Plan Review Details - Permit 05071134
Plan Review Stops For Permit 05071134 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-08-20 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-08-20 |
Time |
09:08 |
Rev Time |
0.33 |
Received By |
jwitmer |
Date |
2005-08-20 |
Time |
09:06 |
Sent To |
PC |
|
Notes |
2005-08-20 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 05071134 | | ADD: 5407 S FLAGLER DR | | CONT:SNOWDEN | | TEL: (561)841-9344 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | ) GENERATOR SLAB & ANCHOR REQUIREMENT | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | PLUS PROVIDE PLANS WITH THE INFORMATION | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | THE DEVICE REQUIRES WITHOUT LOAD | | REDUCTION. | | SECOND, PROVIDE INFORMATION ON THE | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | WILL BEUSED. | | THE NEW SLAB AND HOLD DOWN DETAILS: | | 104.2.1* ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-08-09 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-08-09 |
Time |
11:33 |
Rev Time |
0.75 |
Received By |
btrobaug |
Date |
2005-08-09 |
Time |
08:53 |
Sent To |
M |
|
Notes |
2005-08-09 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE LOCATE THE ATS IN THE RISER | | DIAGRAM. | | | | 2} THE PERSON RESPONSIBLE NEEDS TO PRINT | | AND SIGN NAME ON THE PLANS. | | | | 3} THE SUBJECT PROPERTY IS IN A "A5" | | FLOOD ZONE. PLEASE PROVIDE AN ELEVATION | | CERTIFICATE. SEE 94-544 AND 94-546 OF | | THE CITY ORDINANCE. | | | | 4} INDICATE THE FEEDER CONDUCTOR SIZE | | FROM THE GEN SET TO THE DISCONNECT. SEE | | 445.13(115%). | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-08-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-08-03 |
Time |
09:29 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-08-03 |
Time |
09:29 |
Sent To |
E |
|
Notes |
2005-08-03 00:00:00 | TO "E" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-07-27 |
Time |
16:07 |
Sent To |
|
|
Notes |
2005-07-27 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2005-08-16 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2005-08-16 |
Time |
08:00 |
Rev Time |
0.35 |
Received By |
pkrauss |
Date |
2005-08-16 |
Time |
07:49 |
Sent To |
|
|
Notes |
2005-08-16 00:00:00 | GAS PERMIT FOR THE GENERATOR 05080022 | | | | SITE PLAN INDICATES GENERATOR 3 FT FROM | | THE BUILDING.PER 2001 FBC(M)804.3.5 | | ITEM #6, EXHAUST TERMINATION SHALL BE A | | MINIMUM OF 3 FT HORIZONTALLY FROM ANY | | PORTION OF THE ROOF STRUCTURE.SHOW | | COMPLIANCE WITH 2001 FBC(M)804.3.3 | | THROUGH 804.3.5. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
|
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2005-08-02 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-08-02 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-08-02 |
Time |
11:19 |
Sent To |
I |
|
Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy