2005-09-13 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- ENERGY CALCS ARE GETTING THE CEILING |
| FAN CREDIT. NEED TO SPECIFY CEILING |
| SIZES IN THE ELECTRICAL PLAN, INCLUDING |
| FANS REQUIRED AT GREAT ROOM. SEE TABLE |
| 6-6 CHAPTER 13 FBC 2001. |
| |
| 3- ROOF FRAMING PLAN NEEDS TO BE REVISED |
| AT ENTRY PORCH AREA TO MATCH FOUNDATION |
| AND FLOOR PLAN. CONCRETE BEAM DOESN'T |
| EXTEND ALL THE WAY BACK TO THE FOYER. |
| CONCRETE BEAM IS ONLY AT ENTRY PORCH |
| AREA. REVISE ROOF FRAMING PLAN AS |
| REQUIRED AND SPECIFY CORRESPONDING |
| CONNECTORS. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 4- TRUSS ANCHOR SCHEDULE: REVISE NUMBER |
| OF NAILS SPECIFIED FOR CONNECTOR HUS26. |
| SEE 2005 CATALOGUE. |
| |
| 5- ONE HR FIRE RATED DOOR AT ATRIUM |
| PRODUCT APPROVAL SUBMITTED IS FOR |
| OUTSWING DOOR. PLANS SHOW INSWING DOORS. |
| REVISE AS REQUIRED. |
| |
| 6- SPECIFY MULLION SIZE AND ANCHORS FOR |
| FIXED WINDOWS AT GREAT ROOM. SIZE OF |
| MULLION SPECIFIED ON WINDOW SCHEDULE |
| DOESN'T RESIST THE CALCULATED DESIGN |
| PRESSURES. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 7- PROVIDE PRODUCT APPROVAL FOR WINDOW |
| MULLION SIZE AS SPECIFIED ABOVE. |
| |
| 8- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL (FLORIDA APPROVAL WAS NOT |
| SUBMITTED) FOR: |
| A) ROOF TILE. |
| B) SINGLE HUNG WINDOWS. |
| C) FIXED WINDOWS. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT (561)805-6712. |