Plan Review Details - Permit 05071035
Plan Review Stops For Permit 05071035
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-09-20 Cont ID  
Sent By jgomez Date 2005-09-20 Time 11:21 Rev Time 0.33
Received By jgomez Date 2005-09-20 Time 11:21 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-09-07 Cont ID  
Sent By jgomez Date 2005-09-07 Time 08:26 Rev Time 0.33
Received By jgomez Date 2005-09-07 Time 08:26 Sent To  
Notes
2005-09-07 00:00:00BUILDING REVIEW THIRD CHECKLIST:
 1- STILL UNABLE TO PERFORM PLAN REVIEW
 TO VERIFY COMPLIANCE OF PRODUCT USE IF
 COMPLETE INSTALLATION INFORMATION IS NOT
 PROVIDED.
 CONTRACTOR WAS ASKED TO MARK ON DRAWINGS
 SPECIFIC MOUNTING CONDITIONS AND ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING TO
 THE DESIGN PRESSURES, EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO (CONCRETE,
 CONCRETE BLOCK OR WOOD). SECTION
 104.2.1.2 CITY AMENDMENTS TO THE FBC
 2001 AND THE CITY IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION. IN ADDITION ANCHOR NOTE #2
 ON PAGE 5 OF 5 OF THE ACCORDION DRAWINGS
 CALLS FOR THE SAME INFORMATION I
 REQUESTED ON THE FIRST CHECKLIST.
  
 BY PROVIDING THIS SIMPLE INFORMATION
 PLAN REVIEWER CAN VERIFY THAT PROPER
 ANCHOR TYPE AND SPACING IS USED.
  
 INSTALLATION SCHEDULE CALLS FOR TAPCON
 AS THE ANCHOR TO BE USED. THE ANCHOR
 SCHEDULE IN PAGE 5 OF 5 SHOWS THREE
 DIFFERENT TYPES OF TAPCONS. SOME WORK
 FOR THE SPACING SPECIFIED IN THE
 INSTALLATION SCHEDULE AND SOME DON'T.
 THAT'S WHY IS IMPORTANT TO BE SPECIFIC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-08-19 Cont ID  
Sent By jgomez Date 2005-08-19 Time 14:01 Rev Time 0.33
Received By jgomez Date 2005-08-19 Time 14:01 Sent To PC
Notes
2005-08-19 00:00:00BUILDING REVIEW SECOND CHECKLIST:
  
 1- STILL UNABLE TO DO PLAN REVIEW TO
 VERIFY COMPLIANCE OF PRODUCT APPROVAL IF
 PROPOSED INSTALLATION IS NOT PROVIDED.
 INFORMATION SUBMITTED IS NOT COMPLETE.
 INSTALLATION SCHEDULE CHART IS
 INCOMPLETE AND ON THE ANCHOR SCHEDULE
 CHART (PAGE 5 OF 5)ONLY THE WORD HOLLOW
 CONCRETE BLOCK WAS CIRCLED. NOT
 ADDITIONAL INFORMATION WAS GIVEN.
  
 ON PREVIOUS CHECKLIST IT WAS REQUESTED
 TO PROVIDE THE FOLLOWING INFORMATION:
  
 A) CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE AND
 SPACING TO BE USED ACCORDING TO THE
 DESIGN PRESSURES, EDGE DISTANCE, PANEL
 SPAN, CONNECTION TYPE AND STRUCTURE TO
 BE ATTACHED TO (CONCRETE BLOCK, CONCRETE
 OR WOOD).
  
 B) PROVIDE A COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
  
 SECTION 104.2.1.2 CITY AMENDMENTS TO FBC
 2001 AND CITY'S IMPLEMENTATION STANDARD
 FOR HURRICANE MISSILE IMPACT PROTECTION.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-04 Cont ID  
Sent By jgomez Date 2005-08-04 Time 09:24 Rev Time 0.33
Received By jgomez Date 2005-08-04 Time 09:23 Sent To PC
Notes
2005-08-04 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- PROVIDE THE FOLLOWING INFORMATION TO
 REVIEW COMPLIANCE WITH THE DESIGN
 PRESSURES AND LIMITATIONS OF THE
 SHUTTERS:
 A) CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE AND
 SPACING TO BE USED ACCORDING TO THE
 DESIGN PRESSURES, EDGE DISTANCE, PANEL
 SPAN, CONNECTION TYPE AND STRUCTURE TO
 BE ATTACHED TO (MASONRY, CONCRETE OR
 WOOD).
 B) PROVIDE A COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
 SECTION 104.2.1.2 OF CITY AMENDMENTS TO
 FBC 2001 AND CITY'S IMPLEMENTATION
 STANDARD FOR HURRICANE MISSILE IMPACT
 PROTECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-09-19 Cont ID  
Sent By adarroug Date 2005-09-19 Time 15:59 Rev Time 0.00
Received By adarroug Date 2005-09-19 Time 15:59 Sent To B
Notes
2005-09-19 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-09-02 Time 15:32 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 15:32 Sent To B
Notes
2005-09-02 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-08-18 Cont ID  
Sent By adarroug Date 2005-08-18 Time 15:46 Rev Time 0.00
Received By adarroug Date 2005-08-18 Time 15:46 Sent To B
Notes
2005-08-18 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-07-26 Cont ID  
Sent By adarroug Date 2005-07-26 Time 10:25 Rev Time 0.00
Received By adarroug Date 2005-07-26 Time 10:25 Sent To B
Notes
2005-07-26 00:00:00TO "MISC" BOX#1