Plan Review Details - Permit 05071304
Plan Review Stops For Permit 05071304
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-08-17 Cont ID  
Sent By mwennerg Date 2005-08-17 Time 13:41 Rev Time 0.00
Received By mwennerg Date 2005-08-17 Time 06:30 Sent To  
Notes
2005-08-17 00:00:00APPROVED PER J. WITMER-OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-03 Cont ID  
Sent By jwitmer Date 2005-08-03 Time 17:49 Rev Time 0.55
Received By jwitmer Date 2005-08-03 Time 17:49 Sent To PC
Notes
2005-08-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05071304
 ADD: 580 VILLAGE BLVD
 CONT: ANDERSON-MOORE
 TEL: (561)662-1819
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-08-16 Cont ID  
Sent By dpalmer Date 2005-08-16 Time 18:13 Rev Time 0.30
Received By dpalmer Date 2005-08-16 Time 18:13 Sent To  
Notes
2005-08-16 00:00:00ELEC OK,
 ELECTRICAL PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By dpalmer Date 2005-08-01 Time 19:28 Rev Time 0.30
Received By dpalmer Date 2005-08-01 Time 19:28 Sent To  
Notes
2005-08-01 00:00:00******** UNSAT ********
  
 1)NOTE: PLEASE SEE THE MISSING REQUIRED
 "PRINTED NAME AND LICENSE NUMBER " FOR
 THE ARCHITECT OF RECORD ON PLANS.
 FAC 61G1-16.004
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
 PLEASE SEE "NOTES" TO POWER PLANS
 MENTIONS, "R" INDICATES RELOCATED
 OUTLETS TO EXSITING CIRCUITS? PLEASE SEE
 AN "R" COULD NOT BE LCOATED IF INDEED
 RECEPTS ARE EXSITNG.
  
 3)NOTE: PLEASE VERIFY BY NOTE IF TENANT
 OCCUPANTS HAVE ACCESS TO OVER CURRENT
 PROTECTIVE DEVICES FOR THEIR SPACE.
 IS BLDG UNDER 24 HR MANG?
 PLEASE SEE NEC 240.24
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELETCRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-08-17 Cont ID  
Sent By mwennerg Date 2005-08-17 Time 13:32 Rev Time 0.00
Received By mwennerg Date 2005-08-17 Time 13:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-04 Cont ID  
Sent By mwennerg Date 2005-08-04 Time 09:33 Rev Time 0.00
Received By mwennerg Date 2005-08-04 Time 09:32 Sent To  
Notes
2005-08-04 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER REVIEW COMMENTS IN
 REGARDS TO FS AND FAC REQUIREMENTS FOR
 PLANS.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 3) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 804-4756
 PLAN REVIEW(561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-16 Cont ID  
Sent By adarroug Date 2005-08-16 Time 16:00 Rev Time 0.00
Received By adarroug Date 2005-08-16 Time 16:00 Sent To  
Notes
2005-08-16 00:00:00TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-04 Cont ID  
Sent By mwennerg Date 2005-08-04 Time 09:41 Rev Time 0.00
Received By mwennerg Date 2005-07-29 Time 08:54 Sent To  
Notes
2005-07-29 00:00:00TO "BOB" #9

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-02 Cont ID  
Sent By hmoser Date 2005-08-02 Time 18:44 Rev Time 0.00
Received By hmoser Date 2005-08-02 Time 18:44 Sent To  
Notes
2005-08-02 00:00:008/2/05 NO PLANS HM.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-04 Cont ID  
Sent By mwennerg Date 2005-08-04 Time 09:41 Rev Time 0.00
Received By mwennerg Date 2005-08-04 Time 09:41 Sent To  
Notes
***NONE***