Plan Review Details - Permit 05080087
Plan Review Stops For Permit 05080087
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-08-09 Cont ID  
Sent By jhiggins Date 2005-08-09 Time 14:32 Rev Time 0.00
Received By rmcdouga Date 2006-09-05 Time 09:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2007-01-03 Cont ID  
Sent By rmcdouga Date 2007-01-03 Time 14:16 Rev Time 0.00
Received By rmcdouga Date 2007-01-03 Time 14:16 Sent To  
Notes
2007-01-03 14:17:45REVISED TRUSS LAYOUT AND DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2006-12-06 Cont ID  
Sent By rmcdouga Date 2006-12-06 Time 12:56 Rev Time 0.00
Received By rmcdouga Date 2006-12-06 Time 12:56 Sent To  
Notes
2006-12-06 12:56:38BUILDING REVISIONS TO STRUCTURAL PAGES S1, S2, S3 AND
 S6 ARE OK.FIRE PENETRATIONS AND CALKING DETAILS AND
 STAIR AND BALCONY RAIL SHOP DRAWINGS WERE SUBMITTED.
  
 PROVISO NOTE:
  
 ALTHOUGH SOME OF THE ACTUAL UPLIFTS SPECIFIED ON THE
 ROOF FRAMING PLAN ARE LESS THAN THOSE SHOWN ON THE
 TRUSS DRAWINGS,THE CONNECTORS SPECIFIED IN THE ANCHOR
 LEGEND ARE ADEQUATE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2006-09-21 Cont ID  
Sent By rmcdouga Date 2006-09-21 Time 12:17 Rev Time 0.00
Received By rmcdouga Date 2006-09-21 Time 12:17 Sent To  
Notes
2006-09-21 00:00:00DENIED BY BUILDING
  
 REVISION TO SHEET 6-A1 TO CHANGE FROM
 BATHROOMS FROM FAIR HOUSING
 SPECIFICATION "A" TO SPECIFICATION "B"
 IS DENIED. SEE PLUMBING REVIEW COMMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status N Date 2006-09-05 Cont ID  
Sent By rmcdouga Date 2006-09-05 Time 08:00 Rev Time 0.00
Received By rmcdouga Date 2006-09-05 Time 08:00 Sent To  
Notes
2006-09-05 00:00:00REVISION TO CHANGE ROOFING DENIED
  
 1) THE PRODUCT EVALUATION SUBMITTED FOR
 THE TILE ROOFING IS NOT THE ONE THAT
 CORRESPONDS WITH THE ONE LISTED ON THE
 STATE WEBSITE FOR FL560-R1. A MIAMI-DADE
 NOA IS LISTED.
  
 2) SPECIFY THE SPECIFIC FASTENER AND
 NUMBER OF FASTENERS PER TILE THAT WILL
 BE USED. HIGHLITE OR CIRCLE THE
 APPROPRIATE FASTENER ON THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-06-09 Cont ID  
Sent By rmcdouga Date 2006-06-09 Time 14:20 Rev Time 0.00
Received By rmcdouga Date 2006-06-09 Time 14:20 Sent To  
Notes
2006-06-09 00:00:00REVISED STRUCTURAL PAGES S1-S6 ARE OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-04-10 Cont ID  
Sent By rmcdouga Date 2006-04-10 Time 09:21 Rev Time 0.00
Received By rmcdouga Date 2006-04-07 Time 16:16 Sent To  
Notes
2006-04-07 00:00:00BUILDING PROVISO
  
 1) STRUCTURE IS LOCATED IN AN "AO" FLOOD
 ZONE. AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2) SUBMIT STRUCTURAL DRAWINGS FOR THE
 CONCRETE STAIRS.
  
 3) SUBMIT SHOP DRAWINGS FOR THE INTERIOR
 AND EXTERIOR GUARDRAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-02-17 Cont ID  
Sent By rmcdouga Date 2006-02-17 Time 07:25 Rev Time 0.00
Received By rmcdouga Date 2006-02-17 Time 07:25 Sent To  
Notes
2006-02-17 00:00:00DENIED
 (3RD REVIEW)
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "AO"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 3) ADDITIONAL PERMIT FEES ARE DUE. THE
 CALCULATED VALUE OF THE STRUCTURE IS
 $674,294.00. A WESTWARD EXPANSION FEE OF
 $750.00 PER UNIT IS ALSO REQUIRED.
  
 4)CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, A 'DECLARATION OF
 CONDOMINIUM' SHALL BE SUBMITTED TO THE
 STATE FOR APPROVAL, AND THEN RECORDED
 WITH THE CLERK OF THE COUNTY COURT.A
 RECORDED COPY SHALL BE SUBMITTED TO THE
 CITY FOR RECORDS, ADDRESSING PURPOSES,
 AND TO PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE PRIOR TO C.O.
  
 5)UNDER STRUCTURAL DESIGN CRITERIA ON
 S5, THE CORRECT EDITIONS OF THE
 REFERENCE STANDARDS ARE ACI 318-02 AND
 ACI 530.1-02. PLEASE CORRECT.
  
 6) SUBMIT SHOP DRAWINGS FOR THE
 EXTERIOR GUARDRAILS. SPECIFY THE
 ATTACHMENTS TO THE STRUCTURE.
  
 7) PROVIDE SHOP DRAWINGS WITH
 STRUCTURAL DETAILS FOR THE INTERIOR
 GUARDRAIL AT THE SECOND FLOOR STAIRWELL
 OPENING.
  
 8) THE CONSTRUCTION TYPE IS SPECIFIED AS
 TYPE V UNPROTECTED, UNSPRINKLERED. FBC
 2001 TABLE 600 REQUIRES EXTERIOR BEARING
 WALLS TO BE FIRE RATED BASED ON DISTANCE
 TO PROPERTY LINES OR ASSUMED PROPERTY
 LINES. SPECIFY THE REQUIRED FIRE RATINGS
 AND LOCATIONS OF THE RATED WALLS.
 PROVIDE DETAILS AND SECTIONS OF WALLS
 AND SPECIFY THE LISTED ASSEMBLIES FOR
 THE FIRE RATED WALLS.
  
 9) VERIFY THAT THE PERCENTAGE OF WALL
 AREA ALLOWED AS OPENINGS BY TABLE 600
 BASED ON DISTANCE TO THE PROPERTY LINE
 OR ASSUMED PROPERTY LINE IS NOT
 EXCEEDED.
  
 10) FBC 705 REQUIRES 3/4 HOUR OPENING
 PROTECTIVES FOR FIRE RATED EXTERIOR
 WALLS WITHIN 15' OF THE PROPERTY LINE.
 SPECIFY HOW COMPLIANCE WILL BE
 ACCOMPLISHED.
  
 11) PLEASE REVISE NOTE 8 ON SHEET A9
 SECTION 1626 IS ONLY APPLICABLE TO THE
 HVHZ. THE APPROPRIATE SECTION FOR AREAS
 OUTSIDE THE HVHZ, WHICH ARE IN THE
 WINDBOURNE DEBRIS REGION IS 1606.1.4.
 THIS SECTION REQUIRES GLAZING TO BE
 PROTECTED FROM WIND BOURNE DEBRIS.
  
 12) SUBMIT PRODUCT APPROVALS FOR
 STRUCTURAL WINDOW MULLIONS AND ROOF
 COVERING MATERIAL. SPECIFY WHICH METHOD
 OF ATTACHMENT WILL BE USED TO FASTEN THE
 ROOF TILES.
  
 13) ON SHEET A8GL THE 16' X 7' GARAGE
 DOOR HAS THE WRONG ID TAG.
  
 14) THE ROOF SHEATHING FASTENING NOTES
 ON S4 AND S5 ARE INCORRECT. CITY
 AMENDMENTS TO 2001 FBC TABLE 2306.1
 REQUIRE FASTENER SPACING TO BE 4"OC AT
 THE EDGES AND 6"OC INTERMEDIATE IN ROOF
 ZONE 3. PLEASE CORRECT.
  
 15) SPECIFY THE TRUSS CONNECTORS THAT
 WILL BE USED TO ATTACH THE TRUSSES
 ABOVE THE GARAGES TO THE ONE HOUR FIRE
 RATED TENANT SEPARATION WALLS. PROVIDE
 DETAILS AND SECTION. SEE SHEET S-2.
  
 16) SPECIFY THE TRUSS ANCHORS FOR THE
 THREE PLY (A12) GIRDERS AT THE EXTERIOR
 WALLS. TRUSS DRAWINGS SPECIFY 1795#
 UPLIFT. SEE SHEET S-3.
  
 17) THE OWNER/AGENT IS REQUIRED TO SIGN
 THE ENERGY CALC. FORMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-01-17 Cont ID  
Sent By rmcdouga Date 2006-01-17 Time 16:36 Rev Time 0.00
Received By rmcdouga Date 2006-01-17 Time 16:36 Sent To  
Notes
2006-01-20 00:00:00DENIED
 (2ND REVIEW)
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "AO"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 3) ADDITIONAL PERMIT FEES ARE DUE. THE
 CALCULATED VALUE OF THE STRUCTURE IS
 $674,294.00. A WESTWARD EXPANSION FEE OF
 $550.00 PER UNIT IS ALSO REQUIRED.
  
 4) THE SITE PLANS ARE REQUIRED WHICH
 SPECIFY THE DISTANCE TO ASSUMED PROPERTY
 LINES BETWEEN ADJACENT BUILDINGS LOCATED
 ON THE SAME LOT. THIS IS REQUIRED IN
 ORDER TO DETERMINE THE PERCENTAGE OF
 WALL AREA THAT IS ALLOWED AS OPENINGS BY
 FBC TABLE 600.
  
 5) SHEETS A1 AND A9 REFERENCE THE 2004
 FBC AND THE STRUCTURAL PLANS ARE ON THE
 2001 FBC. THE PLANS WERE REVIEWED TO THE
 2001 FLORIDA BUILDING CODE. PLEASE
 CORRECT THE CODE REFERENCE AND SECTIONS.
  
 6) THE CONSTRUCTION TYPE SPECIFIED ON
 SHEET 4-A1 IS FROM THE 2004 FBC. SPECIFY
 THE CONSTRUCTION TYPE FROM THE 2001 FBC.
  
 7)CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, A 'DECLARATION OF
 CONDOMINIUM' SHALL BE SUBMITTED TO THE
 STATE FOR APPROVAL, AND THEN RECORDED
 WITH THE CLERK OF THE COUNTY COURT.A
 RECORDED COPY SHALL BE SUBMITTED TO THE
 CITY FOR RECORDS, ADDRESSING PURPOSES,
 AND TO PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE PRIOR TO C.O.
  
 8) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 9)UNDER STRUCTURAL DESIGN CRITERIA ON
 S5, THE CORRECT EDITIONS OF THE
 REFERENCE STANDARDS ARE ACI 318-02 AND
 ACI 530.1-02. PLEASE CORRECT.
  
 10) SPECIFY THE METHOD OF TERMITE
 PROTECTION THAT WILL BE USED AS REQUIRED
 BY FBC 1816.
  
 11)PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. PLEASE
 SUBMIT THE FLORIDA PRODUCT APPROVAL
 COVERSHEET WITH THE APPROPRIATE FL # AND
 THE CORRESPONDING PRODUCT EVALUATION AND
 INSTALLATION INSTRUCTIONS AS LISTED WITH
 THE STATE ON THE PRODUCT APPROVAL
 WEBSITE.
  
 12) SPECIFY HOW IMPACT PROTECTION WILL
 BE PROVIDED FOR THE GLAZED OPENINGS AS
 REQUIRED BY FBC 1606.1.4. ITEM #13 OF
 THE CITY OF WPB IMPLEMENTATION STANDARD
 FOR HURRICANE MISSLE IMPACT PROTECTION
 REQUIRES PRE-STORM PREPARATION PLANS TO
 BE SUBMITTED FOR REVIEW IF USING STORM
 SHUTTERS. A KEY PLAN, INSTALLATION
 SCHEDULE AND PRODUCT APPROVALS ARE ALSO
 REQUIRED. NOTE: STORM PANELS ARE NOT
 ALLOWED ABOVE THE FIRST FLOOR FOR THIS
 TYPE OF STRUCTURE AND OCCUPANCY.
  
 13) SUBMIT THE EVALUATION REPORT AND
 INSTALLATION INSTRUCTIONS FROM NATIONAL
 ACCREDITATION ANS MANAGEMENT INSTITUTE
 FOR THE THERMA-TRU DOORS WITH FL # 1170.
 THE INFORMATION THAT WAS SUBMITTED TO
 THE STATE FOR STATE PRODUCT APPROVAL IS
 REQUIRED TO BE SUBMITTED WITH THE STATE
 COVER SHEET.
  
 14) SUBMIT PRODUCT APPROVAL FOR THE
 SMALL (8' X 7') OVERHEAD GARAGE DOOR
 WHICH IS LESS THAN THE MINIMUM SIZE
 ALLOWED BY THE PRODUCT APPROVAL FOR THE
 LARGE DOOR THAT WAS SUBMITTED.
  
 15) SUBMIT PRODUCT APPROVALS FOR THE
 TRUSS CONNECTORS.
  
 16) THE ENGINEER IS REQUIRED TO SIGN HIS
 NAME TO THE PLANS HE SEALS PER FAC
 61G15-23.002. PLEASE SUBMIT A NOTARIZED
 LETTER SIGNED, SEALED AND DATED BY THE
 ENGINEER ATTESTING HIS LEGAL SIGNATURE.
  
 17) SUBMIT SIGNED AND SEALED TRUSS
 DRAWINGS AND LAYOUTS THAT HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD FOR THE STRUCTURE.
  
 18) SUBMIT SHOP DRAWINGS FOR THE
 EXTERIOR GUARDRAILS. SPECIFY THE
 ATTACHMENTS TO THE STRUCTURE.
  
 19) PROVIDE SHOP DRAWINGS WITH
 STRUCTURAL DETAILS FOR THE INTERIOR
 GUARDRAIL AT THE SECOND FLOOR STAIRWELL
 OPENING.
  
 20) THE STRUCTURAL PLANS DO NOT SHOW THE
 ELEVATOR RECESSES OR THE ELEVATOR
 OPENINGS AT THE SECOND FLOOR. SUBMIT
 STRUCTURAL DETAILS FOR THESE AREAS.
  
 21) PROVIDE STRUCTURAL DETAILS FOR THE
 INFILL FLOOR FRAMING AT THE ELEVATOR
 RECESSES AND OPENINGS WHEN THE CLOSET
 OPTION IS USED IN LEIU OF THE ELEVATOR.
 SEE DETAILS 6 AND 7 ON A11.
  
 22) ON SHEET A7GL THE DOOR TO THE
 ELEVATOR HAS I.D. MARK #11 WHICH
 ACCORDING TO THE DOOR SCHEDULE ON A9 IS
 A 16' X 7' GARAGE DOOR. PLEASE CORRECT.
  
 23) THE 16' X 7' GARAGE DOOR ON SHEETS
 A8GR AND A8GL HAVE THE WRONG ID MARKS.
 PLEASE CORRECT.
  
 24) THE SCALE FOR SHEET A4 LISTED IN THE
 DRAWING INDEX ON A1 IS INCORRECT. PLEASE
 CORRECT.
  
 25) THE WALL SECTION ON A13 SITES FBC
 SECTIONS 2507.3 THRU 2507.5. THESE
 SECTIONS DO NOT APPLY TO METAL LATH AND
 THEY ARE REQUIREMENTS FOR THE HIGH
 VELOCITY HURRICANE ZONE ONLY (DADE AND
 BROWARD COUNTIES). PLEASE CORRECT.
  
 26) THE 5' WIDE BI-PASS DOOR (#7 IN
 SCHEDULE) SPECIFIED FOR HER WALK-IN
 CLOSET DOES NOT COMPLY WITH FAIR HOUSING
 REQUIREMENTS. CLOSET DOORS THAT REQUIRE
 USERS TO PASS THROUGH THE DOORWAY TO
 REACH THE CONTENTS ARE REQUIRED TO
 PROVIDE AT LEAST A 31-5/8" CLEAR
 OPENING.
  
 27) NOTE 3 ON SHEET S5 UNDER PLYWOOD
 ROOF DIAPHRAGM CONFLICTS WITH THE ROOF
 NAILING SPECIFIED ON S4. CITY AMENDMENTS
 TO FBC TABLE 2306.1 REQUIRE 8D RING
 SHANK NAILS AT 4"OC AT EDGES AND 6"OC
 INTERMEDIATE IN ZONE 3 FOR MEAN ROOF
 HEIGHTS OF 25'-35'.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2006-01-12 Cont ID  
Sent By rmcdouga Date 2006-01-12 Time 07:28 Rev Time 0.00
Received By rmcdouga Date 2006-01-12 Time 07:27 Sent To  
Notes
2006-01-12 00:00:00NOTE:
  
 DID NOT COMPLETE REVIEW. ARCHITECTURAL
 PLANS WERE CHANGED FROM 2001 TO 2004
 EDITION OF FBC, WITHOUT CHANGING
 STRUCTURAL PLANS. PER PHONE CONVERSATION
 WITH SANDY AT LENNAR, NEW ARCH SHEETS
 WILL BE BROUGHT IN DESIGNED TO 2001 FBC
 CODE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-12 Cont ID  
Sent By rmcdouga Date 2005-09-08 Time 16:14 Rev Time 0.00
Received By rmcdouga Date 2005-09-08 Time 16:14 Sent To  
Notes
2005-09-08 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "AO"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 3) ADDITIONAL PERMIT FEES ARE DUE. THE
 CALCULATED VALUE OF THE STRUCTURE IS
 $674,294.00. A WESTWARD EXPANSION FEE OF
 $550.00 PER UNIT IS ALSO REQUIRED.
  
 4) THE SITE PLANS ARE REQUIRED WHICH
 SPECIFY THE DISTANCE TO ASSUMED PROPERTY
 LINES BETWEEN ADJACENT BUILDINGS LOCATED
 ON THE SAME LOT. THIS IS REQUIRED IN
 ORDER TO DETERMINE THE PERCENTAGE OF
 WALL AREA THAT IS ALLOWED AS OPENINGS BY
 FBC TABLE 600.
  
 5) THESE UNITS DO NOT MEET THE
 DEFINITION OF TOWNHOUSE IN THE 2001
 FLORIDA BUILDING CODE. PLEASE REMOVE THE
 TITLE OF TOWNHOMES FROM THE TITLE BLOCKS
 OF THE M.E.P. DRAWINGS.
  
 6) SPECIFY THE SCALE OF THE DRAWINGS ON
 THE PLANS.
  
 7) SPECIFY THE OCCUPANCY, CONSTRUCTION
 TYPE, PROTECTED OR UNPROTECTED AND
 SPRINKLERED OR UNSPRINKLERED.
  
 8)CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, A 'DECLARATION OF
 CONDOMINIUM' SHALL BE SUBMITTED TO THE
 STATE FOR APPROVAL, AND THEN RECORDED
 WITH THE CLERK OF THE COUNTY COURT.A
 RECORDED COPY SHALL BE SUBMITTED TO THE
 CITY FOR RECORDS, ADDRESSING PURPOSES,
 AND TO PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE PRIOR TO C.O.
  
 9) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 10) FBC 705.1.3.2.1 CLASSIFIES FIRE
 DOORS AS 3 HOUR, 1-2/2 HOUR, 1 HOUR, 3/4
 HOUR OR 20 MINUTE. REVISE THE 'C' LABEL
 DOOR SPECIFIED ON SHEET A9. FBC
 705.1.3.2.2 ALLOWS 20 MINUTE RATED DOORS
 IN WALLS REQUIRED TO HAVE A FIRE
 RESISTANCE RATING OF 1 HOUR OR LESS.
  
 11) FBC 705.1.3.5 REQUIRES FIRE DOORS TO
 BE EQUIPED WITH AN APPROVED CLOSER.
  
 12) PROVIDE A ROOF SHEATHING NAILING
 PLAN FOR THE LOWER ROOFS THAT ARE NOT
 SHOWN ON S4.
  
 13) THE SPACING OF THE TAPCON FASTENERS
 FOR THE GARAGE DOOR HEADER IN DETAIL 1
 ON S4 APPEAR TO CONFLICT. 16"OC IS
 SPECIFIED IN ONE PLACE AND 8" OC IS
 SPECIFIED UNDER NOTES. PLEASE CORRECT.
  
 14) FBC TABLE 1604.1 REQUIRES THE BOTTOM
 CORD LIVE LOAD TO BE 10 PSF FOR ATTICS
 WITHOUT STORAGE AND 30 PSF FOR ATTICS
 WITH STORAGE. REVISE ROOF LOADS ON S5.
  
 15) UNDER GENERAL NOTES ON S5, ITEM # 24
 SPECIFIES THE WRONG EDITIONS OF ACI,
 ASCE 5 AND TMS. THE 2002 EDITIONS ARE
 REFERENCED IN CHAPTER 35 OF THE 2001 FBC
  
 16) UNDER STRUCTURAL DESIGN CRITERIA ON
 S5, THE CORRECT EDITIONS OF THE
 REFERENCE STANDARDS ARE ACI 318-02 AND
 ACI 5301-02.
  
 17) THE EXTERIOR WALL SECTION 5 ON S6
 SPECIFIES 6" FROM THE TOP OF THE
 MONOLITHIC SLAB TO FINISH GRADE. THIS
 WILL NOT ALLOW THE BOTTOM OF THE 16"
 DEEP FOOTER TO BE A MINIMUM 12" BELOW
 FINISH GRADE AS REQUIRED BY FBC 1804.1.3
  
 18) THE ROOF PITCH ON THE WALL SECTION 5
 ON S6 IS SPECIFIED AS 5/12 AND THE
 ELEVATIONS ON A4 SPECIFY 4/12.
  
 19) THE UL SYSTEM SPECIFIED FOR THE ONE
 HOUR FIRE RATED TENANT SEPARATION WALLS
 "U 907" IS FOR NONBEARING WALLS ONLY.
 PLEASE SPECIFY A SYSTEM FOR BEARING
 WALLS.
  
 20) THE DRAWINGS ARE MISLABELED ON SHEET
 A7GR. THEY SHOULD BE GARAGE RIGHT.
  
 21) PROVIDE A DETAIL OF THE GUARDRAILS
 AT THE OPEN SIDE OF THE STAIRS (LOWER
 SECTION). SEE FBC 1015.
  
 22) PROVIDE AN AREA TABULATION TABLE
 LISTING THE FIRST AND SECOND FLOOR A/C
 AREAS AND UNCONDITIONED AREAS FOR EACH
 UNIT AND THE TOTALS FOR THE STRUCTURE.
  
 23) THE ELEVATORS ARE REQUIRED TO COMPLY
 WITH ASME A17.1 AND ANSI A117.1 (FAIR
 HOUSING).
  
 24) SPECIFY METHOD OF TERMITE PROTECTION
 AS REQUIRED BY FBC 1816.
  
 25)PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 24) SPECIFY HOW IMPACT PROTECTION WILL
 BE PROVIDED FOR THE GLAZED OPENINGS AS
 REQUIRED BY FBC 1606.1.4. ITEM #13 OF
 THE CITY OF WPB IMPLEMENTATION STANDARD
 FOR HURRICANE MISSLE IMPACT PROTECTION
 REQUIRES PRE-STORM PREPARATION PLANS TO
 BE SUBMITTED FOR REVIEW IF USING STORM
 SHUTTERS, IN ADDITION TO A KEY PLAN,
 INSTALLATION SCHEDULE AND PRODUCT
 APPROVALS. STORM PANELS ARE NOT ALLOWED
 ABOVE THE FIRST FLOOR FOR THIS TYPE OF
 STRUCTURE AND OCCUPANCY.
  
 25) SUBMIT THE EVALUATION REPORT AND
 INSTALLATION INSTRUCTIONS FROM NATIONAL
 ACCREDITATION ANS MANAGEMENT INSTITUTE
 FOR THE THERMA-TRU DOORS WITH FL # 1170.
 THE INFORMATION THAT WAS SUBMITTED TO
 THE STATE FOR STATE PRODUCT APPROVAL IS
 REQUIRED TO BE SUBMITTED WITH THE STATE
 COVER SHEET.
  
 26) SUBMIT PRODUCT APPROVAL FOR THE
 SMALL (8' X 7') OVERHEAD GARAGE DOOR
 WHICH IS LESS THAN THE MINIMUM SIZE
 ALLOWED BY THE PRODUCT APPROVAL FOR THE
 LARGE DOOR THAT WAS SUBMITTED.
  
 27) SUBMIT PRODUCT APPROVALS FOR THE
 TRUSS CONNECTORS.
  
 28) THE ENGINEER'S FIRM # IS REQUIRED TO
 BE LISTED IN THE TITLE BLOCK. SEE FAC
 61G15-23.002.
  
 29) THE ENGINEER IS REQUIRED TO SIGN HIS
 NAME TO THE PLANS HE SEALS PER FAC
 61G15-23.002. PLEASE SUBMIT A NOTARIZED
 LETTER SIGNED, SEALED AND DATED BY THE
 ENGINEER ATTESTING HIS LEGAL SIGNATURE.
  
 30) THE ARCHITECT IS REQUIRED TO
 PERSONALLY SIGN ALL DOCUMENTS SEALED BY
 HIM PER FAC 61G1-16.003. PLEASE SUBMIT A
 NOTARIZED LETTER SIGNED, SEALED AND
 DATED BY THE ARCHITECT ATTESTING HIS
 LEGAL SIGNATURE.
  
 31) SHOW COMPLIANCE WITH THE FAIR
 HOUSING ACT. ALL BUILDING ENTRANCES ARE
 REQUIRED TO BE ACCESSIBLE AND BE ON AN
 ACCESSIBLE ROUTE.
 - THE PRIMARY ENTRANCE DOOR MUST MEET
 THE REQUIREMENTS FOR ACCESSIBLE DOORS
 (32" CLEAR OPENING, LOW OR NO THRESHOLD-
 3/4"MAX, HARDWARE COMPLYING WITH ANSI
 4.13.9, ETC.)
 - DOORS WITHIN UNITS MUST BE USEABLE
 DOORS. MUST PROVIDE AT LEAST A 31-5/8"
 CLEAR OPENING.
 - CLOSET DOORS THAT REQUIRE USERS TO
 PASS THROUGH THE DOORWAY TO REACH THE
 CONTENTS MUST HAVE DOORS THAT PROVIDE AT
 LEAST 32 INCHES NOMINAL CLEAR OPENING.
 - LIGHT SWITCHES, ELECTRICAL OUTLETS,
 THERMOSTATS AND CONTROLS SHALL BE IN
 ACCESSIBLE LOCATIONS.
 - INDICATE THE MINIMUM CLEAR FLOOR
 SPACES AT THE FIXTURES AND APPLIANCES IN
 THE KITCHENS.
 - THE FAIR HOUSING ACT REQUIRES THE
 BATHROOMS TO BE DESIGNED TO COMPLY WITH
 SPECIFICATION "A" OR "B" BATHROOMS.
 INDICATE WHICH ONE WILL BE USED AND SHOW
 COMPLIANCE WITH DESIGN METHOD SELECTED.
  
 32) SUBMIT SIGNED AND SEALED TRUSS
 DRAWINGS AND LAYOUTS THAT HAVE BEEN
 REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD FOR THE STRUCTURE.
  
 33) PROVIDE STRUCTURAL DETAILS FOR THE
 CONCRETE STAIRS. SPECIFY THE LOCATION
 AND SIZE OF STEEL REINFORCEMENT IN THE
 LANDINGS, STAIRS AND AT TOP AND BOTTOM
 LOAD POINTS.
  
 34) SUBMIT SHOP DRAWINGS FOR THE
 EXTERIOR GUARDRAILS. SPECIFY THE
 ATTACHMENTS TO THE STRUCTURE.
  
 35) PROVIDE STRUCTURAL DETAILS OF THE
 INTERIOR GUARDRAIL AT THE SECOND FLOOR
 STAIRWELL OPENING.
  
 36) THE STRUCTURAL PLANS DO NOT SHOW THE
 ELEVATOR RECESSES OR THE ELEVATOR
 OPENINGS AT THE SECOND FLOOR. SUBMIT
 STRUCTURAL DETAILS FOR THESE AREAS.
  
 37) PROVIDE STRUCTURAL DETAILS FOR THE
 INFILL FLOOR FRAMING AT THE ELEVATOR
 RECESSES AND OPENINGS WHEN THE CLOSET
 OPTION IS USED IN LEIU OF THE ELEVATOR.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-01-06 Cont ID  
Sent By dpalmer Date 2007-01-06 Time 18:01 Rev Time 0.00
Received By dpalmer Date 2007-01-06 Time 17:50 Sent To  
Notes
2007-01-06 18:05:40PLANS REDLINED.
  
 SEPARATE PERMIT REQUIRED FOR LV SPEAKER WIRING. MAY
 REFERENCE BACK TO THESE PLANS FOR THE LOCATIONS,
 HOWEVER NEEDS TO BE A SEPARATE PERMIT FOR LV SPKRS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-13 Cont ID  
Sent By dpalmer Date 2006-09-13 Time 18:32 Rev Time 0.00
Received By dpalmer Date 2006-09-13 Time 18:32 Sent To PC
Notes
2006-09-13 00:00:00ENGINEER BROUGHT IN NEW ELECTRICAL
 SHEETS AND MADE CORRECTIONS ON 9/7/06
 PREVIOUSELECTRICAL REV'S WERE PLACED
 ON "HOLD" BY THE ENGINEER AND CONTRACTOR
 WAS NOTIFIED.
  
  
 REV STAMPED

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-05 Cont ID  
Sent By dpalmer Date 2005-12-05 Time 14:38 Rev Time 0.00
Received By dpalmer Date 2005-12-05 Time 13:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-26 Cont ID  
Sent By dpalmer Date 2005-08-26 Time 11:12 Rev Time 3.00
Received By dpalmer Date 2005-08-24 Time 17:51 Sent To  
Notes
2005-08-26 00:00:00***********UNSAT ************
  
 BLDG #1.
  
  
 1)NOTE: PLEASE CHECK AND VERIFY ALL SETS
 AND CORRECT SHEETS. PLEASE SEE ONE SET
 DOES NOT CONTAIN THE CORRECT 2NR FLR
 PLAN. (BLDG #2).
  
 2)NOTE: PLEASE SEE APPLICATION SHOWS
 THESE BEING SUBMITTED AS "TOWNHOUSES"??
 PLEASE SEE BUILDING REVIEW COMMENTS.
 THESE DO NOT SEEM TO BE CONSIDERED TRUE
 "TOWNHOUSES" AS DEFINED UNDER THE FBC.
 PLEASE SEE PALM BEACH COUNTY IMPACT FEE
 STAMPED INDICATES BUILDINGS AS 4 AND 6
 UNIT MULTI FAMILY DWELLINGS.
  
 PLEASE SEE THE FOLLOWING COMMENT FOR
 ELECTRICAL SERVICE.
  
 3)NOTE: PLEASE SEE DUE TO THESE NOT
 BEING CONSIDERED AS TOWNHOUSES WITH
 SEPARATE PROPERTY LINES, FEE SIMPLE ETC.
 ONLY ONE ELECTRICAL SERVICE WILL BE
 PERMITTED. PLEASE SEE GROUPING OF MAINS
 WILL BE REQUIRED FOR ALL FOUR UNITS IN
 THIS BLDG UNDER ONE SERVICE.
 PLEASE ADJUST SIZE OF SERVICE
 ACCORDINGLY. (SEC'S, GROUNDING,
 CONDUITS, ETC.
 230.2,230.70,230.72,240.4,310.16
  
 4)NOTE: PLEASE SEE MISSING AREAS FOR
 EGRESS LIGHTING. PLEASE SEE SOME AREAS
 WHERE AS "J-BOX" IS SHOWN, A LT FIXTURE
 OFSOME TYPE WILL BE REQUIRED. PLEASE
 SEE ENTRIES, TERRACE(1ST FLR) LIV RMS,
 KITCHENS ETC.
 PLEASE SEE 2-STORY UNITS, A 3-WAY OR
 4-WAY SWITCH WILL BE REQUIRED AT THE
 LANDINGS LOCATED IN BETWEEN FLRS.
 THIS IS ALSO REQUIRED FROM 210.70,LS 101
 5-8
  
 5)NOTE: PLEASE SEE MISSING SMOKE
 DETECTORS FOR AREAS LEADING TO FLR
 ABOVE. PLEASE SEE ENTRY FOYER'S FOR
 2-STORY UNITS. NFPA-72 8-1.4.1.6.2
 PLEASE ALSO SEE SD'S FOR MASTER BEDRM
 SHALL BE MOED "INTO" BEDRM AREA. PLEASE
 SEE ALL SD'S ARE TO BE INSTALLED WITHIN
 3' OF THE PEAK IN A SLOPE CEILING AND IN
 TRAY/ELEVATED CEILINGS WITHIN 12" OF MAX
 CEILING HEIGHT.
 NFPA-72 CHAPTER 2.
 PLEASE SEE SD'S ARE TO BE LOCATED NO
 CLOSER THAN 3' TO ANY KITCHEN OR BATH
 DOOR. AND 5' TO A RETURN AIR GRILL.
 NFAP-72 8-1.4.2
 PLEASE SEE SOME OF THESE HAVE BEEN
 REDLINED ON ONE SET OF PLANS.
  
 6)NOTE: PLEASE SEE SD'S ARE CIRCUITED TO
 KITCHEN/DINING LTS. THIS IS OK, HOWEVER
 PLEASE KNOW, THIS CIRCUIT WOULD BE ARC
 FAULT PROTECTED. PLEASE SEE THIS MEANS
 KITCHEN AND DINING RM LTS AS SHOWN WOULD
 BE INDICATED AS AFCI.
 PLEASE SEE SD'S MAY BE ON AN EXISITNG
 BEDRM ARC FAULT PROTECTED CIRCUIT.
 210.12, 2002 NEC.
  
 7)NOTE: PLEASE VERIFY OF GFI SHOWN IN
 KITCHEN IS "IN" THE PANTRY? PLEASE SEE
 KITCHENS WHEREPANTRY IS NOT SHOWN, AND
 A COUNTERSPACE IS ALSO NOT INDICATED??
  
 8)NOTE: PLEASE SEE MISSING GFI RECEPTS
 AND LTS FOR ELEVATOR PITAND EQUIPMENT
 SPACE. EACH SHALL CONTAIN DEDICATED
 CIRCUITS PER 620.23,620.24
  
 9)NOTE: PLEASE SEE PANEL "A" LOCATED IN
 UNIT, HOWEVER PANEL SCHEDULES INDICATES
 PANEL LOCATION IN GARAGE.
  
 PLEASE SEE MANY OF THE ABOVE ITEMS WERE
 REDLINED ON PLANS FOR AREAS OF NOTES.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS, WHICH MAY AFFECT
 ELECTRICAL PLANS. (BLDG).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-08-24 00:00:00IN ELECTRICAL FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-08-09 Cont ID  
Sent By mamini Date 2005-08-09 Time 09:00 Rev Time 0.50
Received By mamini Date 2005-08-09 Time 09:00 Sent To  
Notes
2005-08-09 00:00:00PASSED:
  
 1. SEE PERMIT# 05070365FOR
 UNDERGROUND UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-25 Cont ID  
Sent By mawillia Date 2007-01-25 Time 14:51 Rev Time 0.00
Received By mawillia Date 2007-01-25 Time 14:51 Sent To  
Notes
2007-01-25 14:55:33*****APPROVED*****
  
  
 REVISED E-1 SHEETS (HOME -101, 102, 201, AND 202) WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-16 Cont ID  
Sent By mwennerg Date 2005-12-16 Time 09:34 Rev Time 0.00
Received By mwennerg Date 2005-12-16 Time 09:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-28 Cont ID  
Sent By mwennerg Date 2005-09-28 Time 14:21 Rev Time 0.00
Received By mwennerg Date 2005-09-28 Time 14:21 Sent To  
Notes
2005-09-28 00:00:00******DENIED******
  
 1) ADDRESS IS REQUIRED ON EACH BUILDING.
 IT SHALL BE A MINIMUM OF 3" AND
 CONTRASTING TO THE BACKGROUND.
  
 2) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDS.
  
 3) ARE THESE BUILDINGS FIRE SPRINKLERED?
  
  
 4) FIRE HYDRANTS SHALL BE WET BEFORE,
 DURING AND AFTER CONSTRUCTION.
  
 5) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED FOR EACH UNIT.
  
 6) ELEVATORS SHALL COMPLY WITH A.S.M.E
 A-17.1.
  
 7) PLEASE USE THE 2003 EDITION WHEN
 REFERENCING NFPA 101. SHT 4-A9.
  
 8) SMOKE DETECTORS SHALL BE ARRANGED
 WHERE ACTIVATION OF ONE CAUSES ALL IN
 THE UNIT TO SOUND.
  
 9) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 10) STAIRS TO COMPLY WITH NFPA 101,
 SECTION 7.2.2.
  
 11) SMOKE DETECTORS TO BE INSTALLED A
 MINIMUM OF 3' FROM HVAC DIFFUSERS.
  
 12) PLEASE SEE SOME OF THE SMOKE
 DETECTORS NEAR #2 BEDROOMS APPEAR TO
 CLOSE TO THE BATHROOM.
  
 13) HANDRAILS REQUIRED ON BOTH SIDES OF
 STAIRS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 17:30 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 17:30 Sent To B
Notes
2006-12-17 17:30:15TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-12-14 Cont ID  
Sent By adarroug Date 2006-12-14 Time 15:14 Rev Time 0.00
Received By adarroug Date 2006-12-14 Time 15:14 Sent To  
Notes
2007-01-06 17:51:33TO COMM BOARD #20
2006-12-14 15:19:12WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-11-20 Cont ID  
Sent By adarroug Date 2006-11-20 Time 09:18 Rev Time 0.00
Received By adarroug Date 2006-11-20 Time 09:18 Sent To M
Notes
2006-11-20 09:19:29TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-01 Cont ID  
Sent By adarroug Date 2006-09-01 Time 08:18 Rev Time 0.00
Received By adarroug Date 2006-09-01 Time 08:18 Sent To E
Notes
2006-09-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 15:10 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 15:10 Sent To B
Notes
2006-08-12 00:00:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 15:57 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 15:56 Sent To B
Notes
2006-06-08 00:00:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-01 Cont ID  
Sent By adarroug Date 2006-01-31 Time 13:53 Rev Time 0.00
Received By adarroug Date 2006-01-31 Time 14:51 Sent To  
Notes
2006-01-31 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-10-14 Time 16:09 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 16:09 Sent To  
Notes
2005-10-14 00:00:00TO "COMM" BD#30/PLANS ON RACK/11 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-07 Cont ID  
Sent By rmcdouga Date 2005-09-08 Time 10:57 Rev Time 0.00
Received By rmcdouga Date 2005-08-03 Time 13:23 Sent To  
Notes
2005-08-08 00:00:00TO "COMM" BD#16/PLANS AND ROLLS ON RACK
2005-08-03 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-01-22 Cont ID  
Sent By pkrauss Date 2007-01-22 Time 07:30 Rev Time 0.00
Received By pkrauss Date 2007-01-22 Time 07:30 Sent To  
Notes
2007-01-22 08:13:28DENIED: UNITS 101 & 102 ONLY
  
 REVISION TO UNITS 101, 102, 201, & 202 - PLANS INDICATE
 REVISING THE DUCT BOARD & FLEX DUCT TO R-4 FROM R-6 IN
 UNITS 101 & 102.PLANS CAN NOT BE APPROVED WITHOUT
 REVISING THE ENERGY CALCULATIONS.LETTER INDICATES
 REVISED ENERGY CALCUALTIONS THAT ARE NOT WITH THE
 SUBMITTAL PACKAGE.
  
