Plan Review Details - Permit 05080084
Plan Review Stops For Permit 05080084
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-08-09 Cont ID  
Sent By jhiggins Date 2005-08-09 Time 14:06 Rev Time 0.00
Received By jhiggins Date 2005-08-09 Time 14:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-01-03 Cont ID  
Sent By rmcdouga Date 2007-01-03 Time 12:46 Rev Time 0.00
Received By rmcdouga Date 2007-01-03 Time 12:46 Sent To  
Notes
2007-01-03 12:47:03REVISED TRUSS LAYOUT AND DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-12-06 Cont ID  
Sent By rmcdouga Date 2006-12-06 Time 08:45 Rev Time 0.00
Received By rmcdouga Date 2006-12-06 Time 07:18 Sent To  
Notes
2006-12-06 09:26:17BUILDING REVISIONS TO STRUCTURAL PAGES S1, S2, S3 AND
 S6 ARE OK.FIRE PENETRATIONS AND CALKING DETAILS AND
 STAIR AND BALCONY RAIL SHOP DRAWINGS WERE SUBMITTED.
  
 PROVISO NOTE:
  
 ALTHOUGH SOME OF THE ACTUAL UPLIFTS SPECIFIED ON THE
 ROOF FRAMING PLAN ARE LESS THAN THOSE SHOWN ON THE
 TRUSS DRAWINGS,THE CONNECTORS SPECIFIED IN THE ANCHOR
 LEGEND ARE ADEQUATE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-09-21 Cont ID  
Sent By rmcdouga Date 2006-09-21 Time 13:33 Rev Time 0.00
Received By rmcdouga Date 2006-09-21 Time 13:33 Sent To  
Notes
2006-09-21 00:00:00DENIED BY BUILDING
  
 REVISION TO SHEET 6-A1 TO CHANGE FROM
 BATHROOMS FROM FAIR HOUSING
 SPECIFICATION "A" TO SPECIFICATION "B"
 IS DENIED. SEE PLUMBING REVIEW COMMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2006-09-05 Cont ID  
Sent By rmcdouga Date 2006-09-05 Time 10:51 Rev Time 0.00
Received By rmcdouga Date 2006-09-05 Time 10:51 Sent To  
Notes
2006-09-05 00:00:00REVISION TO CHANGE ROOFING DENIED
  
 1) THE PRODUCT EVALUATION SUBMITTED FOR
 THE TILE ROOFING IS NOT THE ONE THAT
 CORRESPONDS WITH THE ONE LISTED ON THE
 STATE WEBSITE FOR FL560-R1. A MIAMI-DADE
 NOA IS LISTED.
  
 2) SPECIFY THE SPECIFIC FASTENER AND
 NUMBER OF FASTENERS PER TILE THAT WILL
 BE USED. HIGHLITE OR CIRCLE THE
 APPROPRIATE FASTENER ON THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-06-12 Cont ID  
Sent By rmcdouga Date 2006-06-12 Time 07:49 Rev Time 0.00
Received By rmcdouga Date 2006-06-12 Time 07:49 Sent To  
Notes
2006-06-12 00:00:00REVISED STRUCTURAL PAGES S1-S6 ARE OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-06 Cont ID  
Sent By rmcdouga Date 2006-04-06 Time 08:32 Rev Time 0.00
Received By rmcdouga Date 2006-04-06 Time 07:12 Sent To  
Notes
2006-04-06 00:00:00BUILDING PROVISO
  
 1) STRUCTURE IS LOCATED IN AN "AO" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2) SUBMIT STRUCTURAL DRAWINGS FOR THE
 CONCRETE STAIRS.
  
 3) SUBMIT SHOP DRAWINGS FOR THE INTERIOR
 AND EXTERIOR GUARDRAILS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-23 Cont ID  
Sent By rmcdouga Date 2006-01-23 Time 10:11 Rev Time 0.00
Received By rmcdouga Date 2006-01-20 Time 11:53 Sent To  
Notes
2006-01-23 00:00:00DENIED
 (2ND REVIEW)
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "AO"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 3) ADDITIONAL PERMIT FEES ARE DUE. THE
 CALCULATED VALUE OF THE STRUCTURE IS
 $1,001,140.00. A WESTWARD EXPANSION FEE
 OF $550.00 PER UNIT IS ALSO REQUIRED.
  
 4) SITE PLANS ARE REQUIRED WHICH
 SPECIFY THE DISTANCE TO ASSUMED PROPERTY
 LINES BETWEEN ADJACENT BUILDINGS LOCATED
 ON THE SAME LOT. THIS IS REQUIRED IN
 ORDER TO DETERMINE THE PERCENTAGE OF
 WALL AREA THAT IS ALLOWED AS OPENINGS BY
 FBC TABLE 600.
  
 5) THE SCALE SPECIFIED IN THE INDEX ON
 A1 FOR THE DRAWINGS ON SHEET A4 IS
 INCORRECT. THE CORRECT SCALE IS 1/8".
  
 6) THE CONSTRUCTION TYPE SPECIFIED ON A1
 IS FROM THE 2004 FBC. THESE PLANS WERE
 REVIEWED UNDER THE 2001 FBC AND THE
 STRUCTURAL PLANS ARE ON THE 2001 FBC.
 PLEASE REVISE SHEETS A1 AND A9.
  
 7) BASED ON TYPE VI CONSTRUCTION,
 UNPROTECTED AND UNSPRINKLERED, 2001 FBC
 TABLE 500 LIMITS THE AREA PER FLOOR TO
 7000 SQFT. USING THE FORMULA FOR AREA
 INCREASES ALLOWED BY SECTION 503.3, AND
 THE FRONT AND REAR BUILDING PERIMETERS
 WHICH 30FT WIDE HORIZONTAL SEPARATIONS
 THE ALLOWABLE AREAS ARE EXCEEDED AT THE
 SECOND FLOOR. IF THE PORTIONS OF THE
 LEFT AND RIGHT SIDE PERIMETERS THAT HAVE
 30FT TO THE ASSUMED PROPERTY LINE
 BETWEEN BUILDINGS (SEE SECTION 505) WERE
 USED IN THE CALCULATIONS THE AREA
 INCREASE ALLOWED MAY COMPLY. HOWEVER, NO
 SITE PLAN INDICATING ASSUMED PROPERTY
 LINES WAS SUBMITTED. SUBMIT AREA
 INCREASE CALCULATIONS.
  
 8)CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, A 'DECLARATION OF
 CONDOMINIUM' SHALL BE SUBMITTED TO THE
 STATE FOR APPROVAL, AND THEN RECORDED
 WITH THE CLERK OF THE COUNTY COURT.A
 RECORDED COPY SHALL BE SUBMITTED TO THE
 CITY FOR RECORDS, ADDRESSING PURPOSES,
 AND TO PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE PRIOR TO C.O.
  
 9) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 10) ON SHEET S5 UNDER PLYWOOD ROOF
 DIAPHRAGM, NOTE #3 SPECIFIES 8D GAL.
 NAILS AT 6"OC AT EDGES AND INTERMEDIATE.
 THIS CONFLICTS WITH ROOF PLAN ON S4,
 WHICH SPECS. 10D NAILS 4"OC AT EDGES AND
 6"OC INTERMEDIATE. THE CITY AMENDMENTS
 TO FBC TABLE 2306.1 REQUIRE 8D
 RING-SHANK NAILS 4"OC AT EDGES AND 6"OC
 INTERMEDIATE IN ZONE 3 FOR ROOFS WITH A
 MEAN ROOF HEIGHT OF MORE THAN 25'.
  
 11) PLEASE REVISE THE STANDARDS
 REFERENCED UNDER DESIGN CRITERIA ON S5
 TO THE EDITIONS LISTED IN CHAPTER 35 OF
 THE 2001 FBC. (ACI 318-02 AND 530.1-02)
  
 12) SPECIFY METHOD OF TERMITE PROTECTION
 AS REQUIRED BY FBC 1816.
  
 13) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 14) SPECIFY HOW IMPACT PROTECTION WILL
 BE PROVIDED FOR THE GLAZED OPENINGS AS
 REQUIRED BY FBC 1606.1.4. ITEM #13 OF
 THE CITY OF WPB IMPLEMENTATION STANDARD
 FOR HURRICANE MISSLE IMPACT PROTECTION
 REQUIRES PRE-STORM PREPARATION PLANS TO
 BE SUBMITTED FOR REVIEW IF USING STORM
 SHUTTERS, IN ADDITION TO A KEY PLAN,
 INSTALLATION SCHEDULE AND PRODUCT
 APPROVALS. STORM PANELS ARE NOT ALLOWED
 ABOVE THE FIRST FLOOR FOR THIS TYPE OF
 STRUCTURE AND OCCUPANCY.
  
 15) SUBMIT THE EVALUATION REPORT AND
 INSTALLATION INSTRUCTIONS FROM NATIONAL
 ACCREDITATION AND MANAGEMENT INSTITUTE
 FOR THE THERMA-TRU DOORS WITH FL # 1170.
 THE INFORMATION THAT WAS SUBMITTED TO
 THE STATE FOR STATE PRODUCT APPROVAL IS
 REQUIRED TO BE SUBMITTED WITH THE STATE
 COVER SHEET.
  
 16) SUBMIT PRODUCT APPROVAL FOR THE
 SMALL (8' X 7') OVERHEAD GARAGE DOOR
 WHICH IS LESS THAN THE MINIMUM SIZE
 ALLOWED BY THE PRODUCT APPROVAL FOR THE
 LARGE DOOR THAT WAS SUBMITTED.
  
 17) SUBMIT THE SBCCI REPORT (2139A) THAT
 IS LISTED ON THE FL PRODUCT APPROVAL
 WEBSITE FOR THE COLLIER GARAGE DOORS.
  
 18) SUBMIT PRODUCT APPROVALS FOR THE
 TRUSS CONNECTORS.
  
 19) PROVIDE A STRUCTURAL DETAIL ON THE
 PLANS FOR THE CONCRETE STAIRS. SPECIFY
 STEEL REINFORCEMENT FOR THE STAIRS,
 LANDINGS AND AT THE BASE OF THE STAIRS.
  
 20) SUBMIT SIGNED AND SEALED TRUSS
 DRAWINGS AND LAYOUTS THAT HAVE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD
 FOR THE STRUCTURE.
  
 21) SUBMIT A TECHNICAL BULLETIN OR
 REPORT FROM USP THAT ALLOWS TRUSS HANGER
 JUS26-2 TO BE ATTACHED TO MASONRY WITH
 TAPCON FASTENERS AND SPECIFYING THE
 ALLOWABLE LOADS FOR THE APPLICATION.
  
 22) PROVIDE SHOP DRAWINGS WITH
 STRUCTURAL DETAILS FOR THE TYPICAL
 INTERIOR GUARDRAIL DETAIL AS
 REFERENCED BY THE SECTION ON A12.
  
 23) SUBMIT SHOP DRAWINGS FOR THE
 EXTERIOR GUARDRAILS. INDICATING HOW THEY
 WILL BE ATTACHED TO THE STRUCTURE.
  
 24) THE ENGINEER IS REQUIRED TO SIGN HIS
 NAME TO THE PLANS HE SEALS PER FAC
 61G15-23.002. PLEASE SUBMIT A NOTARIZED
 LETTER SIGNED, SEALED AND DATED BY THE
 ENGINEER ATTESTING HIS LEGAL SIGNATURE.
  
