Plan Review Details - Permit 05080235
Plan Review Stops For Permit 05080235
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-11-21 Cont ID  
Sent By shill Date 2005-11-21 Time 17:38 Rev Time 0.50
Received By shill Date 2005-11-21 Time 17:31 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-19 Cont ID  
Sent By shill Date 2005-09-19 Time 14:49 Rev Time 0.50
Received By shill Date 2005-09-19 Time 14:38 Sent To  
Notes
2005-09-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SEE PREVIOUS LIST.THE TITLE BLOCK
 IS NOT IN COMPLIANCE WITH
 FAC61G1-16.004, PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-14 Cont ID  
Sent By shill Date 2005-08-14 Time 10:11 Rev Time 0.50
Received By shill Date 2005-08-14 Time 10:11 Sent To FIRE
Notes
2005-08-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) THE ARCHITECT'S TITLE BLOCK IS TO BE
 IN COMPLIANCE WITH FAC61G1-16.003,004.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-11-15 Cont ID  
Sent By dpalmer Date 2005-11-15 Time 09:43 Rev Time 0.00
Received By dpalmer Date 2005-11-15 Time 09:38 Sent To  
Notes
2005-11-15 00:00:00COVER SHEET INDICATES 2004NEC , REDLINED
 2002 NEC.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-15 Cont ID  
Sent By dpalmer Date 2005-09-15 Time 11:13 Rev Time 0.00
Received By dpalmer Date 2005-09-15 Time 10:49 Sent To  
Notes
2005-09-15 00:00:00********** PROVISO/ REVISION *********
  
 1)NOTE: PLEASE REVISE LOAD CALCULATIONS
 AND ANY POSSIBLE CIRCUITING PER 220.3B4,
 PLEASE SEE RECESSED LTS NOT USED FOR
 GENERAL LIGHTING SHALL BE FIGURED AT MAX
 WATTAGE PER FIXTUREPER ABOVE.
 PLEASE SEE CIRCUITING MAY BE AFFECTED
 DUE THE WATTAGE PER CIRCUIT.
  
  
 PLEASE SUBMIT THE REVISED ITEMS ABOVE
 ALONG WITH ANY OTHER ELECTRICAL
 REVISIONS, BEFORE ROUGH ELECTRICAL
 INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-09 Cont ID  
Sent By dpalmer Date 2005-08-09 Time 20:33 Rev Time 0.25
Received By dpalmer Date 2005-08-09 Time 20:33 Sent To  
Notes
2005-08-09 00:00:00******** UNSAT ********
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCK AS REQUIRED UDNER FAC
 61G1-16.004.
 TITLE BLOCK MISSING THE "PRINTED NAME
 AND PRINTED LICENSE NUMBER" OF ARCHITECT
 OF RECORD.
 PLEAS KNOW THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE SUBMIT ELECTRICAL PLANS
 SHWOING A LAYOUT FOR ALL PROPOSED
 ELECTRICAL WORK.
 IF ALL EXISTING LOCATIONS, AND ALL WILL
 BE PLACED BACK, THEN PLEASE SHOW.
 PLEASE SEE THAT ANY AREAS OPENED UP WILL
 BE REQUIRED TO MEET THE 2002 NEC.
 PLEASE SEE AN ELECTRICAL CONTRACTOR IS
 SIGNED ON PERMIT APPLICATION.
  
 PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
 PLEASE BE SURE ALL OLD/VOIDED SHEETS ARE
 REVMOVED FROM SETS AND ONLY INSERT NEW
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STMAPING. ONE SET OF ANY OLD/VOIDED
 SHEETS SHALL BE SUBMITTED FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-11-15 Cont ID  
Sent By mwennerg Date 2005-11-15 Time 14:25 Rev Time 0.00
Received By mwennerg Date 2005-11-15 Time 14:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-21 Cont ID  
Sent By mwennerg Date 2005-09-21 Time 15:09 Rev Time 0.00
Received By mwennerg Date 2005-09-21 Time 15:09 Sent To  
Notes
2005-09-21 00:00:00******OK******
  
  
 PLANS STAMPED REF: FIRE SPRINKLER
 REMODEL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By mwennerg Date 2005-08-23 Time 09:15 Rev Time 0.00
Received By mwennerg Date 2005-08-23 Time 09:14 Sent To  
Notes
2005-08-23 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING FAC REQUIREMENT FOR ALL
 SHEETS.
  
 2) WILL THIS WORK IMPACT EXISTING FIRE
 SPRINKLER SYSTEM?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-17 Cont ID  
Sent By adarroug Date 2005-10-17 Time 10:01 Rev Time 0.00
Received By adarroug Date 2005-10-17 Time 10:01 Sent To  
Notes
2005-11-14 00:00:00TO "COMM" BD#13
2005-10-17 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-13 Cont ID  
Sent By adarroug Date 2005-09-13 Time 13:29 Rev Time 0.00
Received By adarroug Date 2005-09-13 Time 13:29 Sent To  
Notes
2005-09-13 00:00:00TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-14 Cont ID  
Sent By shill Date 2005-08-14 Time 10:15 Rev Time 0.00
Received By shill Date 2005-08-14 Time 10:15 Sent To FIRE
Notes
2005-08-14 00:00:00TOOK OFF OF BOARD; ROUTED TO MW'S DESK
 (FIRE)

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-13 Cont ID  
Sent By mwennerg Date 2005-08-23 Time 09:24 Rev Time 0.00
Received By adarroug Date 2005-08-04 Time 15:53 Sent To  
Notes
2005-08-05 00:00:00TO "COMM" BD#50
2005-08-04 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-23 Cont ID  
Sent By mwennerg Date 2005-08-23 Time 09:26 Rev Time 0.00
Received By mwennerg Date 2005-08-23 Time 09:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-23 Cont ID  
Sent By mwennerg Date 2005-08-23 Time 09:26 Rev Time 0.00
Received By mwennerg Date 2005-08-23 Time 09:26 Sent To  
Notes
***NONE***