Plan Review Details - Permit 05081135
Plan Review Stops For Permit 05081135
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-10-13 Cont ID  
Sent By shill Date 2005-10-13 Time 09:49 Rev Time 1.00
Received By shill Date 2005-10-13 Time 09:49 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-07 Cont ID  
Sent By shill Date 2005-09-07 Time 12:35 Rev Time 1.00
Received By shill Date 2005-09-07 Time 12:08 Sent To  
Notes
2005-09-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)FBC704.2.1.4 CORRIDOR PARTITIONS,
 SMOKESTOP PARTITIONS, HORIZONTAL EXIT
 PARTITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION.SUCH
 IDENTIFICATION SHALL BE ABOVE ANY
 DECORATIVE CEILING AND IN CONCEALED
 SPACES.SUGGESTED WORDING:FIRE AND
 SMOKE BARRIER PROTECT ALL OPENINGS.
  
 2.)TITLE BLOCKS FOR ENGINEERS ARE
 REQUIRED TO HAVE THE CA NUMBER FOR THE
 FIRM, FAC61G15-23.002 (FILE CABINET
 DETAILS PREPARED BY ONM&J).

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-20 Cont ID  
Sent By dpalmer Date 2005-12-20 Time 21:09 Rev Time 0.00
Received By dpalmer Date 2005-12-20 Time 20:48 Sent To  
Notes
2005-12-20 00:00:00REDLINED
 MISSING EQUIPMENT GROUNDS, 250.122,
 250.110, 250.30 FOR TRANSFORMER
  
 KITCHEN RECEPTS PER 2002 NEC 210.8B3

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-09-01 Cont ID  
Sent By dpalmer Date 2005-09-01 Time 18:38 Rev Time 0.50
Received By dpalmer Date 2005-09-01 Time 18:12 Sent To  
Notes
2005-09-01 00:00:00REDLINEDMISSING EQUIPMENT GROUNDING
 CONDUCTORS, 250.110,250.122
  
 REDLINED 210.8B3 FOR KITCHEN RECEPTS IN
 OTHER THAN DWELLING UNITS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-10-12 Cont ID  
Sent By mwennerg Date 2005-10-12 Time 13:38 Rev Time 0.00
Received By mwennerg Date 2005-10-12 Time 13:38 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-09 Cont ID  
Sent By mwennerg Date 2005-09-09 Time 14:36 Rev Time 0.00
Received By mwennerg Date 2005-09-09 Time 14:36 Sent To  
Notes
2005-09-09 00:00:00******DENIED******
  
 1) PLANS SHOW ONE SET OF DOORS 1 HOUR
 RATED AND THE OTHER DOOR FROM CORRIDOR
 TO SUITE ISN'T? PLEASE EXPLAIN.
  
 2) PLEASE SHOW LOCATIONS OF REQUIRED
 FIRE EXTINGUISHERS THAT SHALL BE MOUNTED
 TO SATISFY 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 3) PLEASE PROVIDE FLAME SPREAD
 INFORMATION FOR PROPOSED WALL SURFACE
 FABRIC SYSTEM.
  
 4) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, NEW DUCT SMOKE DETECTORS
 SHALL BE WIRED TO CAUSE A GENERAL FIRE
 ALARM CONDITION WHEN ACTIVATED.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 14:33 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 14:33 Sent To E
Notes
2005-12-16 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-10 Cont ID  
Sent By adarroug Date 2005-12-10 Time 14:02 Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 14:02 Sent To M
Notes
2005-12-10 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 13:11 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 13:11 Sent To  
Notes
2005-10-11 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-05 Time 08:48 Rev Time 0.00
Received By adarroug Date 2005-08-19 Time 15:27 Sent To  
Notes
2005-08-23 00:00:00TO "COMM" #45
2005-08-19 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-12-14 Cont ID  
Sent By pkrauss Date 2005-12-14 Time 15:37 Rev Time 0.00
Received By pkrauss Date 2005-12-14 Time 15:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-10-12 Cont ID  
Sent By hmoser Date 2005-10-12 Time 11:28 Rev Time 0.00
Received By hmoser Date 2005-10-12 Time 11:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-10-05 Cont ID  
Sent By hmoser Date 2005-10-05 Time 13:35 Rev Time 0.00
Received By hmoser Date 2005-10-05 Time 13:35 Sent To  
Notes
2005-10-05 00:00:00PLAN DENIED
 1) HEAT PUMPS THAT CAN PRODUCE OVER 2000
 CFM.MUST HAVE FAN SHUTDOWN.SECTION
 606.2.1 FBC(M).
 2) PLEASE REFER TO SECTION 307.2.3
 AUXILIARY DRAIN PANS.
 3) PLEASE PROVIDE MORE INFORMATION ON
 SMOKE EVACUATION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-10-12 Cont ID  
Sent By pschmitz Date 2005-10-12 Time 12:27 Rev Time 0.00
Received By pschmitz Date 2005-10-12 Time 12:27 Sent To  
Notes
2005-10-12 00:00:00SEE LETTER: REVISION TO FOLLOW ON BOTH
 BREAK RM SINKS COMPLYING WITH 11-4.24

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-05 Cont ID  
Sent By pschmitz Date 2005-10-05 Time 08:50 Rev Time 0.00
Received By pschmitz Date 2005-10-05 Time 08:48 Sent To  
Notes
2005-09-30 00:00:00PAUL SCHMITZ PLUMBING PLAN REVIEW
 FBC 2001, CH 11
 SHT A-200,P-1.DENIED
 ALL BREAK ROOM SINKS TO COMPLY WITH
 FLORIDA ACCESSIBILITY CODE.
  
 11-4.24 SINKS.
  
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
  
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
  
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
  
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
  
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
  
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
  
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
 END OF COMMENTS, QUESTIONS 561-805-6692