPLIFTS ARE 1265# FOR THE HETAL
 12 AND 11,150 FOR THE USC WITH 4 BOLTS
 PER 2005 CATALOGS. THESE ARE THE VALUES
 THAT DO NOT INCLUDE A STRESS INCREASE
 FOR THE STEEL CALULATIONS.
  
 8) THE STATE PRODUCT APPROVALS SUBMITTED
 FOR THE TRUSS CONNECTORS DO NOT LIST ALL
 THE CONNECTORS THAT ARE LISTED IN THE
 TRUSS ANCHORS SCHEDULE.
  
 9) SUBMIT STATE PRODUCT APPROVALS FOR
 THE 3/4 HOUR FIRE RATED 6 PANEL DOOR AT
 THE ENTRY. DOOR #1 IN THE SCHEDULE.
  
 10) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS HAS THE INSTALLATION
 DRAWINGS FOR THE FIXED GLASS WINDOWS
 ATTACHED. PLEASE REMOVE AND ATTACH THE
 CORRECT DRAWINGS.
  
 11) THE DECORATIVE SHUTTERS ARE REQUIRED
 TO BE APPLIED FOR UNDER A SEPARATE
 PERMIT.
  
 12)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-29 Cont ID  
Sent By rmcdouga Date 2005-11-30 Time 13:26 Rev Time 0.00
Received By rmcdouga Date 2005-11-29 Time 13:25 Sent To  
Notes
2005-11-29 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE COUNTY IMPACT FEE STAMP DOES NOT
 HAVE THE PLAN REVIEW NUMBER ON THE
 PLANS. PLANS MUST BE RETURNED TO THE
 COUNTY TO HAVE THIS NUMBER NOTED ON THE
 PLANS.
  
 3) FL. BLD CODE 1606.1.7 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) IN ORDER TO DETERMINE THE PERCENTAGE
 OF WALL AREA ALLOWED AS OPENINGS BY FBC
 TABLE 600, SUBMIT A SURVEY INDICATING
 THE LOCATIONS OF THE ASSUMED PROPERTY
 LINES BETWEEN THE BUILDINGS.
  
 5) PROVIDE AN AREA CALCULATION TABLE
 LISTING THE FLOOR AREA BREAKDOWNS BY
 FLOOR FOR EACH UNIT AND THE TOTALS FOR
 ALL SIX UNITS.
  
 6) THE FBC DOES NOT ALLOW HEIGHT AND
 AREA INCREASES FOR NFPA 13R SPRINKLER
 SYSTEMS. SEE FBC TABLE 500 FOOTNOTE (D).
  
 7) THE WALL AND FLOOR/CEILING ASSEMBLIES
 BETWEEN THE GARAGE AND LIVING SPACE ARE
 REQUIRED TO HAVE A ONE HOUR FIRE RATING.
  
 8) THE GUTTER DOWNSPOUTS ARE REQUIRED TO
 DISCHARGE ONE FOOT AWAY FROM THE
 STRUCTURE PER FBC 1503.4.4.
  
 9) THE DOOR TO THE EXIT STAIRS AT THE
 SECOND FLOOR MUST PROVIDE A 32" CLEAR
 OPENING FROM THE FACE OF THE DOOR TO THE
 STOP WITH THE DOOR OPEN 90 DEGREES. SEE
 FBC 1003.2.1 AND 1003.2.2
  
 10) SHOW COMPLIANCE WITH FBC MECH. TABLE
 403.3 FOR REQUIRED OUTDOOR AIR
 VENTILATION AT GARAGES OF 100 CFM PER
 CAR.
  
 11) WALL SECTION #4 ON A-7.01 IS
 MISLABELED FOR GENERAL NOTES 4 AN 10.
  
 12) SPECIFY THE EXTERIOR FINISH AT THE
 UNDERSIDE OF THE BAY WINDOW SHOWN ON
 A-7.1.1. SPECIFY THE EXTERIOR SHEATHING,
 LATH AND STUCCO. NOTE: SEE ASTM C 926
 FOR REQUIRED STUCCO THICKNESS.
  
 13) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE. THIS IS THE VERTICAL DISTANCE
 FROM FINISHED GRADE TO THE A POINT AT
 THE AVERAGE HEIGHT OF THE ROOF.
  
 14) PROVIDE A DETAIL OF THE BALCONY
 GUARDRAILS. SPECIFY ATTACHMENTS, SPACING
 OF INTERMEDIATE RAILS, ETC.
  
 15) SPECIFY THE METHOD OF ATTACHMENT FOR
 THE ROOF TILES. THE PRODUCT APPROVAL
 THAT WAS SUBMITTED HAS AN ATTACHMENT
 RESISTANCE MOMENT OF 24.5 FT-LBF FOR
 MORTAR SET TILE. FOR 140 MPH EXPOSURE B
 WITH 40FT MRH, THE REQUIRED MOMENT IS
 28.3 FT-LBF. PLEASE REVISE ROOF TILE
 DETAILS TO COMPLY WITH CODE.
  
 16) UL ASSEMBLY U 906 HAS A 2 HOUR FIRE
 RATING NOT ONE HOUR AS SPECIFIED ON THE
 PLANS FOR WALL TYPES IN DETAILS 2 AND 6
 ON A-10.00.
  
 17) THE DRYWALL SPECIFIED IN THE RATED
 ASSEMBLY IN DETAIL 5 ON A 10.2.0 SHOULD
 BE FIRE-SHIELD C NOT "D". PLEASE
 CORRECT.
  
 18) PROVIDE INFORMATION FOR MECHINICAL
 DUCT PENETRATIONS THROUGH THE FIRE RATED
 ASSEMBLIES.
  
 19) TRUSS LAYOUT AND DRAWINGS ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD FOR THE
 STRUCTURE.
  
 20) THE UPLIFT LOAD VALUES LISTED IN THE
 TRUSS ANCHOR SCHEDULE ON S-3 FOR THE
 SIMPSON HETAL 16 & 20 ARE INCORRECT.THE
 ONE THIRD STRESS INCREASE FOR STEEL
 CALCULATIONS IS NO LONGER ALLOWED. SEE
 THE 2005 SIMPSON CATALOG.
  
 21) THE HUGHES "USC" CONNECTORS ALSO
 HAVE INCORRECT UPLIFT VALUES. HUGHES WAS
 PURCHASED BY USP SEVERAL YEARS AGO AND
 IS LONGER IN BUSINESS. SEE THE 2005 USP
 CATALOG FOR VALUES. UPDATE THE TRUSS
 ANCHOR SCHEDULE.
  
 22) UNDER KEY NOTES/ LEGEND ON A-4.0 AND
 OTHER SHEETS REFERENCE IS MADE TO SHEET
 A-13 FOR THE WALL TYPES. HOWEVER, THERE
 IS NO SHEET A-13.
  
 23) THE ENERGY CALCULATIONS CONTAIN
 SEVERAL ERRORS. THESE ARE CONSIDERED
 MULTIFAMILY NOT SINLE FAMILY. THE
 ADJACENT WALL AT THE GARAGE IS WOOD
 FRAME AND THE CEILING INSULATION IS
 SPECIFIED AS R-20 ICYENE.
  
 24)PROVIDE MANUFACTURER'S SPECIFICATIONS
 FOR THE ICYENE INSULATION.
  
 25) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. IN
 ADDITION TO THE COVERSHEET THE
 INSTALLATION INSTRUCTIONS OR PRODUCT
 EVALUATION AS LISTED ON THE STATE
 WEBSITE IS ALSO REQUIRED.
  
 26) SUBMIT STATE PRODUCT APPROVALS FOR
 THE TRUSS CONNECTORS AND GARAGE DOORS.
  
 27) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS HAS THE INFO FROM THE FIXED
 GLASS WINDOWS ATTACHED TO THE NOA
 COVERSHEET.
  
 28) SUBMIT MANUFACTURER'S SPECS. FOR THE
 DOOR CLOSERS.
  
 29) THE CALCULATED VALUE OF THE
 STRUCTURE HAS BEEN INCREASED TO
 $912,590.00. ADDITIONAL PERMIT FEES OF
 $2740.49 ARE REQUIRED.
  
 30) THE FIRST FLOOR PLAN ON SHEETS
 A-4.0.1 AND A-4.3.1 SHOW THE DOOR FROM
 THE GARAGE OPENING DIRECTLY INTO A GREAT
 ROOM. FBC 411.2.8 PROHIBITS OPENINGS
 FROM A PARKING GARAGE DIRECTLY INTO A
 ROOM USED FOR SLEEPING PURPOSES. PLEASE
 INDICATE ON THE PLANS AT THE GREAT ROOM
 THAT THIS ROOM IS NOT TO BE USED FOR
 SLEEPING PURPOSES.
  
 31) FIRE SPRINKLER PLANS ARE REQUIRED TO
 BE SUBMITTED WHEN REQUIRED FOR HEIGHT OR
 AREA INCREASE ALLOWED BY FBC TABLE 500.
 SEE FBC 903.2 AND 104.3.3.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE COUNTY IMPACT FEE STAMP DOES NOT
 HAVE THE PLAN REVIEW NUMBER ON THE
 PLANS. PLANS MUST BE RETURNED TO THE
 COUNTY TO HAVE THIS NUMBER NOTED ON THE
 PLANS.
  
 3) FL. BLD CODE 1606.1.7 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) IN ORDER TO DETERMINE THE PERCENTAGE
 OF WALL AREA ALLOWED AS OPENINGS BY FBC
 TABLE 600, SUBMIT A SURVEY INDICATING
 THE LOCATIONS OF THE ASSUMED PROPERTY
 LINES BETWEEN THE BUILDINGS.
  
 5) PROVIDE AN AREA CALCULATION TABLE
 LISTING THE FLOOR AREA BREAKDOWNS BY
 FLOOR FOR EACH UNIT AND THE TOTALS FOR
 ALL SIX UNITS.
  
 6) THE FBC DOES NOT ALLOW HEIGHT AND
 AREA INCREASES FOR NFPA 13R SPRINKLER
 SYSTEMS. SEE FBC TABLE 500 FOOTNOTE (D).
  
 7) THE WALL AND FLOOR/CEILING ASSEMBLIES
 BETWEEN THE GARAGE AND LIVING SPACE ARE
 REQUIRED TO HAVE A ONE HOUR FIRE RATING.
  
 8) THE GUTTER DOWNSPOUTS ARE REQUIRED TO
 DISCHARGE ONE FOOT AWAY FROM THE
 STRUCTURE PER FBC 1503.4.4.
  
 9) THE DOOR TO THE EXIT STAIRS AT THE
 SECOND FLOOR MUST PROVIDE A 32" CLEAR
 OPENING FROM THE FACE OF THE DOOR TO THE
 STOP WITH THE DOOR OPEN 90 DEGREES. SEE
 FBC 1003.2.1 AND 1003.2.2
  
 10) SHOW COMPLIANCE WITH FBC MECH. TABLE
 403.3 FOR REQUIRED OUTDOOR AIR
 VENTILATION AT GARAGES OF 100 CFM PER
 CAR.
  
 11) WALL SECTION #4 ON A-7.01 IS
 MISLABELED FOR GENERAL NOTES 4 AN 10.
  
 12) SPECIFY THE EXTERIOR FINISH AT THE
 UNDERSIDE OF THE BAY WINDOW SHOWN ON
 A-7.1.1. SPECIFY THE EXTERIOR SHEATHING,
 LATH AND STUCCO. NOTE: SEE ASTM C 926
 FOR REQUIRED STUCCO THICKNESS.
  
 13) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE. THIS IS THE VERTICAL DISTANCE
 FROM FINISHED GRADE TO THE A POINT AT
 THE AVERAGE HEIGHT OF THE ROOF.
  
 14) PROVIDE A DETAIL OF THE BALCONY
 GUARDRAILS. SPECIFY ATTACHMENTS, SPACING
 OF INTERMEDIATE RAILS, ETC.
  
 15) SPECIFY THE METHOD OF ATTACHMENT FOR
 THE ROOF TILES. THE PRODUCT APPROVAL
 THAT WAS SUBMITTED HAS AN ATTACHMENT
 RESISTANCE MOMENT OF 24.5 FT-LBF FOR
 MORTAR SET TILE. FOR 140 MPH EXPOSURE B
 WITH 40FT MRH, THE REQUIRED MOMENT IS
 28.3 FT-LBF. PLEASE REVISE ROOF TILE
 DETAILS TO COMPLY WITH CODE.
  
 16) UL ASSEMBLY U 906 HAS A 2 HOUR FIRE
 RATING NOT ONE HOUR AS SPECIFIED ON THE
 PLANS FOR WALL TYPES IN DETAILS 2 AND 6
 ON A-10.00.
  
 17) THE DRYWALL SPECIFIED IN THE RATED
 ASSEMBLY IN DETAIL 5 ON A 10.2.0 SHOULD
 BE FIRE-SHIELD C NOT "D". PLEASE
 CORRECT.
  
 18) PROVIDE INFORMATION FOR MECHINICAL
 DUCT PENETRATIONS THROUGH THE FIRE RATED
 ASSEMBLIES.
  
 19) TRUSS LAYOUT AND DRAWINGS ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD FOR THE
 STRUCTURE.
  
 20) THE UPLIFT LOAD VALUES LISTED IN THE
 TRUSS ANCHOR SCHEDULE ON S-3 FOR THE
 SIMPSON HETAL 16 & 20 ARE INCORRECT.THE
 ONE THIRD STRESS INCREASE FOR STEEL
 CALCULATIONS IS NO LONGER ALLOWED. SEE
 THE 2005 SIMPSON CATALOG.
  
 21) THE HUGHES "USC" CONNECTORS ALSO
 HAVE INCORRECT UPLIFT VALUES. HUGHES WAS
 PURCHASED BY USP SEVERAL YEARS AGO AND
 IS LONGER IN BUSINESS. SEE THE 2005 USP
 CATALOG FOR VALUES. UPDATE THE TRUSS
 ANCHOR SCHEDULE.
  
 22) UNDER KEY NOTES/ LEGEND ON A-4.0 AND
 OTHER SHEETS REFERENCE IS MADE TO SHEET
 A-13 FOR THE WALL TYPES. HOWEVER, THERE
 IS NO SHEET A-13.
  
 23) THE ENERGY CALCULATIONS CONTAIN
 SEVERAL ERRORS. THESE ARE CONSIDERED
 MULTIFAMILY NOT SINLE FAMILY. THE
 ADJACENT WALL AT THE GARAGE IS WOOD
 FRAME AND THE CEILING INSULATION IS
 SPECIFIED AS R-20 ICYENE.
  
 24)PROVIDE MANUFACTURER'S SPECIFICATIONS
 FOR THE ICYENE INSULATION.
  
 25) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. IN
 ADDITION TO THE COVERSHEET THE
 INSTALLATION INSTRUCTIONS OR PRODUCT
 EVALUATION AS LISTED ON THE STATE
 WEBSITE IS ALSO REQUIRED.
  
 26) SUBMIT STATE PRODUCT APPROVALS FOR
 THE TRUSS CONNECTORS AND GARAGE DOORS.
  
 27) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS HAS THE INFO FROM THE FIXED
 GLASS WINDOWS ATTACHED TO THE NOA
 COVERSHEET.
  
 28) SUBMIT MANUFACTURER'S SPECS. FOR THE
 DOOR CLOSERS.
  
 29) THE CALCULATED VALUE OF THE
 STRUCTURE HAS BEEN INCREASED TO
 $912,590.00. ADDITIONAL PERMIT FEES OF
 $2740.49 ARE REQUIRED.
 DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE COUNTY IMPACT FEE STAMP DOES NOT
 HAVE THE PLAN REVIEW NUMBER ON THE
 PLANS. PLANS MUST BE RETURNED TO THE
 COUNTY TO HAVE THIS NUMBER NOTED ON THE
 PLANS.
  
 3) FL. BLD CODE 1606.1.7 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) IN ORDER TO DETERMINE THE PERCENTAGE
 OF WALL AREA ALLOWED AS OPENINGS BY FBC
 TABLE 600, SUBMIT A SURVEY INDICATING
 THE LOCATIONS OF THE ASSUMED PROPERTY
 LINES BETWEEN THE BUILDINGS.
  
 5) PROVIDE AN AREA CALCULATION TABLE
 LISTING THE FLOOR AREA BREAKDOWNS BY
 FLOOR FOR EACH UNIT AND THE TOTALS FOR
 ALL SIX UNITS.
  
 6) THE FBC DOES NOT ALLOW HEIGHT AND
 AREA INCREASES FOR NFPA 13R SPRINKLER
 SYSTEMS. SEE FBC TABLE 500 FOOTNOTE (D).
  
 7) THE WALL AND FLOOR/CEILING ASSEMBLIES
 BETWEEN THE GARAGE AND LIVING SPACE ARE
 REQUIRED TO HAVE A ONE HOUR FIRE RATING.
  
 8) THE GUTTER DOWNSPOUTS ARE REQUIRED TO
 DISCHARGE ONE FOOT AWAY FROM THE
 STRUCTURE PER FBC 1503.4.4.
  
 9) THE DOOR TO THE EXIT STAIRS AT THE
 SECOND FLOOR MUST PROVIDE A 32" CLEAR
 OPENING FROM THE FACE OF THE DOOR TO THE
 STOP WITH THE DOOR OPEN 90 DEGREES. SEE
 FBC 1003.2.1 AND 1003.2.2
  
 10) SHOW COMPLIANCE WITH FBC MECH. TABLE
 403.3 FOR REQUIRED OUTDOOR AIR
 VENTILATION AT GARAGES OF 100 CFM PER
 CAR.
  
 11) WALL SECTION #4 ON A-7.01 IS
 MISLABELED FOR GENERAL NOTES 4 AN 10.
  
 12) SPECIFY THE EXTERIOR FINISH AT THE
 UNDERSIDE OF THE BAY WINDOW SHOWN ON
 A-7.1.1. SPECIFY THE EXTERIOR SHEATHING,
 LATH AND STUCCO. NOTE: SEE ASTM C 926
 FOR REQUIRED STUCCO THICKNESS.
  
 13) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE. THIS IS THE VERTICAL DISTANCE
 FROM FINISHED GRADE TO THE A POINT AT
 THE AVERAGE HEIGHT OF THE ROOF.
  
 14) PROVIDE A DETAIL OF THE BALCONY
 GUARDRAILS. SPECIFY ATTACHMENTS, SPACING
 OF INTERMEDIATE RAILS, ETC.
  
 15) SPECIFY THE METHOD OF ATTACHMENT FOR
 THE ROOF TILES. THE PRODUCT APPROVAL
 THAT WAS SUBMITTED HAS AN ATTACHMENT
 RESISTANCE MOMENT OF 24.5 FT-LBF FOR
 MORTAR SET TILE. FOR 140 MPH EXPOSURE B
 WITH 40FT MRH, THE REQUIRED MOMENT IS
 28.3 FT-LBF. PLEASE REVISE ROOF TILE
 DETAILS TO COMPLY WITH CODE.
  
 16) UL ASSEMBLY U 906 HAS A 2 HOUR FIRE
 RATING NOT ONE HOUR AS SPECIFIED ON THE
 PLANS FOR WALL TYPES IN DETAILS 2 AND 6
 ON A-10.00.
  
