Plan Review Details - Permit 05081151
Plan Review Stops For Permit 05081151
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-11-09 Cont ID  
Sent By jwitmer Date 2005-11-09 Time 11:40 Rev Time 0.55
Received By jwitmer Date 2005-11-09 Time 11:40 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-12 Cont ID  
Sent By jwitmer Date 2005-09-12 Time 07:17 Rev Time 0.55
Received By jwitmer Date 2005-09-12 Time 07:16 Sent To PC
Notes
2005-09-12 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05081151
 ADD: 7317 HORIZON DR
 CONT: DANIEL ELECTRICAL
 TEL: (561)718-5324
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-09 Cont ID  
Sent By dpalmer Date 2005-11-09 Time 10:34 Rev Time 0.00
Received By dpalmer Date 2005-11-09 Time 10:34 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-01 Cont ID  
Sent By dpalmer Date 2005-09-01 Time 09:00 Rev Time 1.00
Received By dpalmer Date 2005-09-01 Time 08:59 Sent To M
Notes
2005-09-01 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S). BLDG FOR SLAB DETAIL
 SUBMITTED.
  
 2)NOTE: PLEASE SEE SITE PLAN SUBMITTED
 SHOWS GENERATOR RIGHT NEXT TO HOUSE??
 PLEASE SHOW SET BACK AND DIMENTIONS FROM
 DWELLING STRUCTURE.
 PLEASE SEE MECH NOTES, MUST BE 10' FROM
 ANY OPENINGS TO HOUSE,ATTIC VENTILATION,
 DOORS AND WINDOWS.
  
 3)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANEL SCHEDULES SUBMITTED.
 PLEASE SEE RISER SHOWS 2 PANELS, BOTH
 200A WITH 2/0'S. PLEASE SEE PANEL "A"
 SHOWN AS 150A W/ #1 AS FEEDERS??
 PLEASE SEE PANEL "C" IS NOT SHOWN ON
 RISER AND SEE PANEL "B" SHOWS 100A OCP
 ON #6 AWG. PLEASE SEE 240.4,310.16 ETC.
  
 4)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTOR SHOWN FROM METER TO FIRST
 MEANS OF DISCONNECT.
 PLEASE SEE 250.6,
  
 5)NOTE: PLEASE SEE EXISTING SERVICE IS
 SHOWN AS 400A, YET NEW MAIN AND ATS
 SHOWN BRINGS SERVICE DOWN TO 300A'S??
 PLEASE SUBMIT MORE INFORMATION ON NEW
 MAIN SHOWN ON RISER. OCP? ETC
 AIC RATINGS FOR ALL EQUIPMENT BEING
 INSTALLED, MAIN, ATS ETC
 702.6,110.9 ETC.
  
 6)NOTE: PLEASE SUBMIT SPEC ON ATS,
 SHEETS SUBMITTED DOES NOT PROVIDE
 INFORMATION FOR RATING PER 225.36,
 230.70
 MUST INDICATE BEING RATED AS SERVICE
 EQUIPMENT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-17 Cont ID  
Sent By adarroug Date 2005-10-17 Time 08:42 Rev Time 0.00
Received By adarroug Date 2005-10-17 Time 08:42 Sent To E
Notes
2005-10-17 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-25 Cont ID  
Sent By adarroug Date 2005-08-25 Time 10:57 Rev Time 0.00
Received By adarroug Date 2005-08-25 Time 10:57 Sent To E
Notes
2005-08-25 00:00:00TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 17:45 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 17:45 Sent To Z
Notes
2005-08-18 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-11-09 Cont ID  
Sent By jwitmer Date 2005-11-09 Time 16:38 Rev Time 0.33
Received By jwitmer Date 2005-11-09 Time 16:38 Sent To PC
Notes
2005-11-09 00:00:00MECHANICAL PROVISO:
 GENERATOR EXHAUSST MUST BE 10' AWAY FROM
 ANY BUILDING OPENINGS (WINDOWS, DOORS,
 ROOF/ EAVE VENTS.
  
 NATURAL GAS PIPING WILL REQUIRE A GAS
 PERMIT APPLICATION BY A LICENSED
 PLUMBING CONTRACTOR.
 JIM WITMER
 MECHANICAL PLAN REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-08 Cont ID  
Sent By tgordon Date 2005-09-08 Time 13:30 Rev Time 0.15
Received By tgordon Date 2005-09-08 Time 13:30 Sent To P
Notes
2005-09-08 00:00:00*** DENIDE ***
 1) GENERATOR EXHAUET MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF/EAVE VENTS),
 AND TEN FEET AWAY FROM ADJACENT
 BUILDING OPENINGS. 2001 FBC/M 804.3.3
 2) NATURAL GAS PIPING WILL REQUIRE A
 GAS PERMIT APPLICATION BY A LICENSE
 PLUMBING CONTRACTOR.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-09-09 Cont ID  
Sent By jleech Date 2005-09-09 Time 08:26 Rev Time 0.33
Received By jleech Date 2005-09-09 Time 08:26 Sent To B
Notes
2005-09-09 00:00:00GAS APP. RECIEVED # 05080241

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-24 Cont ID  
Sent By mmclean Date 2005-08-24 Time 17:09 Rev Time 0.00
Received By mmclean Date 2005-08-24 Time 17:09 Sent To I
Notes
2005-08-24 00:00:00GENERATOR CAN ONLY ENCROACH 4FT INTO
 SETBACK.