Plan Review Details - Permit 05080920
Plan Review Stops For Permit 05080920
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-07 Cont ID  
Sent By shill Date 2005-09-07 Time 09:22 Rev Time 1.00
Received By shill Date 2005-09-07 Time 09:22 Sent To  
Notes
2005-09-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 2.)IMPACT PROTECTION REQUIRED
 FBC1606.1.4.
  
 3.)THE FLOOR PLAN IS NOT CLEAR.
 SUBMIT A FLOOR PLAN SHOWING ALL WINDOW
 LOCATIONS, SIZES, WINDOW TYPE.
  
 4.)DECLARE AN OCCUPANCY FBC CHAPTER 3.
  
 5.)SHOW EMERGENCY EGRESS REQUIRED BY
 FBC1005.4.2 FOR EDUCATIONAL OCCUPANCY,
 IF APPLICABLE.
  
 6.)SEE ATTACHED POLICY, ITEM #13, IN
 REGARDS TO MISSILE IMPACT PROTECTION.
 IMPACT GLASS REQUIRED ABOVE THE FIRST
 FLOOR.IF YOU WOULD LIKE TO USE
 SHUTTERS FOR COMPLIANCE WITH FBC1606.1.4
 SUBMIT AN INSTALLATION PLAN.
  
 7.)FBC104.2.1, THE DRAWINGS SHALL BEAR
 THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-13 Cont ID  
Sent By mwennerg Date 2005-09-13 Time 13:55 Rev Time 0.00
Received By mwennerg Date 2005-09-13 Time 13:55 Sent To  
Notes
2005-09-13 00:00:00******DENIED******
  
 1) PLEASE PROVIDE OCCUPANCY TYPE
 CLASSIFICATION.
  
 2) PLANS DON'T SHOW REQUIRED MARKED
 MEANS OF EGRESS. DOES THIS PROJECT MEET
 THE EXCEPTION TO ELIMINATE WINDOWS FOR
 RESCUE?
  
 3) IS THIS A FIRE SPRINKLERED BUILDING?
 FIRE ALARM SYSTEM?
  
 4) PLEASE SUBMIT MORE INFORMATION, AND
 CLEARLY ILLUSTRATE USE OF ROOMS AND
 OVERALL BUILDING.
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-08-15 Time 11:31 Sent To  
Notes
2005-08-29 00:00:00TO "COMM" BD#10
2005-08-15 00:00:00WAITING FOR "COMM" BD/AS PER ALANGE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***