 17) THE DRYWALL SPECIFIED IN THE RATED
 ASSEMBLY IN DETAIL 5 ON A 10.2.0 SHOULD
 BE FIRE-SHIELD C NOT "D". PLEASE
 CORRECT.
  
 18) PROVIDE INFORMATION FOR MECHINICAL
 DUCT PENETRATIONS THROUGH THE FIRE RATED
 ASSEMBLIES.
  
 19) TRUSS LAYOUT AND DRAWINGS ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD FOR THE
 STRUCTURE.
  
 20) THE UPLIFT LOAD VALUES LISTED IN THE
 TRUSS ANCHOR SCHEDULE ON S-3 FOR THE
 SIMPSON HETAL 16 & 20 ARE INCORRECT.THE
 ONE THIRD STRESS INCREASE FOR STEEL
 CALCULATIONS IS NO LONGER ALLOWED. SEE
 THE 2005 SIMPSON CATALOG.
  
 21) THE HUGHES "USC" CONNECTORS ALSO
 HAVE INCORRECT UPLIFT VALUES. HUGHES WAS
 PURCHASED BY USP SEVERAL YEARS AGO AND
 IS LONGER IN BUSINESS. SEE THE 2005 USP
 CATALOG FOR VALUES. UPDATE THE TRUSS
 ANCHOR SCHEDULE.
  
 22) UNDER KEY NOTES/ LEGEND ON A-4.0 AND
 OTHER SHEETS REFERENCE IS MADE TO SHEET
 A-13 FOR THE WALL TYPES. HOWEVER, THERE
 IS NO SHEET A-13.
  
 23) THE ENERGY CALCULATIONS CONTAIN
 SEVERAL ERRORS. THESE ARE CONSIDERED
 MULTIFAMILY NOT SINLE FAMILY. THE
 ADJACENT WALL AT THE GARAGE IS WOOD
 FRAME AND THE CEILING INSULATION IS
 SPECIFIED AS R-20 ICYENE.
  
 24)PROVIDE MANUFACTURER'S SPECIFICATIONS
 FOR THE ICYENE INSULATION.
  
 25) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. IN
 ADDITION TO THE COVERSHEET THE
 INSTALLATION INSTRUCTIONS OR PRODUCT
 EVALUATION AS LISTED ON THE STATE
 WEBSITE IS ALSO REQUIRED.
  
 26) SUBMIT STATE PRODUCT APPROVALS FOR
 THE TRUSS CONNECTORS AND GARAGE DOORS.
  
 27) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS HAS THE INFO FROM THE FIXED
 GLASS WINDOWS ATTACHED TO THE NOA
 COVERSHEET.
  
 28) SUBMIT MANUFACTURER'S SPECS. FOR THE
 DOOR CLOSERS.
  
 29) THE CALCULATED VALUE OF THE
 STRUCTURE HAS BEEN INCREASED TO
 $912,590.00. ADDITIONAL PERMIT FEES OF
 $2740.49 ARE REQUIRED.
  
 30) THE FIRST FLOOR PLAN ON SHEETS
 A-4.0.1 AND A-4.3.1 SHOW THE DOOR FROM
 THE GARAGE OPENING DIRECTLY INTO A GREAT
 ROOM. FBC 411.2.8 PROHIBITS OPENINGS
 FROM A PARKING GARAGE DIRECTLY INTO A
 ROOM USED FOR SLEEPING PURPOSES. PLEASE
 INDICATE ON THE PLANS AT THE GREAT ROOM
 THAT THIS ROOM IS NOT TO BE USED FOR
 SLEEPING PURPOSES.
  
 31) FIRE SPRINKLER PLANS ARE REQUIRED TO
 BE SUBMITTED WHEN REQUIRED FOR HEIGHT OR
 AREA INCREASE ALLOWED BY FBC TABLE 500.
 SEE FBC 903.2 AND 104.3.3.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 19:41 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 19:16 Sent To  
Notes
2006-05-14 00:00:00REDLINED PLANS.
  
 OCP FOR AHU, MIN 125%, SHOWS 40A OCP.
 424.3B.
  
 MIN SIZE GEC TO BE 2/0 PER SEC'S PER
 250.66
  
 **
 PLEASE ONLY REVISE WHEN AND IF OTHER
 REVISIONS ARE MADE , AFTER PERMIT IS
 ISSUED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 19.10 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 17:10 Sent To  
Notes
2006-01-20 00:00:00************** UNSAT 2ND REVIEW ********
  
 **PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE SOME NEW NOTES DUE TO
 CHANGES IN PLANS.
  
  
 SUB 1)NOTE: PLEASE SEE PREVIOUS NOTE
 WITH RESPECT TO THE 2003 NFPA-101 BEING
 ADOPTED AS OF JAN 1ST,2005, HOWEVER
 PLANS ARE STILL SHOWING 2002 EDITION.
 PLEASE SEE ALL PLANS, A-SHEETS AND
 ELECTRICAL SHEETS SHOULD REFERENCE
 CURRENT CODES IN EFFECT.
 PLEASE LIST THE 2002 NFPA-72, 2003
 NFPA-101, AND THE 2002 NFPA-72.
 PLEASE ALSO SEE A-0.00
  
  
  
  
 1)NOTE: NOTE #1 OK, HOWEVER SEE NEW
 NOTES DUE TO NEW SERVICE FOR BLDG BEING
 SHOWN. SEE NEW NOTES LISTED SEPARATELY
 BELOW.
  
  
 2)NOTE: NOTE #2 NO:
 ** PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATINGS ARE SHOWN FOR EACH PANEL,
 BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW
 SERVICE).
 PLEASE SEE CALCUALTIONS SUBMITTED ARE
 BASED ON UNIT MAINS, WHICH ARE OK,
 HOWEVER PLEASE SEE THE MAIN IS ALSO
 REQUIRED. THE SEC'S ARE NOT 2/0'S.
  
  
 3)NOTE: NOTE #3 OK, RECEPT RELOCATED.
  
 4))NOTE: NOTE #4 OK, CORRECTED.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7 NO, ??PLEASE SEE THIS
 COULD NOT BE LOCATED ON LOAD CALCS.
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS NEEDS
 TO BE SHOWN ABOVE THE GEN. KT/RECEPT
 LOADS. THIS SHOULD BE ABOVE THE FIGURED
 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 8)NOTE: NOTE #8 NO, PLEASE SEE AN EFFORT
 WAS MADE TO LIST THESE, HOWEVER PLEASE
 SEE LISTING INDICATES "GFI" WHEREAS
 "AFCI" PROTECTION IS REQUIRED.
  
 ** PLEASE LIST ALL THE REQUIRD ARC
 FAULT PROECTED CIRCUITS AS REQUIRED PER
 2002 210.12
 PLEASE KNOW, SD'S ARE BEING SHOWN
 CIRCUITED TO KITCHEN LIGHTING CIRCUIT,
 THIS IS OK, HOWEVER PLEASE KNOW, THIS
 WOULD ALSO REQUIRE ARC FAULT PROTECTION
 FOR THIS ADDITIONAL CIRCUIT.
 THIS IS ONLY A NOTE:
  
 9)NOTE: NOTE #9 OK, NOTE WAS ADDED TO
 PLANS, HOWEVER PLEASE SEE SD'S ARE STILL
 BEING SHOWN WITHIN 20' OF COOKING
 APPLIANCES. THIS IS PERMITTED, HOWEVER
 PLEASE SPECIFY THE SD TO BE INSTALLED IN
 ORDER TO MEET EXCEPTION AS LISTED.
  
 **PLEEASE SEE NFPA-72 (2002)
 EDITION,11.8.3.5.
 PLEASE PLACE NOTE ON PLANS WHICH STATES
 LOCATIONS OF SD'S TO BE A MIN OF 3' FROM
 BATH(S) AND KITCHEN DOORS AND 20' FROM
 KITCHEN COOKING APPLIANCES.
 ** PLEASE SEE EXCEPTION TO 20' FROM
 COOKING WITH TYPE OF SD USED.**
 PLEASE SEE PLANS SHOWS A SD IN KITCHEN
 AREA AT THIS TIME.
  
 10)NOTE: NOTE #10 OK, REMOVED.
  
 11)NOTE: NOTE #11 NO.
 THIS IS REQUIRED ON ALL SHEETS.
  
 **PLEASE SEE ARCHITECTS TITLE
 BLOCK SHALL ALSO CONTAIN THE PRINTED
 LICENSE NUMBER FOR ARCHITECT OF RECORD.
 FAC 61G1-16.004.
 PLEASE SEE THIS COMMENT IS FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
 PLEASE KNOW THIS COMMENT DOES NOT APPLY
 TO KAMM CONSULTING'S TITLE BLOCK.
  
 ********** NEW NOTES *************
  
 1)NOTE: PLEASE SEE 250.66 FOR MIN
 GROUNDING ELECTRODE CONDUCTOR REQUIRED.
 #4 AWG SHOWN, MIN 3/0 AWG.
  
 2)NOTE: PLEASE SEE CONDUITS FROM FPL IS
 SHOWING AN "EQUIPMENT GROUNDING
 CONDUCTOR" TO THE METER CENTER. PLEASE
 SEE 250.6,250.24.
 AN "EQUIPMENT GROUNDING CONDUCTOR" IS
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
 PLEASE REMOVE.
  
 3)NOTE: PLEASE INDICATE THE OCP AT THE
 METER CENTER FOR ALL UNIT BRKRS.215.5
  
 4)NOTE: PLEASE SHOW SERVICE ON PLANS.
 PLEASE SEE ELECTRICAL PLANS DO NOT
 INDICATE THE LOCATION OF SERVICE ON
 EITHER END OF BLDG. PLEASE ALSO NEEDS TO
 BE SHOWN ON THE A-SHEETS, FLR PLANS,
 ELEVATION.
  
 5)NOTE: PLEASE SEE PLANS SHALL CONTAIN
 THE SIGNATURE OF THE ENGINEER OF RECORD.
 PLEASE SEE NEW SHEETS CONTAIN "INITIALS"
 ONLY AND DO NOT CORRELATE WITH THE
 ORIGINAL PLANS.
 FS 471.025, FAC 61G15-23.002
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES. PLEASE SEE
 PLUMB SHEETS WHICH ARE ALSO INITIALED.
 PLEASE SEE "RAISED SEAL" SHALL BE CLEAR
 AND VISABLE WITH ALL INFORMATION ON
 SIADE SEAL. PLEASE SEESHEETS,
 INFORMATION ON SEAL IS NOT VISABLE EVEN
 WHEN "SHADOWED WITH PENCIL".
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-04 Cont ID  
Sent By dpalmer Date 2005-09-04 Time 09:54 Rev Time 2.00
Received By dpalmer Date 2005-09-03 Time 21:10 Sent To  
Notes
2005-10-17 00:00:00*** NOTE ADDED ***
  
  
 PLEASE KNOW, AS OF JAN 1ST, 2005, WE ARE
 NOW UNDER THE 2003 NFPA-101.
2005-09-04 00:00:00***************************************
  
 PLEASE BEAR IN MIND CODES CHANGES AS OF
 OCTOBER 1, 2005 WILL TAKE AFFECT.
 ONLY PROJECTS/BUILDING PERMITS SUBMITTED
 BEFORE SUCH DATE WILL FALL UNDER PRESENT
 CODE.
 THIS WILL NOT AFFECT ELECTRICAL CODE
 CHANGE, AS 2005 NEC IS NOT SCHEDULED FOR
 ADOPTION UNTIL OCT 1ST, 2006.
  
 ***************************************
  
  
  
 ********* UNSAT *********
  
 1)NOTE: PLEASE SEE PROJECT IS SUBMITTED
 AS CONDO'S YET ELECTRICALSERVICES
 PROVIDED IS SHOWN AS EACH WOULD BE A
 TOWNHOUSE (FEE SIMPLE).
 PLEASE SEE WATER SERVICE SHOWS
 MULTI-FAMILY BLDG.
 PLEASE KNOW, IF THESE AS MULTI-FAMILY
 CONDO BLDGS; ONE SERVICE FOR EACH BLDG
 IS PERMITTED,230.2,230.70MAINS WILL BE
 REQUIRED TO BE GROUPED PER 230.72.
 MCB'S SHOWN IN EACH GARAGE PANEL IS
 PERMITTED.
 PLEASE ADJUST SERVICE FOR BLDG.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATINGS ARE SHOWN FOR EACH PANEL,
 BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW
 SERVICE).
  
