Plan Review Details - Permit 05071070
Plan Review Stops For Permit 05071070
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-09-06 Cont ID  
Sent By jgomez Date 2005-09-06 Time 11:07 Rev Time 0.33
Received By jgomez Date 2005-09-06 Time 11:07 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-05 Cont ID  
Sent By jgomez Date 2005-08-05 Time 14:57 Rev Time 0.50
Received By jgomez Date 2005-08-05 Time 14:57 Sent To PC
Notes
2005-08-05 00:00:00BUILDING REVIEW CHECKLIST:
 1- A)PROVIDE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL FOR
 WINDOW MULLION TO BE INSTALLED.
  
 B) CLEARLY SPECIFY MULLION SIZE AND
 ANCHORS TO BE USED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES CALCULATED BY
 THE ENGINEER.
  
 C) MULLION DADE COUNTY NOA SUBMITTED IS
 FOR 2X HEAVY WALL MULLION. MULLION SIZE
 SPECIFIED ON CUSTOMER ORDER FORM IS
 1X2.75X.650. NEED PRODUCT APPROVAL FOR
 ACTUAL MULLION SIZE TO BE INSTALLED TO
 VERIFY FOR DESIGN PRESSURES COMPLIANCE.
  
 2- CUSTOMER QUOTE AND SALES AGREEMENT
 CALL FOR SINGLE HUNG WINDOWS WITH
 TEMPERED GLASS. PRODUCT APPROVAL
 SUBMITTED IS FOR IMPACT GLASS. PROVIDE
 PRODUCT APPROVAL FOR CORRECT WINDOW TO
 BE INSTALLED.
 *NOTE: ENGINEER CALCS ASSUME BUILDING TO
 BE ENCLOSED. THEREFORE, WINDOWS NEED TO
 HAVE IMPACT GLAZING.
 **UPDATE VALUATION OF PROJECT AS REQ.D .
 SEE QUOTE LIST OF PRICES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By jgomez Date 2005-08-01 Time 10:47 Rev Time 0.33
Received By jgomez Date 2005-08-01 Time 10:47 Sent To PC
Notes
2005-08-01 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- PROVIDE FLORIDA PRODUCT APPROVAL FOR
 SINGLE HUNG WINDOWS AND MULLIONS AS
 REQUIRED BY RULE 9B-72 OF DCA AS OF OCT.
 2003. SEE WWW.FLORIDABUILDING.ORG.
 DADE COUNTY NOA ALONE IS NOT
 AUTOMATICALLY AN STATEWIDE FLORIDA
 PRODUCT APPROVAL. MANUFATURER MAY APPLY
 FOR LOCAL PRODUCT APPROVAL USING THE
 DADE COUNTY NOA BY COMPLETING THE LOCAL
 PRODUCT APPROVAL FORM DOWNLOADED FROM
 WWW.FLORIDABUILDING.ORG.
  
 2- CLEARLY INDICATE MULLION SIZE AND
 ANCHORS TO BE USED TO VERIFY FOR DESIGN
 PRESSURES COMPLIANCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-01 Cont ID  
Sent By adarroug Date 2005-09-01 Time 18:57 Rev Time 0.00
Received By adarroug Date 2005-09-01 Time 18:57 Sent To B
Notes
2005-09-01 00:00:00TO "JGOMEZ" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-04 Cont ID  
Sent By adarroug Date 2005-08-04 Time 12:01 Rev Time 0.00
Received By adarroug Date 2005-08-04 Time 12:01 Sent To B
Notes
2005-08-04 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-01 Cont ID  
Sent By jgomez Date 2005-08-01 Time 10:59 Rev Time 0.00
Received By jgomez Date 2005-07-25 Time 16:52 Sent To  
Notes
2005-07-25 00:00:00TO "MISC" BOX #1