Plan Review Details - Permit 05070977
Plan Review Stops For Permit 05070977
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-09-14 Cont ID  
Sent By jwitmer Date 2005-09-14 Time 06:43 Rev Time 0.55
Received By jwitmer Date 2005-09-14 Time 06:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-08-25 Cont ID  
Sent By jwitmer Date 2005-08-25 Time 07:07 Rev Time 0.77
Received By jwitmer Date 2005-08-25 Time 06:50 Sent To Z
Notes
2005-08-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05070977
 ADD: 301 CLEMATIS ST
 CONT: BSL
 TEL: (561)317-8315
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION:
 PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 2) 304.2 SUBCLASSIFICATIONS
 A-2:SMALL ASSEMBLY SHALL INCLUDE
 THEATERS AND OTHER PLACES OF
 ASSEMBLY WITH OR WITHOUT A STAGE
 REQUIRING PROSCENIUM OPENING
 PROTECTION AND WITH AN OCCUPANT LOAD OF
 50 OR MORE PERSONS, BUT WITH AN OCCUPANT
 LOAD LESS THAN DESIGNATED FOR LARGE
 ASSEMBLY.
 PLANS INDICATE 48 SEAT PLUS THE
 STAFF WILL PLACE THIS RESTRAUNT INTO A
 A-2 OCCUPANCY CLASSIFICATION.PROVIDE THE
  
 2HR TENANT SEPERATION FOR WALLS AND
 FLOOR/CEILING ASSEMBLY.
  
 3) PLANS DO NOT PROVIDE WHAT TYPE OF
 BUILDING TYPE THIS BUILDING IS LOCATED
 IN?
  
 601.2.1 EVERY BUILDING SHALL BE
 CLASSIFIED BY THE BUILDING OFFICIAL
 INTO ONE OF THE TYPES OF CONSTRUCTION
 AS SET FORTH IN THIS SECTION.
  
 TYPE ITYPE V
 TYPE II1-HOUR PROTECTED
 TYPE IIIUNPROTECTED
 TYPE IV TYPE VI
 1-HOUR PROTECTED1-HOUR PROTECTED
 UNPROTECTED UNPROTECTED
  
 4) INDICATE TO WHICH CODE YOU ARE
 DESIGNING, FL 2001 OR FL 2004.
  
 5) FIRE INDICATES THIS IS A FIRE
 SPRINKLERED BLDG, INDICATE ON BLDG TYPE
 OF CONSTRUCTION, IF FIRE SPRINKLER
 CHANGES ARE TO BE MADE PROVIDE ON FIRE
 SPRINKLER PLANS.
  
 6) SHEET 1.0A BACK WALL OF RESTROOMS,
 THE MINIMUM LENGTH OF THE GRAB BAR IS
 36" .
  
 7) PLANS INDICATE A 48" HIGH WALL W/
 SNEEZE GUARD ABOVE, INDICATE COMPLIANCE
 WITH 11-5.2 COUNTERS AND BARS.
  
 8)11-5.4 DINING AREA: 11-5.4 INDICATE
 COMPLIANCE FOR HANDICAPPED SEATING.
  
 9)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-10-14 Cont ID  
Sent By dpalmer Date 2005-10-14 Time 16:25 Rev Time 0.50
Received By dpalmer Date 2005-10-14 Time 16:24 Sent To P
Notes
2005-10-14 00:00:00REDLINED
  
 SHOW WINDOW LENGTH TO BE VERIFIED IN
 FEILD. 210.62
  
 LOAD ON PANEL STILL SHOWN AS 6KW, DEMAND
 LOAD WAS CORRECTED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-09-03 Cont ID  
Sent By dpalmer Date 2005-09-03 Time 15:20 Rev Time 0.33
Received By dpalmer Date 2005-09-03 Time 15:20 Sent To  
Notes
2005-09-03 00:00:00REDLINED
  
 SHOW WINDOW LENGTH TO BE VERIFIED IN
 FEILD. 210.62
  
 LOAD ON PANEL STILL SHOWN AS 6KW, DEMAND
 LOAD WAS CORRECTED.
  