 3)NOTE: PLEASE CLARIFY LOCATION OF
 DISHWASHER RECEPT. APPEARS TO BE SHOWN
 BEHIND UNIT? THIS IS ONLY A NOTE:
  
 4))NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE PLANS REDLINED FOR SOME
 MISSING W/IN 2' OF THE END OF A COUNTER
 OR 4' SPACING.
 UNIT "A"/STANDARD 2FLR,,,
  
 5)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE THESE HAVE BEEN REDLINED AT
 LOCATIONS OF NOTES.
 UNIT "B",3RD FLR OPT 6 2'OF WALL, UNIT
 "A"2ND FLR, WALL APPEARS TO BE OVER 12'?
 PLEASE SEE A COUPLE OF OTHER LOCATIONS.
  
 6)NOTE: PLEASE SEE LOCATION OF A
 RECESSED LT FIXTURE IN CLOSET
 WASHER/DRYER LOCATION. THESE LOCATIONS
 TYPICALLY CONTAIN SHELVING ABOVE THE
 WASHER/DRYER'S. PLEASE SEE 410.8 FOR MIN
 CLEARENCE FROM LT AND FIXTURE TYPES.
 (WALL MOUNT)? AS SHOWN IN OTHER CLOSETS?
  
 7 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS NEEDS
 TO BE SHOWN ABOVE THE GEN. KT/RECEPT
 LOADS. THIS SHOULD BE ABOVE THE FIGURED
 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 8)NOTE: PLEASE LIST ALL THE REQUIRD ARC
 FAULT PROECTED CIRCUITS AS REQUIRED PER
 2002 210.12
 PLEASE KNOW, SD'S ARE BEING SHOWN
 CIRCUITED TO KITCHEN LIGHTING CIRCUIT,
 THIS IS OK, HOWEVER PLEASE KNOW, THIS
 WOULD ALSO REQUIRE ARC FAULT PROTECTION
 FOR THIS ADDITIONAL CIRCUIT.
 THIS IS ONLY A NOTE:
  
 9)NOTE: PLEEASE SEE NFPA-72 (2002)
 EDITION,11.8.3.5.
 PLEASE PLACE NOTE ON PLANS WHICH STATES
 LOCATIONS OF SD'S TO BE A MIN OF 3' FROM
 BATH(S) AND KITCHEN DOORS AND 20' FROM
 KITCHEN COOKING APPLIANCES.
 ** PLEASE SEE EXCEPTION TO 20' FROM
 COOKING WITH TYOE OF SD USED.**
 PLEASE SEE PLANS SHOWS A SD IN KITCHEN
 AREA AT THIS TIME.
  
 10)NOTE: PLEASE SEE MECHANICAL NOTES
 PERTAINING TO "DRYER BOOSTER FANS".
 AS PER MECHANICAL THESE MAY NOT BE
 PERMITTED AND ANY COMMENT THEY MAY HAVE
 WILL DIRECTLY AFFECT ELECTRICAL PLANS.
 THIS IS A NOTE, AS IT IS NOT AN NEC
 ISSUE.
 PLEASE SEE ALL SYSTEMS DO HAVE BE
 LISTED.110.3,90.7
  
 11)NOTE: PLEASE SEE ARCHITECTS TITLE
 BLOCK SHALL ALSO CONTAIN THE PRINTED
 LICENSE NUMBER FOR ARCHITECT OF RECORD.
 FAC 61G1-16.004.
 PLEASE SEE THIS COMMENT IS FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
 PLEASE KNOW THIS COMMENT DOES NOT APPLY
 TO KAMM CONSULTING'S TITLE BLOCK.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLF/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 ** PLEASE SEE THIS MAY BE CONSIDERED A
 "THRESHOLD" PROJECT. IF SO, THREE SETS
 OF PLANS WILL BE REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
2005-09-03 00:00:00IN ELEC FOR REVIEW
 NOTES TO FOLLOW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-08-31 Cont ID  
Sent By mamini Date 2005-08-31 Time 09:57 Rev Time 0.50
Received By mamini Date 2005-08-31 Time 09:56 Sent To  
Notes
2005-08-31 00:00:00PASSED:
  
 1. SEE PERMIT # 04120439 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-10-05 Cont ID  
Sent By nmccray Date 2005-10-05 Time 12:05 Rev Time 0.00
Received By nmccray Date 2005-10-05 Time 10:20 Sent To  
Notes
2005-10-05 00:00:00PROVISO:
  
 1) INTERIOR FINISH FOR WALLS AND
 CEILINGS SHALL BE CLASS A, CLASS B, OR
 CLASS C.
  
 2) SEPARATE PLANS AND PERMIT APPLICATION
 ARE REQUIRED FOR FIRE ALARM SYSTEMS. THE
 FIRE ALARM SYSTEM SHALL BE UL
 CERTIFICATED FOR CENTRAL STATION
 SERVICES.
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-15 Cont ID  
Sent By dpalmer Date 2006-05-15 Time 06:57 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2006-05-15 00:00:00ON COMM BOARD #4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-30 Cont ID  
Sent By adarroug Date 2005-12-19 Time 13:25 Rev Time 0.00
Received By adarroug Date 2005-12-19 Time 08:53 Sent To  
Notes
2006-01-30 00:00:00TO "COMM" BD#45
2005-12-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-29 Cont ID  
Sent By rmcdouga Date 2005-11-29 Time 13:26 Rev Time 0.00
Received By rmcdouga Date 2005-08-23 Time 11:57 Sent To  
Notes
2005-08-24 00:00:00TO "COMM" BD#39
2005-08-23 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-06-07 Cont ID  
Sent By pkrauss Date 2006-06-06 Time 13:47 Rev Time 0.00
Received By pkrauss Date 2006-06-06 Time 13:47 Sent To  
Notes
2006-06-06 00:00:00PROVISO:2001 FBC/BUILDING 6/6 UNITS
  
 PLEASE REVISE PLANS TO REFLECT THE
 IMPLEMENTATION OF THE PROVISO'S.
  
 1.THE FIRST FLOOR MECHANICAL PLAN (M1)
 DOES NOT MATCH THE FIRST FLOOR
 ARCHITECTURAL PLAN (A-2.0.1).PLEASE
 NOTE, RETURN AIR BETWEEN THE GARAGE DOOR
 & THE FOYER DOOR IS NOT REQURIED PER
 2001 FMC 601.4 EXCEPTION #3, R/A IS ONLY
 REQUIRED FROM HABITABLE SPACES.
  
