Plan Review Details - Permit 05071213
Plan Review Stops For Permit 05071213 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2005-08-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-08-16 |
Time |
17:36 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2005-08-16 |
Time |
17:36 |
Sent To |
|
|
Notes |
2005-08-16 00:00:00 | REDLINED. | | | | | | RISER SHOWS AN EQUIPMENT GROUNDING | | CONDUCTOR METER TO MAIN/FIRST MEASN OF | | DISCONNECT. | | PLEASE SEE 250.6,250.24, AN "EQUIPMENT | | GROUNDING" CONDUCTOR IS ONLY INSTALLED | | AFTER THE FIRST MEANS OF DISCONNECT. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2005-08-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-08-09 |
Time |
07:45 |
Rev Time |
0.33 |
Received By |
dpalmer |
Date |
2005-08-09 |
Time |
07:45 |
Sent To |
|
|
Notes |
2005-08-09 00:00:00 | ********** UNSAT ************ | | | | PLEASE SEE NOTES FROM FIRST REVIEW ALSO. | | | | | | 1)NOTE: PLEASE SEE A MEANS OF DISCONNECT | | ALONG WITH OVERCURRENT PROTECTION IS | | REQUIRED ON THE "OUTSIDE" OF BLDG. | | PLEASE SEE 230.70,230.6. | | | | 2)NOTE: PLEASE SHOW ANY FPL METERING | | DEVICES. | | PLEASE SEE MIN GROUNDING ELECTRODE | | SYSTEM SHALL BE SHOWN ON RISER AT | | SERVICE LOCATION. | | PLEASE SEE ANY EQUIPMENT GORUNDING | | CONDUCTORS FROM MAIN TO SUB PANEL SHALL | | BE SIZED PER 250.122 | | | | 3)NOTE: PLEASE SEE FEEDER SIZE HAS | | DECREASED TO 500MCM. IS THIS COPPER | | (CU)? | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-07-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-07-29 |
Time |
10:50 |
Rev Time |
0.25 |
Received By |
dpalmer |
Date |
2005-07-29 |
Time |
10:50 |
Sent To |
|
|
Notes |
2005-07-29 00:00:00 | ********** UNSAT ********** | | | | 1)NOTE: PLEASE SEE 240.6, 310.16 600MCM | | ALUM IS NOT RATED FOR 400A'S. | | MAX 350A'S. | | | | 2)NOTE: PLEASE SEE NO MORE THAN 8' OF | | UNPROTECTED CONDUCTOR ARE PERMITTED | | INSIDE BLDG WITH OUT OCP . 230.70 | | PLEASE ALSO SEE NO MAIN SHOWN. 230.70 | | | | 3)NOTE: PLEASE SEE 250.6, AN EQUIPMENT | | GROUNDING CONDUCTOR IS ONLY INSTALLED | | AFTER THE FIRST MEANS OF DISCONNECT. | | 250.24. | | | | PLEASE REVISE AND SUBMIT THE ABOVE | | INFORMATION FOR REVIEW. IF THERE ARE ANY | | QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-08-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-08-16 |
Time |
09:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-08-16 |
Time |
09:43 |
Sent To |
E |
|
Notes |
2005-08-16 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-08-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-08-04 |
Time |
10:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-08-04 |
Time |
10:29 |
Sent To |
E |
|
Notes |
2005-08-04 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-07-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-07-28 |
Time |
14:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-28 |
Time |
14:07 |
Sent To |
E |
|
Notes |
2005-07-28 00:00:00 | TO "E" BOX |
|
|
|