Plan Review Details - Permit 05080141
Plan Review Stops For Permit 05080141
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-17 Cont ID  
Sent By jwitmer Date 2005-08-17 Time 13:23 Rev Time 0.44
Received By jwitmer Date 2005-08-17 Time 07:33 Sent To PC
Notes
2005-08-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080141
 ADD: 1555 PALM BEACH LAKES BLVD
 CONT:ANDREW'S ROOFING
 TEL: (561) 688-1066
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THIS BUILDING IS A HIGH RISE! PROVIDE
 A SITE PLAN INDICATING WHERE ON THIS
 BUILDING THIS SYSTEM IS TO BE USED.
  
 2) FROM PREVIOUS REVIEW, SPECIFY THE
 DECK MATERIAL, ANSWER IS " 5/8" CDX
 PLYWOOD SHEATHING BY OTHERS OVER
 EXISTING, NO PERMIT HAS BEEN APPPLIED
 FOR FOR THIS WORK. PROVIDE WHERE THIS
 WORK IS TO OCCUR, THIS IS A TYPEII
 BUILDING WHERE NO PLYWOODSHEATHING IS TO
 BE USED. IS THIS THE AREA OF GREENHOUSE
 LOCATED ON THE FIRST FLOOR? IF SO WHAT
 MATERIAL WIL MAKE UP THE ROOF DECK?
  
 3) THIS BUILDING BEING A HIGH RISE THE
 NEGATIVE PRESSURES ARE TAKEN FROM THE
 ROOF HEIGHT, ENGINEERED SYSTEM SHOWING
 ZONES 1,2 & 3.
  
 4) SINCE THIS BUILDING REQUIRES A 1HR
 RATED ROOF ASSEMBLY PROVIDE HOW THIS
 COMPLIANCE WILLBE ACHIEVED.
  
 5)THE SUBMITTED ROOF REPORT HAS LOW
 PRESSURES FOR END ZONE. TO BE AN
 ENGINEERED SYSTEM.
  
 6) 1507.5 METAL ROOF PANELS SLOPE
 MINIMUM OF A 3:12 SLOPE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-03 Cont ID  
Sent By rmcdouga Date 2005-08-03 Time 16:43 Rev Time 0.00
Received By rmcdouga Date 2005-08-03 Time 16:43 Sent To  
Notes
2005-08-03 00:00:00DENIED
  
 1) SPECIFY WHICH ONE OF THE APPROVED
 ASSEMBLIES FROM THE PRODUCT APPROVAL
 WILL BE INSTALLED.
  
 2) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE.
  
 3) SPECIFY THE DECK MATERIAL.
  
 4) ROOF PITCH SPECIFIED ON THE
 APPLICATION IS 1:12, THE MINIMUM SLOPE
 ALLOWED FOR THIS PRODUCT IS 2:12.
  
 5) SUBMIT SIGNED AND SEALED CALCULATIONS
 FROM A FLORIDA RESISTERED ENGINEER
 INDICATING THE REQUIRED DESIGN PRESSURES
 FOR THE ROOF OF THE STRUCTURE.
  
 6) SUBMIT SIGNED AND SEALED CALCULATIONS
 FROM A FLORIDA REGISTERED ENGINEER FOR
 INCREASED DESIGN PRESSURES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  