Plan Review Details - Permit 05080065
Plan Review Stops For Permit 05080065
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-14 Cont ID  
Sent By alange Date 2005-12-14 Time 14:45 Rev Time 0.25
Received By alange Date 2005-12-14 Time 14:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-08-30 Cont ID  
Sent By alange Date 2005-08-30 Time 07:59 Rev Time 0.50
Received By alange Date 2005-08-30 Time 07:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-01-04 Cont ID  
Sent By btrobaug Date 2006-01-04 Time 17:21 Rev Time 0.50
Received By btrobaug Date 2006-01-04 Time 17:06 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-11-08 Cont ID  
Sent By btrobaug Date 2005-11-08 Time 06:50 Rev Time 0.33
Received By btrobaug Date 2005-11-08 Time 06:43 Sent To P
Notes
2005-11-08 00:00:00 
 PLEASE PROVIDE A SITE PLAN INDICATING
 THE LOCATION OF ALL SERVICE AND
 GENERATOR EQUIPMENT SO THAT COMPLIANCE
 WITH 225.31 THROUGH 225.37 CAN BE
 DETERMINED.ONLY THE GENERATOR WAS SHOWN
 ON THE RESUB.
  
 THE GEC CONNECTION NEEDS TO BE AT THE
 METER OR THE FIRST MEANS OF DISCONNECT,
 NOT THE TRANSFER SWITCH. PLEASE SHOW
 SAME.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-18 Cont ID  
Sent By btrobaug Date 2005-08-18 Time 13:07 Rev Time 0.50
Received By btrobaug Date 2005-08-18 Time 13:04 Sent To M
Notes
2005-08-18 00:00:00 
  
 PLEASE PROVIDE A SITE PLAN INDICATING
 THE LOCATION OF ALL SERVICE AND
 GENERATOR EQUIPMENT SO THAT COMPLIANCE
 WITH 225.31 THROUGH 225.37 CAN BE
 DETERMINED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-04 Cont ID  
Sent By adarroug Date 2006-01-04 Time 10:42 Rev Time 0.00
Received By adarroug Date 2006-01-04 Time 10:42 Sent To E
Notes
2006-01-04 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-17 Cont ID  
Sent By adarroug Date 2005-10-17 Time 08:58 Rev Time 0.00
Received By adarroug Date 2005-10-17 Time 08:58 Sent To E
Notes
2005-10-17 00:00:00TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 13:50 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 13:50 Sent To E
Notes
2005-08-16 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-30 Cont ID  
Sent By alange Date 2005-08-30 Time 07:59 Rev Time 0.00
Received By alange Date 2005-08-03 Time 12:59 Sent To  
Notes
2005-08-03 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-11-21 Cont ID  
Sent By pkrauss Date 2005-11-21 Time 16:02 Rev Time 0.40
Received By pkrauss Date 2005-11-21 Time 15:43 Sent To P
Notes
2005-11-21 00:00:00PROVISO:
 SITE PLAN DOES NOT INDICATE DISTANCES
 FROM OPENING INTO THE HOME (DOORS,
 WINDOWS, OR FRESH AIR INTAKES).PER
 2001 FBC(M)804.3.4 #3, VENT SYSTEM SHALL
 TERMINATE AT LEAST 4 FT BELOW, 4 FT
 HORIZONTALLY FROM OR 1 FT ABOVE OF THE
 ABOVE MENTIONED INTAKES. #6 THE BOTTOM
 OF THE VENT TERMINATION SHALL BE LOCATED
 AT 12 INCHES ABOVE FINISHED GRADE.
  
 2001 FBC(M)804.3.5 #3 WHERE VENT
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 STRUCTURE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-24 Cont ID  
Sent By prafter Date 2005-08-24 Time 08:14 Rev Time 1.50
Received By prafter Date 2005-08-24 Time 08:14 Sent To P
Notes
2005-08-24 00:00:00MECH.PLAN REVIEW:
  
 1. GENERATOR MANF. RECOMBINATION FOR
 AERVICE CLEARANCE/VENILATION IN
 FEET/INCHES IN ALL DIRECTION MUST ACCM.
 GENERATIR PERMIT APP. .
  
 2. GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENING, AND
 EXHAUST MUST BE DIRECTED AWAY FROM
 BUILDING .AND BE TEN FEET FROM PROPITY
 LINE.2001 FBC/M 804.3.3TERMINATION.
 2001 FBC/M SECTION 915
 REQUIRMENT OF NFPA 37
 8.2.3.2.
 3. INFORMATION ON TYPE OF FUEL.
  
 4.LP/NAT GAS REQUIRE PERMIT, FROM
 LICENSED GAS CONTRACTOR.
  
 PAT RAFTER 561/805/6719 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-12-06 Cont ID  
Sent By jleech Date 2005-12-06 Time 14:36 Rev Time 0.25
Received By jleech Date 2005-12-06 Time 14:36 Sent To M
Notes
2005-12-06 00:00:00GAS APPLICATION HAS BEEN RECIEVED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-30 Cont ID  
Sent By jleech Date 2005-08-30 Time 07:28 Rev Time 0.33
Received By jleech Date 2005-08-30 Time 07:28 Sent To B
Notes
2005-08-30 00:00:00GAS PERMIT REQUIRED. GAS CONTRACTOR TO
 SUBMIT A RISER DIAGRAM WITH APPLICATION,
 SHOWING TYPE AND PRESSURE OF GAS LONGEST
 RUNAND BTU'S OF EXISTING APPLIANCES.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-10 Cont ID  
Sent By mmclean Date 2005-08-10 Time 15:57 Rev Time 0.00
Received By mmclean Date 2005-08-10 Time 15:57 Sent To I
Notes
2005-08-10 00:00:00GENERATOR CAN ONLY ENCROACH 4FT INTO
 SETBACK.