 2.PLAN SHEET M0.1 THE AHU MOUNTING
 DETAIL NOTE 15 STATES, "NO COMBUSTIBLES
 ALLOWED IN THE MECHANICAL CLOSET" AS
 THIS SERVES AS A RETURN AIR PLENUM.THE
 DOOR SCHEDULE ON PLAN SHEET A-4.1.1
 INDICATES THE AHU CLOSET DOOR AS A WOOD
 LOUVERED DOOR.PLEASE VERIFY WITH THE
 DOOR MANUFACTURE THAT THIS WILL MEET THE
 REQUIRED 25 FLAME/50 SMOKE INDEX AS
 SPECIFIED IN 2001 FMC 602.2.1.
  
 3.OUTSIDE AIR CALCULATIONS INDICATED
 ON PLAN SEET M0.1 ARE BASED ON
 INFLITRATION RATES.THE INFILTRATION
 RATES ARE THE "MAXIMUM" ALLOWED BY CODE
 & MAY NOT BE A "TRUE/ACTUAL" RATE.
 PLEASE PROVIDE CALCS IN ACCORDANCE WITH
 2001 FMC 402.2, 402.2.1 OR TABLE 403.3.
 PLEASE NOTE, 6" O.A. DUCT IS INDICATED
 ON M2.PLEASE REMOVE FROM THE PLAN IF
 THIS DUCT WILL NOT BE INSTALLED.
  
 4.SPECIFIC DRYERS ARE TO BE INSTALLED
 BY FINAL INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-02-14 Cont ID  
Sent By pkrauss Date 2006-02-14 Time 12:13 Rev Time 0.00
Received By pkrauss Date 2006-02-14 Time 11:23 Sent To  
Notes
2006-02-14 00:00:00DENIED:BUILDING #6 / 6 UNITS
 PLEASE REFERENCE COMMENTS FROM REVIEW
 DATED 9-28-05, SINCE A RESPONSE SHEET
 WAS NOT SUBMITTED & FOR CONSISTENCY THE
 SAME NUMBER SEQUENCE WILL BE USED.
  
 1.COMMENT ADDRESSED
  
 2.PLAN SHEET A-0.0.0, PROJECT
 INFORMATION; PLEASE INDICATE WHAT TYPE
 OF SPRINLERED SYSTEM WILL BE INSTALLED
 I.E. 13, 13D, 13R?
  
 3.COMMENT ADDRESSED.
  
 4.PLAN SHEET A-10.2.0 INDICATES FIRE
 RATED ASSEMBLIES.DETAIL #5 SHOWS A 1
 HR FIRE RATED FLOOR/CEILING ASSEMBLY.
 PLEASE INDICATE WHAT EDITION OF THE UL
 BOOK THIS ASSEMBLY WAS TAKEN FROM? THE
 DETAIL #6 FOR THE DUCT PENETRATION DOES
 NOT ADDRESS THE MEMBRANE PENETRATION
 WHERE THE DUCT & GRILLES ARE LOCATED
 BETWEEN THE RATING OF THE FLOOR/CEILING
 ASSEMBLY.PLEASE CLARIFY.PLESE NOTE
 DETAIL #1 & 2 ARE PENETRATIONS THROUGH
 CONCRETE FLOOR OR WALL ASSEMBLY. PLEASE
 PROVIDE DETAIL FOR THE WOOD FLOOR
 SYSTEM.
  
 5 THROUGH 10COMMENTS ADDRESSED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-28 Cont ID  
Sent By pkrauss Date 2005-09-28 Time 07:29 Rev Time  
Received By pkrauss Date 2005-09-28 Time 07:19 Sent To  
Notes
2005-09-28 00:00:00DENIED:
 1.THE ENERGY CALCULATIONS INDICATE
 'SINGLE FAMILY' & PLAN SHEET A-0.0.0,
 INDICATES OCCUPANCY CLASSIFICATION AS
 GROUP R2, MULTI-FAMILY.ENERGY
 CALUCALTIONS SHOULD REFLECT
 MULTI-FAMILY.
  
 2.PLAN SHEET A-0.0.0, PROJECT
 INFORMATION; TABLE 500 THE TYPE OF
 CONSTRUCTION IS LISTED AS TYPE VI,
 UNPROTECTED, SPRINKLERED.PER 2001 FBC
 TABLE 500 NOTE D; HEIGHT INCREASES NOT
 PERMITTED IN APPLICATIONS UTILIZING NFPA
 13R SYSTEMS.
  
 3.PLAN SHEETS A-4.0.2 THROUGH A-4.5.3
 NOTE #25 1-HOUR RATED CHASE REFER TO
 DETAIL 11/A-13 (AT LIVE WORK OPTION
 ONLY).PLEASE CLARIFY IF THE INTENT IS
 FOR FUTURE 'LIVE WORK' UNITS.
  
 4.PLAN SHEET A-10.2.0 INDICATES FIRE
 RATED ASSEMBLIES.DETAIL #5 SHOWS A 1
 HOUR FIRE RATED FLOOR/CEILING ASSEMBLY.
 PLEASE PROVIDE A DETAIL FOR THE DUCT
 PENETRATIONS.PLEASE NOTE, PER 2001
 FBC(M)607.4 DUCTS EXTENDING THROUGH MORE
 THAN ONE FLOOR SHALL BE PROTECTED BY A
 SHAFT ENCLOSURRE.PROVIDE UL DESIGN #
 FOR DUCT PENETRATIONS.
  
 5.PLAN SHEET M1, CONDENSING UNIT SLAB
 SHALL BE A MINIMUM OF 3 1/2" AND EXTEND
 A MINIMUM OF 2" ABOVE THE ADJOINING
 GRADE.
  
 6.PLAN SHEET M3 UNIT A OPT.7, TRANSFER
 GRILLE FROM THE MASTER SUITE IS NOT
 SIZED PROPERLY.PER 2001 FBC(M)601.4
 EXCEPTION #2 & 3, TO ACHIEVE PROPER AIR
 BALANCE TRANSFER GRILLES SHALL USE 50 SQ
 INCHES OF GRILLE AREA TO 100 CFM OF
 SUPPLY AIR.ALL AIR INTO THE MASTER
 SUITE IS TO BE INCLUDED.PLAN INDICATES
 375 CFM INTO THE MASTER SUITE THEREFOR
 THE TRANSFER GRILLE SHALL HAVE A MINIMUM
 OF 187.5 SQ INCHES OF GRILLE AREA.DOOR
 SHALL HAVE A 1" UNDERCUT.PLEASE REVISE
 PLANS ACCORDINGLY.
  
 7.PLEASE PROVIDE OUTSIDE AIR
 CALUCLATIONS IN ACCORDANCE WITH 2001
 FBC(M) 402.2, 402.2.1 OR TABLE 403.3.
  