 PLANS FOR UNITS 201 & 202 ARE APPROVED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-11-27 Cont ID  
Sent By rregueir Date 2006-11-27 Time 18:48 Rev Time 0.00
Received By rregueir Date 2006-11-27 Time 17:59 Sent To  
Notes
2006-11-27 18:49:32MECH RE SEPERATED, STRUCTURAL SENT TO RMC

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-21 Cont ID  
Sent By pkrauss Date 2006-01-21 Time 07:25 Rev Time 0.00
Received By pkrauss Date 2006-01-21 Time 07:25 Sent To  
Notes
2006-01-21 00:00:00PROVISO:BUILDING #1/4 UNITS
  
 UNIT #201 & 202 INDICATE 5 TON UNIT,
 PER 2001 FMC 606.2.2 OR 606.4, FAN
 SHUTDOWN REQUIRED BY DUCT SMOKE DETECTOR
 OR BY AREA SMOKE DETECTORS.PLEASE
 SUBMIT WHICH METHOD WILL BE USED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
 PER CONVERSATION WITH MIKE WILLIAMS
 (LENNAR), M-2 PAGE INDICATES EQUIPMENT
 SCHEDULE & WILL BE SUBMITTED FOR REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-13 Cont ID  
Sent By pkrauss Date 2005-09-13 Time 06:56 Rev Time 0.00
Received By pkrauss Date 2005-09-13 Time 06:56 Sent To  
Notes
2005-09-13 00:00:00DENIED:BUILDING 1 (4 UNIT)
 UNIT#101
 1.PLEASE CLARIFY ELEVATION & DISTANCE
 OF THE TERMINATION OF THE EXHAUST FROM
 THE GARAGE IN RELATION TO THE WINDOW
 FROM BEDROOM #2.PER 2001 FBC(M)
 401.5.1, NOXIOUS EXHAUST SHALL BE
 TERMINATED A MINIMUM OF 10 FT FROM FRESH
 AIR INTAKES (I.E. DOORS OR WINDOWS).
 EXHAUST SHALL TERMINTE IN SUCH A MANNER
 AS NOT TO BE RECIRCULATED, 2001 FBC(M)
 501.3.
  
 2.RETURN AIR JUMPER FROM THE MASTER
 BEDROOM ARE NOT SIZED PROPERLY. THE
 MASTER BEDROOM SHALL BE A MINIMUM OF 15"
 ROUND, 10" X 19", OR EQUAL TO.
  
 3.PLAN SHEET M-1 INDICATES 4" O.A.
 DUCT CONNECTING TO THE RETURN AIR PLENUM
 BOX BELOW THE AHU.THE DETAIL ON PLAN
 SHEET M-2, AHU MOUNTING DETAIL DOES NOT
 REFLECT THE RETURN AIR PLENUM BOX.THE
 DETAIL INDICATES AN AUXILIARY DRAIN PAN
 IN THE RETURN AIR PLENUM?PLEASE
 CLARIFY.SHOULD THE AHU CLOSET BE THE
 RETURN AIR PLENUM, ALL COMPONENTS OF THE
 CLOSET SHALL COMPLY WITH 2001 FBC(M)
 602.2.1 & 2001 FBC CHAPTER 13 SUB
 CHAPTER 610.1.ABC.3.7.
  
 UNIT #102
 1.SEE COMMENT #1 FOR UNIT 101
 2.RETURN AIR FROM THE MASTER SUITE IS
 BOARDER LINE, SHOULD BE INCREASED TO 10"
 X 17" RECTANGLE OR EQUAL.
 3.SEE COMMENT #3 FOR UNIT 101.
  
 UNIT #201
 1.RETURN AIR NOT REQUIRED FROM THE
 LAUNDRY ROOM AREA.
 2.SEE COMMENT #3 FOR UNIT 101.
 3.FAN SHUTDOWN REQUIRED IN ACCORDANCE
 WITH 2001 FBC(M)606.2.1 & 606.4.1.
  
 UNIT 202
 1. RETURN AIR NOT REQUIRED FROM THE
 LAUNDRY ROOM AREA.
 2.SEE COMMENT #3 FOR UNIT 101.
 3.FAN SHUTDOWN REQUIRED IN ACCORDANCE
 WITH 2001 FBC(M)606.2.1 & 606.4.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 5 Status F Date 2006-09-19 Cont ID  
Sent By kstevens Date 2006-09-19 Time 11:27 Rev Time 0.00
Received By kstevens Date 2006-09-19 Time 11:27 Sent To  
Notes
2006-09-19 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FHA DESIGN MANUAL 98
  
 1. SHT 4-A1 OF 17 THE LAST REVISION
 SHOWN ON THE PERMITED SET OF PLANS IS
 DATED 2/15/06. THE ONLY REVISION CLOUDED
 IS DATED 2/20/06. FOUR OTHER REVISIONS
 ARE SHOWN DATED 2/23/06, 4/10/06,
 6/19/06, AND 7/26/06 FOR THIS SHEET. THE
 LAST FOUR REVISIONS CAN NOT BE FOUND.
 PLEASE INDICATE REVISIONS BY CLOUDING
 AND INDICATE REVISIONS WITH A NUMBERED
 DART OR TRIANGLE. SECTION 104.2.1.
  
 2. SHT 4-A1 OF 17 REVISION INDICATES A
 CHANGE FROM SPECIFICATION "A", ALL
 BATHROOMS, TO SPECIFICATION "B" WHERE
 ONLY ONE BATHROOM IS REQUIRED. THE NOTE
 REFERENCES 1/4" SCALE FLOOR PLANS. THESE
 1/4" SCALE FLOOR PLANS HAVE NOT BEEN
 SUBMITTED AS REVISIONS SO SPECIFICATION
 "B" BATHROOM IS NOT INDICATED. EITHER
 INDICATE ON THE REVISION FOR SHT 4-A1 OF
 17 WHICH BATHROOM IS SPECIFICATION "B"
 OR REVISE THE 1/4" SCALE FLOOR PLANS
 SHOWING SPECIFICATION "B" FOR REQUIRED
 BATHROOM. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-04-07 Cont ID  
Sent By jleech Date 2006-04-07 Time 09:04 Rev Time 0.00
Received By jleech Date 2006-04-07 Time 09:04 Sent To  
Notes
2006-04-07 00:00:00PROVISO;
 SPECIFICATION "A" APPLIES TO ALL
 BATHROOMS, AND ALL FIXTURES IN THOSE
 BATHROOS MUST BE USABLE. IF A LAVATORY
 IS INSTALLED WHERE SPACE DOES NOT PERMIT
 A CLOSE PARALLEL APPROACH WITH THE 30" X
 48" CLEAR FLOOR SPACE CENTERED ON THE
 BASIN, THE CENTER LINE OF THE BASIN MUST
 BE AT LEAST 15" FROM AN ADJOINING WALL
 OR FIXTURE. IT MUST HAVE KNEE SPACE AT
 LEAST 30" WIDE TO ALLOW A USER TO
 EXECUTE A FORWARD APPROACH INTO CLEAR
 FLOOR SPACE BENEATH THE FIXTURE. EITHER
 REMOVABLE VANITY CABINETS OR OPEN CLEAR
 FLOOR SPACE REQUIRED. PAGE 7.49 THE TOP
 OF ALL VANITY CABINETS SHALL BE 34"
 MAXIMUM. PAGE 7.52

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-02-21 Cont ID  
Sent By kstevens Date 2006-02-21 Time 16:47 Rev Time 0.00
Received By kstevens Date 2006-02-21 Time 16:47 Sent To  
Notes
2006-02-21 00:00:00DENIED
 REFERENCE: FHA-98 DESIGN MANUAL
  
 1. SPECIFICATION "A" APPLIES TO ALL
 FIXTURES IN ALL BATHROOMS. THE SECOND
 LAV IN THE MASTER BATHS SHALL HAVE A
 CLEAR FLOOR SPACE SUPERIMPOSED ON THE
 PLANS. IF LAV CAN NOT BE CENTERED ON THE
 48" LENGTH OF THE CLEAR FLOOR SPACE,
 THEN A FORWARD APPROACH SHALL BE SHOWN
 AND THE BASE CABINET SHALL BE REMOVABLE
 FOR THAT LAV. PLEASE SUBMIT A DETAIL FOR
 BASE CABINET REMOVAL IF REQUIRED. SEE
 PAGES 7.49, 7.50, & 7.51.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-12-14 Cont ID  
Sent By kstevens Date 2005-12-14 Time 15:29 Rev Time 0.00
Received By kstevens Date 2005-12-14 Time 15:29 Sent To  
Notes
2005-12-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
  
 ***FROM PREVIOUS REVIEW***
  
 1. ALL FIRST FLOOR UNITS SHALL COMPLY
 WITH REQUIREMENTS 1 THRU 7 OF THE FAIR
 HOUSING ACT DESIGN MANUAL. PLEASE SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH ALL
 REQUIREMENTS. INDICATE SPECIFICATION "A"
 OR "B" AS REQUIRED ON PAGE 7.34. THE
 CLEAR FLOOR SPACE FOR ALL USABLE
 FIXTURES SHALL BE APPLIED OR
 SUPERIMPOSED OVER THE FLOOR PLAN. FOR
 THE W/C SEE PAGE 7.43. - CLEAR FLOOR
 SPACE FOR THE W/C'S NOT SHOWN.
 4. SHTS P2 OF 2 ALL UNITS WATER HEATER
 DETAIL. P/T DISCHARGE LINE SHALL NOT
 HAVE ANY TRAPED SECTIONS. SECTION
 504.7.1. (SEE WATER HEATER NOTES).
 ****************NEW COMMENT*************
 1B. WATER HEATER PANS ON THE FIRST FLOOR
 ARE NOT REQUIRED. IF INSTALLED, THE
 ELEVATION ABOVE GRADE FOR THE PAN SHALL
 BE INDICATED SO AS TO INSURE THE PAN
 WILL DRAIN AS THE TERMINATION OF THE PAN
 DRAIN IS SHOWN AS 6" ABOVE GRADE.
 SECTIONS 104.2.1 & 504.8.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-09-10 Cont ID  
Sent By kstevens Date 2005-09-10 Time 15:28 Rev Time 0.50
Received By kstevens Date 2005-09-10 Time 15:28 Sent To  
Notes
2005-09-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
  
 1. ALL FIRST FLOOR UNITS SHALL COMPLY
 WITH REQUIREMENTS 1 THRU 7 OF THE FAIR
 HOUSING ACT DESIGN MANUAL. PLEASE SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH ALL
 REQUIREMENTS. INDICATE SPECIFICATION "A"
 OR "B" AS REQUIRED ON PAGE 7.34. THE
 CLEAR FLOOR SPACE FOR ALL USABLE
 FIXTURES SHALL BE APPLIED OR
 SUPERIMPOSED OVER THE FLOOR PLAN. FOR
 THE W/C SEE PAGE 7.43.
 2. SHTS P1 OF 2 FOR UNITS 101, 102, 201,
 & 202, MAXIMUM 6 FT. FROM SHOWER
 TRAP TO VENT PER TABLE 906.1. ON THE
 FLOOR PLAN IT SCALES OUT TO APPROX. 8'
 TO 9'.
 3. SHTS P2 OF 2 FOR UNITS 101, 102, 201,
 & 202, WATER RISER DIAGRAM. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING AS SOME ARE SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 4. SHTS P2 OF 2 ALL UNITS WATER HEATER
 DETAIL. P/T DISCHARGE LINE SHALL NOT
 HAVE ANY TRAPED SECTIONS. SECTION
 504.7.1. (SEE WATER HEATER NOTES).
 5. SHTS P2 OF 2 ALL UNITS SANITARY RISER
 DIAGRAM. THE WASH MACHINES DRAIN LINE
 SHALL HAVE A STANDPIPE, SECTION 1002.1.,
 AND THE CLEANOUT SHALL BE LOCATED 4'
 ABOVE THE FLOOR, SECTION 708.10 FOR
 ACCESS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2006-03-10 Cont ID  
Sent By eschneid Date 2006-03-10 Time 15:14 Rev Time 0.00
Received By eschneid Date 2006-03-10 Time 15:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2006-02-28 Cont ID  
Sent By eschneid Date 2006-02-28 Time 15:14 Rev Time 0.00
Received By eschneid Date 2006-02-28 Time 15:41 Sent To  
Notes
2006-02-28 00:00:003RD TIME FOR THE FOLLOWING NOTE:
  
 AN OVERALL LANDSCAPE PLAN SHALL BE
 PROVIDED.ON THE LANDSCAPE PLAN,
 INDICATED WHICH AREAS WILL BE INSTALLED,
 INSPECTED & C.O.'D WITH EACH BUILDINGS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-01-24 Cont ID  
Sent By jroach Date 2006-01-24 Time 10:30 Rev Time 0.00
Received By jroach Date 2006-01-24 Time 10:30 Sent To  
Notes
2006-01-24 00:00:001/24/06 ***FAILED***
  
 SEE COMMENTS FROM REVIEW ON 9/2/05...
  
 1) AN OVERALL SITE PLAN SHALL BE
 PROVIDED.
  
 2) AN OVERALL LANDSCAPE PLAN SHALL BE
 PROVIDED.ON THE LANDSCAPE PLAN, PLEASE
 INDICATE WHICH AREAS WILL BE INSPECTED
 AND CO'D WITH EACH BUILDING.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 PLANNER AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-02 Cont ID  
Sent By jroach Date 2005-09-02 Time 15:08 Rev Time 0.00
Received By jroach Date 2005-09-02 Time 15:08 Sent To  
Notes
2005-09-02 00:00:009/2/2005 ***FAILED***
  
 1) AN OVERALL SITE PLAN SHALL BE
 PROVIDED.
  
 2) AN OVERALL LANDSCAPE PLAN SHALL BE
 PROVIDED.
  
 ON THE LANDSCAPE PLAN, PLEASE INDICATE
 WHICH AREAS WILL BE CO'D WITH EACH
 BUILDING.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 PLANNER AT (561) 822-1435.