 GFI CIRCUITS IN KITCHEN ONLY REQUIRED
 PER 210.8B3 WHICH REQUIRES ALL 15- AND
 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-08-01 Cont ID  
Sent By dpalmer Date 2005-08-01 Time 13:10 Rev Time 1.00
Received By dpalmer Date 2005-08-01 Time 13:10 Sent To  
Notes
2005-08-01 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE LOAD CALCULATIONS ON
 THE RIGHT SIDE OF PANEL SCHEDULE. PLEASE
 SEE LOAD ADDS UP TO 6KW, HOWEVER, LOADS
 LISTED ON PANEL SCHEDULE ADDS UP TO MORE
 THAN TOTAL OF 6KVA.?
 PLEASE SEE 220,215.5
  
 2)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS
 WHICH REQUIRES ALL 15- AND 20-AMPERE,
 125-VOLT RECEPTACLES IN NONDWELLING-TYPE
 KITCHENS TO BE GFCI PROTECTED. THIS
 REQUIREMENT APPLIES TO EACH AND EVERY
 15- AND 20-AMPERE, 125-VOLT KITCHEN
 RECEPTACLE, WHETHER OR NOT THE
 RECEPTACLE SERVES COUNTERTOP APPLIANCES.
  
  
 3)NOTE: PLEASE SEE CIRCUITING FOR
 "SHOW/DISPLAY WINDOW" RECEPTS, PLEASE
 ALSO SEE # OF RECEPTS FOR EACH12
 LINEAR FT, OR POSTION THERE-OF.
 210.62,220.12
  
 4)NOTE: PLEASE SHOW THE "EXISTING" SIGN
 CIRCUIT J-BOX LOCATION ETC ON PLANS.
  
 PLEASE ANY POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-09-14 Cont ID  
Sent By mwennerg Date 2005-09-14 Time 13:17 Rev Time 0.00
Received By mwennerg Date 2005-09-14 Time 13:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-08-24 Cont ID  
Sent By mwennerg Date 2005-08-24 Time 10:36 Rev Time 0.00
Received By mwennerg Date 2005-08-24 Time 10:36 Sent To  
Notes
2005-08-24 00:00:00******DENIED******
  
 1) APPROVED HOOD AND SUPPRESSION SYSTEMS
 ARE REQUIRED FOR FOODS THAT PRODUCE HEAT
 LADEN VAPORS. SEPARATE SHOP DRAWINGS AND
 PERMITS ARE REQUIRED FOR HOOD AND
 SUPPRESSION SYSTEMS.
  
 2) PLEASE ILLUSTRATE LIFE SAFETY PLAN TO
 SHOW REQUIRED MEANS OF EGRESS.
  
 3) PLEASE INDICATE THE OCCUPANT LOAD FOR
 SPACE TO DETERMINE OCCUPANCY
 CLASSIFICATION. PLANS SHOW 48 SEATS.
  
 4) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING
 THAT IS SPECIFIC FOR THIS PROJECT.
  
 5) IF THIS PROJECT IS PART OF A FULLY
 FIRE SPRINKLERED BUILDING, SEPARATE SHOP
 DRAWINGS AND PERMITS WILL BE REQUIRED
 FOR FIRE SPRINKLER AND FIRE ALARM
 REMODEL. PLEASE CLARIFY.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2005-10-19 Cont ID  
Sent By kstevens Date 2005-10-19 Time 11:48 Rev Time 0.50
Received By kstevens Date 2005-10-19 Time 11:48 Sent To  
Notes
2005-10-19 00:00:00GAS REVISION PROVISO
  
 GAS SOV'S SHALL BE LOCATED MAXIMUM 6'
 FROM GAS APPLIANCE. SECTION 409.7

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 17:14 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 17:14 Sent To  
Notes
2005-10-11 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-22 Cont ID  
Sent By adarroug Date 2005-09-22 Time 15:14 Rev Time 0.00
Received By adarroug Date 2005-09-22 Time 15:14 Sent To P
Notes
2005-09-22 00:00:00TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-09-02 Time 08:33 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 08:33 Sent To  
Notes
2005-09-02 00:00:00TO "COMM" BD#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-08-29 Cont ID  
Sent By mmclean Date 2005-08-29 Time 15:52 Rev Time 0.00
Received By mmclean Date 2005-07-26 Time 09:34 Sent To  
Notes
2005-07-26 00:00:00TO "COMM" BD#14

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-08-03 Cont ID  
Sent By hmoser Date 2005-08-03 Time 17:54 Rev Time 0.00
Received By hmoser Date 2005-08-03 Time 17:50 Sent To  
Notes
2005-08-03 00:00:008/3/05 NO PLANS HM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-09-21 Cont ID  
Sent By kstevens Date 2005-09-21 Time 15:22 Rev Time 2.50
Received By kstevens Date 2005-09-21 Time 15:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-08-23 Cont ID  
Sent By kstevens Date 2005-08-23 Time 18:28 Rev Time 1.45
Received By kstevens Date 2005-08-23 Time 18:28 Sent To  
Notes
2005-08-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHT 1.0A EQUIPMENT SCHEDULE ITEM #5
 DOES NOT SHOW WATER SUPPLY OR DRAINAGE.
 PLEASE CLARIFY. SECTION 104.2.1.
 2. SHT 1.0A EQUIPMENT PLAN INDICATES
 EXISTING GREASE INTECEPTOR. THIS IS A
 NEW RESTURANT AND AS INDICATED BY
 ENVIRONMENTAL COMPLIANCE THERE IS NO
 GREASE INTECEPTOR AND THE REQUIREMENT
 HAS BEEN WAIVED. PLEASE CLARIFY. SECTION
 104.2.1.
 3. SHT 1.0A INDICATE THE FOLLOWING
 ACCESSIBLITY REQUIREMENTS ON THE
 DETAILS:
 A. 11-4.16.5 FLUSH CONTROLS
 B. 11-4.18.4 FLUSH CONTROLS
 C. 11-4.19.5 FAUCETS
 4. SHT 3.0P WATER RISER DIAGRAM WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201. -
 PLUMBING NOTES:
 #8 1/4"/FT FOR 2-1/2" AND SMALLER PIPE
 PER TABLE 704.1.
 #11 "L" OR "K" COPPER REQUIRED
 UNDERGROUND. "M" COPPER NOT MANUF. IN
 ROLL COPPER AND JOINTS FOR COPPER NOT
 APPROVE UNDER THE SLAB.
 #12 AIR CHAMBERS NOT APPROVED. DELETE
 FROM REFERENCE. SECTION 604.9
 5. THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
 A. TYPE OF GAS, (LP OR NATURAL)
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 C. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 D. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 E. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 F. GAS RISER DIAGRAM INDICATES 2PSI
 PRESSURE FROM THE METER. INDICATE
 LOCATION OF 2LB TO 1/2LB REGULATOR IN
 GAS SYSTEM AND SUBMIT MANUF.
 SPECIFICATION SHEETS FOR REGULATOR.
 6. SHT 1.0A WITH DBPR STAMPS SHALL BE
 SIGNED, SEALED AND DATED PER SECTION
 104.2.2. - TWO PAGE "WORKSHEETS" SHALL
 BE ATTACHED TO EACH SET OF PLANS BEING
 SUBMITTED FOR REVIEW. SECTION 101.4.7.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-08-29 Cont ID  
Sent By astelly Date 2005-08-29 Time 15:39 Rev Time 0.00
Received By astelly Date 2005-08-29 Time 15:39 Sent To  
Notes
***NONE***