 8.PLEASE PROVIDE DETAIL FOR THE
 HANGING OF THE AHU LOCATED AT THE 2ND
 FLOOR CEILING.
  
 9. AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 10. ELECTRICAL PLANS INDICATE A 'DRYER
 BOOSTER FAN'.THIS WILL HAVE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL AS
 ALTERNATE MATERIALS AND METHODS
 (AMMENDED 2001 FBC SECTION 103.7).
 PLEASE PROVIDE LETTER FROM THE ENGINEER
 OF THE DRYER MANUFACTURER APPROVING THE
 INSTALLATION OF THE BOOSTER FAN WITHOUT
 VOIDING THE WARRANTY OF THE DRYER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-05-25 Cont ID  
Sent By kstevens Date 2006-05-25 Time 08:58 Rev Time 0.00
Received By kstevens Date 2006-05-25 Time 08:58 Sent To  
Notes
2006-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEWS:
  
 1. SHTS P2.1.1, P2.1, P3.1.1, & P3.1,
 UNDERGROUND DRAINAGE PIPING PARALLEL
 WITH THE FOOTER SHALL COMPLY WITH
 SECTION 307.4. BUILDING DRAIN SHOULD BE
 MOVED AWAY FROM THE FOOTERS. "OUT OF THE
 MONOLITHIC FOOTER". (MINIMUM 4' FROM
 BLOCK WALL).
  
 **************NEW COMMENTS**************
 1B. SHTS P2.2, P2.3, P2.3.2, P3.2,
 P3.2.4, P3.3, P3.3.1, P3.3.2, & P4.1 THE
 INFORMATION REQUIRED ON THE SEAL IS NOT
 BEING IMPRESSED ON THE SHEET AS REQUIRED
 IN FAC 61G15-23.002 & FS 471.025.-
 THE ENGINEER SHALL SIGN HIS/HER NAME.
 THE INITIALS ARE NOT ACCEPTABLE AND DO
 NOT APPEAR TO MATCH THE SIGNATURE ON THE
 OTHER SHEETS. FAC 61G15-23.002(1) & FS
 471.025.(ONE SET OF PLUMBING SHEETS
 WILL BE WITH-HELD FOR POSSIBLE REVIEW BY
 DBPR).-NEW SEAL WITH "LICENCE"
 REQUIRED ON ALL SHEETS SEALED AFTER DEC.
 31, 2005 PER THE LETTER FROM THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-02-04 Cont ID  
Sent By pschmitz Date 2006-02-04 Time 10:23 Rev Time 0.00
Received By pschmitz Date 2006-02-04 Time 10:23 Sent To  
Notes
2006-02-04 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2001
 FBC FUEL GAS 2001
 DENIED
 1) PLEASE ADDRESS PREVIOUS NOTES.
 BY JOHN LEECH DATED 11-19-05
  
 2.U/G DRAINAGE PIPE PARALLEL TO THE
 FOOTER MUST COMPLY WITH SECTION 307.4.
 BUILDING DRAIN SHOULD BE MOVED AWAY FROM
 FOOTERS.
 "OUT OF THE MONOLITHIC FOOTER."
  
 3.WATER HEATER RELIEF VALVE DISCHARGE.
 SHT P0.1 (WATER HEATER DETAIL) SHOWS
 DISCHARGE TO GARAGE FLOOR. PAGE P2.1
 (FLAT DRAWING) SHOWS P & T DISCHARGE TO
 OUTSIDE. REFERE TO SEC.504.7.1. REVISE
 PLANS.
 "CORRELATE SHT P0.1 WITH P2.1 SHOW
 METHOD, NOT THE CODE SECTION."

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-19 Cont ID  
Sent By jleech Date 2005-11-19 Time 10:42 Rev Time 6.00
Received By jleech Date 2005-11-19 Time 10:42 Sent To  
Notes
2005-11-19 00:00:00DENIED;
 1.GUTTERS AND DOWN SPOUTS; SHOW
 CALCULATIONS AND SIZES PER FBC PLUMBING
 CHAPTER 11.
 2.U/G DRAINAGE PIPE PARALLEL TO THE
 FOOTER MUST COMPLY WITH SECTION 307.4.
 BUILDING DRAIN SHOULD BE MOVED AWAY FROM
 FOOTERS.
 3.WATER HEATER RELIEF VALVE DISCHARGE.
 SHT P0.1 (WATER HEATER DETAIOL) SHOWS
 DISCHARGE TO GARAGE FLOOR. PAGE P2.1
 (FLAT DRAWING) SHOWS P & T DISCHARGE TO
 OUTSIDE. REFURE TO SEC.504.7.1. REVISE
 PLANS.
 4.BACKFLOW PROTECTION FOR EACH BUILDING
 IS REQUIRED. PLEASE ADD NOTE TO
 DRAWINGS.
 5.SHOW HOW THERMAL EXPANTION WILL BE
 CONTROLLED. SEC. 607.3 THRU 606.3.2.
 6.SHOW SHUTOFF VALVE FOR WATER HEATER ON
 RISER DIAGRAMS.
 7.SHOCK ARRESTORS TO BE INSTALLED PER.
 MANUFACTURES INSTALLATION INSTUCTIONS,
 AS CLOSE TO THE SOURCE OF HAMMER IN A
 DIRECT LINE.
 8.WATER RISER DIAGRAMS (FIRST FLOOR)
 CHANGE 1/2" HOT TO 3/4" HOT. SECOND
 FLOOR WATER RISERS SHOW 3/4" UP FROM
 FIRST FLOOR.
 9.SHOCK ARRESTORS ARE REQUIRED ON W/M'S
 SEC. 604.9. SHOW ON WATER RISER
 DIAGRAMS.
 10.SHOW CLEANOUT ON WASHER STACK AT 48"
 A.F.F. SO W/M DOES NOT HAVE TO BE MOVED
 IF CLEANING IS REQUIRED.
 11.ALL THIRD FLOOR SAN. RISER DIAGRAMS;
 OFFSET VENT THRU ROOF AND ADD A NOTE. NO
 PENATRATIONS THRU FIRE RESISTANT
 PLYWOOD. SEE PAGE S-2 NOTE 2.
 12.PAGE P3.2.4 FLAT DRAWING UNIT B
 OPTION 5 REVERSE, W/M VENTNOT PER RISER
 DIAGRAM (MARKED IN RED ON ON SET OF
 PLANS)
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-10-13 Cont ID  
Sent By gjoyce Date 2005-10-13 Time 08:38 Rev Time 0.00
Received By gjoyce Date 2005-10-13 Time 08:38 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy