Plan Review Details - Permit 05080048
Plan Review Stops For Permit 05080048
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-08-29 Cont ID  
Sent By alange Date 2005-08-29 Time 09:25 Rev Time 0.33
Received By alange Date 2005-08-29 Time 09:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-11 Cont ID  
Sent By btrobaug Date 2005-08-11 Time 08:45 Rev Time 0.50
Received By btrobaug Date 2005-08-11 Time 06:53 Sent To M
Notes
2005-08-11 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} IT APPEARS THE TRANSFER SWITCH
 REFEEDS THE METER. PLEASE CLARIFY
  
 2} SUBMIT SPECS FOR THE GENERATOR AND
 TRANSFER SWITCH (TWO COPIES).SEE 225.31
 THROUGH 225.37.
  
 3} PLEASE SUBMIT A SITE PLAN INDICATING
 THE PHYSICAL LOCATION OF THE OF ALL
 SERVICE AND STANDBY EQUIPMENT SO
 COMPLIANCE WITH THE ABOVE MENTIONED
 ARTICLES CAN BE DETERMINED.
  
 4} PLEASE SEE NOMINAL VOLTAGE FOR USE IN
 LOAD CALCS. 220.2, 240 VOLTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-10 Cont ID  
Sent By adarroug Date 2005-08-10 Time 09:33 Rev Time 0.00
Received By adarroug Date 2005-08-10 Time 09:33 Sent To E
Notes
2005-08-10 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-01 Cont ID  
Sent By adarroug Date 2005-08-01 Time 16:46 Rev Time 0.00
Received By adarroug Date 2005-08-01 Time 16:46 Sent To Z
Notes
2005-08-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-08-19 Cont ID  
Sent By prafter Date 2005-08-19 Time 10:19 Rev Time 0.50
Received By prafter Date 2005-08-19 Time 10:19 Sent To P
Notes
2005-08-19 00:00:00MECH. PLAN REVIEW:
  
 MECH. PROVISO:
  
 ELECTRICAL GENERATOR EXHAUST IS
 LOCATED MINIUM OF TEN FEET FROM THE
 PROPITY LOT LINE OR FROM ADJACENT
 BUILDING AND THE EXHAUST IS DIRECTED
 AWAY FROM THE BUILDING.
  
 THIS MEET INTENT OF THE MECH. CODE.
 2001 FBC/M 804.3.3 TERMINATION.
  
 2001 FBC/M SECTION 915
 REQUIRMENT OF NFPA 378.2.3.2
 EXHAUST SYSTEM TERMINATION.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-26 Cont ID  
Sent By kstevens Date 2005-08-26 Time 14:06 Rev Time 0.25
Received By kstevens Date 2005-08-26 Time 14:06 Sent To B
Notes
2005-08-26 00:00:00SEPARATE GAS PLANS & PERMIT REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-09 Cont ID  
Sent By mmclean Date 2005-08-09 Time 17:43 Rev Time 0.00
Received By mmclean Date 2005-08-09 Time 17:43 Sent To I
Notes
2005-08-09 00:00:00GENERATOR CAN ONLY ENROACH 4FT INTO
 SETBACK.