 25) THE 5' BI-PASS DOOR AT HER WALK-IN
 CLOSET (#7 IN SCHEDULE) DOES NOT COMPLY
 WITH FAIR HOUSING REQUIREMENTS. USEABLE
 DOORS WITHIN THE DWELLING UNIT MUST HAVE
 A CLEAR OPENING OF AT LEAST 31-5/8"
 CLEAR.
  
 26) THE STRUCTURAL PLANS DO NOT SHOW THE
 ELEVATOR RECESSES ON THE FOUNDATION PLAN
 OR THE OPENINGS AT THE SECOND FLOOR FOR
 THE ELEVATORS. PROVIDE STRUCTURAL
 DETAILS FOR THESE AREAS.
  
 27) PROVIDE STRUCTURAL DETAILS FOR THE
 INFILL FLOOR FRAMING AT THE ELEVATOR
 RECESSES AND OPENINGS WHEN THE CLOSET
 OPTION IS USED IN LEIU OF AN ELEVATOR.
 SEE DETAILS 6 AND 7 ON A11.
  
 28) THE 16' GARAGE DOORS ON SHEETS A8GR
 AND A8GL HAVE THE WRONG ID MARKS
 ACCORDING TO THE DOOR SCHEDULE ON A9.
  
 29) THE 8' WIDE GARAGE DOOR ON A8GL-C
 HAS THE WRONG ID MARK PER THE DOOR
 SCHEDULE.
  
 30) ON A6GR-C THE DOOR ID MARKS DO NOT
 CORRESPOND WITH THE DOOR SCHEDULE ON A9.
  
 31) THE WALL SECTION ON A13 STATES THAT
 METAL LATH SHALL COMPLY WITH SECTIONS
 2507.3 THRU 2507.5. THESE SECTIONS ARE
 FROM THE HIGH VELOCITY HURRICANE ZONE
 (DADE & BROWARD COUNTIES) AND APPLY TO
 GYPSUM LATH. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-20 Cont ID  
Sent By rmcdouga Date 2005-09-20 Time 17:58 Rev Time 0.00
Received By rmcdouga Date 2005-09-20 Time 17:58 Sent To  
Notes
2005-09-20 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE STRUCTURE IS LOCATED IN AN "AO"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 3) ADDITIONAL PERMIT FEES ARE DUE. THE
 CALCULATED VALUE OF THE STRUCTURE IS
 $1,001,140.00. A WESTWARD EXPANSION FEE
 OF $550.00 PER UNIT IS ALSO REQUIRED.
  
 4) SITE PLANS ARE REQUIRED WHICH
 SPECIFY THE DISTANCE TO ASSUMED PROPERTY
 LINES BETWEEN ADJACENT BUILDINGS LOCATED
 ON THE SAME LOT. THIS IS REQUIRED IN
 ORDER TO DETERMINE THE PERCENTAGE OF
 WALL AREA THAT IS ALLOWED AS OPENINGS BY
 FBC TABLE 600.
  
 5) THESE UNITS DO NOT MEET THE
 DEFINITION OF TOWNHOUSE IN THE 2001
 FLORIDA BUILDING CODE. PLEASE REMOVE THE
 TITLE OF TOWNHOMES FROM THE TITLE BLOCKS
 OF THE M.E.P. DRAWINGS.
  
 6) SPECIFY THE SCALE OF THE DRAWINGS ON
 THE PLANS.
  
 7) SPECIFY THE OCCUPANCY, CONSTRUCTION
 TYPE, PROTECTED OR UNPROTECTED AND
 SPRINKLERED OR UNSPRINKLERED. PROVIDE
 ARES INCREASE CALCULATIONS.
  
 8)CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, A 'DECLARATION OF
 CONDOMINIUM' SHALL BE SUBMITTED TO THE
 STATE FOR APPROVAL, AND THEN RECORDED
 WITH THE CLERK OF THE COUNTY COURT.A
 RECORDED COPY SHALL BE SUBMITTED TO THE
 CITY FOR RECORDS, ADDRESSING PURPOSES,
 AND TO PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE PRIOR TO C.O.
  
 9) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 10) FBC 705.1.3.2.1 CLASSIFIES FIRE
 DOORS AS 3 HOUR, 1-2/2 HOUR, 1 HOUR, 3/4
 HOUR OR 20 MINUTE. REVISE THE 'C' LABEL
 DOOR SPECIFIED ON SHEET A9. FBC
 705.1.3.2.2 ALLOWS 20 MINUTE RATED DOORS
 IN WALLS REQUIRED TO HAVE A FIRE
 RESISTANCE RATING OF 1 HOUR OR LESS.
  
 11) FBC 705.1.3.5 REQUIRES FIRE DOORS TO
 BE EQUIPED WITH AN APPROVED CLOSER.
  
 12) PROVIDE A ROOF SHEATHING NAILING
 PLAN FOR THE LOWER ROOFS THAT ARE NOT
 SHOWN ON S4.
  
 13) THE SPACING OF THE TAPCON FASTENERS
 FOR THE GARAGE DOOR HEADER IN DETAIL 1
 ON S4 APPEAR TO CONFLICT. 16"OC IS
 SPECIFIED IN ONE PLACE AND 8" OC IS
 SPECIFIED UNDER NOTES. PLEASE CORRECT.
  
 14) FBC TABLE 1604.1 REQUIRES THE BOTTOM
 CORD LIVE LOAD TO BE 10 PSF FOR ATTICS
 WITHOUT STORAGE AND 30 PSF FOR ATTICS
 WITH STORAGE. REVISE ROOF LOADS ON S5.
  
 15) UNDER GENERAL NOTES ON S5, ITEM # 24
 SPECIFIES THE WRONG EDITIONS OF ACI,
 ASCE 5 AND TMS. THE 2002 EDITIONS ARE
 REFERENCED IN CHAPTER 35 OF THE 2001 FBC
  
 16) UNDER STRUCTURAL DESIGN CRITERIA ON
 S5, THE CORRECT EDITIONS OF THE
 REFERENCE STANDARDS ARE ACI 318-02 AND
 ACI 5301-02.
  
 17) THE EXTERIOR WALL SECTION 5 ON S6
 SPECIFIES 6" FROM THE TOP OF THE
 MONOLITHIC SLAB TO FINISH GRADE. THIS
 WILL NOT ALLOW THE BOTTOM OF THE 16"
 DEEP FOOTER TO BE A MINIMUM 12" BELOW
 FINISH GRADE AS REQUIRED BY FBC 1804.1.3
  
 18) THE ROOF PITCH ON THE WALL SECTION 5
 ON S6 AND THE TYPICAL ROOF TRUSS ANCHOR
 DETAIL ON S3 ARE SPECIFIED AS 5/12 AND
 THE ELEVATIONS SPECIFY 4/12.
  
 19) THE UL SYSTEM SPECIFIED FOR THE ONE
 HOUR FIRE RATED TENANT SEPARATION WALLS
 "U 907" IS FOR NONBEARING WALLS ONLY.
 PLEASE SPECIFY A SYSTEM FOR BEARING
 WALLS.
  
 20) THE LABELING OF THE UNITS AS TO
 GARAGE LEFT OR RIGHT IS INCONSISTANT. TO
 AVOID CONFUSION IF THE GARAGE IS LOCATED
 TO THE LEFT OF ITS UNIT LABEL IT GARAGE
 LEFT AND VISE VERSA FOR GARAGE RIGHT.
  
 21) PROVIDE A DETAIL OF THE GUARDRAILS
 AT THE OPEN SIDE OF THE STAIRS (LOWER
 SECTION). SEE FBC 1015.
  
 22) PROVIDE AN AREA TABULATION TABLE
 LISTING THE FIRST AND SECOND FLOOR A/C
 AREAS AND UNCONDITIONED AREAS FOR EACH
 UNIT AND THE TOTALS FOR THE STRUCTURE.
  
 23) THE ELEVATORS ARE REQUIRED TO COMPLY
 WITH ASME A17.1 AND ANSI A117.1 (FAIR
 HOUSING).
  
 24) SPECIFY METHOD OF TERMITE PROTECTION
 AS REQUIRED BY FBC 1816.
  
 25) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 26) SPECIFY HOW IMPACT PROTECTION WILL
 BE PROVIDED FOR THE GLAZED OPENINGS AS
 REQUIRED BY FBC 1606.1.4. ITEM #13 OF
 THE CITY OF WPB IMPLEMENTATION STANDARD
 FOR HURRICANE MISSLE IMPACT PROTECTION
 REQUIRES PRE-STORM PREPARATION PLANS TO
 BE SUBMITTED FOR REVIEW IF USING STORM
 SHUTTERS, IN ADDITION TO A KEY PLAN,
 INSTALLATION SCHEDULE AND PRODUCT
 APPROVALS. STORM PANELS ARE NOT ALLOWED
 ABOVE THE FIRST FLOOR FOR THIS TYPE OF
 STRUCTURE AND OCCUPANCY.
  
 27) SUBMIT THE EVALUATION REPORT AND
 INSTALLATION INSTRUCTIONS FROM NATIONAL
 ACCREDITATION ANS MANAGEMENT INSTITUTE
 FOR THE THERMA-TRU DOORS WITH FL # 1170.
 THE INFORMATION THAT WAS SUBMITTED TO
 THE STATE FOR STATE PRODUCT APPROVAL IS
 REQUIRED TO BE SUBMITTED WITH THE STATE
 COVER SHEET.
  
 28) SUBMIT PRODUCT APPROVAL FOR THE
 SMALL (8' X 7') OVERHEAD GARAGE DOOR
 WHICH IS LESS THAN THE MINIMUM SIZE
 ALLOWED BY THE PRODUCT APPROVAL FOR THE
 LARGE DOOR THAT WAS SUBMITTED.
  
 29) SUBMIT THE SBCCI REPORT (2139A) THAT
 IS LISTED ON THE FL PRODUCT APPROVAL
 WEBSITE FOR THE COLLIER GARAGE DOORS.
  
 30) SUBMIT PRODUCT APPROVALS FOR THE
 TRUSS CONNECTORS.
  
 31) PROVIDE A STRUCTURAL DETAIL ON THE
 PLANS FOR THE CONCRETE STAIRS. SPECIFY
 STEEL REINFORCEMENT FOR THE STAIRS,
 LANDINGS AND AT THE BASE OF THE STAIRS.
  
 32) SUBMIT SIGNED AND SEALED TRUSS
 DRAWINGS AND LAYOUTS THAT HAVE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD
 FOR THE STRUCTURE.
  
 33) SUBMIT A TECHNICAL BULLETIN OR
 REPORT FROM USP THAT ALLOWS TRUSS HANGER
 JUS26-2 TO BE ATTACHED TO MASONRY WITH
 TAPCON FASTENERS AND SPECIFYING THE
 ALLOWABLE LOADS FOR THE APPLICATION.
  
 34) PROVIDE STRUCTURAL DETAILS FOR THE
 TYPICAL INTERIOR GUARDRAIL DETAIL AS
 REFERENCED BY THE SECTION ON A12.
  
 35) SUBMIT SHOP DRAWINGS FOR THE
 EXTERIOR GUARDRAILS. INDICATING HOW THEY
 WILL BE ATTACHED TO THE STRUCTURE.
  
 36) THE ENGINEER'S FIRM # IS REQUIRED TO
 BE LISTED IN THE TITLE BLOCK. SEE FAC
 61G15-23.002.
  
 37) THE ENGINEER IS REQUIRED TO SIGN HIS
 NAME TO THE PLANS HE SEALS PER FAC
 61G15-23.002. PLEASE SUBMIT A NOTARIZED
 LETTER SIGNED, SEALED AND DATED BY THE
 ENGINEER ATTESTING HIS LEGAL SIGNATURE.
  
 38) THE ARCHITECT IS REQUIRED TO
 PERSONALLY SIGN ALL DOCUMENTS SEALED BY
 HIM PER FAC 61G1-16.003. PLEASE SUBMIT A
 NOTARIZED LETTER SIGNED, SEALED AND
 DATED BY THE ARCHITECT ATTESTING HIS
 LEGAL SIGNATURE.
  
 39) SHOW COMPLIANCE WITH THE FAIR
 HOUSING ACT. ALL BUILDING ENTRANCES ARE
 REQUIRED TO BE ACCESSIBLE AND BE ON AN
 ACCESSIBLE ROUTE.
 - THE PRIMARY ENTRANCE DOOR MUST MEET
 THE REQUIREMENTS FOR ACCESSIBLE DOORS
 (32" CLEAR OPENING, LOW OR NO THRESHOLD-
 3/4"MAX, HARDWARE COMPLYING WITH ANSI
 4.13.9, ETC.)
 - DOORS WITHIN UNITS MUST BE USEABLE
 DOORS. MUST PROVIDE AT LEAST A 31-5/8"
 CLEAR OPENING.
 - CLOSET DOORS THAT REQUIRE USERS TO
 PASS THROUGH THE DOORWAY TO REACH THE
 CONTENTS MUST HAVE DOORS THAT PROVIDE AT
 LEAST 32 INCHES NOMINAL CLEAR OPENING.
 - LIGHT SWITCHES, ELECTRICAL OUTLETS,
 THERMOSTATS AND CONTROLS SHALL BE IN
 ACCESSIBLE LOCATIONS.
 - INDICATE THE MINIMUM CLEAR FLOOR
 SPACES AT THE FIXTURES AND APPLIANCES IN
 THE KITCHENS.
 - THE FAIR HOUSING ACT REQUIRES THE
 BATHROOMS TO BE DESIGNED TO COMPLY WITH
 SPECIFICATION "A" OR "B" BATHROOMS.
 INDICATE WHICH ONE WILL BE USED AND SHOW
 COMPLIANCE WITH DESIGN METHOD SELECTED.
 ALL FIRST FLOOR UNITS AND ALL SECOND
 FLOOR UNITS EQUIPPED WITH ELEVATORS ARE
 REQUIRED TO COMPLY WITH THE FAIR HOUSING
 REQUIREMENTS.
  
 40) THE STRUCTURAL PLANS DO NOT SHOW THE
 ELEVATOR RECESSES ON THE FOUNDATION PLAN
 OR THE OPENINGS AT THE SECOND FLOOR FOR
 THE ELEVATORS. PROVIDE STRUCTURAL
 DETAILS FOR THESE AREAS.
  
 41) PROVIDE STRUCTURAL DETAILS FOR THE
 INFILL FLOOR FRAMING AT THE ELEVATOR
 RECESSES AND OPENINGS WHEN THE CLOSET
 OPTION IS USED IN LEIU OF AN ELEVATOR.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-01-05 Cont ID  
Sent By dpalmer Date 2007-01-05 Time 09:25 Rev Time 0.00
Received By dpalmer Date 2007-01-05 Time 09:25 Sent To  
Notes
2007-01-05 09:25:57REDLINED, LV SPKRS NIC.
 MAY USE PLANS TO REFERENCE BACK TO, HOWEVER A SEPARATE
 PERMIT IS REQUIRED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-13 Cont ID  
Sent By dpalmer Date 2006-09-13 Time 18:32 Rev Time 0.00
Received By dpalmer Date 2006-09-13 Time 17:42 Sent To PC
Notes
2006-09-13 00:00:00ENGINEER BROUGHT IN NEW ELECTRICAL
 SHEETS AND MADE CORRECTIONS ON 9/7/06
 PREVIOUSELECTRICAL REV'S WERE PLACED
 ON "HOLD" BY THE ENGINEER AND CONTRACTOR
 WAS NOTIFIED.
  
  
 REV STAMPED

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-05 Cont ID  
Sent By dpalmer Date 2005-12-05 Time 17:52 Rev Time 0.00
Received By dpalmer Date 2005-12-05 Time 17:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-26 Cont ID  
Sent By dpalmer Date 2005-08-26 Time 14:29 Rev Time 1.00
Received By dpalmer Date 2005-08-26 Time 14:29 Sent To  
Notes
2005-08-26 00:00:00***********UNSAT ************
  
 BLDG #3.
  
 1)NOTE: PLEASE CHECK AND VERIFY ALL SETS
 AND CORRECT SHEETS.
  
 2)NOTE: PLEASE SEE APPLICATION SHOWS
 THESE BEING SUBMITTED AS "TOWNHOUSES"??
 PLEASE SEE BUILDING REVIEW COMMENTS.
 THESE DO NOT SEEM TO BE CONSIDERED TRUE
 "TOWNHOUSES" AS DEFINED UNDER THE FBC.
 PLEASE SEE PALM BEACH COUNTY IMPACT FEE
 STAMPED INDICATES BUILDINGS AS 4 AND 6
 UNIT MULTI FAMILY DWELLINGS.
  
 PLEASE SEE THE FOLLOWING COMMENT FOR
 ELECTRICAL SERVICE.
  
 3)NOTE: PLEASE SEE DUE TO THESE NOT
 BEING CONSIDERED AS TOWNHOUSES WITH
 SEPARATE PROPERTY LINES, FEE SIMPLE ETC.
 ONLY ONE ELECTRICAL SERVICE WILL BE
 PERMITTED. PLEASE SEE GROUPING OF MAINS
 WILL BE REQUIRED FOR ALL FOUR UNITS IN
 THIS BLDG UNDER ONE SERVICE.
 PLEASE ADJUST SIZE OF SERVICE
 ACCORDINGLY. (SEC'S, GROUNDING,
 CONDUITS, ETC.
 230.2,230.70,230.72,240.4,310.16
  
 4)NOTE: PLEASE SEE MISSING AREAS FOR
 EGRESS LIGHTING. PLEASE SEE SOME AREAS
 WHERE AS "J-BOX" IS SHOWN, A LT FIXTURE
 OFSOME TYPE WILL BE REQUIRED. PLEASE
 SEE ENTRIES, TERRACE(1ST FLR) LIV RMS,
 KITCHENS ETC.
 PLEASE SEE 2-STORY UNITS, A 3-WAY OR
 4-WAY SWITCH WILL BE REQUIRED AT THE
 LANDINGS LOCATED IN BETWEEN FLRS.
 THIS IS ALSO REQUIRED FROM 210.70,LS 101
 5-8
  
 5)NOTE: PLEASE SEE MISSING SMOKE
 DETECTORS FOR AREAS LEADING TO FLR
 ABOVE. PLEASE SEE ENTRY FOYER'S FOR
 2-STORY UNITS. NFPA-72 8-1.4.1.6.2
 PLEASE ALSO SEE SD'S FOR MASTER BEDRM
 SHALL BE MOED "INTO" BEDRM AREA. PLEASE
 SEE ALL SD'S ARE TO BE INSTALLED WITHIN
 3' OF THE PEAK IN A SLOPE CEILING AND IN
 TRAY/ELEVATED CEILINGS WITHIN 12" OF MAX
 CEILING HEIGHT.
 NFPA-72 CHAPTER 2.
 PLEASE SEE SD'S ARE TO BE LOCATED NO
 CLOSER THAN 3' TO ANY KITCHEN OR BATH
 DOOR. AND 5' TO A RETURN AIR GRILL.
 NFAP-72 8-1.4.2
 PLEASE SEE SOME OF THESE HAVE BEEN
 REDLINED ON ONE SET OF PLANS.
  
 6)NOTE: PLEASE SEE SD'S ARE CIRCUITED TO
 KITCHEN/DINING LTS. THIS IS OK, HOWEVER
 PLEASE KNOW, THIS CIRCUIT WOULD BE ARC
 FAULT PROTECTED. PLEASE SEE THIS MEANS
 KITCHEN AND DINING RM LTS AS SHOWN WOULD
 BE INDICATED AS AFCI.
 PLEASE SEE SD'S MAY BE ON AN EXISITNG
 BEDRM ARC FAULT PROTECTED CIRCUIT.
 210.12, 2002 NEC.
  
 7)NOTE: PLEASE VERIFY OF GFI SHOWN IN
 KITCHEN IS "IN" THE PANTRY? PLEASE SEE
 KITCHENS WHEREPANTRY IS NOT SHOWN, AND
 A COUNTERSPACE IS ALSO NOT INDICATED??
  
 8)NOTE: PLEASE SEE MISSING GFI RECEPTS
 AND LTS FOR ELEVATOR PITAND EQUIPMENT
 SPACE. EACH SHALL CONTAIN DEDICATED
 CIRCUITS PER 620.23,620.24
  
  
  
 PLEASE SEE MANY OF THE ABOVE ITEMS WERE
 REDLINED ON PLANS FOR AREAS OF NOTES.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS, WHICH MAY AFFECT
 ELECTRICAL PLANS. (BLDG).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-08-09 Cont ID  
Sent By mamini Date 2005-08-09 Time 09:13 Rev Time 0.50
Received By mamini Date 2005-08-09 Time 09:13 Sent To  
Notes
2005-08-09 00:00:00PASSED:
  
 1. SEE PERMIT# 05070365FOR
 UNDERGROUND UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-16 Cont ID  
Sent By mwennerg Date 2005-12-16 Time 13:52 Rev Time 0.00
Received By mwennerg Date 2005-12-16 Time 13:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-28 Cont ID  
Sent By mwennerg Date 2005-09-28 Time 14:35 Rev Time 0.00
Received By mwennerg Date 2005-09-28 Time 14:35 Sent To  
Notes
2005-09-28 00:00:00******DENIED******
  
 1) ADDRESS IS REQUIRED ON EACH BUILDING.
 IT SHALL BE A MINIMUM OF 3" AND
 CONTRASTING TO THE BACKGROUND.
  
 2) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDS.
  
 3) ARE THESE BUILDINGS FIRE SPRINKLERED?
  
  
 4) FIRE HYDRANTS SHALL BE WET BEFORE,
 DURING AND AFTER CONSTRUCTION.
  
 5) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED FOR EACH UNIT.
  
 6) ELEVATORS SHALL COMPLY WITH A.S.M.E
 A-17.1.
  
 7) PLEASE USE THE 2003 EDITION WHEN
 REFERENCING NFPA 101. SHT 4-A9.
  
 8) SMOKE DETECTORS SHALL BE ARRANGED
 WHERE ACTIVATION OF ONE CAUSES ALL IN
 THE UNIT TO SOUND.
  
 9) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 10) STAIRS TO COMPLY WITH NFPA 101,
 SECTION 7.2.2.
  
 11) SMOKE DETECTORS TO BE INSTALLED A
 MINIMUM OF 3' FROM HVAC DIFFUSERS.
  
 12) PLEASE SEE SOME OF THE SMOKE
 DETECTORS NEAR #2 BEDROOMS APPEAR TO
 CLOSE TO THE BATHROOM.
  
 13) HANDRAILS REQUIRED ON BOTH SIDES OF
 STAIRS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 17:27 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 17:27 Sent To B
Notes
2006-12-17 17:27:39TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-12-14 Cont ID  
Sent By adarroug Date 2006-12-14 Time 15:27 Rev Time 0.00
Received By adarroug Date 2006-12-14 Time 15:27 Sent To  
Notes
2007-01-04 14:22:24TO "COMM" BD#21
2006-12-14 15:27:30WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-12-12 Cont ID  
Sent By adarroug Date 2006-12-12 Time 15:14 Rev Time 0.00
Received By adarroug Date 2006-12-12 Time 15:14 Sent To M
Notes
2006-12-12 15:14:43TO "PKRAUSS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-11-20 Cont ID  
Sent By adarroug Date 2006-11-20 Time 10:36 Rev Time 0.00
Received By adarroug Date 2006-11-20 Time 10:36 Sent To M
Notes
2006-11-20 10:36:33TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-01 Cont ID  
Sent By adarroug Date 2006-09-01 Time 08:29 Rev Time 0.00
Received By adarroug Date 2006-09-01 Time 08:29 Sent To E
Notes
2006-09-01 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 15:11 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 15:11 Sent To B
Notes
2006-08-12 00:00:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-08 Cont ID  
Sent By adarroug Date 2006-06-08 Time 15:57 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 15:57 Sent To B
Notes
2006-06-08 00:00:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-31 Cont ID  
Sent By adarroug Date 2006-01-31 Time 14:56 Rev Time 0.00
Received By adarroug Date 2006-01-31 Time 14:56 Sent To  
Notes
2006-01-31 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-10-14 Time 16:07 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 16:07 Sent To  
Notes
2005-10-14 00:00:00TO "COMM" BD#30/PLANS ON RACK/11 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-09-28 Time 16:07 Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 13:23 Sent To  
Notes
2005-08-08 00:00:00TO "COMM" BD#16/PLANS AND ROLLS ON RACK
2005-08-03 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-01-23 Cont ID  
Sent By rregueir Date 2007-01-23 Time 13:26 Rev Time 0.00
Received By rregueir Date 2007-01-23 Time 10:48 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-11-28 Cont ID  
Sent By rregueir Date 2006-11-28 Time 18:29 Rev Time 0.00
Received By rregueir Date 2006-11-28 Time 16:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-21 Cont ID  
Sent By pkrauss Date 2006-01-21 Time 07:34 Rev Time 0.00
Received By pkrauss Date 2006-01-21 Time 07:34 Sent To  
Notes
2006-01-21 00:00:00PROVISO:BUILDING #3/6 UNITS
  
 UNIT #201 & 203 INDICATE 5 TON UNIT,
 PER 2001 FMC 606.2.2 OR 606.4, FAN
 SHUTDOWN REQUIRED BY DUCT SMOKE DETECTOR
 OR BY AREA SMOKE DETECTORS.PLEASE
 SUBMIT WHICH METHOD WILL BE USED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
 PER CONVERSATION WITH MIKE WILLIAMS
 (LENNAR), M-2 PAGE INDICATES EQUIPMENT
 SCHEDULE & WILL BE SUBMITTED FOR REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-21 Cont ID  
Sent By pkrauss Date 2006-01-21 Time 07:41 Rev Time 0.00
Received By pkrauss Date 2006-01-21 Time 07:33 Sent To  
Notes
2006-01-21 00:00:00DENIED BY HAROLD MOSER ON 9/16/05 SEE
 PERMIT 05080284 FOR COMMENTS

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-09-20 Cont ID  
Sent By kstevens Date 2006-09-20 Time 07:42 Rev Time 0.00
Received By kstevens Date 2006-09-20 Time 07:42 Sent To  
Notes
2006-09-20 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FHA DESIGN MANUAL 98
  
 1. SHT 6-A1 OF 20 THE LAST REVISION
 SHOWN ON THE PERMITED SET OF PLANS IS
 DATED 2/15/06. THE ONLY REVISION CLOUDED
 IS DATED 2/20/06. FOUR OTHER REVISIONS
 ARE SHOWN DATED 2/23/06, 4/10/06,
 6/19/06, AND 7/26/06 FOR THIS SHEET. THE
 LAST FOUR REVISIONS CAN NOT BE FOUND.
 PLEASE INDICATE REVISIONS BY CLOUDING
 AND INDICATE REVISIONS WITH A NUMBERED
 DART OR TRIANGLE. SECTION 104.2.1.
  
 2. SHT 6-A1 OF 20 REVISION INDICATES A
 CHANGE FROM SPECIFICATION "A", ALL
 BATHROOMS, TO SPECIFICATION "B" WHERE
 ONLY ONE BATHROOM IS REQUIRED. THE NOTE
 REFERENCES 1/4" SCALE FLOOR PLANS. THESE
 1/4" SCALE FLOOR PLANS HAVE NOT BEEN
 SUBMITTED AS REVISIONS SO SPECIFICATION
 "B" BATHROOM IS NOT INDICATED. EITHER
 INDICATE ON THE REVISION FOR SHT 6-A1 OF
 20 WHICH BATHROOM IS SPECIFICATION "B"
 OR REVISE THE 1/4" SCALE FLOOR PLANS
 SHOWING SPECIFICATION "B" FOR REQUIRED
 BATHROOM. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-04-04 Cont ID  
Sent By jleech Date 2006-04-04 Time 10:17 Rev Time 0.00
Received By jleech Date 2006-04-04 Time 10:17 Sent To  
Notes
2006-04-04 00:00:00PROVISO;
  
 SPECIFICATION "A" APPLIES TO ALL
 BATHROOMS, AND ALL FIXTURES IN THOSE
 BATHROOMS MUST COMPLY. IF A LAVATORY IS
 INSTALLED WHERE SPACE DOES NOT PERMIT A
 CLOSE PARALLEL APPROACH WITH THE 30" X
 48" CLEAR FLOOR SPACE CENTERED ON THE
 BASIN, THE CENTER LINE OF THE BASIN MUST
 BE AT LEAST 15" FROM AN ADJOINING WALL
 OR FIXTURE. IT MUST HAVE KNEE SPACE AT
 LEAST 30" WIDE TO ALLOW A USER TO
 EXECUTE A FORWARD APPROACH INTO CLEAR
 FLOOR SPACE BENEATH THE FIXTURE. EITHER
 REMOVABLE VANITY CABINETS OR OPEN CLEAR
 FLOOR SPACE REQUIRED. PAGE 7.49 THE TOP
 OF ALL VANITY CABINETS SHALL BE 34"
 MAXIMUM. PAGE 7.52

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-12-14 Cont ID  
Sent By kstevens Date 2005-12-14 Time 16:50 Rev Time 0.00
Received By kstevens Date 2005-12-14 Time 16:50 Sent To  
Notes
2005-12-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
  
 ***FROM PREVIOUS REVIEW***
  
 1. ALL FIRST FLOOR UNITS SHALL COMPLY
 WITH REQUIREMENTS 1 THRU 7 OF THE FAIR
 HOUSING ACT DESIGN MANUAL. PLEASE SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH ALL
 REQUIREMENTS. INDICATE SPECIFICATION "A"
 OR "B" AS REQUIRED ON PAGE 7.34. THE
 CLEAR FLOOR SPACE FOR ALL USABLE
 FIXTURES SHALL BE APPLIED OR
 SUPERIMPOSED OVER THE FLOOR PLAN. FOR
 THE W/C SEE PAGE 7.43. - CLEAR FLOOR
 SPACE FOR THE W/C'S NOT SHOWN.
 4. SHTS P2 OF 2 ALL UNITS WATER HEATER
 DETAIL. P/T DISCHARGE LINE SHALL NOT
 HAVE ANY TRAPED SECTIONS. SECTION
 504.7.1. (SEE WATER HEATER NOTES).
 ****************NEW COMMENT*************
 1B. WATER HEATER PANS ON THE FIRST FLOOR
 ARE NOT REQUIRED. IF INSTALLED, THE
 ELEVATION ABOVE GRADE FOR THE PAN SHALL
 BE INDICATED SO AS TO INSURE THE PAN
 WILL DRAIN AS THE TERMINATION OF THE PAN
 DRAIN IS SHOWN AS 6" ABOVE GRADE.
 SECTIONS 104.2.1 & 504.8.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-09-10 Cont ID  
Sent By kstevens Date 2005-09-10 Time 13:53 Rev Time 1.50
Received By kstevens Date 2005-09-10 Time 13:53 Sent To  
Notes
2005-09-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
  
 1. ALL FIRST FLOOR UNITS SHALL COMPLY
 WITH REQUIREMENTS 1 THRU 7 OF THE FAIR
 HOUSING ACT DESIGN MANUAL. PLEASE SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH ALL
 REQUIREMENTS. INDICATE SPECIFICATION "A"
 OR "B" AS REQUIRED ON PAGE 7.34. THE
 CLEAR FLOOR SPACE FOR ALL USABLE
 FIXTURES SHALL BE APPLIED OR
 SUPERIMPOSED OVER THE FLOOR PLAN. FOR
 THE W/C SEE PAGE 7.43.
 2. SHTS P1 OF 2 FOR UNITS 101, 102, 103,
 201,202, & 203 MAXIMUM 6 FT. FROM SHOWER
 TRAP TO VENT PER TABLE 906.1. ON THE
 FLOOR PLAN IT SCALES OUT TO APPROX. 8'
 TO 9'.
 3. SHTS P2 OF 2 FOR UNITS 101, 102, 103,
 201, 202, & 203 WATER RISER DIAGRAM.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SOME ARE SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 4. SHTS P2 OF 2 ALL UNITS WATER HEATER
 DETAIL. P/T DISCHARGE LINE SHALL NOT
 HAVE ANY TRAPED SECTIONS. SECTION
 504.7.1. (SEE WATER HEATER NOTES).
 5. SHTS P2 OF 2 ALL UNITS SANITARY RISER
 DIAGRAM. THE WASH MACHINES DRAIN LINE
 SHALL HAVE A STANDPIPE, SECTION 1002.1.,
 AND THE CLEANOUT SHALL BE LOCATED 4'
 ABOVE THE FLOOR, SECTION 708.10 FOR
 ACCESS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2006-03-17 Cont ID  
Sent By jroach Date 2006-03-17 Time 11:37 Rev Time 0.00
Received By jroach Date 2006-03-17 Time 11:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-01-24 Cont ID  
Sent By jroach Date 2006-01-24 Time 10:33 Rev Time 0.00
Received By jroach Date 2006-01-24 Time 10:33 Sent To  
Notes
2006-01-24 00:00:001/24/06 ***FAILED***
  
 SEE COMMENTS FROM REVIEW ON 9/2/05...
  
 1) AN OVERALL SITE PLAN SHALL BE
 PROVIDED.
  
 2) AN OVERALL LANDSCAPE PLAN SHALL BE
 PROVIDED.ON THE LANDSCAPE PLAN, PLEASE
 INDICATE WHICH AREAS WILL BE INSPECTED
 AND CO'D WITH EACH BUILDING.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 PLANNER AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-02 Cont ID  
Sent By jroach Date 2005-09-02 Time 16:11 Rev Time 0.00
Received By jroach Date 2005-09-02 Time 16:10 Sent To  
Notes
2005-09-02 00:00:009/2/2005 ***FAILED***
  
 1) AN OVERALL SITE PLAN SHALL BE
 PROVIDED.
  
 2) AN OVERALL LANDSCAPE PLAN SHALL BE
 PROVIDED.
  
 ON THE LANDSCAPE PLAN, PLEASE INDICATE
 WHICH AREAS WILL BE CO'D WITH EACH
 BUILDING.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 PLANNER AT (561) 822-1435.