Plan Review Details - Permit 05071101
Plan Review Stops For Permit 05071101
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-02 Cont ID  
Sent By alange Date 2005-09-02 Time 07:45 Rev Time 0.33
Received By alange Date 2005-09-02 Time 07:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-20 Cont ID  
Sent By jwitmer Date 2005-08-20 Time 08:56 Rev Time 0.33
Received By jwitmer Date 2005-08-20 Time 08:56 Sent To PC
Notes
2005-08-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05071101
 ADD: 2509
 CONT: BLACK DOG ELEC
 TEL: (561)662-8888
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2005-11-10 Cont ID  
Sent By dpalmer Date 2005-11-10 Time 17:39 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2005-11-10 00:00:00CHANGE IN LOCATION OF GENERATOR, NO
 ELECTRICAL PLANS SUBMITTED,
 PLANS SENT TO MECH REVIEW FOR NOTING OF
 WINDOWS/DOORS ETC.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 09:30 Rev Time 0.50
Received By dpalmer Date 2005-09-10 Time 09:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-08-31 Cont ID  
Sent By dpalmer Date 2005-08-31 Time 20:29 Rev Time 0.60
Received By dpalmer Date 2005-08-31 Time 20:29 Sent To M
Notes
2005-08-31 00:00:00******* UNSAT *******
  
 1)NOTE:PLEASE SEE MECH NOTES, SITE
 PLANS, PLANS ARE TO INDICATE 10'
 CLEARENCE FROM ANY OPENINGS IN HOUSE,
 ATTIC VENTILATION, OPERABLE WINDOWS,
 DOORS. ETC.
 PLEASE SEE SITE PLANS DO NOT INDICATE
 DIMENTIONS FROM DWELLINGS.
  
 2)NOTE: PLEASE SUBMIT SPECS FOR TRANSFER
 SWITCH WHICHINDICATE BEING "SERVICE
 EQUIPMENT RATED" AS REQUIRED UNDER
 225.36
 PLEASE ALSO SEE THE ATS AS SHOWN DOES
 NOT MEET 230.76, 230.79, 110.27
 MUST CONTAIN AN MANUAL MEANS OF
 DISCONNECT LOCATED ON THE OUTSIDE OF THE
 EQUIPMENT.
 PLEASE SEE THIS MAN MEANS OF DISCONNECT
 MUST BE RATED FOR THE LOAD SERVED.
 110.27
  
 3)NOTE: PLEASE SEE RISER INDICATES AN
 "EQUIPMENT GROUNDING CONDUCTOR" BEING
 INSTALLED FROM METER TO MAIN/FIRST MEANS
 OF DISCONNNECT.
 PLEASE SEE EQUIPMENT GRNDS ARE ONLY
 INSTALLED AFTER THE FIRST MEANS OF DISC.
 250.6
  
 4)NOTE: PLEASE SEE MISSING COLD WATER
 PIPE AS PART OF THE GROUNDING ELECTRODE
 SYSTEM.
 250.50
  
 5)NOTE: PLEASE SEE RISER INDICATES THE
 ENTIRE SERVICE WILL BE FED FROM THIS NEW
 GENERATOR, HOWEVER PLEASE SEE THE
 CIRCUITS AS SHOWN ON LOAD CALCULATIONS,
 DO NOT SEEM TO INDICATE ALL CIRCUITS IN
 THIS HOUSE.
 PUMPS, SPECIFIC APPLIANCES, MOTOR LOADS
 ETC, ETC.
 PLEASE SUPPLY COMPLETE PANEL SCHEDULES
 INDICATING ALL CIRCUITS AND LOADS.
 PLEASE SEE MIN KW RATING FOR RANGES.8KW.
 PLEASE ADJUST AND SUBMIT REVISED LOAD
 CALCULATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-04 Cont ID  
Sent By btrobaug Date 2005-08-04 Time 12:45 Rev Time 0.50
Received By btrobaug Date 2005-08-04 Time 12:19 Sent To M
Notes
2005-08-04 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE GROUNDING
 ELECTRODE SYSTEM COMPONENTS AND SIZES.
  
 2} THE COST OF THE EQUIPMENT INCLUDING
 THE GENERATOR AND TRANSFER SWITCH, MUST
 BE PART OF THE VALUE OF THE PERMIT.
 104.6.5 FBC.
  
 3} PLEASE SUBMIT THE TRANSFER SWITCH
 SPECIFICATION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-11-10 Cont ID  
Sent By adarroug Date 2005-11-10 Time 08:15 Rev Time 0.00
Received By adarroug Date 2005-11-10 Time 08:15 Sent To E
Notes
2005-11-10 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 14:45 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 14:45 Sent To Z
Notes
2005-10-11 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 16:18 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 16:18 Sent To E
Notes
2005-09-07 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-08-29 Cont ID  
Sent By adarroug Date 2005-08-29 Time 13:58 Rev Time 0.00
Received By adarroug Date 2005-08-29 Time 13:58 Sent To E
Notes
2005-08-29 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-03 Cont ID  
Sent By adarroug Date 2005-08-03 Time 10:00 Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 10:00 Sent To E
Notes
2005-08-03 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-24 Cont ID  
Sent By adarroug Date 2005-08-20 Time 10:25 Rev Time  
Received By shill Date 2005-07-26 Time 14:17 Sent To Z
Notes
2005-07-26 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-09-01 Cont ID  
Sent By tgordon Date 2005-09-01 Time 10:24 Rev Time 0.00
Received By tgordon Date 2005-09-01 Time 10:44 Sent To B
Notes
2005-09-01 00:00:00*** PROVISO ***
 GENERATOR EXHAUST MUST BE 10 FT. FROM
 ALL OPENINGS TO BUILDING.TG

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-04 Cont ID  
Sent By hmoser Date 2005-08-04 Time 14:49 Rev Time 0.00
Received By hmoser Date 2005-08-04 Time 14:49 Sent To P
Notes
2005-08-04 00:00:00PLAN DENIED
 PLEASE INDICATE TYPE OF FUEL USED FOR
 GENERATOR.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-08-08 Cont ID  
Sent By jleech Date 2005-08-08 Time 07:12 Rev Time 0.25
Received By jleech Date 2005-08-08 Time 07:12 Sent To B
Notes
2005-08-08 00:00:00FUEL PERMIT REQUIRED FOR GENERATOR.

Review Stop Z ZONING
Rev No 2 Status P Date 2005-10-31 Cont ID  
Sent By mmclean Date 2005-10-31 Time 15:14 Rev Time 0.00
Received By mmclean Date 2005-10-31 Time 15:14 Sent To I
Notes
2005-10-31 00:00:00APPROVING RELOCATING OF GENERATOR.
 GENERATOR CAN ONLY ENCROACH 4FT INTO A
 SETBACK.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-02 Cont ID  
Sent By shill Date 2005-08-24 Time 10:25 Rev Time 0.00
Received By mmclean Date 2005-08-02 Time 10:32 Sent To I
Notes
***NONE***