2005-09-10 00:00:00 | ******** UNSAT ********** |
| |
| 1)NOTE: PLEASE SEE RISER DIAGRAM NEEDS |
| TO BE COMPLETELYREVISED TO MEET ZONING |
| GREEN CARD. |
| THIS MAY ONLY BE A MAIN HOUSE W/ A |
| GARAGE APT. THIS WOULD ONLY BE ALLOWED |
| TO HAVE TWO METERS. ONE FOR EACH AND NO |
| HOUSE PANEL. |
| |
| PLEASE SEE ANY LEGAL CONVERSIONS, MUST |
| BE RESERCHED TO ALLOW FOR ANY MORE THAN |
| THE TWO ON GREEN CARDS AS INDICATED. |
| ALL RESERCH REQUESTS MUST GO THROUGH |
| APRIL PICCIRILLO, 805-6658 |
| |
| |
| |
| 2)NOTE: PLEASE SEE RISER SUBMITTED IF |
| APPROVED BY ZONING HAS CORRECTION |
| NEEDED. |
| PLEASE SEE ALL FEEDS FOR EACH COME FROM |
| LEFT SIDE OF METER CENTER. |
| PLEASE LABEL ALL MAINS ON METER CENTER |
| FOR EACH HOUSE/APT. |
| PLEASE SEE TWO APT "B"'S ARE SHOWN. |
| PLEASE SEE MAIN HOUSE IS ALSO INDICATED |
| AS APT "B".?? |
| |
| |
| 3)NOTE: PLEASE SEE ALL CONTINUOUS LOADS |
| ARE TO BE SHOWN AT 125%. |
| HEAT PUMP, POOL PUMP ETC. |
| 215.3,230.42,680.9 |
| |
| 4)NOTE: PLEASE SEE MIN BRANCH CIRCUIT |
| CONDUCTOR AMPACITY FOR TANKLESS WATER |
| HEATER UNITS MUST BE 125%. |
| 422.13 |
| PLEASE ALSO SEE 422.11F1 |
| |
| 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 6)NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52 |
| |
| 7 )NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| 2002 NEC 210.12 |
| |
| 8)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210.8A-6 |
| |
| 9) NOTE: PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. PER 210.52D, 210.11C3 |
| MUST BE 20A AND #12. |
| |
| 10) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| FRONT AND/OR REAR OF DWELLING. |
| 210.52E |
| ALSO 210.8 FOR GFI. |
| |
| 11)NOTE: PLEASE SEE MISSING RECEPT |
| REQ'D FOR A/C EQUIPMENT. 210.63 |
| |
| 12)NOTE: PLEASE SEE RECEPTS SERVING |
| KITCHEN COUNTERSPACE TO MEET 210.52C- |
| SEC'S 1,2,3,4 AND 5 |
| SEE REDLINED PLANS FOR MISSING. |
| |
| 13)NOTE: PLEASE SEE SEE SPA TUB SHOWN, |
| HOWEVER NO ELECTRICAL GFI ETC?? |
| 680.71 |
| IS THIS AN ELECTRICAL JACUZZI TUB? |
| |
| 14)NOTE: PLEASE SEE FBC CHAPTER 34 WITH |
| RENOVATIONS TO EXSITNG DWELLINGS. |
| PLEASE SEE ALL MUST BE BROUGHT UP TO |
| CODE, INCLUDING 2NF FLR AT DEATCHED |
| BLDG. |
| PLEASE PROVIDE COMPLETE LAYOUT FOR |
| EITHER EXSITNG TO MEET CODE OR NEW TO BE |
| DONE ON SCOPE OF WORK. |
| |
| 15)NOTE: PLEASE SEE ADMINISTRATIVE |
| AMENDMENTS, 104.6.5, WHICH REQUIRES ALL |
| LABOR AND MATERIALS TO BE INCLUDED IN |
| VALUE OF PERMIT APPLICATION. |
| PLEASE SEE VALUE FOR SERVICE CHANGE |
| PERMIT WILL ALSO BE REQUIRED TO BE |
| UPGRADED. |
| IFVALUES ARE NOT AJUSTED, A VALUATION |
| WILL BE GIVEN BASED ON TABLE IN "MARSHAL |
| SWIFT " GUIDES ADOPTED UNDER FBC. |
| |
| ** PLEASE SEE MANY OF THE ABOVE COMMENTS |
| DEPEND ON ZONING AND APPROVAL FOR MORE |
| THAN TWO METERS AND DETACHED BLDG |
| POSSIBLY REMAINING GARAGE WITH APT |
| ABOVE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |