Plan Review Details - Permit 05071080
Plan Review Stops For Permit 05071080
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-12-01 Cont ID  
Sent By alange Date 2005-12-01 Time 09:24 Rev Time 0.75
Received By alange Date 2005-12-01 Time 09:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-11-15 Cont ID  
Sent By alange Date 2005-11-15 Time 14:51 Rev Time 0.50
Received By alange Date 2005-11-15 Time 14:47 Sent To  
Notes
2005-11-15 00:00:00DENIED
  
 THIRD REVIEW:
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 4.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-22 Cont ID  
Sent By alange Date 2005-09-22 Time 12:55 Rev Time 1.00
Received By alange Date 2005-09-22 Time 11:31 Sent To  
Notes
2005-09-22 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3.SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING:LINTELS AND STRAPS AND
 TIE-DOWNS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.SUBMIT TWO COPIES OF ENERGY CALCS
 PER FBC CH.13
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-11 Cont ID  
Sent By alange Date 2005-08-11 Time 15:48 Rev Time 2.00
Received By alange Date 2005-08-11 Time 14:45 Sent To  
Notes
2005-08-11 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SHOW EXISTING ROOM ADJACENT TO ROOM
 ADDITION.ARE ANY OF THESE ROOMS A
 BEDROOM AND ARE THERE ANY WINDOWS TO IT
 BEING BLOCKED OFF.
  
 3.SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING:LINTELS AND STRAPS AND
 TIE-DOWNS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.SUBMIT TWO COPIES OF ENERGY CALCS
 PER FBC CH.13
  
 6.SHOW A ROOF SHEATHING NAILING
 SCHEDULE COMPLYING WITH FBC 2306.1 WPB
 AMMENDMENTS.
  
 7.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS.FBC 2309.6
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-11 Cont ID  
Sent By btrobaug Date 2006-09-11 Time 11:34 Rev Time 0.50
Received By btrobaug Date 2006-09-11 Time 11:28 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-08-25 Cont ID  
Sent By btrobaug Date 2006-08-25 Time 07:32 Rev Time 0.75
Received By btrobaug Date 2006-08-25 Time 06:50 Sent To PC
Notes
2006-08-25 00:00:00 
  
 NONCOMPLIANT
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1 THE LOADS, EXISTING AND ADDED, EXCEED
 THE RATING OF THE SERVICE. SEE ARTICLE
 230.42.
  
 2} A SMOE DETECTOR IS REQUIRED OIUTSIDE
 THE ADDED BEDROOM PER 313.1.1 FBC
 (RESIDENTIAL).
  
 3} THE RECEPTACLE ADDED IN THE POOL AREA
 AT THE EXISTING PATR OF THE RESIDENCE
 MUST BE GFI PROTECTED PER 210.8(A)(3).
  
 4} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-13 Cont ID  
Sent By btrobaug Date 2005-09-13 Time 12:56 Rev Time 0.50
Received By btrobaug Date 2005-09-13 Time 12:49 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-04 Cont ID  
Sent By btrobaug Date 2005-08-04 Time 12:10 Rev Time 0.50
Received By btrobaug Date 2005-08-04 Time 11:46 Sent To P
Notes
2005-08-04 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE GARAGE RECEPTACLES MIST BE GFI
 PER 210.8(A)(2).
  
 2} SMOKE DETECTORS ARE REQUIRED PER NFPA
 72. 8-1.4.1.6.2.
  
 3} THE PERSON RESPONSIBLE FOR THE PLAN
 MUST PRINT AND SIGN THEIR NAME ON SAME,
 ALL COPIES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-15 Cont ID  
Sent By adarroug Date 2006-08-15 Time 16:39 Rev Time 0.00
Received By adarroug Date 2006-08-15 Time 16:39 Sent To E
Notes
2006-08-15 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 11:03 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 11:03 Sent To M
Notes
2006-08-11 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-11-30 Cont ID  
Sent By ptjomsto Date 2005-11-30 Time 13:54 Rev Time 0.00
Received By ptjomsto Date 2005-11-30 Time 13:54 Sent To  
Notes
2005-11-30 00:00:003RD RESUB GIVEN TO LUIS MARTINEZ

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 08:15 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 08:15 Sent To M
Notes
2005-11-15 00:00:00TO "TGORDON" DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-12 Cont ID  
Sent By adarroug Date 2005-09-12 Time 14:45 Rev Time 0.00
Received By adarroug Date 2005-09-12 Time 14:45 Sent To E
Notes
2005-09-12 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-03 Cont ID  
Sent By adarroug Date 2005-08-03 Time 09:57 Rev Time 0.00
Received By adarroug Date 2005-08-03 Time 09:57 Sent To E
Notes
2005-08-03 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-11 Cont ID  
Sent By alange Date 2005-08-11 Time 15:48 Rev Time 0.00
Received By alange Date 2005-07-27 Time 08:25 Sent To  
Notes
2005-07-27 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-08-11 Cont ID  
Sent By tgordon Date 2006-08-11 Time 13:40 Rev Time 0.25
Received By tgordon Date 2006-08-11 Time 13:40 Sent To  
Notes
2006-08-11 00:00:00*** PROVISO ***
 1) NO OPENED A/C DUCTS ARE PERMITED IN A
 GARAGE.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-11-15 Cont ID  
Sent By tgordon Date 2005-11-15 Time 09:26 Rev Time 0.35
Received By tgordon Date 2005-11-15 Time 09:26 Sent To B
Notes
2005-11-15 00:00:00*** PROVISO ***
 1) NO OPENED A/C DUCTS ARE PERMITED IN A
 GARAGE.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-09-13 Cont ID  
Sent By tgordon Date 2005-09-13 Time 16:12 Rev Time 0.20
Received By tgordon Date 2005-09-13 Time 16:12 Sent To B
Notes
2005-09-13 00:00:00*** DENIED ***
 AS NOTED IN LAST MECHANICAL REVIEW.
 1) FLORIDA ENERGY CALCALATIONS REQUIRED.
 2) MECHANICAL (A/C) PLANS AND EQUIPMENT
 INFORMATION REQUIRED.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-08-08 Cont ID  
Sent By prafter Date 2005-08-08 Time 11:42 Rev Time 0.50
Received By prafter Date 2005-08-08 Time 11:42 Sent To B
Notes
2005-08-08 00:00:00MECH. PLAN REVIEW:
  
 1. FL. ENERGY CALCULATIONS REQUIRED.
  
 2. A/C PLANS AND EQUIPMENT INFORMATION
 REQUIRED.
  
 PAT RAFTER 651/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-13 Cont ID  
Sent By jleech Date 2005-09-13 Time 13:05 Rev Time 0.25
Received By jleech Date 2005-09-13 Time 13:05 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-08 Cont ID  
Sent By jleech Date 2005-08-08 Time 07:21 Rev Time 0.33
Received By jleech Date 2005-08-08 Time 07:21 Sent To M
Notes
2005-08-08 00:00:00DENIED;
 THE PERSON RESPONSIBLE FOR THE PLAN MUST
 PRINT AND SIGN THEIR NAME ON SAME, ALL
 COPIES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-02 Cont ID  
Sent By mmclean Date 2005-08-02 Time 10:52 Rev Time 0.00
Received By mmclean Date 2005-08-02 Time 10:52 Sent To I
Notes
***NONE***