Plan Review Stops For Permit 05071101 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2005-09-02 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2005-09-02 |
Time |
07:45 |
Rev Time |
0.33 |
Received By |
alange |
Date |
2005-09-02 |
Time |
07:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2005-08-20 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2005-08-20 |
Time |
08:56 |
Rev Time |
0.33 |
Received By |
jwitmer |
Date |
2005-08-20 |
Time |
08:56 |
Sent To |
PC |
|
Notes |
2005-08-20 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 05071101 | | ADD: 2509 | | CONT: BLACK DOG ELEC | | TEL: (561)662-8888 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | 1) GENERATOR SLAB & ANCHOR REQUIREMENT | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | PLUS PROVIDE PLANS WITH THE INFORMATION | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | THE DEVICE REQUIRES WITHOUT LOAD | | REDUCTION. | | SECOND, PROVIDE INFORMATION ON THE | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | WILL BEUSED. | | THE NEW SLAB AND HOLD DOWN DETAILS: | | 104.2.1* ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
N |
Date |
2005-11-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-11-10 |
Time |
17:39 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2005-11-10 00:00:00 | CHANGE IN LOCATION OF GENERATOR, NO | | ELECTRICAL PLANS SUBMITTED, | | PLANS SENT TO MECH REVIEW FOR NOTING OF | | WINDOWS/DOORS ETC. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2005-09-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-09-10 |
Time |
09:30 |
Rev Time |
0.50 |
Received By |
dpalmer |
Date |
2005-09-10 |
Time |
09:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2005-08-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2005-08-31 |
Time |
20:29 |
Rev Time |
0.60 |
Received By |
dpalmer |
Date |
2005-08-31 |
Time |
20:29 |
Sent To |
M |
|
Notes |
2005-08-31 00:00:00 | ******* UNSAT ******* | | | | 1)NOTE:PLEASE SEE MECH NOTES, SITE | | PLANS, PLANS ARE TO INDICATE 10' | | CLEARENCE FROM ANY OPENINGS IN HOUSE, | | ATTIC VENTILATION, OPERABLE WINDOWS, | | DOORS. ETC. | | PLEASE SEE SITE PLANS DO NOT INDICATE | | DIMENTIONS FROM DWELLINGS. | | | | 2)NOTE: PLEASE SUBMIT SPECS FOR TRANSFER | | SWITCH WHICHINDICATE BEING "SERVICE | | EQUIPMENT RATED" AS REQUIRED UNDER | | 225.36 | | PLEASE ALSO SEE THE ATS AS SHOWN DOES | | NOT MEET 230.76, 230.79, 110.27 | | MUST CONTAIN AN MANUAL MEANS OF | | DISCONNECT LOCATED ON THE OUTSIDE OF THE | | EQUIPMENT. | | PLEASE SEE THIS MAN MEANS OF DISCONNECT | | MUST BE RATED FOR THE LOAD SERVED. | | 110.27 | | | | 3)NOTE: PLEASE SEE RISER INDICATES AN | | "EQUIPMENT GROUNDING CONDUCTOR" BEING | | INSTALLED FROM METER TO MAIN/FIRST MEANS | | OF DISCONNNECT. | | PLEASE SEE EQUIPMENT GRNDS ARE ONLY | | INSTALLED AFTER THE FIRST MEANS OF DISC. | | 250.6 | | | | 4)NOTE: PLEASE SEE MISSING COLD WATER | | PIPE AS PART OF THE GROUNDING ELECTRODE | | SYSTEM. | | 250.50 | | | | 5)NOTE: PLEASE SEE RISER INDICATES THE | | ENTIRE SERVICE WILL BE FED FROM THIS NEW | | GENERATOR, HOWEVER PLEASE SEE THE | | CIRCUITS AS SHOWN ON LOAD CALCULATIONS, | | DO NOT SEEM TO INDICATE ALL CIRCUITS IN | | THIS HOUSE. | | PUMPS, SPECIFIC APPLIANCES, MOTOR LOADS | | ETC, ETC. | | PLEASE SUPPLY COMPLETE PANEL SCHEDULES | | INDICATING ALL CIRCUITS AND LOADS. | | PLEASE SEE MIN KW RATING FOR RANGES.8KW. | | PLEASE ADJUST AND SUBMIT REVISED LOAD | | CALCULATIONS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2005-08-04 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2005-08-04 |
Time |
12:45 |
Rev Time |
0.50 |
Received By |
btrobaug |
Date |
2005-08-04 |
Time |
12:19 |
Sent To |
M |
|
Notes |
2005-08-04 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE INDICATE THE GROUNDING | | ELECTRODE SYSTEM COMPONENTS AND SIZES. | | | | 2} THE COST OF THE EQUIPMENT INCLUDING | | THE GENERATOR AND TRANSFER SWITCH, MUST | | BE PART OF THE VALUE OF THE PERMIT. | | 104.6.5 FBC. | | | | 3} PLEASE SUBMIT THE TRANSFER SWITCH | | SPECIFICATION. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2005-11-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-11-10 |
Time |
08:15 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-11-10 |
Time |
08:15 |
Sent To |
E |
|
Notes |
2005-11-10 00:00:00 | TO "DPALMER" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2005-10-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-10-11 |
Time |
14:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-10-11 |
Time |
14:45 |
Sent To |
Z |
|
Notes |
2005-10-11 00:00:00 | TO "Z" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2005-09-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-09-07 |
Time |
16:18 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-09-07 |
Time |
16:18 |
Sent To |
E |
|
Notes |
2005-09-07 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2005-08-29 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-08-29 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-08-29 |
Time |
13:58 |
Sent To |
E |
|
Notes |
2005-08-29 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2005-08-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-08-03 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2005-08-03 |
Time |
10:00 |
Sent To |
E |
|
Notes |
2005-08-03 00:00:00 | TO "E" BOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2005-08-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2005-08-20 |
Time |
10:25 |
Rev Time |
|
Received By |
shill |
Date |
2005-07-26 |
Time |
14:17 |
Sent To |
Z |
|
Notes |
2005-07-26 00:00:00 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2005-09-01 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2005-09-01 |
Time |
10:24 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2005-09-01 |
Time |
10:44 |
Sent To |
B |
|
Notes |
2005-09-01 00:00:00 | *** PROVISO *** | | GENERATOR EXHAUST MUST BE 10 FT. FROM | | ALL OPENINGS TO BUILDING.TG |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2005-08-04 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2005-08-04 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2005-08-04 |
Time |
14:49 |
Sent To |
P |
|
Notes |
2005-08-04 00:00:00 | PLAN DENIED | | PLEASE INDICATE TYPE OF FUEL USED FOR | | GENERATOR. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2005-08-08 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2005-08-08 |
Time |
07:12 |
Rev Time |
0.25 |
Received By |
jleech |
Date |
2005-08-08 |
Time |
07:12 |
Sent To |
B |
|
Notes |
2005-08-08 00:00:00 | FUEL PERMIT REQUIRED FOR GENERATOR. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2005-10-31 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2005-10-31 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-10-31 |
Time |
15:14 |
Sent To |
I |
|
Notes |
2005-10-31 00:00:00 | APPROVING RELOCATING OF GENERATOR. | | GENERATOR CAN ONLY ENCROACH 4FT INTO A | | SETBACK. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2005-08-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2005-08-24 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2005-08-02 |
Time |
10:32 |
Sent To |
I |
|
Notes |
|
|