Plan Review Details - Permit 05080028
Plan Review Stops For Permit 05080028
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-12-02 Cont ID  
Sent By alange Date 2005-12-02 Time 10:27 Rev Time 0.33
Received By alange Date 2005-12-02 Time 10:27 Sent To  
Notes
2005-12-02 00:00:00FOOTING REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-22 Cont ID  
Sent By alange Date 2005-09-22 Time 07:56 Rev Time 1.25
Received By alange Date 2005-09-21 Time 16:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-18 Cont ID  
Sent By alange Date 2005-08-18 Time 15:18 Rev Time 2.25
Received By alange Date 2005-08-18 Time 11:15 Sent To  
Notes
2005-08-18 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SHOW BEDROOM #2 EGRESS COMPLYING
 WITH 1005.4.
  
 3.SUBMIT PRODUCT APPROVALS WITH
 QUALITY ASSURANCE FOR THE FOLLOWING:
 SHUTTERS, SKYLIGHTS LINTELS AND
 TIE-DOWNS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.SHOW FOOTING DETAILS COMPLYING WITH
 FBC 1804.1.3SHOW ALSO FINISHED FLOOR
 ELEVATIONS.
  
 6.STRUCTURAL NOTES #4.IF ENGINEER IS
 NOT RESPOSIBLE FOR ALL NEW STRUCTURAL
 ITEMS ON THIS PLAN PLEASE HAVE PERSON
 RESPOSIBLE FOR THE DESIGN PRINT NAME,
 SIGN AND DATE PLANS FBC 104.2.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-06 Cont ID  
Sent By btrobaug Date 2006-06-06 Time 10:46 Rev Time 0.50
Received By btrobaug Date 2006-06-06 Time 08:45 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 16:11 Rev Time 0.40
Received By dpalmer Date 2005-09-10 Time 16:04 Sent To P
Notes
2005-09-10 00:00:00********** PROVISO/ REVISION *********
  
 1)NOTE: PLEASE SEE FBC CHAPTER 34
 3401.7.1.2.1 WHICH REQUIRES ADDITIONS IN
 AN R-3 OCCUPANCY OF 25% OR MORE TO BRING
 ALL SMOKE DETECTORS AND LOCATIONS FOR
 GFI RECEPTS UP TO THE CURRENT CODES.
 210.8,1-7 AND NFPA-7211.5.1.1
  
 PLEASE SUBMIT REVISED PLANS BEFORE ROUGH
 ELECTRICAL INSPECTIONS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-11 Cont ID  
Sent By btrobaug Date 2005-08-11 Time 09:56 Rev Time 0.50
Received By btrobaug Date 2005-08-11 Time 08:55 Sent To P
Notes
2005-08-11 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SHOW FOOTER STEEL AS PART OF
 THE GEC SINCE IT WILL BE AVAILABLE PER
 250.50. ALSO SEE 230.70 CWPB AMMENDMENTS
 FOR DISCONNECT REQUIREMENT.
  
 2} LIST THE BATH GFI AS REQUIRED BY
 210.11(C)(3), ON THE PANEL SCHEDULE.
  
 3} THE PERSON RESPONSIBLE FOR THE DESIGN
 SHALL PPRINT AND SIGN NAME ON SAME PER
 104.2.1 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-05 Cont ID  
Sent By adarroug Date 2006-06-05 Time 14:16 Rev Time 0.00
Received By adarroug Date 2006-06-05 Time 14:16 Sent To E
Notes
2006-06-05 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-23 Cont ID  
Sent By adarroug Date 2005-11-23 Time 16:07 Rev Time 0.00
Received By adarroug Date 2005-11-23 Time 16:07 Sent To B
Notes
2005-11-23 00:00:00TO "ALANGE"DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-08 Cont ID  
Sent By adarroug Date 2005-09-08 Time 09:44 Rev Time 0.00
Received By adarroug Date 2005-09-08 Time 09:44 Sent To E
Notes
2005-09-08 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-10 Cont ID  
Sent By adarroug Date 2005-08-10 Time 09:48 Rev Time 0.00
Received By adarroug Date 2005-08-10 Time 09:48 Sent To E
Notes
2005-08-10 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-18 Cont ID  
Sent By alange Date 2005-08-18 Time 15:18 Rev Time 0.00
Received By alange Date 2005-08-01 Time 11:32 Sent To  
Notes
2005-08-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-16 Cont ID  
Sent By tgordon Date 2005-08-16 Time 09:28 Rev Time 0.30
Received By tgordon Date 2005-08-16 Time 09:28 Sent To B
Notes
2005-08-16 00:00:001. MECHANICAL CONTRACTOR WILL NEED TO
 SUBMIT MECHANICAL PLANS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-21 Cont ID  
Sent By jleech Date 2005-09-21 Time 08:13 Rev Time 0.33
Received By jleech Date 2005-09-21 Time 08:13 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-12 Cont ID  
Sent By jleech Date 2005-08-12 Time 10:14 Rev Time 0.50
Received By jleech Date 2005-08-12 Time 10:14 Sent To M
Notes
2005-08-12 00:00:00DENIED;
 1.PAGE E-1 HAS NOT BEEN SIGNED. (SEE
 ELECTRICAL NOTE 3)
 2.W/M AND L/T CANNOT CONNECT WITH A
 SANITARY CROSS. FBC-2001 PLUMBING SEC.
 706.3. INSTALL L/T ABOVE W/M OUTLET.
 3.A CLEANOUT IS REQUIRED ON W/M STACK AT
 48" ABOVE FINISH FLOOR, SHOW ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2005-08-11 Cont ID  
Sent By mmclean Date 2005-08-11 Time 16:18 Rev Time 0.00
Received By mmclean Date 2005-08-11 Time 16:18 Sent To P
Notes
2005-08-11 00:00:00APPROVED BY SHIRLEY GRAHAM, RETURNED TO
 PLUMBING.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-08-09 Cont ID  
Sent By mmclean Date 2005-08-09 Time 16:39 Rev Time 0.00
Received By mmclean Date 2005-08-09 Time 16:39 Sent To I
Notes
2005-08-09 00:00:00DENIED,
 1. SITEPLAN MUST SHOW THE ADDRESS OF THE
 PROPERTY (THIS WILL INDICATE THE FRONT
 OF THE PROPERTY).
 2. MUST SHOW THE SIDE & REAR SETBACK OF
 THE STRUCTURE FROM PROPERTY LINE.
 3. MUST PROVIDE TWO COPY OF UPDATED
 SURVEY SHOWING THE EXISTING STRUCTURE &
 SETBACKS.
 4. NEW CARPORT MUST BE BEYOND THE 25FT
 FRONT SETBACK.
 5. NEW OFFICE IS ENCROACHING INTO THE
 25FT FRONT SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720