2005-09-14 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- IMPACT FEES PAID RECEIPT SUBMITTED |
| PR#05040709 DOESN'T MATCH PR# STAMPED ON |
| PLANS. REVISE AS REQUIRED. |
| |
| 3- ENERGY CALCS ARE GETTING THE CEILING |
| FAN CREDIT. THEREFORE, NEED TO SPECIFY |
| CEILING FAN SIZES IN THE ELECTRICAL |
| PLAN, INCLUDING FANS REQUIRED IN THE |
| GREAT ROOM. SEE TABLE 6-6 CHAPTER 13 FBC |
| |
| 4- ROOF FRAMING PLAN NEEDS TO BE REVISED |
| AT ENTRY PORCH AREA. CONCRETE BM DOESN'T |
| EXTEND ALL THE WAY BACK TO THE FOYER. |
| ALSO, REVISE THE KNEEWALL AT THE LEFT |
| HAND SIDE OF THE ROOF. IT'S NOT CONCRETE |
| BEAM. SEE PLANS AND REVISE FRAMING PLAN |
| AS REQUIRED AND SPECIFY CORRESPONDING |
| CONNECTOR. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 5- TRUSS ANCHOR SCHEDULE: REVISE NUMBER |
| OF NAILS FOR HUS26. SEE 2005 CATALOGUE. |
| |
| 6- PROVIDE PRODUCT APPROVAL FOR: |
| A)INSWING 1HR FIRE RATED DOOR AS SHOWN |
| AT ATRIUM.PRODUCT APPROVAL SUBMITTED IS |
| FOR "OUTSWING" APPLICATION. |
| |
| B) WINDOW MULLION SPECIED @ GREAT RM |
| FIXED WINDOWS. |
| |
| C) 12'-0" SLIDING GLASS DOORS. |
| |
| 7- SPECIFY MULLION SIZE AND ANCHORS FOR |
| FIXED WINDOWS AT GREAT ROOM. . SIZE |
| SPECIFIED ON WINDOW SCHEDULE DOESN'T |
| MEET THE CALCULATED DESIGN PRESSURES. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |